type b.3 final submittal government... · 32 12 15.13 hot-mix asphalt airfield paving 32 12 16...

783
C-17 Type III Hydrant Refueling System and Ramp Expansion PN FJRP159073 145th Airlift Wing Charlotte, NC North Carolina Air National Guard Type B.3 Final Submittal Technical Specifications (Vol 2 of 2) Burns & McDonnell Engineering Co., Inc. Kansas City, Missouri October 2017 W9133L-15-D-0003 Delivery Order D301

Upload: others

Post on 20-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

  • C-17 Type III Hydrant Refueling System and Ramp Expansion

    PN FJRP159073

    145th Airlift Wing Charlotte, NC

    North Carolina Air National Guard

    Type B.3 Final Submittal Technical Specifications (Vol 2 of 2)

    Burns & McDonnell Engineering Co., Inc. Kansas City, Missouri

    October 2017

    W9133L-15-D-0003 Delivery Order D301

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    PROJECT TABLE OF CONTENTS

    DI VI SI ON 01 - GENERAL REQUI REMENTS

    01 11 00 SUMMARY OF WORK01 14 00 WORK RESTRI CTI ONS01 20 00. 00 20 PRI CE AND PAYMENT PROCEDURES01 30 00 ADMI NI STRATI VE REQUI REMENTS01 32 16. 00 20 PROJECT CONSTRUCTI ON PROGRESS SCHEDULES01 33 00 SUBMI TTAL PROCEDURES01 33 23. 33 AVI ATI ON FUEL SYSTEM SPECI FI C SUBMI TTAL REQUI REMENTS01 33 29 SUSTAI NABI LI TY REPORTI NG01 35 13 SPECI AL PROJECT PROCEDURES01 35 26 GOVERNMENTAL SAFETY REQUI REMENTS01 35 29. 13 HEALTH, SAFETY, AND EMERGENCY RESPONSE PROCEDURES FOR

    CONTAMI NATED SI TES01 45 00. 00 20 QUALI TY CONTROL01 45 35 SPECI AL I NSPECTI ONS01 50 00 TEMPORARY CONSTRUCTI ON FACI LI TI ES AND CONTROLS01 57 19 TEMPORARY ENVI RONMENTAL CONTROLS01 74 19 CONSTRUCTI ON AND DEMOLI TI ON WASTE MANAGEMENT01 78 00 CLOSEOUT SUBMI TTALS01 78 23 OPERATI ON AND MAI NTENANCE DATA01 78 23. 33 OPERATI ON AND MAI NTENANCE MANUALS FOR AVI ATI ON FUEL

    SYSTEMS

    DI VI SI ON 02 - EXI STI NG CONDI TI ONS

    02 41 00 DEMOLITION02 61 13 EXCAVATI ON AND HANDLI NG OF CONTAMI NATED MATERI AL02 81 00 TRANSPORTATI ON AND DI SPOSAL OF HAZARDOUS MATERI ALS

    DI VI SI ON 03 - CONCRETE

    03 30 00 CAST- I N- PLACE CONCRETE

    DI VI SI ON 04 - MASONRY

    04 20 00 UNI T MASONRY

    DI VI SI ON 05 - METALS

    05 12 00 STRUCTURAL STEEL05 40 00 COLD- FORMED METAL FRAMI NG05 50 13 MI SCELLANEOUS METAL FABRI CATI ONS05 59 10 ROLLI NG COVER FOR AVI ATI ON REFUELI NG VAULTS

    DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES

    06 10 00 ROUGH CARPENTRY

    DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON

    07 11 13 BI TUMI NOUS DAMPPROOFI NG07 21 13 BOARD AND BLOCK I NSULATI ON07 27 26 FLUI D- APPLI ED AI R AND VAPOR BARRI ERS07 60 00 FLASHI NG AND SHEET METAL07 61 14. 00 20 STEEL STANDI NG SEAM ROOFI NG07 84 00 FIRESTOPPING

    PROJECT TABLE OF CONTENTS Page 1

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    07 92 00 JOI NT SEALANTS

    DI VI SI ON 08 - OPENI NGS

    08 11 13 STEEL DOORS AND FRAMES 08 51 13 ALUMI NUM WI NDOWS08 71 00 DOOR HARDWARE08 81 00 GLAZING08 91 00 METAL WALL LOUVERS

    DI VI SI ON 09 - FI NI SHES

    09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD09 29 00 GYPSUM BOARD09 51 00 ACOUSTI CAL CEI LI NGS09 65 00 RESI LI ENT FLOORI NG09 77 20 DECORATI VE FI BERGLASS REI NFORCED WALL PANELS09 90 00 PAI NTS AND COATI NGS09 96 00 HI GH- PERFORMANCE COATI NGS09 97 13. 17 THREE COAT EPOXY I NTERI OR COATI NG OF WELDED STEEL

    PETROLEUM FUEL TANKS09 97 13. 27 EXTERI OR COATI NG OF STEEL STRUCTURES

    DI VI SI ON 10 - SPECI ALTI ES

    10 14 00. 20 I NTERI OR/ EXTERI OR SI GNAGE10 28 13 TOI LET ACCESSORI ES10 44 16 FI RE EXTI NGUI SHERS

    DI VI SI ON 13 - SPECI AL CONSTRUCTI ON

    13 34 19 METAL BUI LDI NG SYSTEMS13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT13 48 00. 00 10 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT13 73 19 JET BLAST DEFLECTOR FENCE FOR HI GH POWER RUN- UP VELOCI TI ES

    DI VI SI ON 22 - PLUMBI NG

    22 00 00 PLUMBI NG, GENERAL PURPOSE

    DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)

    23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS23 03 00. 00 20 BASI C MECHANI CAL MATERI ALS AND METHODS23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS23 82 02. 00 10 UNI TARY HEATI NG AND COOLI NG EQUI PMENT23 82 46. 00 40 ELECTRI C UNI T HEATERS

    DI VI SI ON 26 - ELECTRI CAL

    26 00 00. 00 20 BASI C ELECTRI CAL MATERI ALS AND METHODS26 05 48. 00 10 SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT26 08 00 APPARATUS I NSPECTI ON AND TESTI NG26 12 19. 10 THREE- PHASE PAD- MOUNTED TRANSFORMERS26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM26 24 13 SWITCHBOARDS26 28 01. 00 10 COORDI NATED POWER SYSTEM PROTECTI ON26 32 15. 00 10 DI ESEL- GENERATOR SET STATI ONARY 100- 2500 KW, WI TH

    AUXILIARIES

    PROJECT TABLE OF CONTENTS Page 2

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    26 36 00. 00 10 AUTOMATI C TRANSFER SWI TCH AND BY- PASS/ I SOLATI ON SWI TCH26 41 00 LI GHTNI NG PROTECTI ON SYSTEM26 42 19. 00 10 CATHODI C PROTECTI ON BY I MPRESSED CURRENT 26 51 00 I NTERI OR LI GHTI NG26 56 00 EXTERI OR LI GHTI NG

    DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY

    28 31 64. 00 10 FI RE DETECTI ON AND ALARM SYSTEM, ADDRESSABLE

    DI VI SI ON 31 - EARTHWORK

    31 00 00 EARTHWORK31 11 00 CLEARI NG AND GRUBBI NG31 24 00 SETTLEMENT MONI TORI NG31 32 11 SOI L SURFACE EROSI ON CONTROL31 36 00 WI RE MESH GABI ONS31 63 26 DRI LLED SHAFTS

    DI VI SI ON 32 - EXTERI OR I MPROVEMENTS

    32 01 16. 71 COLD MI LLI NG ASPHALT PAVI NG32 01 19 FI ELD MOLDED SEALANTS FOR SEALI NG JOI NTS I N RI GI D

    PAVEMENTS32 05 33 LANDSCAPE ESTABLI SHMENT32 11 23 GRADED- CRUSHED AGGREGATE BASE COURSE32 12 10 BI TUMI NOUS TACK AND PRI ME COATS32 12 15. 13 HOT- MI X ASPHALT AI RFI ELD PAVI NG32 12 16 HOT- MI X ASPHALT ( HMA) FOR ROADS32 13 11 CONCRETE PAVEMENT FOR AI RFI ELDS AND OTHER HEAVY- DUTY

    PAVEMENTS32 16 13 CONCRETE SI DEWALKS AND CURBS AND GUTTERS32 17 23 PAVEMENT MARKI NGS32 31 13 CHAI N LI NK FENCES AND GATES32 32 23 MECHANI CALLY STABI LI ZED EARTH RETAI NI NG WALL32 92 19 SEEDING

    DI VI SI ON 33 - UTI LI TI ES

    33 08 53 AVI ATI ON FUEL DI STRI BUTI ON SYSTEM START- UP33 09 53 AVI ATI ON FUEL PUMP CONTROL AND ANNUNCI ATI ON SYSTEM33 11 00 WATER UTI LI TY DI STRI BUTI ON PI PI NG33 30 00 SANI TARY SEWERS AND CONTAI NMENT DRAI NS33 40 00 STORM DRAI NAGE UTI LI TI ES33 52 43. 11 AVI ATI ON FUEL MECHANI CAL EQUI PMENT33 52 43. 13 AVI ATI ON FUEL PI PI NG33 52 43. 14 AVI ATI ON FUEL CONTROL VALVES33 52 43. 23 AVI ATI ON FUEL PUMPS33 52 43. 28 FI LTER SEPARATOR, AVI ATI ON FUELI NG SYSTEM33 52 80 LI QUI D FUELS PI PELI NE COATI NG SYSTEMS33 52 90. 00 20 WELDI NG FOR POL SERVI CE PI PI NG33 56 10 FACTORY- FABRI CATED FUEL STORAGE TANKS33 56 13. 13 STEEL TANKS WI TH FI XED ROOFS33 56 19 FUEL I MPERMEABLE LI NER SYSTEM33 65 00 CLEANI NG PETROLEUM STORAGE TANKS33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP)

    DI VI SI ON 34 - TRANSPORTATI ON

    PROJECT TABLE OF CONTENTS Page 3

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    34 73 16 JET BLAST DEFLECTOR FENCE FOR HI GH POWER RUN- UP VELOCI TI ES

    - - End of Pr oj ect Tabl e of Cont ent s - -

    PROJECT TABLE OF CONTENTS Page 4

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    SECTI ON 26 24 13

    SWITCHBOARDS05/15

    PART 1 GENERAL

    1. 1 REFERENCES

    The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by t he basi c desi gnat i on onl y.

    AMERI CAN NATI ONAL STANDARDS I NSTI TUTE ( ANSI )

    ANSI C12. 1 ( 2008) El ect r i c Met er s Code f or El ect r i c i t y Met er i ng

    ASTM I NTERNATI ONAL ( ASTM)

    ASTM A780 ( 2009; R 2015) St andar d Pr act i ce f or Repai r of Damaged and Uncoat ed Ar eas of Hot - Di p Gal vani zed Coat i ngs

    ASTM D1535 ( 2014) Speci f y i ng Col or by t he Munsel l System

    ASTM D709 ( 2016) St andar d Speci f i cat i on f or Lami nat ed Ther moset t i ng Mat er i al s

    I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

    I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms

    I EEE C2 ( 2017) Nat i onal El ect r i cal Saf et y Code

    I EEE C37. 90. 1 ( 2013) St andar d f or Sur ge Wi t hst and Capabi l i t y ( SWC) Test s f or Rel ays and Rel ay Syst ems Associ at ed wi t h El ect r i c Power Appar at us

    I NTERNATI ONAL ELECTRI CAL TESTI NG ASSOCI ATI ON ( NETA)

    NETA ATS ( 2013) St andar d f or Accept ance Test i ng Speci f i cat i ons f or El ect r i cal Power Equi pment and Syst ems

    NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

    ANSI / NEMA PB 2. 1 ( 2013) Gener al I nst r uct i ons f or Pr oper Handl i ng, I nst al l at i on, Oper at i on and Mai nt enance of Deadf r ont Di st r i but i on Swi t chboar ds Rat ed 600 V or Less

    NEMA I CS 6 ( 1993; R 2011) I ndust r i al Cont r ol and Syst ems: Encl osur es

    SECTI ON 26 24 13 Page 1

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    NEMA PB 2 ( 2011) Deadf r ont Di st r i but i on Swi t chboar ds

    NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

    NFPA 70 ( 2017) Nat i onal El ect r i cal Code

    UNDERWRI TERS LABORATORI ES ( UL)

    UL 489 ( 2016) UL St andar d f or Saf et y Mol ded- Case Ci r cui t Br eaker s, Mol ded- Case Swi t ches and Ci r cui t - Br eaker Encl osur es

    UL 891 ( 2005; Repr i nt Oct 2012) Swi t chboar ds

    1. 2 RELATED REQUI REMENTS

    Sect i on 26 08 00 APPARATUS I NSPECTI ON AND TESTI NG appl i es t o t hi s Sect i on, wi t h t he addi t i ons and modi f i cat i ons speci f i ed her ei n.

    1. 3 DEFINITIONS

    Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese speci f i cat i ons, and on t he dr awi ngs, ar e as def i ned i n I EEE 100.

    1. 4 SUBMITTALS

    Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on; submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or QC appr oval . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y eNot ebook, i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

    SD- 02 Shop Dr awi ngs

    Swi t chboar d Dr awi ngs; G

    SD- 03 Pr oduct Dat a

    Swi t chboar d; G

    SD- 06 Test Repor t s

    Swi t chboar d Desi gn Test s; G

    Swi t chboar d Pr oduct i on Test s; G

    Accept ance Checks and Test s; G

    SD- 10 Oper at i on and Mai nt enance Dat a

    Swi t chboar d Oper at i on and Mai nt enance, Dat a Package 5; G

    SD- 11 Cl oseout Submi t t al s

    Assembl ed Oper at i on and Mai nt enance Manual s; G

    Equi pment Test Schedul e; G

    SECTI ON 26 24 13 Page 2

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    Ser vi ce Ent r ance Avai l abl e Faul t Cur r ent Label ; G

    1. 5 QUALI TY ASSURANCE

    1. 5. 1 Pr oduct Dat a

    I ncl ude manuf act ur er ' s i nf or mat i on on each submi t t al f or each component , devi ce and accessor y pr ovi ded wi t h t he swi t chboar d i ncl udi ng:

    a. Ci r cui t br eaker t ype, i nt er r upt i ng r at i ng, and t r i p devi ces, i ncl udi ng avai l abl e set t i ngs.

    b. Manuf act ur er ' s i nst r uct i on manual s and publ i shed t i me- cur r ent cur ves ( i n el ect r oni c f or mat ) of t he mai n secondar y br eaker and l ar gest secondar y f eeder devi ce.

    1. 5. 2 Swi t chboar d Dr awi ngs

    I ncl ude wi r i ng di agr ams and i nst al l at i on det ai l s of equi pment i ndi cat i ng pr oposed l ocat i on, l ayout and ar r angement , cont r ol panel s, accessor i es, pi pi ng, duct wor k, and ot her i t ems t hat must be shown t o ensur e a coor di nat ed i nst al l at i on. I dent i f y c i r cui t t er mi nal s on wi r i ng di agr ams and i ndi cat e t he i nt er nal wi r i ng f or each i t em of equi pment and t he i nt er connect i on bet ween each i t em of equi pment . I ndi cat e on t he dr awi ngs adequat e c l ear ance f or oper at i on, mai nt enance, and r epl acement of oper at i ng equi pment devi ces. I ncl ude t he namepl at e dat a, s i ze, and capaci t y on submi t t al . Al so i ncl ude appl i cabl e f eder al , mi l i t ar y, i ndust r y, and t echni cal soci et y publ i cat i on r ef er ences on submi t t al s. I ncl ude t he following:

    a. One- l i ne di agr am i ncl udi ng br eaker s, cur r ent t r ansf or mer s, and met er s.

    b. Out l i ne dr awi ngs i ncl udi ng f r ont el evat i on, sect i on v i ews, f oot pr i nt , and over al l di mensi ons.

    c. Bus conf i gur at i on i ncl udi ng di mensi ons and amper e r at i ngs of bus bar s.

    d. Mar ki ngs and NEMA namepl at e dat a.

    e. Ci r cui t br eaker t ype, i nt er r upt i ng r at i ng, and t r i p devi ces, i ncl udi ng avai l abl e set t i ngs.

    f . Wi r i ng di agr ams and el ement ar y di agr ams wi t h t er mi nal s i dent i f i ed, and i ndi cat i ng pr ewi r ed i nt er connect i ons bet ween i t ems of equi pment and t he i nt er connect i on bet ween t he i t ems.

    g. Manuf act ur er ' s i nst r uct i on manual s and publ i shed t i me- cur r ent cur ves ( i n el ect r oni c f or mat ) of t he mai n secondar y br eaker and l ar gest secondar y f eeder devi ce. Use t hi s i nf or mat i on ( desi gner of r ecor d) t o pr ovi de br eaker set t i ngs t hat ensur es pr ot ect i on and coor di nat i on ar e achieved.

    1. 5. 3 Regul at or y Requi r ement s

    I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " or " must " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Pr ovi de equi pment ,

    SECTI ON 26 24 13 Page 3

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    mat er i al s, i nst al l at i on, and wor kmanshi p i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.

    1. 5. 4 St andar d Pr oduct s

    Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p, and:

    a. Have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng i ncl udi ng appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze.

    b. Have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od.

    c. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, pr ovi de pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t hi s Sect i on.

    1. 5. 4. 1 Al t er nat i ve Qual i f i cat i ons

    Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s furnished.

    1. 5. 4. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e

    Pr oduct s manuf act ur ed mor e t han 1 year pr i or t o dat e of del i ver y t o s i t e ar e not accept abl e.

    1. 6 MAINTENANCE

    1. 6. 1 Swi t chboar d Oper at i on and Mai nt enance Dat a

    Submi t Oper at i on and Mai nt enance Manual s i n accor dance wi t h Sect i on 01 78 23 OPERATI ON AND MAI NTENANCE DATA.

    1. 6. 2 Assembl ed Oper at i on and Mai nt enance Manual s

    Assembl e and secur el y bi nd manual s i n dur abl e, har d cover ed, wat er r esi st ant bi nder s. Assembl e and i ndex t he manual s i n t he f ol l owi ng or der wi t h a t abl e of cont ent s:

    a. Manuf act ur er ' s O&M i nf or mat i on r equi r ed by t he par agr aph SD- 10, OPERATI ON AND MAI NTENANCE DATA.

    b. Cat al og dat a r equi r ed by t he par agr aph SD- 03, PRODUCT DATA.

    c. Dr awi ngs r equi r ed by t he par agr aph SD- 02, SHOP DRAWI NGS.

    d. Pr i ces f or spar e par t s and suppl y l i s t .

    e. I nf or mat i on on met er i ng.

    f . Desi gn t est r epor t s.

    SECTI ON 26 24 13 Page 4

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    g. Pr oduct i on t est r epor t s.

    1. 7 WARRANTY

    Pr ovi de equi pment i t ems t hat ar e suppor t ed by ser v i ce or gani zat i ons r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .

    PART 2 PRODUCTS

    2. 1 PRODUCT COORDI NATI ON

    Pr oduct s and mat er i al s not consi der ed t o be swi t chboar ds and r el at ed accessor i es ar e speci f i ed i n Sect i on 33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON and Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM.

    2. 2 SWITCHBOARD

    NEMA PB 2 and UL 891.

    2. 2. 1 Ratings

    Pr ovi de equi pment wi t h t he f ol l owi ng r at i ngs:

    a. Vol t age r at i ng: 480Y/ 277 vol t s AC, t hr ee- phase, 4- wi r e.

    b. Cont i nuous cur r ent r at i ng of t he mai n bus: 1200 amper es as i ndi cat ed.

    c. Shor t - c i r cui t cur r ent r at i ng: 50k r ms symmet r i cal amper es as i ndi cat ed.

    d. UL l i s t ed and l abel ed as ser v i ce ent r ance equi pment .

    2. 2. 2 Construction

    Pr ovi de t he f ol l owi ng:

    a. Swi t chboar d: Consi st i ng of one ver t i cal sect i on and al i gned as indicated.

    b. Al l c i r cui t br eaker s: Fr ont accessi bl e.

    c. Rear al i gned swi t chboar ds: Fr ont accessi bl e l oad connect i ons.

    d. Wher e i ndi cat ed, " space f or f ut ur e" or " space" means t o i ncl ude a ver t i cal bus pr ovi ded behi nd a bl ank f r ont cover . Wher e i ndi cat ed, " pr ovi s i on f or f ut ur e" means f ul l har dwar e pr ovi ded t o mount a br eaker sui t abl e f or t he l ocat i on.

    e. Compl et el y f act or y engi neer ed and assembl ed, i ncl udi ng pr ot ect i ve devi ces and equi pment i ndi cat ed wi t h necessar y i nt er connect i ons, i nst r ument at i on, and cont r ol wi r i ng.

    2. 2. 2. 1 Enclosure

    Pr ovi de t he f ol l owi ng:

    a. Encl osur e: NEMA I CS 6 Type 1.

    SECTI ON 26 24 13 Page 5

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    b. Encl osur e: Bol t ed t oget her wi t h r emovabl e bol t - on s i de and r ear cover s.

    c. Fr ont door s: Pr ovi ded wi t h padl ockabl e vaul t handl es wi t h a t hr ee poi nt cat ch.

    d. Base: I ncl udes any par t of encl osur e t hat i s wi t hi n 3 i nches of concr et e pad.

    e. Pai nt col or : ASTM D1535 l i ght gr ay No. 61 or No. 49 over r ust inhibitor.

    2. 2. 2. 2 Bus Bar s

    Pr ovi de t he f ol l owi ng:

    a. Bus bar s: Copper wi t h s i l ver - pl at ed cont act sur f aces.

    ( 1) Phase bus bar s: Uni nsul at ed.

    ( 2) Neut r al bus: Rat ed 100 per cent of t he mai n bus cont i nuous cur r ent r at i ng. Neut r al bus f or ser vi ce ent r ance onl y.

    b. Make bus connect i ons and j oi nt s wi t h har dened st eel bol t s.

    c. Mai n- bus ( t hr ough bus) : Rat ed at t he f ul l ampaci t y of t he mai n t hr oughout t he swi t chboar d.

    d. Mi ni mum 1/ 4 by 2 i nch copper gr ound bus secur ed t o each ver t i cal sect i on al ong t he ent i r e l engt h of t he swi t chboar d.

    2. 2. 2. 3 Mai n Sect i on

    Pr ovi de t he mai n sect i on consi st i ng of a combi nat i on sect i on wi t h mol ded- case ci r cui t br eaker s f or t he mai n devi ces as i ndi cat ed.

    2. 2. 3 Pr ot ect i ve Devi ce

    Pr ovi de mai n pr ot ect i ve devi ces as i ndi cat ed.

    2. 2. 3. 1 Mol ded- Case Ci r cui t Br eaker

    Pr ovi de t he f ol l owi ng:

    a. UL 489. UL l i s t ed and l abel ed, st andar d r at ed br anch br eaker s, el ect r i cal l y oper at ed, l ow vol t age mol ded- case ci r cui t br eaker , wi t h a shor t - c i r cui t cur r ent r at i ng of 50k r ms symmet r i cal amper es.

    b. Br eaker f r ame si ze: 1200 amper es.

    c. Ser i es r at ed c i r cui t br eaker s ar e unaccept abl e.

    2. 2. 4 El ect r oni c Tr i p Uni t s

    Equi p mai n br eaker s wi t h a sol i d- st at e t r i ppi ng syst em consi st i ng of t hr ee cur r ent sensor s and a mi cr opr ocessor - based t r i p uni t t hat pr ovi des t r ue r ms sensi ng adj ust abl e t i me- cur r ent c i r cui t pr ot ect i on. I ncl ude t he f ol l owi ng:

    SECTI ON 26 24 13 Page 6

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    a. Cur r ent sensor s amper e r at i ng: The same as t he br eaker f r ame r at i ng.

    b. Tr i p uni t amper e r at i ng: As i ndi cat ed.

    c. El ect r oni c t r i p uni t s: Pr ovi de addi t i onal f eat ur es:

    ( 1) Br eaker s: I ncl ude l ong del ay pi ck- up and t i me set t i ngs, and LED i ndi cat i on of cause of c i r cui t br eaker t r i p.

    ( 2) Mai n br eaker s: I ncl ude shor t del ay pi ck- up and t i me set t i ngs, i nst ant aneous set t i ngs, and gr ound f aul t set t i ngs.

    2. 2. 5 Metering

    2. 2. 5. 1 Di gi t al Met er s

    I EEE C37. 90. 1 f or sur ge wi t hst and. Pr ovi de t r ue r ms, pl us/ mi nus one per cent accur acy, pr ogr ammabl e, mi cr opr ocessor - based met er encl osed i n a seal ed case wi t h t he f ol l owi ng f eat ur es.

    a. Di spl ay capabi l i t y :

    ( 1) Mul t i - Funct i on Met er : Di spl ay a sel ect ed phase t o neut r al vol t age, phase t o phase vol t age, per cent phase t o neut r al vol t age THD, per cent phase t o phase vol t age THD; a sel ect ed phase cur r ent , neut r al cur r ent , per cent phase cur r ent THD, per cent neut r al cur r ent ; sel ect ed t ot al PF, kW, KVA, kVAR, FREQ, kVAh, kWh. Det ect ed al ar m condi t i ons i ncl ude over / under cur r ent , over / under vol t age, over / under KVA, over / under f r equency, over / under sel ect ed PF/ kVAR, vol t age phase r ever sal , vol t age i mbal ance, r ever se power , over per cent THD. I ncl ude a For m C KYZ pul se out put r el ay on t he meter.

    b. Desi gn met er s t o accept i nput f r om st andar d 5A secondar y i nst r ument t r ansf or mer s and vol t age moni t or i ng r ange t o 600 vol t s, phase t o phase.

    c. Pr ovi de pr ogr ammi ng vi a a f r ont panel di spl ay and a communi cat i on i nt er f ace accessi bl e by a comput er .

    d. Pr ovi de passwor d secur ed pr ogr ammi ng st or ed i n non- vol at i l e EEPROM memory.

    e. Pr ovi de di gi t al communi cat i ons i n a Modbus [ RTU] pr ot ocol v i a a RS485 ser i al por t .

    f . Pr ovi de met er t hat cal cul at es and st or es aver age max/ mi n demand val ues wi t h t i me and dat e f or al l r eadi ngs based on a user sel ect abl e s l i di ng wi ndow aver agi ng per i od.

    g. Pr ovi de met er wi t h pr ogr ammabl e hi / l ow set l i mi t s wi t h t wo For m C dr y cont act r el ays when exceedi ng al ar m condi t i ons.

    h. I ncl ude hi st or i cal t r end l oggi ng capabi l i t y wi t h t he abi l i t y t o st or e up t o 100, 000 dat a poi nt s wi t h i nt er val s of 1 second t o 180 mi nut es. Pr ovi de a uni t t hat can st or e and t i me st amp up t o 1000 pr ogr ammabl e t r i gger ed condi t i ons.

    i . Pr ovi de event wavef or m r ecor di ng t r i gger ed by t he r ms of 2 cycl es of vol t age or cur r ent exceedi ng pr ogr ammabl e set poi nt s. St or e wavef or ms

    SECTI ON 26 24 13 Page 7

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    f or al l 6 channel s of vol t age and cur r ent f or a mi ni mum of 10 cycl es pr i or t o t he event and 50 cycl es past t he event .

    2. 2. 6 Ter mi nal Boar ds

    Pr ovi de wi t h engr aved pl ast i c t er mi nal st r i ps and scr ew t ype t er mi nal s f or ext er nal wi r i ng bet ween component s and f or i nt er nal wi r i ng bet ween r emovabl e assembl i es. Pr ovi de shor t - c i r cui t i ng t ype t er mi nal boar ds associ at ed wi t h cur r ent t r ansf or mer . Ter mi nat e conduct or s f or cur r ent t r ansf or mer s wi t h r i ng- t ongue l ugs. Pr ovi de t er mi nal boar d i dent i f i cat i on t hat i s i dent i cal i n s i mi l ar uni t s. Pr ovi de col or coded ext er nal wi r i ng t hat i s col or coded consi st ent l y f or s i mi l ar t er mi nal boar ds.

    2. 2. 7 Wi r e Mar ki ng

    Mar k cont r ol and met er i ng conduct or s at each end. Pr ovi de f act or y i nst al l ed, whi t e, pl ast i c t ubi ng, heat st amped wi t h bl ack bl ock t ype l et t er s on f act or y- i nst al l ed wi r i ng. On f i el d- i nst al l ed wi r i ng, pr ovi de whi t e, pr epr i nt ed, pol yvi nyl chl or i de ( PVC) s l eeves, heat st amped wi t h bl ack bl ock t ype l et t er s. Pr ovi de a s i ngl e l et t er or number on each sl eeve, el l i pt i cal l y shaped t o secur el y gr i p t he wi r e, and keyed i n such a manner t o ensur e al i gnment wi t h adj acent s l eeves. Pr ovi de speci f i c wi r e mar ki ngs usi ng t he appr opr i at e combi nat i on of i ndi v i dual s l eeves. I ndi cat e on each wi r e mar ker t he devi ce or equi pment , i ncl udi ng speci f i c t er mi nal number t o whi ch t he r emot e end of t he wi r e i s at t ached.

    2. 3 MANUFACTURER' S NAMEPLATE

    Pr ovi de a namepl at e on each i t em of equi pment bear i ng t he manuf act ur er ' s name, addr ess, model number , and ser i al number secur el y af f i xed i n a conspi cuous pl ace; t he namepl at e of t he di st r i but i ng agent i s not accept abl e. Thi s namepl at e and met hod of at t achment may be t he manuf act ur er ' s st andar d i f i t cont ai ns t he r equi r ed i nf or mat i on.

    2. 4 FI ELD FABRI CATED NAMEPLATES

    ASTM D709. Pr ovi de l ami nat ed pl ast i c namepl at es f or each swi t chboar d, equi pment encl osur e, r el ay, swi t ch, and devi ce; as speci f i ed i n t hi s sect i on or as i ndi cat ed on t he dr awi ngs. I dent i f y on each namepl at e i nscr i pt i on t he f unct i on and, when appl i cabl e, t he posi t i on. Pr ovi de namepl at es of mel ami ne pl ast i c, 0. 125 i nch t hi ck, whi t e wi t h bl ack cent er cor e. Pr ovi de mat t e f i ni sh sur f ace. Pr ovi de squar e cor ner s. Accur at el y al i gn l et t er i ng and engr ave i nt o t he cor e. Pr ovi de namepl at es wi t h mi ni mum si ze of one by 2. 5 i nches. Pr ovi de l et t er i ng t hat i s a mi ni mum of 0. 25 i nch hi gh nor mal bl ock st y l e.

    2. 5 SOURCE QUALI TY CONTROL

    2. 5. 1 Equi pment Test Schedul e

    The Gover nment r eser ves t he r i ght t o wi t ness t est s. Pr ovi de equi pment t est schedul es f or t est s t o be per f or med at t he manuf act ur er ' s t est f aci l i t y . Submi t r equi r ed t est schedul e and l ocat i on, and not i f y t he Cont r act i ng Of f i cer 30 cal endar days bef or e schedul ed t est dat e. Not i f y Cont r act i ng Of f i cer 15 cal endar days i n advance of changes t o schedul ed dat e.

    Pr ovi de t he f ol l owi ng as par t of t est equi pment cal i br at i on:

    a. Pr ovi de a cal i br at i on pr ogr am whi ch assur es t hat al l appl i cabl e t est

    SECTI ON 26 24 13 Page 8

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    i nst r ument s ar e mai nt ai ned wi t hi n r at ed accur acy.

    b. Accur acy: Tr aceabl e t o t he Nat i onal I nst i t ut e of St andar ds and Technology.

    c. I nst r ument cal i br at i on f r equency schedul e: Less t han or equal t o 12 mont hs f or bot h t est f l oor i nst r ument s and l eased speci al t y equi pment .

    d. Dat ed cal i br at i on l abel s: Vi s i bl e on al l t est equi pment .

    e. Cal i br at i ng st andar d: Hi gher accur acy t han t hat of t he i nst r ument tested.

    f . Keep up- t o- dat e r ecor ds t hat i ndi cat e dat es and t est r esul t s of i nst r ument s cal i br at ed or t est ed. For i nst r ument s cal i br at ed by t he manuf act ur er on a r out i ne basi s, i n l i eu of t hi r d par t y cal i br at i on, i ncl ude t he f ol l owi ng:

    ( 1) Mai nt ai n up- t o- dat e i nst r ument cal i br at i on i nst r uct i ons and pr ocedur es f or each t est i nst r ument .

    ( 2) I dent i f y t he t hi r d par t y/ l abor at or y cal i br at ed i nst r ument t o ver i f y t hat cal i br at i ng st andar d i s met .

    2. 5. 2 Swi t chboar d Desi gn Test s

    NEMA PB 2 and UL 891.

    2. 5. 2. 1 Desi gn Test s

    Fur ni sh document at i on showi ng t he r esul t s of desi gn t est s on a pr oduct of t he same ser i es and r at i ng as t hat pr ovi ded by t hi s Speci f i cat i on.

    a. Shor t - c i r cui t cur r ent t est .

    b. Encl osur e t est s.

    c. Di el ect r i c t est .

    2. 5. 3 Swi t chboar d Pr oduct i on Test s

    NEMA PB 2 and UL 891. Fur ni sh r epor t s whi ch i ncl ude r esul t s of pr oduct i on t est s per f or med on t he act ual equi pment f or t hi s Pr oj ect . These t est s include:

    a. 60- her t z di el ect r i c t est s.

    b. Mechani cal oper at i on t est s.

    c. El ect r i cal oper at i on and cont r ol wi r i ng t est s.

    d. Gr ound f aul t sensi ng equi pment t est .

    2. 6 ARC FLASH WARNI NG LABEL

    Pr ovi de war ni ng l abel f or swi t chboar ds. Locat e t hi s sel f - adhesi ve war ni ng l abel on t he out s i de of t he encl osur e war ni ng of pot ent i al el ect r i cal ar c f l ash hazar ds and appr opr i at e PPE r equi r ed. Pr ovi de l abel f or mat as indicated.

    SECTI ON 26 24 13 Page 9

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    2. 7 SERVI CE ENTRANCE AVAI LABLE FAULT CURRENT LABEL

    Pr ovi de l abel on ext er i or of swi t chboar ds used as ser vi ce equi pment l i s t i ng t he maxi mum avai l abl e f aul t cur r ent at t hat l ocat i on. I ncl ude on t he l abel t he dat e t hat t he f aul t cal cul at i on was per f or med and t he cont act i nf or mat i on f or t he or gani zat i on t hat compl et ed t he cal cul at i on. Locat e t hi s sel f - adhesi ve war ni ng l abel on t he out s i de of t he swi t chboar d. Pr ovi de l abel f or mat as i ndi cat ed.

    PART 3 EXECUTI ON

    3. 1 INSTALLATION

    Conf or m t o I EEE C2, NFPA 70, and t o t he r equi r ement s speci f i ed her ei n. Pr ovi de new equi pment and mat er i al s unl ess i ndi cat ed or speci f i ed ot her wi se.

    3. 2 I NSTALLATI ON OF EQUI PMENT AND ASSEMBLI ES

    I nst al l and connect equi pment f ur ni shed under t hi s sect i on as i ndi cat ed on pr oj ect dr awi ngs, t he appr oved shop dr awi ngs, and as speci f i ed her ei n.

    3. 2. 1 Switchboard

    ANSI / NEMA PB 2. 1.

    3. 2. 2 Met er s and I nst r ument Tr ansf or mer s

    ANSI C12. 1.

    3. 2. 3 Fi el d Appl i ed Pai nt i ng

    Wher e f i el d pai nt i ng of encl osur es i s r equi r ed t o cor r ect damage t o t he manuf act ur er ' s f act or y appl i ed coat i ngs, pr ovi de manuf act ur er ' s r ecommended coat i ngs and appl y i n accor dance wi t h manuf act ur er ' s i nst r uct i ons.

    3. 2. 4 Gal vani z i ng Repai r

    Repai r damage t o gal vani zed coat i ngs usi ng ASTM A780, z i nc r i ch pai nt , f or gal vani z i ng damaged by handl i ng, t r anspor t i ng, cut t i ng, wel di ng, or bol t i ng. Do not heat sur f aces t hat r epai r pai nt has been appl i ed t o.

    3. 2. 5 Fi el d Fabr i cat ed Namepl at e Mount i ng

    Pr ovi de number , l ocat i on, and l et t er desi gnat i on of namepl at es as i ndi cat ed. Fast en namepl at es t o t he devi ce wi t h a mi ni mum of t wo sheet - met al scr ews or t wo r i vet s.

    3. 3 FOUNDATI ON FOR EQUI PMENT AND ASSEMBLI ES

    3. 3. 1 I nt er i or Locat i on

    Mount swi t chboar d on concr et e s l ab as f ol l ows:

    a. Unl ess ot her wi se i ndi cat ed, pr ovi de t he s l ab wi t h di mensi ons at l east 4 i nches t hi ck.

    b. I nst al l s l ab such t hat t he t op of t he concr et e s l ab i s appr oxi mat el y 4 i nches above t he f i ni shed gr ade.

    SECTI ON 26 24 13 Page 10

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    c. Pr ovi de edges above gr ade 1/ 2 i nch chamf er .

    d. Pr ovi de s l ab of adequat e s i ze t o pr oj ect at l east 8 i nches beyond t he equipment.

    e. Pr ovi de condui t t ur nups and cabl e ent r ance space r equi r ed by t he equi pment t o be mount ed.

    f . Seal voi ds ar ound condui t openi ngs i n s l ab wi t h wat er - and oi l - r esi st ant caul k i ng or seal ant .

    g. Cut of f and bush condui t s 3 i nches above sl ab sur f ace.

    h. Pr ovi de concr et e wor k as speci f i ed i n Sect i on 03 30 00 CAST- I N- PLACE CONCRETE.

    3. 4 FI ELD QUALI TY CONTROL

    3. 4. 1 Per f or mance of Accept ance Checks and Test s

    Per f or m i n accor dance wi t h t he manuf act ur er ' s r ecommendat i ons and i ncl ude t he f ol l owi ng v i sual and mechani cal i nspect i ons and el ect r i cal t est s, per f or med i n accor dance wi t h NETA ATS.

    3. 4. 1. 1 Swi t chboar d Assembl i es

    a. Vi sual and Mechani cal I nspect i on:

    ( 1) Compar e equi pment namepl at e dat a wi t h speci f i cat i ons and appr oved shop dr awi ngs.

    ( 2) I nspect physi cal , el ect r i cal , and mechani cal condi t i on.

    ( 3) Ver i f y appr opr i at e anchor age, r equi r ed ar ea c l ear ances, and cor r ect al i gnment .

    ( 4) Cl ean swi t chboar d and ver i f y shi ppi ng br aci ng, l oose par t s, and document at i on shi pped i nsi de cubi c l es have been r emoved.

    ( 5) I nspect al l door s, panel s, and sect i ons f or pai nt , dent s, scr at ches, f i t , and mi ssi ng har dwar e.

    ( 6) Ver i f y t hat c i r cui t br eaker s i zes and t ypes cor r espond t o appr oved shop dr awi ngs as wel l as t o t he c i r cui t br eaker ’ s addr ess f or mi cr opr ocessor - communi cat i on packages.

    ( 7) I nspect al l bol t ed el ect r i cal connect i ons f or hi gh r esi st ance usi ng l ow- r esi st ance ohmmet er , ver i f y i ng t i ght ness of accessi bl e bol t ed el ect r i cal connect i ons by cal i br at ed t or que- wr ench met hod, or per f or mi ng t her mogr aphi c sur vey.

    ( 8) Conf i r m cor r ect oper at i on and sequenci ng of el ect r i cal and mechani cal i nt er l ock syst ems.

    ( 9) Conf i r m cor r ect appl i cat i on of manuf act ur er ' s r ecommended lubricants.

    ( 10) I nspect i nsul at or s f or evi dence of physi cal damage or

    SECTI ON 26 24 13 Page 11

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    cont ami nat ed sur f aces.

    ( 11) Ver i f y cor r ect bar r i er i nst al l at i on and oper at i on.

    ( 12) Exer ci se al l act i ve component s.

    ( 13) I nspect al l mechani cal i ndi cat i ng devi ces f or cor r ect oper at i on.

    ( 14) Ver i f y t hat f i l t er s ar e i n pl ace and vent s ar e c l ear .

    ( 15) Test oper at i on, al i gnment , and penet r at i on of i nst r ument t r ansf or mer wi t hdr awal di sconnect s.

    ( 16) I nspect cont r ol power t r ansf or mer s.

    b. El ect r i cal Test s:

    ( 1) Per f or m i nsul at i on- r esi st ance t est s on each bus sect i on.

    ( 2) Per f or m di el ect r i c wi t hst and vol t age t est s.

    ( 3) Per f or m i nsul at i on- r esi st ance t est on cont r ol wi r i ng; Do not per f or m t hi s t est on wi r i ng connect ed t o sol i d- st at e component s.

    ( 4) Per f or m cont r ol wi r i ng per f or mance t est .

    ( 5) Per f or m pr i mar y cur r ent i nj ect i on t est s on t he ent i r e cur r ent c i r cui t i n each sect i on of assembl y.

    3. 4. 1. 2 Ci r cui t Br eaker s

    Low Vol t age Mol ded Case wi t h Sol i d St at e Tr i ps.

    a. Vi sual and Mechani cal I nspect i on:

    ( 1) Compar e namepl at e dat a wi t h speci f i cat i ons and appr oved shop drawings.

    ( 2) I nspect c i r cui t br eaker f or cor r ect mount i ng.

    ( 3) Oper at e c i r cui t br eaker t o ensur e smoot h oper at i on.

    ( 4) I nspect case f or cr acks or ot her def ect s.

    ( 5) I nspect al l bol t ed el ect r i cal connect i ons f or hi gh r esi st ance usi ng l ow r esi st ance ohmmet er , ver i f y i ng t i ght ness of accessi bl e bol t ed connect i ons and/ or cabl e connect i ons by cal i br at ed t or que- wr ench met hod, or per f or mi ng t her mogr aphi c sur vey.

    ( 6) I nspect mechani sm cont act s and ar c chut es i n unseal ed uni t s.

    b. El ect r i cal Test s:

    ( 1) Per f or m cont act - r esi st ance t est s.

    ( 2) Per f or m i nsul at i on- r esi st ance t est s.

    ( 3) Per f or m Br eaker adj ust ment s f or f i nal set t i ngs i n accor dance wi t h Gover nment pr ovi ded set t i ngs.

    SECTI ON 26 24 13 Page 12

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    ( 4) Per f or m l ong- t i me del ay t i me- cur r ent char act er i st i c t est s

    ( 5) Det er mi ne shor t - t i me pi ckup and del ay by pr i mar y cur r ent i nj ect i on.

    ( 6) Det er mi ne gr ound- f aul t pi ckup and t i me del ay by pr i mar y cur r ent injection.

    ( 7) Det er mi ne i nst ant aneous pi ckup cur r ent by pr i mar y i nj ect i on.

    3. 4. 1. 3 Met er i ng and I nst r ument at i on

    a. Vi sual and Mechani cal I nspect i on:

    ( 1) Compar e equi pment namepl at e dat a wi t h speci f i cat i ons and appr oved shop dr awi ngs.

    ( 2) I nspect physi cal and mechani cal condi t i on.

    ( 3) Ver i f y t i ght ness of el ect r i cal connect i ons.

    b. El ect r i cal Test s:

    ( 1) Det er mi ne accur acy of met er s at 25, 50, 75, and 100 per cent of f ul l scal e.

    ( 2) Cal i br at e wat t hour met er s accor di ng t o manuf act ur er ' s publ i shed data.

    ( 3) Ver i f y al l i nst r ument mul t i pl i er s.

    ( 4) El ect r i cal l y conf i r m t hat cur r ent t r ansf or mer and vol t age t r ansf or mer secondar y c i r cui t s ar e i nt act .

    3. 4. 2 Fol l ow- Up Ver i f i cat i on

    Upon compl et i on of accept ance checks, set t i ngs, and t est s, show by demonst r at i on i n ser vi ce t hat c i r cui t s and devi ces ar e i n good oper at i ng condi t i on and pr oper l y per f or mi ng t he i nt ended f unct i on. Tr i p c i r cui t br eaker s by oper at i on of each pr ot ect i ve devi ce. Test each i t em t o per f or m i t s f unct i on not l ess t han t hr ee t i mes. As an except i on t o r equi r ement s st at ed el sewher e i n t he cont r act , pr ovi de t he Cont r act i ng Of f i cer 5 wor ki ng days advance not i ce of t he dat es and t i mes f or checks, set t i ngs, and t est s.

    - - End of Sect i on - -

    SECTI ON 26 24 13 Page 13

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    SECTI ON 26 28 01. 00 10

    COORDI NATED POWER SYSTEM PROTECTI ON10/07

    PART 1 GENERAL

    1. 1 REFERENCES

    The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

    I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

    I EEE 242 ( 2001; Er r at a 2003) Recommended Pr act i ce f or Pr ot ect i on and Coor di nat i on of I ndust r i al and Commer ci al Power Syst ems - Buf f Book

    I EEE 399 ( 1997) Br own Book I EEE Recommended Pr act i ce f or Power Syst ems Anal ysi s

    I EEE C2 ( 2017) Nat i onal El ect r i cal Saf et y Code

    NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

    NFPA 70 ( 2017) Nat i onal El ect r i cal Code

    U. S. DEPARTMENT OF DEFENSE ( DOD)

    UFC 3- 310- 04 ( 2013) Sei smi c Desi gn f or Bui l di ngs

    UNDERWRI TERS LABORATORI ES ( UL)

    UL 489 ( 2016) Mol ded- Case Ci r cui t Br eaker s, Mol ded- Case Swi t ches, and Ci r cui t - Br eaker Enclosures

    1. 2 SYSTEM DESCRI PTI ON

    The power syst em cover ed by t hi s speci f i cat i on consi st s of :

    a. New Type I I I Hydr ant Syst em, 12. 47, 480/ 277 vol t , pad- mount ed t r ansf or mer , gener at or , swi t ch boar d, MCC, l ow- vol t age t r ansf or mer , and panelboards.

    1. 3 SUBMITTALS

    Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on; submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y Not ebook, i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

    SD- 03 Pr oduct Dat a

    SECTI ON 26 28 01. 00 10 Page 1

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    Faul t Cur r ent Anal ysi s

    Pr ot ect i ve Devi ce Coor di nat i on St udy

    Equipment

    Syst em Coor di nat or

    Installation

    SD- 06 Test Repor t s

    Fi el d Test i ng

    SD- 07 Cer t i f i cat es

    Devi ces and Equi pment

    1. 4 QUALI TY ASSURANCE

    1. 4. 1 Syst em Coor di nat or

    Syst em coor di nat i on, r ecommended r at i ngs and set t i ngs of pr ot ect i ve devi ces, and desi gn anal ysi s shal l be accompl i shed by a Regi st er ed Pr of essi onal El ect r i cal Power Engi neer wi t h a mi ni mum of 3 year s of cur r ent exper i ence i n t he coor di nat i on of el ect r i cal power syst ems. Submi t ver i f i cat i on of exper i ence and l i cense number , of a r egi st er ed Pr of essi onal Engi neer as speci f i ed above. Exper i ence dat a shal l i ncl ude at l east f i ve r ef er ences f or wor k of a magni t ude compar abl e t o t hi s Cont r act , i nc l udi ng poi nt s of cont act , addr esses, and t el ephone number s.

    1. 4. 2 Syst em I nst al l er

    Cal i br at i on, t est i ng, adj ust ment , and pl aci ng i nt o ser vi ce of t he pr ot ect i ve devi ces shal l be accompl i shed by a manuf act ur er ' s pr oduct f i el d ser vi ce engi neer or i ndependent t est i ng company wi t h a mi ni mum of t wo year s of cur r ent pr oduct exper i ence i n pr ot ect i ve devi ces.

    1. 5 DELI VERY, STORAGE, AND HANDLI NG

    Devi ces and equi pment shal l be v i sual l y i nspect ed when r ecei ved and pr i or t o accept ance f r om conveyance. Pr ot ect st or ed i t ems f r om t he envi r onment i n accor dance wi t h t he manuf act ur er ' s publ i shed i nst r uct i ons. Damaged i t ems shal l be r epl aced.

    1. 6 PROJECT/ SI TE CONDI TI ONS

    Submi t cer t i f i cat es at t est i ng t hat al l devi ces or equi pment meet t he r equi r ement s of t he Cont r act Document s. Devi ces and equi pment f ur ni shed under t hi s sect i on shal l be sui t abl e f or t he f ol l owi ng s i t e condi t i ons. Sei smi c det ai l s shal l conf or m t o UFC 3- 310- 04 and Sect i ons 13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT, 13 48 00. 00 10 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT, and 26 05 48. 00 10 SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT.

    Altitude 750 f eet

    SECTI ON 26 28 01. 00 10 Page 2

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    Ambi ent Temper at ur e 85 degr ees F

    Frequency 60 Hz

    Fungus Cont r ol No

    Hazar dous Cl assi f i cat i on Wher e i ndi cat ed on dr awi ngs

    Humi di t y Cont r ol None

    Ventilation I nt er i or : HVAC

    Sei smi c Par amet er s Ref er t o Sei smi c Pr ot ect i on speci f i cat i ons l i s t ed above

    Other

    PART 2 PRODUCTS

    2. 1 STANDARD PRODUCT

    Pr ovi de pr ot ect i ve devi ces and equi pment whi ch ar e t he st andar d pr oduct of a manuf act ur er r egul ar l y engaged i n t he manuf act ur e of t he pr oduct and t hat essent i al l y dupl i cat e i t ems t hat have been i n sat i sf act or y ut i l i t y t ype use f or at l east 2 year s pr i or t o bi d openi ng. Submi t dat a consi st i ng of manuf act ur er ' s t i me- cur r ent char act er i st i c cur ves f or i ndi v i dual pr ot ect i ve devi ces, r ecommended set t i ngs of adj ust abl e pr ot ect i ve devi ces, and r ecommended r at i ngs of non- adj ust abl e pr ot ect i ve devi ces. Pr ot ect i ve devi ces ar e speci f i ed i n Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM.

    2. 2 NAMEPLATES

    Pr ovi de namepl at es t o i dent i f y al l pr ot ect i ve devi ces and equi pment . Namepl at e i nf or mat i on shal l be i n accor dance wi t h UL 489.

    2. 3 CORROSI ON PROTECTI ON

    Met al l i c mat er i al s shal l be pr ot ect ed agai nst cor r osi on. Fer r ous met al har dwar e shal l be z i nc or chr ome- pl at ed.

    2. 4 COORDI NATED POWER SYSTEM PROTECTI ON

    Anal yses shal l be pr epar ed t o demonst r at e t hat t he equi pment sel ect ed and syst em const r uct ed meet t he Cont r act Requi r ement s f or r at i ngs, coor di nat i on, and pr ot ect i on. They shal l i ncl ude a l oad f l ow anal ysi s, a f aul t cur r ent anal ysi s, ar c f l ash st udy, and a pr ot ect i ve devi ce coor di nat i on st udy. Submi t t he st udy al ong wi t h pr ot ect i ve devi ce equi pment submi t t al s. No t i me ext ensi ons or s i mi l ar cont act modi f i cat i ons wi l l be gr ant ed f or wor k ar i s i ng out of t he r equi r ement s f or t hi s st udy. Appr oval of pr ot ect i ve devi ces pr oposed wi l l be based on r ecommendat i ons of t hi s st udy. The Gover nment shal l not be hel d r esponsi bl e f or any changes t o equi pment , devi ce r at i ngs, set t i ngs, or addi t i onal l abor f or i nst al l at i on of equi pment or devi ces or der ed and/ or pr ocur ed pr i or t o appr oval of t he st udy. The st udi es shal l be per f or med by a r egi st er ed Pr of essi onal Engi neer wi t h demonst r at ed exper i ence i n power syst em coor di nat i on i n t he l ast 3 year s. Pr ovi de a l i s t of r ef er ences compl et e wi t h poi nt s of cont act , addr esses, and t el ephone number s. The sel ect i on of t he engi neer i s subj ect t o t he appr oval of t he Cont r act i ng Of f i cer .

    SECTI ON 26 28 01. 00 10 Page 3

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    2. 4. 1 Scope of Anal yses

    The f aul t cur r ent anal ysi s, and pr ot ect i ve devi ce coor di nat i on st udy shal l begi n at : The sour ce bus and ext end down t o syst em buses wher e f aul t avai l abi l i t y i s 10, 000 amper es ( symmet r i cal ) f or bui l di ng/ f aci l i t y 600 vol t l evel di st r i but i on buses. The near est upst r eam devi ce i n t he exi st i ng sour ce syst em and ext end t hr ough t he downst r eam devi ces at t he l oad end.

    2. 4. 2 Det er mi nat i on of Fact s

    The t i me- cur r ent char act er i st i cs, f eat ur es, and namepl at e dat a f or each exi st i ng pr ot ect i ve devi ce shal l be det er mi ned and document ed.

    2. 4. 3 Si ngl e Li ne Di agr am

    A si ngl e l i ne di agr am shal l be pr epar ed t o show t he el ect r i cal syst em buses, devi ces, t r ansf or mat i on poi nt s, and al l sour ces of f aul t cur r ent ( i ncl udi ng gener at or and mot or cont r i but i ons) . A f aul t - i mpedance di agr am or a comput er anal ysi s di agr am may be pr ovi ded. Each bus, devi ce or t r ansf or mat i on poi nt shal l have a uni que i dent i f i er . I f a f aul t - i mpedance di agr am i s pr ovi ded, i mpedance dat a shal l be shown. Locat i on of swi t ches, br eaker s, and ci r cui t i nt er r upt i ng devi ces shal l be shown on t he di agr am t oget her wi t h avai l abl e f aul t dat a, and t he devi ce i nt er r upt i ng r at i ng.

    2. 4. 4 Faul t Cur r ent Anal ysi s

    2. 4. 4. 1 Method

    The f aul t cur r ent anal ysi s shal l be per f or med i n accor dance wi t h met hods descr i bed i n I EEE 242, I EEE 399, and I EEE 551.

    2. 4. 4. 2 Data

    Act ual dat a shal l be ut i l i zed i n f aul t cal cul at i ons. Bus char act er i st i cs and t r ansf or mer i mpedance shal l be t hose pr oposed. Dat a shal l be document ed i n t he r epor t .

    2. 4. 4. 3 Faul t Cur r ent Avai l abi l i t y

    Bal anced t hr ee- phase f aul t , bol t ed l i ne- t o- l i ne f aul t , and l i ne- t o- gr ound f aul t cur r ent val ues shal l be pr ovi ded at each vol t age t r ansf or mat i on poi nt and at each power di st r i but i on bus. The maxi mum and mi ni mum val ues of f aul t avai l abl e at each l ocat i on shal l be shown i n t abul ar f or m on t he di agr am or i n t he r epor t .

    2. 4. 5 Coor di nat i on St udy

    The st udy shal l demonst r at e t hat t he maxi mum possi bl e degr ee of sel ect i v i t y has been obt ai ned bet ween devi ces speci f i ed, consi st ent wi t h pr ot ect i on of equi pment and conduct or s f r om damage f r om over l oads and f aul t condi t i ons. The st udy shal l i ncl ude a descr i pt i on of t he coor di nat i on of t he pr ot ect i ve devi ces i n t hi s Pr oj ect . A wr i t t en nar r at i ve shal l be pr ovi ded descr i bi ng: Whi ch devi ces may oper at e i n t he event of a f aul t at each bus; t he l ogi c used t o ar r i ve at devi ce r at i ngs and set t i ngs; s i t uat i ons wher e syst em coor di nat i on i s not achi evabl e due t o devi ce l i mi t at i ons ( an anal ysi s of any devi ce cur ves whi ch over l ap) ; coor di nat i on bet ween upst r eam and downst r eam devi ces; and r el ay set t i ngs. Recommendat i ons t o i mpr ove or enhance syst em r el i abi l i t y , and det ai l wher e such changes woul d i nvol ve

    SECTI ON 26 28 01. 00 10 Page 4

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    addi t i ons or modi f i cat i ons t o t he Cont r act and cost damages ( addi t i on or r educt i on) shal l be pr ovi ded. Composi t e coor di nat i on pl ot s shal l be pr ovi ded on l og- l og gr aph paper .

    2. 4. 6 Ar c Fl ash St udy

    Per f or m st udy i n accor dance wi t h I EEE 1584.

    2. 4. 7 St udy Repor t

    a. The r epor t shal l i ncl ude a nar r at i ve descr i bi ng: The anal yses per f or med; t he bases and met hods used; and t he desi r ed met hod of coor di nat ed pr ot ect i on of t he power syst em.

    b. The st udy shal l i ncl ude descr i pt i ve and t echni cal dat a f or exi st i ng devi ces and new pr ot ect i ve devi ces pr oposed. The dat a shal l i ncl ude manuf act ur er ' s publ i shed dat a, namepl at e dat a, and def i ni t i on of t he f i xed or adj ust abl e f eat ur es of t he exi st i ng or new pr ot ect i ve devi ces.

    c. The r epor t shal l document ut i l i t y company dat a i ncl udi ng syst em vol t ages, f aul t MVA, syst em X/ R r at i o, t i me- cur r ent char act er i st i c cur ves, cur r ent t r ansf or mer r at i os, and r el ay devi ce number s and set t i ngs; and exi st i ng power syst em dat a i ncl udi ng t i me- cur r ent char act er i st i c cur ves and pr ot ect i ve devi ce r at i ngs and set t i ngs.

    d. The r epor t shal l cont ai n f ul l y coor di nat ed composi t e t i me- cur r ent char act er i st i cs cur ves f or each bus i n t he syst em, as r equi r ed t o ensur e coor di nat ed power syst em pr ot ect i on bet ween pr ot ect i ve devi ces or equi pment . The r epor t shal l i ncl ude r ecommended r at i ngs and set t i ngs of al l pr ot ect i ve devi ces i n t abul at ed f or m.

    e. The r epor t shal l pr ovi de cal cul at ed ar c f l ash boundar i es, i nci dent ener gy l evel s, mi ni mum cl ot hi ng r at i ngs, l i mi t ed and r est r i c t ed appr oach boundar y di st ances.

    e. The r epor t shal l pr ovi de t he cal cul at i on per f or med f or t he anal yses, i ncl udi ng comput er anal ysi s pr ogr ams ut i l i zed. The name of t he sof t war e package, devel oper , and ver si on number shal l be pr ovi ded.

    PART 3 EXECUTI ON

    3. 1 EXAMINATION

    Af t er becomi ng f ami l i ar wi t h det ai l s of t he wor k, ver i f y di mensi ons i n t he f i el d, and advi se t he Cont r act i ng Of f i cer of any di scr epancy bef or e per f or mi ng any wor k.

    3. 2 INSTALLATION

    Submi t pr ocedur es i ncl udi ng di agr ams, i nst r uct i ons, and pr ecaut i ons r equi r ed t o pr oper l y i nst al l , adj ust , cal i br at e, and t est t he devi ces and equi pment . I nst al l pr ot ect i ve devi ces i n accor dance wi t h t he manuf act ur er ' s publ i shed i nst r uct i ons and i n accor dance wi t h t he r equi r ement s of NFPA 70 and I EEE C2.

    3. 3 FI ELD TESTI NG

    Pr i or t o f i el d t est s, submi t t he pr oposed t est pl an consi st i ng of compl et e f i el d t est pr ocedur e, t est s t o be per f or med, t est equi pment r equi r ed, and

    SECTI ON 26 28 01. 00 10 Page 5

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    t ol er ance l i mi t s, and compl et e t est i ng and ver i f i cat i on of t he gr ound f aul t pr ot ect i on equi pment , wher e used. Submi t per f or mance t est r epor t s i n bookl et f or m showi ng al l f i el d t est s per f or med t o adj ust each component and al l f i el d t est s per f or med t o pr ove compl i ance wi t h t he speci f i ed per f or mance cr i t er i a, upon compl et i on and t est i ng of t he i nst al l ed syst em. Each t est r epor t shal l i ndi cat e t he f i nal posi t i on of cont r ol s.

    3. 3. 1 General

    Per f or m f i el d t est i ng i n t he pr esence of t he Cont r act i ng Of f i cer . Not i f y t he Cont r act i ng Of f i cer 30 days pr i or t o conduct i ng t est s. Fur ni sh al l mat er i al s, l abor , and equi pment necessar y t o conduct f i el d t est s. Per f or m al l t est s and i nspect i ons r ecommended by t he manuf act ur er unl ess speci f i cal l y wai ved by t he Cont r act i ng Of f i cer . Mai nt ai n a wr i t t en r ecor d of al l t est s whi ch i ncl udes dat e, t est per f or med, per sonnel i nvol ved, devi ces t est ed, ser i al number and name of t est equi pment , and t est r esul t s.

    3. 3. 2 Safety

    Pr ovi de and use saf et y devi ces such as r ubber gl oves, pr ot ect i ve bar r i er s, and danger s i gns t o pr ot ect and war n per sonnel i n t he t est v i c i ni t y . Repl ace any devi ces or equi pment whi ch ar e damaged due t o i mpr oper t est pr ocedur es or handl i ng.

    3. 3. 3 Mol ded- Case Ci r cui t Br eaker s

    Ci r cui t br eaker s shal l be v i sual l y i nspect ed, oper at ed manual l y, and connect i ons checked f or t i ght ness. Cur r ent r at i ngs shal l be ver i f i ed and adj ust abl e set t i ngs i ncor por at ed i n accor dance wi t h t he coor di nat i on st udy.

    3. 3. 4 Power Ci r cui t Br eaker s

    3. 3. 4. 1 General

    Vi sual l y i nspect t he c i r cui t br eaker and oper at e t he c i r cui t br eaker manual l y; adj ust and cl ean pr i mar y cont act s i n accor dance wi t h manuf act ur er ' s publ i shed i nst r uct i ons; check t ol er ances and cl ear ances; check f or pr oper l ubr i cat i on; and ensur e t hat al l connect i ons ar e t i ght . For el ect r i cal l y oper at ed c i r cui t br eaker s, ver i f y oper at i ng vol t ages on c l osi ng and t r i ppi ng coi l s. Ver i f y f use r at i ngs i n cont r ol c i r cui t s; el ect r i cal l y oper at e t he br eaker , wher e appl i cabl e; and i mpl ement set t i ngs i n accor dance wi t h t he coor di nat i on st udy.

    - - End of Sect i on - -

    SECTI ON 26 28 01. 00 10 Page 6

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    SECTI ON 26 32 15. 00 10

    DI ESEL- GENERATOR SET STATI ONARY 100- 2500 KW, WI TH AUXI LI ARI ES10/07

    PART 1 GENERAL

    1. 1 REFERENCES

    The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

    AMERI CAN NATI ONAL STANDARDS I NSTI TUTE ( ANSI )

    ANSI C39. 1 ( 1981; R 1992) Requi r ement s f or El ect r i cal Anal og I ndi cat i ng I nst r ument s

    ASME I NTERNATI ONAL ( ASME)

    ASME B16. 11 ( 2011) For ged Fi t t i ngs, Socket - Wel di ng and Threaded

    ASME B16. 3 ( 2011) Mal l eabl e I r on Thr eaded Fi t t i ngs, Cl asses 150 and 300

    ASME B16. 5 ( 2013) Pi pe Fl anges and Fl anged Fi t t i ngs: NPS 1/ 2 Thr ough NPS 24 Met r i c/ I nch St andar d

    ASME B31. 1 ( 2016) Power Pi pi ng

    ASME BPVC SEC I X ( 2010) BPVC Sect i on I X- Wel di ng and Br azi ng Qualifications

    ASTM I NTERNATI ONAL ( ASTM)

    ASTM A106 ( 2014) St andar d Speci f i cat i on f or Seaml ess Car bon St eel Pi pe f or Hi gh- Temper at ur e Service

    ASTM A181 ( 2014) St andar d Speci f i cat i on f or Car bon St eel For gi ngs, f or Gener al - Pur pose Pi pi ng

    ASTM A234 ( 2013; E 2014) St andar d Speci f i cat i on f or Pi pi ng Fi t t i ngs of Wr ought Car bon St eel and Al l oy St eel f or Moder at e and Hi gh Temper at ur e Ser v i ce

    ASTM A53 ( 2012) St andar d Speci f i cat i on f or Pi pe, St eel , Bl ack and Hot - Di pped, Zi nc- Coat ed, Wel ded and Seaml ess

    ASTM D975 ( 2015b) St andar d Speci f i cat i on f or Di esel Fuel Oi l s

    SECTI ON 26 32 15. 00 10 Page 1

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    ELECTRI CAL GENERATI NG SYSTEMS ASSOCI ATI ON ( EGSA)

    EGSA 101P ( 1995) Per f or mance St andar d f or Engi ne Dr i ven Gener at or Set s

    I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

    I EEE 1 ( 2000; R 2011) Gener al Pr i nci pl es f or Temper at ur e Li mi t s i n t he Rat i ng of El ect r i c Equi pment and f or t he Eval uat i on of El ect r i cal I nsul at i on

    I EEE 115 ( 2009) Gui de f or Test Pr ocedur es f or Synchr onous Machi nes: Par t I Accept ance and Per f or mance Test i ng; Par t I I Test Pr ocedur es and Par amet er Det er mi nat i on f or Dynami c Anal ysi s

    I EEE 120 ( 1989; R 2007) Mast er Test Gui de f or El ect r i cal Measur ement s i n Power Ci r cui t s

    I EEE 43 ( 2013) Recommended Pr act i ce f or Test i ng I nsul at i on Resi st ance of Rot at i ng Machi ner y

    I EEE 519 ( 2014) Recommended Pr act i ces and Requi r ement s f or Har moni c Cont r ol i n El ect r i cal Power Syst ems

    I EEE 81 ( 2012) Gui de f or Measur i ng Ear t h Resi st i v i t y, Gr ound I mpedance, and Ear t h Sur f ace Pot ent i al s of a Gr ound Syst em

    I EEE C2 ( 2017) Nat i onal El ect r i cal Saf et y Code

    I EEE C57. 13 ( 2008; I NT 2009) St andar d Requi r ement s f or I nst r ument Tr ansf or mer s

    I EEE C57. 13. 1 ( 2006; R 2012) Gui de f or Fi el d Test i ng of Rel ayi ng Cur r ent Tr ansf or mer s

    I EEE St ds Di ct i onar y ( 2009) I EEE St andar ds Di ct i onar y: Gl ossar y of Ter ms & Def i ni t i ons

    MANUFACTURERS STANDARDI ZATI ON SOCI ETY OF THE VALVE AND FI TTI NGS I NDUSTRY ( MSS)

    MSS SP- 58 ( 1993; Reaf f i r med 2010) Pi pe Hanger s and Suppor t s - Mat er i al s, Desi gn and Manuf act ur e, Sel ect i on, Appl i cat i on, and Installation

    MSS SP- 80 ( 2013) Br onze Gat e, Gl obe, Angl e and Check Valves

    NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

    NEMA I CS 6 ( 1993; R 2011) I ndust r i al Cont r ol and Syst ems: Encl osur es

    SECTI ON 26 32 15. 00 10 Page 2

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    NEMA MG 1 ( 2016) Mot or s and Gener at or s

    NEMA/ ANSI C12. 11 ( 2007) I nst r ument Tr ansf or mer s f or Revenue Met er i ng, 10 kV BI L t hr ough 350 kV BI L ( 0. 6 kV NSV t hr ough 69 kV NSV)

    NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

    NFPA 110 ( 2016) St andar d f or Emer gency and St andby Power Syst ems

    NFPA 30 ( 2015) Fl ammabl e and Combust i bl e Li qui ds Code

    NFPA 37 ( 2015) St andar d f or t he I nst al l at i on and Use of St at i onar y Combust i on Engi nes and Gas Tur bi nes

    NFPA 70 ( 2017) Nat i onal El ect r i cal Code

    SOCI ETY OF AUTOMOTI VE ENGI NEERS I NTERNATI ONAL ( SAE)

    SAE J537 ( 2016) St or age Bat t er i es

    U. S. DEPARTMENT OF DEFENSE ( DOD)

    UFC 3- 310- 04 ( 2013) Sei smi c Desi gn f or Bui l di ngs

    UNDERWRI TERS LABORATORI ES ( UL)

    UL 1236 ( 2015) St andar d f or Bat t er y Char ger s f or Char gi ng Engi ne- St ar t er Bat t er i es

    UL 142 ( 2006; Repr i nt Jul 2013) St eel Abovegr ound Tanks f or Fl ammabl e and Combust i bl e Li qui ds

    1. 2 SUBMITTALS

    Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on; submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y Not ebook, i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

    SD- 02 Shop Dr awi ngs

    Det ai l ed Dr awi ngs; G

    Accept ance; G

    SD- 03 Pr oduct Dat a

    Har moni c Requi r ement s

    Engi ne- Gener at or Par amet er Schedul e

    Heat Exchanger

    SECTI ON 26 32 15. 00 10 Page 3

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    Gener at or ; G

    Manuf act ur er ' s Cat al og

    Si t e Wel di ng

    Spar e Par t s

    Onsi t e Tr ai ni ng

    Vibration-Isolation

    Post ed Dat a and I nst r uct i ons; G

    I nst r uct i ons; G

    Experience

    Fi el d Engi neer

    Gener al I nst al l at i on

    SD- 05 Desi gn Dat a

    Per f or mance Cr i t er i a

    Sound Li mi t at i ons; G

    I nt egr al Mai n Fuel St or age Tank

    Power Fact or

    Ti me- Del ay on Al ar ms

    Bat t er y Char ger

    SD- 06 Test Repor t s

    Fact or y I nspect i on and Test s

    Fact or y Test s

    Onsi t e I nspect i on and Test s; G

    SD- 07 Cer t i f i cat es

    Cool i ng Syst em

    Vi br at i on I sol at i on

    Pr ot ot ype Test

    Rel i abi l i t y and Dur abi l i t y

    Emissions

    Sound Li mi t at i ons

    Si t e Vi s i t

    SECTI ON 26 32 15. 00 10 Page 4

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    Cur r ent Bal ance

    Mat er i al s and Equi pment

    Inspections

    Cool i ng Syst em

    SD- 10 Oper at i on and Mai nt enance Dat a

    Oper at i on and Mai nt enance Manual s; G

    Mai nt enance Pr ocedur es; G

    Speci al Tool s

    Filters

    1. 3 QUALI TY ASSURANCE

    1. 3. 1 Conf or mance t o Codes and St andar ds

    Wher e equi pment i s speci f i ed t o conf or m t o r equi r ement s of any code or st andar d such as UL, NEMA, et c. , t he desi gn, f abr i cat i on, and i nst al l at i on shal l al so conf or m t o t he code.

    1. 3. 2 Si t e Wel di ng

    For al l wel di ng, qual i f y pr ocedur es and wel der s i n accor dance wi t h ASME BPVC SEC I X. Wel di ng pr ocedur es qual i f i ed by ot her s, and wel der s and wel di ng oper at or s qual i f i ed by a pr evi ousl y qual i f i ed empl oyer may be accept ed as per mi t t ed by ASME B31. 1. Submi t a copy of qual i f y i ng pr ocedur es and a l i s t of names and i dent i f i cat i on symbol s of qual i f i ed wel der s and wel di ng oper at or s. A l et t er l i s t i ng t he wel der qual i f y i ng pr ocedur es f or each wel der , compl et e wi t h suppor t i ng dat a such as t est pr ocedur es used, what was t est ed t o, and a l i s t of t he names of al l wel der s and t hei r i dent i f i cat i on symbol s. Per f or m wel der qual i f i cat i on t est s f or each wel der whose qual i f i cat i ons ar e not i n compl i ance wi t h t he r ef er enced st andar ds. Not i f y t he Cont r act i ng Of f i cer 24 hour s i n advance of qual i f i cat i on t est s whi ch shal l be per f or med at t he wor k s i t e, i f pr act i cal . The wel der or wel di ng oper at or shal l appl y t he per sonal l y assi gned symbol near each wel d made as a per manent r ecor d.

    1. 3. 3 Vi br at i on Li mi t at i on

    The maxi mum engi ne- gener at or set v i br at i on i n t he hor i zont al , ver t i cal , and axi al di r ect i ons shal l be l i mi t ed t o 6 mi l s ( peak- peak RMS) , wi t h an over al l vel oci t y l i mi t of 0. 95 i nches/ second RMS, f or al l speeds t hr ough 110 per cent of r at ed speed.

    1. 3. 4 Sei smi c Requi r ement s

    Sei smi c r equi r ement s shal l be i n accor dance wi t h UFC 3- 310- 04 and Sect i ons 13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT, 13 48 00. 00 10 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT, and 26 05 48. 00 10 SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT.

    SECTI ON 26 32 15. 00 10 Page 5

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    1. 3. 5 Experience

    Each component manuf act ur er shal l have exper i ence i n t he manuf act ur e, assembl y and sal e of component s used wi t h st at i onar y di esel engi ne- gener at or set s f or commer ci al and i ndust r i al use. The engi ne- gener at or set manuf act ur er / assembl er shal l have a mi ni mum of 3 year s exper i ence i n t he manuf act ur e, assembl y and sal e of st at i onar y di esel engi ne- gener at or set s. Submi t a st at ement showi ng t hat each component manuf act ur er has a mi ni mum of 3 year s exper i ence i n t he manuf act ur e, assembl y and sal e of component s used wi t h st at i onar y di esel engi ne- gener at or set s. The engi ne- gener at or set manuf act ur er / assembl er has a mi ni mum of 3 year s exper i ence i n t he manuf act ur e, assembl y and sal e of st at i onar y di esel engi ne- gener at or set s f or commer ci al and i ndust r i al use.

    1. 3. 6 Fi el d Engi neer

    The engi ne- gener at or set manuf act ur er or assembl er shal l f ur ni sh a qual i f i ed f i el d engi neer t o super vi se t he compl et e i nst al l at i on of t he engi ne- gener at or set , assi st i n t he per f or mance of t he onsi t e t est s, and i nst r uct per sonnel as t o t he oper at i onal and mai nt enance f eat ur es of t he equi pment . Submi t a l et t er l i s t i ng t he qual i f i cat i ons, school s, f or mal t r ai ni ng, and exper i ence of t he f i el d engi neer . The f i el d engi neer shal l have at t ended t he engi ne gener at or manuf act ur er ' s t r ai ni ng cour ses on i nst al l at i on and oper at i on and mai nt enance of engi ne gener at or set s.

    1. 3. 7 Det ai l ed Dr awi ngs

    Submi t det ai l ed dr awi ngs showi ng t he f ol l owi ng:

    a. Base- mount ed equi pment , compl et e wi t h base and at t achment s, i nc l udi ng anchor bol t t empl at e and r ecommended cl ear ances f or mai nt enance and operation.

    b. Compl et e st ar t i ng syst em.

    c. Compl et e f uel syst em.

    d. Compl et e cool i ng syst em.

    e. Compl et e exhaust syst em.

    f . Layout of r el ays, br eaker s, pr ogr ammabl e cont r ol l er s, swi t chgear , and swi t ches i ncl udi ng appl i cabl e s i ngl e l i ne and wi r i ng di agr ams wi t h wr i t t en descr i pt i on of sequence of oper at i on and t he i nst r ument at i on provided.

    g. The compl et e l ubr i cat i on syst em, i ncl udi ng pi pi ng, pumps, st r ai ner s, f i l t er s, heat exchanger s f or l ube oi l and t ur bochar ger cool i ng, el ect r i c heat er , cont r ol s and wi r i ng.

    h. Locat i on, t ype, and descr i pt i on of v i br at i on i sol at i on devi ces f or al l applications.

    i . The saf et y syst em, t oget her wi t h a det ai l ed descr i pt i on of how i t i s t o wor k. Wi r i ng schemat i cs, saf et y devi ces wi t h a l i s t i ng of t hei r nor mal r anges, al ar m and shut down val ues ( t o i ncl ude oper at i on par amet er s such as pr essur es, t emper at ur es vol t ages, cur r ent s, and speeds) shal l be included.

    SECTI ON 26 32 15. 00 10 Page 6

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    j . One- l i ne schemat i c and wi r i ng di agr ams of t he gener at or , exci t er , r egul at or , gover nor , and i nst r ument at i on.

    k. Layout of each panel .

    l . Mount i ng and suppor t f or each panel and maj or pi ece of el ect r i cal equipment.

    m. Engi ne- gener at or set l i f t i ng poi nt s and r i ggi ng i nst r uct i ons.

    1. 4 DELI VERY, STORAGE, AND HANDLI NG

    Pr oper l y pr ot ect mat er i al and equi pment , i n accor dance wi t h t he manuf act ur er s r ecommended st or age pr ocedur es, bef or e, dur i ng, and af t er i nst al l at i on. Pr ot ect st or ed i t ems f r om t he weat her and cont ami nat i on. Dur i ng i nst al l at i on, pi pi ng and s i mi l ar openi ngs shal l be capped t o keep out di r t and ot her f or ei gn mat t er .

    1. 5 EXTRA MATERI ALS

    Submi t a compl et e l i s t of spar e par t s f or each pi ece of equi pment and a compl et e l i s t of al l mat er i al and suppl i es needed f or cont i nued oper at i on. Li st s shal l i ncl ude suppl y sour ce and cur r ent pr i ces. Separ at e each l i s t i nt o t wo par t s, t hose el ement s r ecommended by t he manuf act ur er t o be r epl aced af t er 3 year s of ser vi ce, and t he r emai ni ng el ement s.

    PART 2 PRODUCTS

    2. 1 SYSTEM REQUI REMENTS

    a. Pr ovi de and i nst al l each engi ne- gener at or set compl et e and t ot al l y f unct i onal , wi t h al l necessar y anci l l ar y equi pment t o i ncl ude: Ai r f i l t r at i on; st ar t i ng syst em; gener at or cont r ol s, pr ot ect i on, and i sol at i on; i nst r ument at i on; l ubr i cat i on; f uel syst em; cool i ng syst em; and engi ne exhaust syst em. Each engi ne- gener at or set shal l sat i sf y t he r equi r ement s speci f i ed i n t he Engi ne- Gener at or Par amet er Schedul e.

    b. Each set shal l consi st of one engi ne, one gener at or , and one exci t er mount ed, assembl ed, and al i gned on one base; and ot her necessar y anci l l ar y equi pment whi ch may be mount ed separ at el y. Set s havi ng a capaci t y of 750 kW or smal l er shal l be assembl ed and at t ached t o t he base pr i or t o shi ppi ng. Set s over 750 kW capaci t y may be shi pped i n sect i ons. Each set component shal l be envi r onment al l y sui t abl e f or t he l ocat i on shown and shal l be t he manuf act ur er ' s st andar d pr oduct of f er ed i n cat al ogs f or commer ci al or i ndust r i al use. Any nonst andar d pr oduct s or component s and t he r eason f or t hei r use shal l be speci f i cal l y identified.

    2. 1. 1 Engi ne- Gener at or Par amet er Schedul e

    Submi t descr i pt i on of t he gener at or f eat ur es whi ch mi t i gat e t he ef f ect s of t he non- l i near l oads l i s t ed.

    ENGI NE- GENERATOR PARAMETER SCHEDULE

    Power Rat i ng Standby

    SECTI ON 26 32 15. 00 10 Page 7

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    ENGI NE- GENERATOR PARAMETER SCHEDULE

    110 per cent of Ser vi ce Load f or 1 hour i n 12 consecut i ve hour s

    Ser vi ce Load 350 kVA ( maxi mum)

    50 kVA ( cont i nuous

    Mot or St ar t i ng kVA ( Max. ) 720 kVA

    Power Fact or 0. 8 l aggi ng

    Engi ne- Gener at or Appl i cat i ons stand-alone

    Maxi mum Speed 1800 r pm

    Heat Exchanger Type f i n- t ube ( r adi at or )

    Vol t age Regul at i on ( No Load t o Ful l Load) ( St and al one appl i cat i ons)

    + 2 per cent ( maxi mum)

    Vol t age Bandwi dt h ( st eady st at e) + 2 per cent

    Frequency 60 Hz

    Voltage 480 vol t s

    Phases 3 Phase, Wye

    Mi ni mum Gener at or Subt r ansi ent React ance 14 per cent

    Nonl i near Loads 10 kVA

    Max St ep Load I ncr ease 75 per cent of Ser vi ce Load at 0. 8 PF

    Tr ansi ent Recover y Ti me wi t h St ep Load I ncr ease ( Vol t age)

    3 seconds

    Tr ansi ent Recover y Ti me wi t h St ep Load I ncr ease ( Fr equency)

    3 seconds

    Maxi mum Vol t age Devi at i on wi t h St ep Load Increase

    15 per cent of r at ed vol t age

    Maxi mum Fr equency Devi at i on wi t h St ep Load I ncr ease

    5 per cent of r at ed f r equency

    Max St ep Load Decr ease ( wi t hout shut down) 100 per cent of Ser vi ce Load at 0. 08 PF

    Max Ti me t o St ar t and be Ready t o Assume Load

    10 seconds

    Max Summer Out door Temp ( Ambi ent ) 100 degr ees F

    SECTI ON 26 32 15. 00 10 Page 8

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    ENGI NE- GENERATOR PARAMETER SCHEDULE

    Mi n Wi nt er Out door Temp ( Ambi ent ) 10 degr ees F

    I nst al l at i on El evat i on 750 above sea l evel

    2. 1. 2 Rat ed Out put Capaci t y

    Each engi ne- gener at or - set shal l pr ovi de power equal t o t he sum of Ser vi ce Load pl us t he machi ne' s ef f i c i ency l oss and associ at ed anci l l ar y equi pment l oads. Rat ed out put capaci t y shal l al so consi der engi ne and/ or gener at or over si z i ng r equi r ed t o meet r equi r ement s i n par agr aph Engi ne- Gener at or Par amet er Schedul e.

    2. 1. 3 Power Rat i ngs

    Power r at i ngs shal l be i n accor dance wi t h EGSA 101P.

    2. 1. 4 Tr ansi ent Response

    The engi ne- gener at or set gover nor and vol t age r egul at or shal l cause t he engi ne- gener at or set t o r espond t o t he maxi mum st ep l oad changes such t hat out put vol t age and f r equency r ecover t o and st abi l i ze wi t hi n t he oper at i onal bandwi dt h wi t hi n t he t r ansi ent r ecover y t i me. The engi ne- gener at or set shal l r espond t o maxi mum st ep l oad changes such t hat t he maxi mum vol t age and f r equency devi at i ons f r om bandwi dt h ar e not exceeded.

    2. 1. 5 Rel i abi l i t y and Dur abi l i t y

    Each st andby engi ne- gener at or set shal l have bot h an engi ne and a gener at or capabl e of del i ver i ng t he speci f i ed power on a st andby basi s wi t h an ant i c i pat ed mean t i me bet ween over haul s of no l ess t han 5, 000 hour s oper at i ng wi t h a l oad f act or of 70 per cent . Two l i ke engi nes and t wo l i ke gener at or s shal l be c i t ed t hat have per f or med sat i sf act or i l y i n a st at i onar y power pl ant , i ndependent and separ at e f r om t he physi cal l ocat i on of t he manuf act ur er ' s and assembl er ' s f aci l i t i es, f or st andby wi t hout any f ai l ur e t o st ar t , i ncl udi ng al l per i odi c exer ci se. Each l i ke engi ne and gener at or shal l have had no f ai l ur es r esul t i ng i n downt i me f or r epai r s i n excess of 72 hour s dur i ng t wo consecut i ve year s of ser vi ce. Li ke engi nes shal l be of t he same model , speed, bor e, st r oke, number and conf i gur at i on of cyl i nder s, and r at ed out put capaci t y. Li ke gener at or s shal l be of t he same model , speed, pi t ch, cool i ng, exci t er , vol t age r egul at or and r at ed out put capaci t y.

    Submi t a r el i abi l i t y and dur abi l i t y cer t i f i cat i on l et t er f r om t he manuf act ur er and assembl er t o pr ove t hat exi st i ng f aci l i t i es ar e and have been successf ul l y ut i l i z i ng t he same component s pr oposed t o meet t hi s speci f i cat i on, i n s i mi l ar ser vi ce. Cer t i f i cat i on may be based on component s, i . e. , engi nes used wi t h di f f er ent model s of gener at or s and gener at or s used wi t h di f f er ent engi nes, and does not excl ude annual t echnol ogi cal i mpr ovement s made by a manuf act ur er i n t he basi c st andar d- model component on whi ch exper i ence was obt ai ned, pr ovi ded par t s i nt er changeabi l i t y has not been subst ant i al l y af f ect ed and t he cur r ent st andar d model meet s t he per f or mance r equi r ement s speci f i ed. Pr ovi de a l i s t wi t h t he name of t he i nst al l at i ons, compl et i on dat es, and name and t el ephone number of a poi nt of cont act .

    SECTI ON 26 32 15. 00 10 Page 9

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    2. 1. 6 Engi ne- Gener at or Set Encl osur e

    The engi ne- gener at or set encl osur e shal l be cor r osi on r esi st ant and f ul l y weat her r esi st ant . The encl osur e shal l cont ai n al l set component s and pr ovi de vent i l at i on t o per mi t oper at i on at Ser vi ce Load under secur ed condi t i ons. Door s shal l be pr ovi ded f or access t o cont r ol s and equi pment r equi r i ng per i odi c mai nt enance or adj ust ment . Removabl e panel s shal l be pr ovi ded f or access t o component s r equi r i ng per i odi c r epl acement . The encl osur e shal l be capabl e of bei ng r emoved wi t hout di sassembl y of t he engi ne- gener at or set or r emoval of component s ot her t han t he exhaust syst em. The encl osur e shal l r educe t he noi se of t he gener at or set t o wi t hi n t he l i mi t s speci f i ed i n t he par agr aph SOUND LI MI TATI ONS.

    2. 1. 7 Vi br at i on I sol at i on

    The engi ne- gener at or set shal l be pr ovi ded wi t h a v i br at i on- i sol at i on syst em i n accor dance wi t h t he manuf act ur er ' s st andar d r ecommendat i on. Submi t v i br at i on i sol at i on syst em per f or mance dat a f or t he r ange of f r equenci es gener at ed by t he engi ne- gener at or set dur i ng oper at i on f r om no l oad t o f ul l l oad and t he maxi mum vi br at i on t r ansmi t t ed t o t he f l oor pl us descr i pt i on of sei smi c qual i f i cat i on of t he engi ne- gener at or mount i ng, base, and vi br at i on i sol at i on. Submi t t or s i onal anal ysi s i ncl udi ng pr ot ot ype t est i ng or and cal cul at i ons whi ch cer t i f y and demonst r at e t hat no damagi ng or danger ous t or s i onal v i br at i ons wi l l occur when t he pr i me mover i s connect ed t o t he gener at or , at synchr onous speeds, + 10 per cent . Vi br at i on- i sol at i on syst ems shal l be desi gned and qual i f i ed ( as an i nt egr al par t of t he base and mount i ng syst em i n accor dance wi t h t he sei smi c par amet er s speci f i ed. Wher e t he v i br at i on- i sol at i on syst em does not secur e t he base t o t he st r uct ur e f l oor or uni t f oundat i on, sei smi c r est r ai nt s shal l be pr ovi ded i n accor dance wi t h t he sei smi c par amet er s speci f i ed.

    2. 1. 8 Har moni c Requi r ement s

    Non- l i near l oads t o be ser ved by each engi ne- gener at or set ar e as i ndi cat ed. The maxi mum l i near l oad demand ( kVA @ PF) when non- l i near l oads wi l l al so be i n use i s as i ndi cat ed.

    2. 1. 9 St ar t i ng Ti me Requi r ement s

    Upon r ecei pt of a s i gnal t o st ar t , each engi ne gener at or set wi l l s t ar t , r each r at ed f r equency and vol t age and be r eady t o assume l oad wi t hi n t he t i me speci f i ed. For st andby set s used i n emer gency power appl i cat i ons, each engi ne gener at or set wi l l s t ar t , r each r at ed f r equency and vol t age, and power wi l l be suppl i ed t o t he l oad t er mi nal s of t he aut omat i c t r ansf er swi t ch wi t hi n t he st ar t i ng t i me speci f i ed.

    2. 2 NAMEPLATES

    Each maj or component of t hi s speci f i cat i on shal l have t he manuf act ur er ' s name, t ype or st y l e, model or ser i al number and r at i ng on a pl at e secur ed t o t he equi pment . As a mi ni mum, namepl at es shal l be pr ovi ded f or :

    Engines Relays

    Generators Tr ansf or mer s ( CT & PT)

    SECTI ON 26 32 15. 00 10 Page 10

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    Regulators I nt egr al Mai n Fuel St or age Tank

    Pumps and pump mot or s Governors

    Gener at or Br eaker

    Economizers Heat exchanger s ( ot her t han base mount ed)

    Wher e t he f ol l owi ng equi pment i s not pr ovi ded as a st andar d component by t he di esel engi ne gener at or set manuf act ur er , t he namepl at e i nf or mat i on may be pr ovi ded i n t he mai nt enance manual i n l i eu of namepl at es.

    Bat t er y char ger Heaters

    Switchboards Exhaust muf f l er s

    Switchgear Silencers

    Battery Exciters

    2. 3 SAFETY DEVI CES

    Exposed movi ng par t s, par t s t hat pr oduce hi gh oper at i ng t emper at ur es, par t s whi ch may be el ect r i cal l y ener gi zed, and par t s t hat may be a hazar d t o oper at i ng per sonnel shal l be i nsul at ed, f ul l y encl osed, guar ded, or f i t t ed wi t h ot her t ypes of saf et y devi ces. The saf et y devi ces shal l be i nst al l ed so t hat pr oper oper at i on of t he equi pment i s not i mpai r ed.

    2. 4 MATERI ALS AND EQUI PMENT

    Submi t cer t i f i cat i on st at i ng t hat wher e mat er i al s or equi pment ar e speci f i ed t o compl y wi t h r equi r ement s of UL, wr i t t en pr oof of such compl i ance has been obt ai ned. The l abel or l i s t i ng of t he speci f i ed agency, or a wr i t t en cer t i f i cat e f r om an appr oved, nat i onal l y r ecogni zed t est i ng or gani zat i on equi pped t o per f or m such ser v i ces, st at i ng t hat t he i t ems have been t est ed and conf or m t o t he r equi r ement s and t est i ng met hods of t he speci f i ed agency ar e accept abl e as pr oof .

    2. 4. 1 Fi l t er El ement s

    Fuel - oi l , l ubr i cat i ng- oi l , and combust i on- ai r f i l t er el ement s shal l be manuf act ur er ' s st andar d.

    2. 4. 2 I nst r ument Tr ansf or mer s

    NEMA/ ANSI C12. 11.

    2. 4. 3 Revenue Met er i ng

    I EEE C57. 13.

    2. 4. 4 Pi pe ( Fuel / Lube- Oi l , Compr essed Ai r , Cool ant , and Exhaust )

    ASTM A53, or ASTM A106 st eel pi pe. Pi pe smal l er t han 2 i nches shal l be Schedul e 80. Pi pe 2 i nches and l ar ger shal l be Schedul e 40.

    SECTI ON 26 32 15. 00 10 Page 11

  • C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d

    2. 4. 4. 1 Fl anges and Fl anged Fi t t i ngs

    ASTM A181, Cl ass 60, or ASME B16. 5, Gr ade 1, Cl ass 150.

    2. 4. 4. 2 Pi pe Wel di ng Fi t t i ngs

    ASTM A234, Gr ade WPB or WPC, Cl ass 150 or ASME B16. 11, 3000 l b.

    2. 4. 4. 3 Thr eaded Fi t t i ngs

    ASME B16. 3, Cl ass 150.

    2. 4. 4. 4 Valves

    MSS SP- 80, Cl ass 150.

    2. 4. 4. 5 Gaskets

    Manuf act ur er ' s st andar d.

    2. 4. 5 Pi pe Hanger s

    MSS SP- 58.

    2. 4. 6 El ect r i cal Encl osur es

    NEMA I CS 6.

    2. 5 ENGINE

    Each engi ne shal l oper at e on No. 2- D di esel f uel conf or mi ng t o ASTM D975, shal l be desi gned f or st at i onar y appl i cat i ons and shal l b