Pr oduct B ul le t in: 42 - 82 4 Application The Type CLC is designed for high current metering on low voltage systems and is available in single or double ratios. It is suitable for use with un-insulated bus bar or cable up to 600 volts, or with insulated primary conductors at higher voltages. CLC current transformers are UL recognized - File No. E96461. Construction Features The ring type core and fully distributed winding are assembled to a glass filled polypropylene window liner and injection molded in thermoplastic rubber. Large clamp type terminals are equipped with slotted hex head tightening screws. A rotatable shorting bar is positioned on a center post located midway between the terminals. The center post also serves as a third terminal on double ratio transformers. A clear polycarbonate cover allows a visual check of connections. The cover is keyed to the shorting bar to insure proper installation and can be sealed with a sealing wire. Four piece mounting feet or single piece bases are available. These are constructed of marine environment resistant aluminum with an electrocoat and baked finish of gray acrylic paint. The CLC may also be secured to a wall panel or bracket by means of mounting holes through the transformer body. Micarta® window plates are used to change the window opening to a cruciform configuration, for direct bus bar sleeve mounting. Primary bar assemblies are available for converting the CLC to a bar type unit. These assemblies vary from a single bar for currents up to 1500 amperes, to a four bar assembly for 4000 amperes. Type CLC Current Transformer Low Voltage Instrument Transformer 600 Volt Indoor or Outdoor, 10 kV BIL Primary Amperes 600-4000 25 through 60 Hertz

Upload: votuyen

Post on 06-Feb-2018

232 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Type CLC Current Transformer - ABB Group · PDF filePrimary bar assemblies are available for converting the CLC to a bar type unit. ... B0.2 B0.5 B0.9 ANSI Relay-ing Accu-racy Class

Product Bulletin:

42-824

Application The Type CLC is designed for high current metering on low voltage systems and is available in single or double ratios. It is suitable for use with un-insulated bus bar or cable up to 600 volts, or with insulated primary conductors at higher voltages. CLC current transformers are UL recognized - File No. E96461. Construction Features The ring type core and fully distributed winding are assembled to a glass filled polypropylene window liner and injection molded in thermoplastic rubber. Large clamp type terminals are equipped with slotted hex head tightening screws. A rotatable shorting bar is positioned on a center post located midway between the terminals. The center post also serves as a third terminal on double ratio transformers. A clear polycarbonate cover allows a visual check of connections. The cover is keyed to the shorting bar to insure proper installation and can be sealed with a sealing wire. Four piece mounting feet or single piece bases are available. These are constructed of marine environment resistant aluminum with an electrocoat and baked finish of gray acrylic paint. The CLC may also be secured to a wall panel or bracket by means of mounting holes through the transformer body. Micarta® window plates are used to change the window opening to a cruciform configuration, for direct bus bar sleeve mounting. Primary bar assemblies are available for converting the CLC to a bar type unit. These assemblies vary from a single bar for currents up to 1500 amperes, to a four bar assembly for 4000 amperes.

Type CLC Current Transformer

Low Voltage Instrument Transformer 600 Volt Indoor or Outdoor, 10 kV BIL

Primary Amperes 600-4000 25 through 60 Hertz

Page 2: Type CLC Current Transformer - ABB Group · PDF filePrimary bar assemblies are available for converting the CLC to a bar type unit. ... B0.2 B0.5 B0.9 ANSI Relay-ing Accu-racy Class

Product Bulle

tin:

42-824

Selector Guide

ANSI

Metering Accuracy

CLC Without

Mounting Feet Style

Number

CLC With Window

Plate Style

Number

Primary Ampere Rating

B0.2 B0.5 B0.9

ANSI Relay-

ing Accu-racy

Class

Rating Factor

7524A58G01 7524A61G01 800 0.3 0.3 C 30 2.00

7524A58G02 7524A61G02 1000 0.3 0.3 C 50 2.00

7524A58G03 7524A61G03 1200 0.3 0.3 0.3 C 30 2.00

B1.8

CLC With 4 Piece

Mounting Feet Style

Number

CLC With 1 Piece

Base Feet Style

Number

7524A59G01 7524A60G01

7524A59G02 7524A60G02

7524A59G03 7524A60G03

7524A58G04 7524A59G04 7524A60G04 7524A61G04 1500 0.3 0.3 0.3 C 30 3.00

7524A58G05 7524A59G05 7524A60G05 7524A61G05 2000 0.3 0.3 0.3 0.3 C 50 2.00

7524A58G06 7524A59G06 7524A60G06 7524A61G06 3000 0.3 0.3 0.3 0.3 C 10 1.33

7524A58G07 7524A59G07 7524A60G07 7524A61G07 4000 0.3 0.3 0.3 0.3 1.33

7524A58G08 7524A59G08 7524A60G08 7524A61G08 600/1200 0.3 X 0.3 0.3 0.3 0.3 C 10/C 30 3.00/2.00

7524A58G09 7524A59G09 7524A60G09 7524A61G09 800/1600 0.3 X 0.3

0.3

0.3

0.3 C 20/C 30 3.00/2.00

7524A58G10 7524A59G10 7524A60G10 7524A61G10 1000/2000 0.3 X 0.3

0.3 X 0.3

0.3

0.3 C 30/C 50 3.00/2.00

7524A58G11 7524A59G11 7524A60G11 7524A61G11 1500/3000 0.3 X 0.3

0.3 X 0.3

0.3 X 0.3

0.3 -/C 10 2.00/1.33

7524A58G12 7524A59G12 7524A60G12 7524A61G12 2000/4000 0.3 X 0.3

0.3 X 0.3

0.3 X 0.3

0.3 X 0.3 2.00/1.33

Optional Accessories • Mounting Feet-Set of 4 with Hardware 9628A05G20 • One Piece Base 9628A05G21 • Window Plate-One required 9628A05G22 • Primary Bar Assemblies

⇒800-1500 Amperes-1 Bar 9628A05G23 ⇒2000 Amperes-2 Bars 9628A05G24 ⇒3000 Amperes-3 Bars 9628A05G25 ⇒4000 Amperes-4 Bars 9628A05G26

X- (X2 - X3 Tap.)

Page 3: Type CLC Current Transformer - ABB Group · PDF filePrimary bar assemblies are available for converting the CLC to a bar type unit. ... B0.2 B0.5 B0.9 ANSI Relay-ing Accu-racy Class

Product Bulletin:

42-824 Dimensions

Page 4: Type CLC Current Transformer - ABB Group · PDF filePrimary bar assemblies are available for converting the CLC to a bar type unit. ... B0.2 B0.5 B0.9 ANSI Relay-ing Accu-racy Class

Product Bulle

tin:

42-824

Page 5: Type CLC Current Transformer - ABB Group · PDF filePrimary bar assemblies are available for converting the CLC to a bar type unit. ... B0.2 B0.5 B0.9 ANSI Relay-ing Accu-racy Class

Product Bulletin:

42-824 Curves B0.1:0.1 Ohm, 90% PF, 60 Hertz, 2.5 VA B0.2:0.2 Ohm, 90% PF, 60 Hertz, 5.0 VA B0.5:0.5 Ohm, 90% PF, 60 Hertz, 12.5 VA

B0.9:0.9 Ohm, 90% PF, 60 Hertz, 22.5 VA B01.8:1.8 Ohm, 90% PF, 60 Hertz, 45.0 VA