Page 1: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

Operating Instructions

TypeMS03

Conductivity sensor cube

Page 2: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

We reserve the right to make technical changes without notice.Technische Änderungen vorbehalten.Sous réserve de modifications techniques.

© Bürkert SAS, 2014

Operating Instructions 1409/0_EU-ML 00566498 Original EN

Page 3: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

1

Contents

1 AbouttheoperAtinginstructions...........................................................................................................................3

1.1 symbolsused..........................................................................................................................................................................3

1.2 Definitionoftheword"product"....................................................................................................................................3

1.3 Definitionoftheword"system"......................................................................................................................................4

1.4 Definitionoftheword"büs".............................................................................................................................................4

2 intenDeDuse....................................................................................................................................................................................4

3 bAsicsAfetyinformAtion....................................................................................................................................................5

4 generAlinformAtion................................................................................................................................................................6

4.1 contact........................................................................................................................................................................................6

4.2 Warrantyconditions..............................................................................................................................................................6

4.3 informationsontheinternet............................................................................................................................................6

5 Description.......................................................................................................................................................................................7

6 technicAlDAtA................................................................................................................................................................................8

6.1 conditionsofuse...................................................................................................................................................................8

6.2 conformitytostandardsanddirectives....................................................................................................................8

6.3 materialstheproductismadeof..................................................................................................................................8

6.4 fluiddata....................................................................................................................................................................................8

6.5 measurementdata................................................................................................................................................................9

6.6 electricaldata..........................................................................................................................................................................9

6.7 communication.......................................................................................................................................................................9

7 instAllAtion...................................................................................................................................................................................10

7.1 safetyinstructions.............................................................................................................................................................10

7.2 mountingtheproductonthebackplane................................................................................................................10

8 ADjustmentAnDoperAtion..............................................................................................................................................11

8.1 safetyinstructions.............................................................................................................................................................11

8.2 howtoadjusttheproduct.............................................................................................................................................11

8.3 Adjustmentsthatmustbedone.................................................................................................................................12

8.4 generalinformationonthedisplaysoftwaretypeme21..............................................................................12

Type MS03

English

Page 4: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

2

Contents

8.5 "Device"viewoftheproduct.........................................................................................................................................13

8.6 "function"viewoftheproduct.....................................................................................................................................14

8.7 Detailedviewsofthebüsfunction...........................................................................................................................15

8.8 "parameter"viewofthesensor...................................................................................................................................16

8.8.1 Settingthetemperaturecompensation.........................................................................................16

8.8.2 Configuringthetriggeringofthewarnings...................................................................................17

8.8.3 Configuringthetriggeringoftheerrors........................................................................................18

8.9 "Diagnosis"viewofthesensor....................................................................................................................................18

8.10 "maintenance"viewofthesensor..............................................................................................................................18

8.10.1 Calibratingthecellconstantoftheconductivitysensor...........................................................19

8.10.2 Doinga1pointcalibrationprocedureoftheconductivitysensor..........................................19

8.10.3 Adjustingtheoffsetvalueofthetemperature..............................................................................21

8.10.4 Simulatingsomedata........................................................................................................................22

8.10.5 Readingthedateofthelastcalibration........................................................................................22

8.10.6 Readingthedateofthenextduecalibration...............................................................................22

8.10.7 Settingthetimeintervalbetweentwocalibrations.....................................................................22

9 mAintenAnceAnDtroubleshooting.......................................................................................................................23

9.1 safetyinstructions.............................................................................................................................................................23

9.2 cleaningoftheproduct...................................................................................................................................................23

9.3 troubleshoutingifnomessageisdisplayed.......................................................................................................23

9.4 troubleshootingifthestatusleDoftheproductisredororange........................................................23

9.4.1 Message"Toohighconductivityvalue".........................................................................................24

9.4.2 Message"Toolowconductivityvalue"..........................................................................................24

9.4.3 Message"Toohightemperaturevalue".........................................................................................25

9.4.4 Message"Toolowtemperaturevalue"..........................................................................................26

10 spArepArtsAnDAccessories......................................................................................................................................27

11 pAckAging,trAnsport..........................................................................................................................................................27

12 storAge..............................................................................................................................................................................................27

13 DisposAloftheproDuct..................................................................................................................................................28

English

Page 5: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

3

About the Operating Instructions

1 AbouT The operATing inSTrucTionSTheOperatingInstructionsdescribetheentirelifecycleoftheproduct.PleasekeeptheOperatingInstructionsinasafeplace,accessibletoallusersandanynewowners.

theoperatinginstructionscontainimportantsafetyinformation.

Failuretocomplywiththeseinstructionscanleadtohazardoussituations.

▶ TheOperatingInstructionsmustbereadandunderstood.

1.1 Symbols used

danger

Warnsagainstanimminentdanger.

▶ Failuretoobservethiswarningcanresultindeathorinseriousinjury.

Warning

Warnsagainstapotentiallydangeroussituation.

▶ Failuretoobservethiswarningcanresultinseriousinjuryorevendeath.

attention

Warnsagainstapossiblerisk.

▶ Failuretoobservethiswarningcanresultinsubstantialorminorinjuries.

note

Warnsagainstmaterialdamage.

• Failuretoobservethiswarningmayresultindamagetotheproductorsystem.

Indicatesadditionalinformation,adviceorimportantrecommendations.

ReferstoinformationcontainedintheOperatingInstructionsorinotherdocuments.

▶ Indicatesaninstructiontobecarriedouttoavoidadanger,awarningorapossiblerisk.

→ Indicatesaproceduretobecarriedout.

» Indicatestheresultofaspecificinstruction.

1.2 Definition of the word "product"

Theword"product"usedwithintheseOperatingInstructionsalwaysreferstotheconductivitysensorcubetypeMS03.

English

Type MS03

Page 6: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

4

About the Operating Instructions

1.3 Definition of the word "system"

Theword"system"usedwithintheseOperatingInstructionsalwaysreferstotheOnlineAnalysisSystemtype8905.

1.4 Definition of the word "büS"

Theword"büS"usedwithintheseOperatingInstructionsalwaysreferstothefieldbusdeveloppedbyBürkert.

2 inTenDeD uSe

useofthisproductthatdoesnotcomplywiththeinstructionscouldpresentriskstopeople,nearbyinstallationsandtheenvironment.

▶ Theproductisintendedsolelyforthemeasurementoftheconductivityofthewaterwithina8905system.

▶ Thisproductmustbeprotectedagainstelectromagneticinterference,ultravioletraysand,wheninstalledoutdoors,theeffectsofclimaticconditions.

▶ ThisproductmustbeusedincompliancewiththecharacteristicsandcommissioninganduseconditionsspecifiedinthecontractualdocumentsandintheOperatingInstructions.

▶ Requirementsforthesafeandproperoperationoftheproductarepropertransport,storageandinstallation,aswellascarefuloperationandmaintenance.

▶ Onlyusetheproductasintended.

▶ Observeanyexistingrestraintswhentheproductisexported.

English

Type MS03

Page 7: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

5

Basic safety information

3 bASic SAfeTy inforMATionThissafetyinformationdoesnottakeintoaccount:

• anycontingenciesoroccurrencesthatmayariseduringassembly,useandmaintenanceoftheproduct.

• thelocalsafetyregulationsthattheoperatormustensurethestaffinchargeofinstallationandmaintenanceobserve.

Variousdangeroussituations.

Toavoidinjurytakecare:

▶ topreventanyunintentionalpowersupplyswitch-on.

▶ tocarryouttheinstallationandmaintenanceworkbyqualifiedandskilledstaffwiththeappropriatetools.

▶ tousetheproductonlyifinperfectworkingorderandincompliancewiththeinstructionsprovidedintheseOperatingInstructions.

▶ toobservethegeneraltechnicalrulesduringtheplanninganduseoftheproduct.

▶ nottousethisproductinexplosiveatmospheres.

▶ nottousethisproductinanenvironmentincompatiblewiththematerialsfromwhichitismade.

▶ nottomakeanyexternalorinternalmodificationstotheproduct.

note

elements/componentssensitivetoelectrostaticdischarges

• Thisproductcontainselectroniccomponentssensitivetoelectrostaticdischarges.Theymaybedamagediftheyaretouchedbyanelectrostaticallychargedpersonorobject.Intheworstcasescenario,thesecompo-nentsareinstantlydestroyedorgooutoforderassoonastheyareactivated.

• Tominimiseorevenavoidalldamageduetoanelectrostaticdischarge,takealltheprecautionsdescribedintheEN61340-5-1norm.

• Alsoensurethatyoudonottouchanyoftheliveelectricalcomponents.

English

Type MS03

Page 8: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

6

General information

4 generAl inforMATion

4.1 contact

Tocontactthemanufactureroftheproductusefollowingaddress:

BürkertSAS

RueduGiessen

BP21

F-67220TRIEMBACH-AU-VAL

TheaddressesofourinternationalbranchescanbefoundontheInternetat:www.burkert.com

4.2 Warranty conditions

TheconditiongoverningthelegalwarrantyistheconforminguseoftheproductinobservanceoftheoperatingconditionsspecifiedintheseOperatingInstructions.

4.3 informations on the internet

YoucanfindtheOperatingInstructionsandtechnicaldatasheetsregardingthetypeMS03at:www.burkert.com

English

Type MS03

Page 9: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

7

Description

5 DeScripTionTheconductivitysensorcubeisusedinthesystemtype8905.

Theelectricalandfluidconnectionsaremadeviatheconnectionpanelofthesystemtype8905.

Leverto:

- lock/unlocktheproduct.

- carryoutmaintenanceoperations.

Unlockedposition

Lockedposition

Maintenanceposition

Push-buttonwithmea-suredprocessvariable

Fluidconnections

Electricalinterface

Pin

Adaptationpins

SensorcubestatusLED

Slotforthemicro-SIMcard

Fig. 1: Description of the product

English

Type MS03

Page 10: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

8

Technical data

6 TechnicAl DATA

6.1 conditions of use

Ambienttemperature 0to+40°C

Airhumidity <90%,withoutcondensation

Protectionratingacc.toEN60529

• IP65,whenpluggedinthebackplane

• IP20,asstandaloneproduct

Max.heightabovesealevel 2000m

6.2 conformity to standards and directives

TheproductconformstotheCEdirectivesofthesystemtype8905,onlywhentheproducttypeMS03ispluggedinthesystemtype8905.

6.3 Materials the product is made of

part material

Housing PPE+PS

Seal EPDM

Lever PC

6.4 fluid data

• Typeoffluid

• pHvalue

• Water,withoutparticles:drinkingwater,industrialwater

• pH4to9Minimalflowrate 3l/h;recommended6l/h

Watersamplepressure PN6

Watersampletemperature 0to+40°C,notfreezing

English

Type MS03

Page 11: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

9

Technical data

6.5 Measurement data

Conductivitymeasurement

• Measuringrange

• Measurementdeviation("measurementbias",asdefinedinthestandardJCGM200:2012)

• Linearity

• Repeatability

• Responsetime(t90)

• Measurementsensor

• 50µS/cmto1000µS/cm

• ±2%ofthemeasuredvalue

• ±0.2%ofthefullscale

• ±0.2%ofthefullscale

• <5s

• systemwithtwographiteelectrodes,C=1Temperaturemeasurementforcompensation

• Measuringrange

• Measurementsensor

• 0to50°C

• Pt1000ClassB,nocontactwiththewatersampleMaintenanceintervaloftheexternalreferenceelectrode 12months,nominal,dependingonthewaterquality

6.6 electrical data

Operatingvoltage 24VDCthroughthebackplaneofthesystemtype8905

Powerconsumption 0.8VA

6.7 communication

Internalcommunication throughbüS

ExternalcommunicationbystatusLED accordingtoNAMURNE107

English

Type MS03

Page 12: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

10

Installation

7 inSTAllATion

7.1 Safety instructions

note

riskofdamagetotheproductduetonon-conforminginstallation.

• Theelectricalandfluidicinstallationscanonlybecarriedoutbyqualifiedandskilledstaffwiththeappropriatetools.

• Respecttheinstallationinstructionsforthesystem.

note

riskofdamagetotheproductduetothepowersupply

• Shutdownandisolatetheelectricalpowersourcebeforecarryingoutworkonthesystem.

note

riskofdamagetotheproductduetotheenvironment

• Protecttheproductagainstelectromagneticinterference,ultravioletraysand,wheninstalledoutdoors,theeffectsoftheclimaticconditions.

7.2 Mounting the product on the backplane

TheproductispluggedinthebackplaneofthesystemType8905.

4

3

3

1. Drythesurfaceofthebackplanethatwillbeincontactwiththeproduct.

2. Drythesurfaceoftheproduct.

3. Whilethepush-buttonispushed,turnthebayonetlevertotheright,

ontheunlockedposition,.Donotpushthelevertothemaintenanceposition.

4. Insertthetwoadaptationpinsintheirholesandthenplugtheproductinthebackplane.

5. Whilethepush-buttonispushed,turnthebayonetlevertotheleft,

onthelockedposition, .

Fig. 2: Mounting a product on the backplane of the system

English

Type MS03

Page 13: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

11

Adjustment and operation

8 ADjuSTMenT AnD operATion

8.1 Safety instructions

note

riskofdamagetotheproductduetonon-conformingadjustment.

• TheoperatorsinchargeofadjustmentmusthavereadandunderstoodthecontentsoftheseOperatingInstructions.

• TheoperatorsinchargeofadjustmentmusthavereadandunderstoodthecontentsoftheOperatingInstruc-tionsofthedisplaysoftwaretypeME21and/orthecontentsoftheOperatingInstructionsoftheBürkertCommunicatorsoftwaretype8920and/ortheOperatingInstructionsofthecontrollermoduletypeME25.

• Inparticular,observethesafetyrecommendationsandintendeduse.

• Theproduct/installationmustonlybeadjustedbysuitablytrainedstaff.

note

riskofdamagetotheproductduetonon-conformingcommissioning.

• Beforecommissioning,makesurethatthestaffinchargehavereadandfullyunderstoodthecontentsoftheseOperatingInstructions.

• Inparticular,observethesafetyrecommendationsandintendeduse.

• Theproduct/theinstallationmustonlybecommissionedbysuitablytrainedstaff.

note

riskofdamagetotheproductduetonon-conformingoperation.

• TheoperatorsinchargeofoperationmusthavereadandunderstoodthecontentsoftheseOperatingInstructions.

• Inparticular,observethesafetyrecommendationsandintendeduse.

• Theproduct/installationmustonlybeoperatedbysuitablytrainedstaff.

8.2 how to adjust the product

Theadjustmentoftheproductcanbemade:

• eitherwiththedisplayofthesystemtype8905.ThedisplayofthesystemismanagedbythesoftwaretypeME21.Seechap.8.4.

• orwithaPCandtheBürkertCommunicatorsoftwaretype8920.Togetgeneralinformationaboutthesoftwaretype8920,refertotheOperatingInstructionsofthetype8920.

English

Type MS03

Page 14: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

12

Adjustment and operation

8.3 Adjustments that must be done

Dotheadjustments:

• aftertheproducthasbeeninstalledinthesystem.

• afterthefluidicandelectricalinstallationshavebeenmadeonthesystem.

• afterthetightnessofthesystemhasbeenchecked.

• afterthesystemhasoperatedforapolarizationtimeof12hours.

• Beforecommissioningtheproduct/systemforthefirsttimeandforthecorrectoperationoftheproductandofthesystem,calibratethecellconstantoftheconductivitysensor.Refertochap.8.10.1.

• Calibratetheproducteverythreemonths.

8.4 general information on the display software type Me21

TheseOperatingInstructionsexplaintheadjustmentsthatarespecifictotheproducttypeMS03.

→ TogetgeneralinformationaboutthedisplaysoftwaretypeME21,refertotheOperatingInstructionsofthetypeME21thatisontheCDdeliveredwiththesystem.

TheOperatingInstructionsofthedisplaysoftwaretypeME21:

• givegeneralinformationonthesoftware,suchas:descriptionoftheuserinterface,structureofthemenus,descriptionofthepossibleviews("Device"viewforexample),descriptionofthenavigationbuttons...

• explainhowtomakethegeneraladjustmentssuchas:thedisplaylanguage,thelocatingoftheproduct...

• explainhowtoconfigureandcustomizethe"Desktop"viewswithvaluesorgraphs.

• givegeneralinformationontheerrormessagesandtheoperatingofthesystemstatuslight.

English

Type MS03

Page 15: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

13

Adjustment and operation

8.5 "Device" view of the product

The"Device"viewshowssomeofthemeasurementdatarelatedtotheproduct.

→ Ifthedisplayshowsa"Desktop"view,tap toaccessthe"Device"view.

→ Todisplaythe"Device"viewoftheproduct,selecttheproductinthelistofdevicesontheleftofthedisplay.

Controller

5648320001

Device 5648320001

Location TreatmentunitNr1 Status N/A

Conductivity 0.00µS/cm Resistivity 2000.00W.m

Temperature 24.10°CBoardtemperature 26.20°C

Deviceview

HMIU

12.08.201416:55

EC

ListofdevicesthatareconnectedtothebüS

Thefollowingdatacanbereadfromthe"Device"viewoftheproduct:

• thedevicesthatareconnectedonthebüSwiththeir"Uniquedevicename".Bydefault,the"Uniquedevicename"isbuiltupwithtwonumbers:theordercodeoftheproduct(forexample564832,fortheconductivitysensorcube)andtheseriesnumber(0001,forexample).

• wheretheproductisgeographicallylocated.

• themeasuredvalueoftheconductivityofthewatersample.

• themeasuredvalueoftheresistivityofthewatersample.

• themeasuredvalueofthetemperatureofthewatersample.

• themeasuredvalueofthetemperatureoftheinternalmeasurementboard.

Table 1: "Device" view of the product

→ Todisplaythe"Function"viewoftheproduct,tap .

English

Type MS03

Page 16: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

14

Adjustment and operation

8.6 "function" view of the product

The"Function"viewshowsthefunctionsavailableforaproductand,foreachfunction,themaindatarelatedtoeachfunction.

Todisplaythe"Function"viewoftheproduct:

1. selecttheproductinthelistofdevices,ontheleftofthedisplay,

2. tap .

büS

function büS

Uniquedevicename 5648320001 Location TreatmentUnitNr1

Description Springwater

ConductivitySensor5648320001 12.08.201416:55

CL2 Sensor

"function"viewofthebüs

→ Todisplaythe"Function"viewofthebüStheproductisconnectedto,select"büS"inthelistofdevicesontheleftofthedisplay.

→ Tap toaccessthe"Parameter"view.Seechap.8.7.

Sensor

function Sensor

Conductivity 0.00µS/cm Resistivity 2000.00W.m

Cellconstant 0.94

Temperature 24.10°COffset 0.00°C

ConductivitySensor5648320001 12.08.201416:55

büS

Cl2

"function"viewofthesensor

→ Todisplaythe"Function"viewofthesensor,select"Sensor"inthelistofdevicesontheleftofthedisplay.

→ Tap toaccessthe"Parameter"view.Seechap.8.8.

Table 2: "Function" view of the product

English

Type MS03

Page 17: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

15

Adjustment and operation

8.7 Detailed views of the büS function

Table 3: "Parameter" view of the "büS" function

parameter büS

BasicSettings UniqueDeviceName 5648320001

TreatmentUnitNr1

0

0

Location

Description

Physicalgroup

Logicalgroup

Conductivitysensor5648320001 04.04.201412:21

Groupingsettings

"parameter"detailedviewofthebüs

Tosettheuser-specificdatafortheidentificationofthedeviceonthebüS:

• UniqueDeviceNameoftheproduct.

→ MakesureyouchooseauniquenamefortheproductbecausethebüSmustrecognizetheproduct.

→ Makesureyouchooseauniquenamethatisselfexplanatorytoidentifytheproductbecause,iftheuniquenameischanged,allthesettingsmadeonthebüSmustbechanged.

• Description

• Location

• Groupingsetting

Table 4: "Diagnosis" view of the "büS" function

Diagnosis büS

büSinformation Address 126

500kbit/s

Conductivitysensor

564832

683328

A.00.02.42

A.01.00.00

Baudrate

Devicename

Identitynumber

Softwareidentitynumber

Softwareversion

Hardwareversion

Conductivitysensor5648320001 04.04.201412:21

Deviceinformation

"Diagnosis"detailedviewofthebüs

ToreadsomebüSdataanddevicedata:

• Addressandbaudrate

• Devicenameanddeviceordercode(Identitynumber)

• Softwareandhardwareinformation

• InformationrelatingtotheTFT

• Devicedriverinformation

Nochangesbyuserarepossible.

English

Type MS03

Page 18: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

16

Adjustment and operation

Table 5: "Maintenance" view of the "büS" function

Maintenance büS

Resettypes Device Reset

Conductivitysensor5648320001 12:21:16"maintenance"detailedviewofthebüs

Restarttheproductforareset.

8.8 "parameter" view of the sensor

→ Inthe"Function"view,tap toaccessthe"Parameter"view.

parameter Sensor

Temperature Desiredunit °C

W.cmDesiredunit

Warnings

Errors

Messagestriggers

ConductivitySensor5648320001 12:21:16

Conductivity

Resistivity

12sResponsetimeFilter

Desiredunit mS/cm

CompensationType

Linearcompensation

OFF

0%

The"Parameter"viewofthesensormakesitpossible:

• tochangetheunitsofthedisplayedconductivityvalue.

• tochoosethetypeoftemperaturecompensationtodeterminetheconductivityofthewatersample,seechap.8.8.1.

• ifalineartemperaturecompensationischosen,tosetthecompensationcoefficient,seechap.8.8.1.

• tochangetheunitsoftheresistivitymeasuredbytheconductivitycell.

• tochangetheunitsofthedisplayedtemperature.

• toenterthevalueoftheT10-90responsetimeforthemeasuredsignal.

• toconfigurethetriggeringofthewarnings,seechap.8.8.2.

• toconfigurethetriggeringoftheerrors,seechap.8.8.3.

Table 6: "Parameter" view of the sensor

8.8.1 Setting the temperature compensation

Todeterminethecorrectvalueoftheconductivityofthewatersample,thetemperatureofthewatersampleshouldbecompensated.

Alineartemperaturecompensationmaybesufficientlyaccurateforyourprocess,providedthetemperatureofyourprocessisalwaysabove0°C.Enteracompensationbetween0.00and9.99%/°C.

Forexample,thelinearcompensationfordrinkingwaterisabout2%/°C.Usethefollowinggraphandequationtocalculatethemeanvalueofthecompensationcoefficientaaccordingto

English

Type MS03

Page 19: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

17

Adjustment and operation

atemperaturerangeDTandtheassociatedconductivityrangeDc:

χ

χ25

25 T [°C]

∆χ

∆T

T

χT

α =

χ25

∆χ

∆Τx

1

Fig. 3: Linear compensation curve of the temperature

Bydefault,thetemperatureisnotcompensated("CompensationType"setto"OFF").

Procedure:

1. Tapconductivity compensationtype inthe"Parameter"viewofthesensor.

Thetemperaturecompensationcanbe:

• eitherlinear(choose"Linear%"),

• oraccordingtothesodiumchloridelaw(choose"NaCl").

2. Selectthetypeofcompensationandvalidate.

3. Ifthecompensationtype"Linear"ischosen,tapconductivity linearcompensation inthe"Parameter"viewofthesensor,andentertheneededcompensationcoefficient.

4. Validate.

8.8.2 configuring the triggering of the warnings

Thevaluesofsomeprocessvariablescanbemonitoredtodetectaproblemintheprocessoronthesensor.

Fortheconductivitysensorcube,thefollowingvaluescanbemonitored:

• theconductivityvalueofthewatersample,

• thetemperatureofthewatersample.

Procedure:

1. TapWarnings inthe"Parameter"viewofthesensor.

2. TapActivationflags inthe"SensorParameter"view.

3. Selecttheprocessvariablestobemonitoredandvalidate.

4. Settheminimumand/ormaximumthresholdvalues.

Whentheparameteredthresholdvaluesarereachedandtheactivationflagoftherelatedprocessvariableis

selected,awarningmessageisgeneratedinthe"MessagesList":tap toaccessthe"MessagesList".Seechap.9.3forthetroubleshootingdetails.

English

Type MS03

Page 20: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

18

Adjustment and operation

8.8.3 configuring the triggering of the errors

Thevaluesofsomeprocessvariablescanbemonitoredtodetectaproblemintheprocessoronthesensor.

Fortheconductivitysensorcube,thefollowingvaluescanbemonitored:

• theconductivityvalueofthewatersample,

• thetemperatureofthewatersample.

Procedure:

1. Taperrors inthe"Parameter"viewofthesensor.

2. TapActivationflags inthe"SensorParameter"view.

3. Selecttheprocessvariablestobemonitoredandvalidate.

4. Settheminimumand/ormaximumthresholdvalues.

Whentheparameteredthresholdvaluesarereachedandtheactivationflagoftherelatedprocessvariableor

sensorvalueisselected,anerrormessageisgeneratedinthe"MessagesList":tap toaccessthe"Mes-sagesList".Seechap.9.3forthetroubleshootingdetails.

8.9 "Diagnosis" view of the sensor

The"Diagnosis"viewmakesitpossibletoreadthefollowingvalues:

• themeasuredvalueoftheconductivityvalueofthewatersample.

• themeasuredvalueoftheresistivityvalueofthewatersample.

• thecellconstantoftheconductivitysensor.

• themeasuredvalueofthewatersampletemperature.

• thetemperatureoffsetthathasbeenenteredinthe"Maintenance"viewofthesensor.

• themeasuredvalueofthetemperatureofthemeasurementboard.

• thetimetheproducthasalreadyoperated.

• thecalibrationlimitsofthecellconstantoftheconductivitysensor.

→ Fromthe"Parameter"viewofthesensor,tap toaccessthe"Diagnosis"view.

8.10 "Maintenance" view of the sensor

The"Maintenance"viewmakesitpossible:

• tomodifythecellconstantoftheconductivitysensor,

• tocalibratetheproduct,withthecalibrationwizard,i.e.automaticallydeterminethecellconstantoftheconduc-tivitysensor,

• tomodifythevalueofthetemperatureoffsetofthewatersample,

English

Type MS03

Page 21: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

19

Adjustment and operation

• tochecktheoperatingoftheproductbysimulatingsomedata,

• toreadthedateofthelastcalibration,

• toreadthedateofthenextduecalibration,

• tosetthenumberofdaysbetweentwocalibrations.

→ Fromthe"Parameter"viewofthesensor,tap toaccessthe"Maintenance"view.

8.10.1 calibrating the cell constant of the conductivity sensor

Tomeasureconductivityvalueswithaslessdeviationaspossibleyoumustcalibratetheconductivitysensor.

Thiscanbedone:

• eitherbyadjustingbyhandthecellconstantoftheconductivitysensor:inthe"Maintenance"viewofthesensor,tapconductivitycellconstant andenterthevalueofthecellconstant.

• orbydoinga1pointcalibrationproceduretoautomaticallydeterminethecellconstantoftheconductivitysensor.Seechap.8.10.2.

8.10.2 Doing a 1 point calibration procedure of the conductivity sensor

Dangerduetothenatureofthefluid

▶ Respecttheregulationsonaccidentpreventionandsafetyrelatingtotheuseofaggressivefluids.

Doa1pointcalibrationproceduretoautomaticallyadjustthevalueofthecellconstantoftheconductivitysensor.

1. Connectaperistalticpumpinthewatersampleinletcircuitofthesystem,asshowninFig.4.Ifthefluidicconnectionsarenotdonecorrectly,theproductandthesystemcanbedamagedbecausethepressureintheproductandinthesystemistoohigh.

English

Type MS03

Page 22: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

20

Adjustment and operation

24 VDC

+-

OUT IN

Peristalticpump

Fig. 4: Installation for the calibration of the product in a system type 8905

2. Makesurethedirectionoftheflowiscorrect.

3. Makesurethefluidicinstallationforthecalibrationistight.

4. Letcleanwaterflowthroughthesystemtorinsetheproduct.

5. Prepareareferencesolutionwithaconductivityvalueascloseaspossibletothewatersample.

6. Inthe"Maintenance"viewofthesensor,tapconductivitycalibrationwizard1point .

7. Step1/5:letthereferencesolutionflowthroughthesensor.

8. Tap .

9. Step2/5:tapinputbuffervalue andentertheconductivityvalueofthereferencesolution.

10. Validate.

11. Tap .

12. Step3/5:whenthemeasurementoftheconductivityvalueisstable,tap .

13. Step4/5:

English

Type MS03

Page 23: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

21

Adjustment and operation

• ifthecalibrationhassucceeded,thecalculatedcellconstantisdisplayedandthedateofthelastcalibrationis

updated(seechap.8.10.5).Tap togotothestep5/5.

• ifanerrormessageisdisplayed,refertoTable7.

• ifawarningmessageisdisplayed,refertoTable8.

14. Step5/5:validateorcancelthecalibration.

Table 7: Error message at the end of the 1 point calibration of the conductivity sensor

Displayedmessage ComputedcalibrationvalueoutoferrorlimitssymboldisplayedontheuniqueDevicenameoftheproductpossiblecause Thesensorcalibrationhasfailedbecausethecalculatedcellconstant

valueisoutoftheerrorrange.Whattodo? 1. Comparethecalculatedcellconstantvaluewiththecalibration

limitsthatcanbereadinthe"Diagnosis"view.

2. Replacetheproductbyanewone.

Table 8: Warning message at the end of the 1 point calibration of the conductivity sensor

Displayedmessage ComputedcalibrationvalueoutofwarninglimitssymboldisplayedontheuniqueDevicenameoftheproductpossiblecause Thecalculatedcellconstantisoutofthewarningrangebecause:

• eitherawrongsolutionhasbeenusedforthecalibration.

• ortheproductisaging.

Whattodo? 1. Makesurethebuffersolutionusedisthecorrectone.

2. Ifitisnotthecorrectone,abortthecalibration.

3. Useacorrectreferencesolutionanddothecompletecalibrationprocedureagain.

→ Youcanchoosetoeitherval-idateorcancelthecalibration.

• Ifyouvalidatethecalibration,thenewcalculatedcellconstantvalueisusedtodeterminetheconductivityvalue,andthelastcalibrationdateisupdated.

• Ifyoucancelthecalibration,thecurrentcellconstantvalueisusedtodeterminetheconduc-tivityvalue,andthelastcali-brationdateisnotupdated.

→ Plantoreplacetheproduct.

8.10.3 Adjusting the value of the temperature offset

Thetemperaturemeasuredbythesensorcanbecorrectedwithanoffsetvalue.

1. Inthe"Maintenance"viewofthesensor,taptemperatureoffset andenterthevalueofthetem-peratureoffset,inthedisplayedtemperatureunits.

2. Tochangetheunitsofthetemperature,gotothe"Parameter"viewofthesensor,taptemperatureDesiredunit andchoosethetemperatureunits:theoffsetvalueofthetemperatureisautomaticallyconverted.

English

Type MS03

Page 24: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

22

Adjustment and operation

8.10.4 Simulating some data

Checktheoperating(forexample,makesurethewarningand/orerrorlimitsarecorrectlyset)oftheproductand/orprocessbysimulatingsomedata.

1. Inthe"Maintenance"viewofthesensor,tapsimulationstatus andchoose"ON"toactivatethesimulation.

2. Validate.

3. Tosimulateaconductivityvalue,tapsimulationconductivity andentertheconductivityvaluevaluetobesimulated.

4. Tosimulateatemperaturevalue,tapsimulationtemperature andenterthetemperaturevaluetobesimulated.

8.10.5 reading the date of the last calibration

Toreadthedateofthelastcalibrationthathassucceeded.

→ Inthe"Maintenance"viewofthesensor,readthedateinthefieldcalibrationschedulelastcalibration.

8.10.6 reading the date of the next due calibration

Toreadthedateofthenextcalibrationthatmustdone.

→ Inthe"Maintenance"viewofthesensor,readthedateinthefieldcalibrationschedulenextcalibration.

8.10.7 Setting the time interval between two calibrations

Tosetthetimeinterval,indays,betweentwocalibrations:

1. Inthe"Maintenance"viewofthesensor,tapcalibrationscheduleintervalindays .

1. Enterthenumberofdaysbetweentwocalibrations.Werecommendtocalibratetheproducteverythreemonths.

2. Validate.

Whentheduecalibrationdateisreached,awarningmessageisdisplayedintheMessagesList.

English

Type MS03

Page 25: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

23

Maintenance and troubleshooting

9 MAinTenAnce AnD TroubleShooTing

9.1 Safety instructions

Warning

riskofinjuryduetonon-conformingmaintenance.

▶ Maintenancemustonlybecarriedoutbyqualifiedandskilledstaffwiththeappropriatetools.

note

riskofdamagetotheproductduetothepowersupply

• Shutdownandisolatetheelectricalpowersourcebeforecarryingoutworkonthesystem.

9.2 cleaning of the product

danger

riskofinjuryduetothenatureofthedetergent.

▶ Respecttheregulationsonaccidentpreventionandsafetyrelatingtotheuseofaggressivefluids.

Theproductcanbecleanedwithaclothdampenedwithwater(max.40°C)orwithanaciddetergent(withmax.5%ofhydrochloricacid).

9.3 Troubleshouting if no message is displayed

colouroftheproductstatusleD OFF

possiblecause Theproduct/thesystemisnotenergized.

Whattodo? 1. Checkthewiring.

2. Makesurethevoltagesupplyis24VDC.

3. Checkthatthepowersupplysourceisworkingproperly.

9.4 Troubleshooting if the status leD of the product is red or orange

Ifanerrororawarningmessagehasbeengeneratedbythesystem:

• thestatuslightofthesystemisredororange,

• thestatusLEDoftheproductisredororange,

• thesymbol or appearsontheUniqueDeviceNameoftheproduct,inthelistofdevices,

• thesymbol appearsinthetopleftcornerofthedisplay.

English

Type MS03

Page 26: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

24

Maintenance and troubleshooting

→ Tap toaccessthe"MessagesList".

9.4.1 Message "Too high conductivity value"

Displayedmessage ToohighconductivityvaluesymboldisplayedontheuniqueDevicenameoftheproductpossiblecause Theconductivityvalueofthewatersampleisoutofrange.

Themessageisdisplayedwhenthefollowingsettingshavebeenmadeinmessagestriggerserrors ("Parameter"viewofthesensor):

• theerror"activationflag"forthehighthresholdoftheconductivityvalueisselected,

• andthehighthresholdsetfortheconductivityvaluehasbeenreached.

Whattodo? → Checktheprocess.

Displayedmessage ToohighconductivityvaluesymboldisplayedontheuniqueDevicenameoftheproductpossiblecause Theconductivityvalueofthewatersampleisoutofrange.

ThemessageisdisplayedwhenthefollowingsettingshavebeenmadeinmessagestriggersWarnings ("Parameter"viewofthesensor):

• thewarning"activationflag"forthehighthresholdoftheconductivityvalueisselected,

• andthehighthresholdsetfortheconductivityvaluehasbeenreached.

Whattodo? → Checktheprocess.

9.4.2 Message "Too low conductivity value"

Displayedmessage ToolowconductivityvaluesymboldisplayedontheuniqueDevicenameoftheproductpossiblecause Theconductivityvalueofthewatersampleisoutofrange.

Themessageisdisplayedwhenthefollowingsettingshavebeenmadeinmessagestriggerserrors ("Parameter"viewofthesensor):

• theerror"activationflag"forthelowthresholdoftheconductivityvalueisselected,

• andthelowthresholdsetfortheconductivityvaluehasbeenreached.Whattodo? → Checktheprocess.

English

Type MS03

Page 27: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

25

Maintenance and troubleshooting

Displayedmessage ToolowconductivityvaluesymboldisplayedontheuniqueDevicenameoftheproductpossiblecause Theconductivityvalueofthewatersampleisoutofrange.

ThemessageisdisplayedwhenthefollowingsettingshavebeenmadeinmessagestriggersWarnings ("Parameter"viewofthesensor):

• thewarning"activationflag"forthelowthresholdoftheconductivityvalueisselected,

• andthelowthresholdsetfortheconductivityvaluehasbeenreached.Whattodo? → Checktheprocess.

9.4.3 Message "Too high temperature value"

Displayedmessage ToohightemperaturevaluesymboldisplayedontheuniqueDevicenameoftheproductpossiblecause Thetemperaturevalueofthewatersampleisoutofrange.

Themessageisdisplayedwhenthefollowingsettingshavebeenmadeinmessagestriggerserrors ("Parameter"viewofthesensor):

• theerror"activationflag"forthehighthresholdofthewatersampletemperaturevalueisselected,

• andthehighthresholdsetforthewatersampletemperaturevaluehasbeenreached.

Whattodo? → Checktheprocess.

Displayedmessage ToohightemperaturevaluesymboldisplayedontheuniqueDevicenameoftheproductpossiblecause Thetemperaturevalueofthewatersampleisoutofrange.

ThemessageisdisplayedwhenthefollowingsettingshavebeenmadeinmessagestriggersWarnings ("Parameter"viewofthesensor):

• thewarning"activationflag"forthehighthresholdofthewatersampletemperaturevalueisselected,

• andthehighthresholdsetforthewatersampletemperaturevaluehasbeenreached.

Whattodo? → Checktheprocess.

English

Type MS03

Page 28: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

26

Maintenance and troubleshooting

9.4.4 Message "Too low temperature value"

Displayedmessage ToolowtemperaturevaluesymboldisplayedontheuniqueDevicenameoftheproductpossiblecause Thetemperaturevalueofthewatersampleisoutofrange.

Themessageisdisplayedwhenthefollowingsettingshavebeenmadeinmessagestriggerserrors ("Parameter"viewofthesensor):

• theerror"activationflag"forthelowthresholdofthewatersampletemperaturevalueisselected,

• andthelowthresholdsetforthewatersampletemperaturevaluehasbeenreached.

Whattodo? → Checktheprocess.

Displayedmessage ToolowtemperaturevaluesymboldisplayedontheuniqueDevicenameoftheproductpossiblecause Thetemperaturevalueofthewatersampleisoutofrange.

ThemessageisdisplayedwhenthefollowingsettingshavebeenmadeinmessagestriggersWarnings ("Parameter"viewofthesensor):

• thewarning"activationflag"forthelowthresholdofthewatersampletemperaturevalueisselected,

• andthelowthresholdsetforthewatersampletemperaturevaluehasbeenreached.

Whattodo? → Checktheprocess.

English

Type MS03

Page 29: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

27

Spare parts and accessories

10 SpAre pArTS AnD AcceSSorieS

caution

riskofinjuryand/ordamagecausedbytheuseofunsuitableparts.

Incorrectaccessoriesandunsuitablereplacementpartsmaycauseinjuriesanddamagetheproductandthesurroundingarea.

▶ UseonlyoriginalaccessoriesandoriginalreplacementpartsfromBürkert.

11 pAckAging, TrAnSporT

note

Damageduetotransport

Transportmaydamageaninsufficientlyprotectedproduct.

• Transporttheproductinshock-resistantpackagingandawayfromhumidityanddirt.

• Donotexposetheproducttotemperaturesthatmayexceedtheadmissiblestoragetemperaturerange.

• Protecttheelectricalinterfacesusingprotectiveplugs.

12 STorAge

note

poorstoragecandamagetheproduct.

▶ Tostoretheproduct:

1. Rinsetheproductwithtapwater.

2. Purgetheproductwithairatamax.pressureof2bar.

3. Storetheproductatroomtemperature(about23°C±10°C).

4. Storetheproductinadryplaceawayfromdust.

▶ Afterastorageperiod:

1. Plugtheproductinthesystem.

2. WhilethepowersupplyofthesystemisOFF,letthewatersampleflowthroughtheproductforatleast2hours.

3. Calibratetheproduct.Seechap.8.8.

English

Type MS03

Page 30: Type MS03 - Burkert USAinstallations and the environment. The product is intended solely for the measurement of the conductivity of the water within a 8905 system. This product must

28

Disposal of the product

13 DiSpoSAl of The proDucT→ Disposeoftheproductanditspackaginginanenvironmentally-friendlyway.

noteDamagetotheenvironmentcausedbyproductscontaminatedbyfluids.

• Keeptotheexistingprovisionsonthesubjectofwastedisposalandenvironmentalprotection.

note:

Complywiththenationaland/orlocalregulationswhichconcerntheareaofwastedisposal.

English

Type MS03