6
TRV Angle Pattern Thermostatic Radiator Valve Vertical or horizontal mounting (15mm) GENERAL INFORMATION Size Pattern No. Pack 1 Qty Code Barcode 8mmx1/2 Angle Pattern TRV 1 632001 5013866012099 10mmx1/2 Angle Pattern TRV 1 632002 5013866012105 15mmx1/2 Angle Pattern TRV 1 632003 5013866012112 DIMENSIONS (mm) Code Description A B C 632001 8MMX1/2 CP TERRIER II TRV 61 130 26 632002 10MMX1/2 CP TERRIER II TRV 61 130 26 632003 15MMX1/2 CP TERRIER II TRV 61 130 26 PRESSURE & TEMPERATURE TRV Minimum Operating Pressure (bar) Maximum Cold Working Pressure (bar) Maximum Hot Working Pressure (bar) 8MMX1/2 CP TERRIER II TRV No Minimum Operating Pressure 10.0 bar at temperatures up to 120oC Not Suitable for Maximum Hot Working Pressure MATERIAL SPECIFICATIONS Number Component Material 1 Body Forged Brass Chrome Plated 2 Head Brass Bar 3 Gland Brass Bar 4 Flow Spindle Stainless Steel 5 Capnut Forged Brass Chrome Plated 6 Cone Brass Bar 7 Adaptor Brass Bar Chrome Plated 8 Thermal Head Cover/Body ABS 9 Thermal Head Element/Housing Noryl SPARES

Upload: vuhanh

Post on 27-Mar-2018

213 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: TRV - mkmbs.co.uk · PDF fileTerrier thermostatic radiator valves are approved to EN 215. ... the manual shut off cap may be used for added security instead of the TRV head. In this

TRVAngle Pattern Thermostatic Radiator Valve Vertical or horizontal mounting (15mm)

GENERAL INFORMATION

Size Pattern No. Pack 1 Qty Code Barcode

8mmx1/2 Angle Pattern TRV 1 632001 5013866012099

10mmx1/2 Angle Pattern TRV 1 632002 5013866012105

15mmx1/2 Angle Pattern TRV 1 632003 5013866012112

DIMENSIONS (mm)

Code Description A B C

632001 8MMX1/2 CP TERRIER II TRV 61 130 26

632002 10MMX1/2 CP TERRIER II TRV 61 130 26

632003 15MMX1/2 CP TERRIER II TRV 61 130 26

PRESSURE & TEMPERATURE

TRV Minimum Operating

Pressure (bar)

Maximum Cold Working

Pressure (bar)

Maximum Hot

Working Pressure (bar)

8MMX1/2 CP TERRIER II

TRV

No Minimum Operating

Pressure

10.0 bar at temperatures up to

120oC

Not Suitable for Maximum Hot Working

Pressure

MATERIAL SPECIFICATIONS

Number Component Material

1 Body Forged Brass Chrome Plated

2 Head Brass Bar

3 Gland Brass Bar

4 Flow Spindle Stainless Steel

5 Capnut Forged Brass Chrome Plated

6 Cone Brass Bar

7 Adaptor Brass Bar Chrome Plated

8 Thermal Head Cover/Body ABS

9 Thermal Head Element/Housing Noryl

SPARES

Page 2: TRV - mkmbs.co.uk · PDF fileTerrier thermostatic radiator valves are approved to EN 215. ... the manual shut off cap may be used for added security instead of the TRV head. In this

1

Pattern / Size Description Code Barcode Date From Date To

Angle Pattern TRV / 8mmx1/2 TH1 THERMAL HEAD - DISCONTINUED 841054 5013866059056 01/01/1990 10/04/2009

Angle Pattern TRV / 8mmx1/2 TH2 THERMAL HEAD 850685 5013866061813 01/06/1998 current

Angle Pattern TRV / 10mmx1/2 TH2 THERMAL HEAD 850685 5013866061813 01/06/1998 current

Angle Pattern TRV / 10mmx1/2 TH1 THERMAL HEAD - DISCONTINUED 841054 5013866059056 01/01/1990 10/04/2009

Angle Pattern TRV / 15mmx1/2 TH1 THERMAL HEAD - DISCONTINUED 841054 5013866059056 01/01/1990 10/04/2009

Angle Pattern TRV / 15mmx1/2 TH2 THERMAL HEAD 850685 5013866061813 01/06/1998 current

2

Pattern / Size Description Code Barcode Date From Date To

Angle Pattern TRV / 8mmx1/2 HK68 COMPLETE CARTRIDGE 1/2 850935 5013866063299 01/06/1998 current

Angle Pattern TRV / 10mmx1/2 HK68 COMPLETE CARTRIDGE 1/2 850935 5013866063299 01/06/1998 current

Angle Pattern TRV / 15mmx1/2 HK68 COMPLETE CARTRIDGE 1/2 850935 5013866063299 01/06/1998 current

3

Pattern / Size Description Code Barcode Date From Date To

Angle Pattern TRV / 8mmx1/2 DC4 DUST CAP 841052 5013866059049 01/01/1990 31/05/1998

Angle Pattern TRV / 8mmx1/2 DC4 DUST CAP 841052 5013866059049 01/06/1998 current

Angle Pattern TRV / 10mmx1/2 DC4 DUST CAP 841052 5013866059049 01/01/1990 31/05/1998

Angle Pattern TRV / 10mmx1/2 DC4 DUST CAP 841052 5013866059049 01/06/1998 current

Angle Pattern TRV / 15mmx1/2 DC4 DUST CAP 841052 5013866059049 01/06/1998 current

Angle Pattern TRV / 15mmx1/2 DC4 DUST CAP 841052 5013866059049 01/01/1990 31/05/1998

4

Pattern / Size Description Code Barcode Date From Date To

Angle Pattern TRV / 8mmx1/2 TP1CP CHROME TAIL PIPE 841006 5013866059001 01/01/1990 31/05/1998

Angle Pattern TRV / 8mmx1/2 TP1CP CHROME TAIL PIPE 841006 5013866059001 01/06/1998 current

Angle Pattern TRV / 10mmx1/2 TP1CP CHROME TAIL PIPE 841006 5013866059001 01/06/1998 current

Angle Pattern TRV / 10mmx1/2 TP1CP CHROME TAIL PIPE 841006 5013866059001 01/01/1990 31/05/1998

Angle Pattern TRV / 15mmx1/2 TP1CP CHROME TAIL PIPE 841006 5013866059001 01/01/1990 31/05/1998

Angle Pattern TRV / 15mmx1/2 TP1CP CHROME TAIL PIPE 841006 5013866059001 01/06/1998 current

5

Pattern / Size Description Code Barcode Date From Date To

Angle Pattern TRV / 8mmx1/2 LP7 LOCKING PIN (PACK OF 2) 850888 5013866062926 01/01/1900 current

Angle Pattern TRV / 10mmx1/2 LP7 LOCKING PIN (PACK OF 2) 850888 5013866062926 01/01/1900 current

Angle Pattern TRV / 15mmx1/2 LP7 LOCKING PIN (PACK OF 2) 850888 5013866062926 01/01/1900 current

CARE & MAINTENANCE

Care The TRV can be easily cleaned with a soft damp cloth wiping over the handle (plastic) and valve body.

Maintenance No maintenance is required for this product. When removing the TRV head for decorating or replacementpurposes, turning the head setting to “5”, this enables an easier removal. A manual shut off cap is provided withthe product to protect the valve whilst any surrounding maintenance work is undertaken.

For any further help or replacement parts please contact the Service Support Team on: 0800 1560050.

REGULATIONS

Regulations Terrier thermostatic radiator valves are approved to EN 215. For valves with compression connections, theconnections are approved to BS EN1254-2; threaded connections comply with BS 21 or BS 2779.

They are designed for use only in an indirect open-vented or sealed water-filled central heating and/or indirect hotwater system and for no other purpose.

They must be used within the pressure and temperature limits stated in the technical information table below.

Operating Conditions Maximum

System Water Temperature (at 5bar) 120°C

Operating pressure (at 65°C) 10 bar

Under no circumstances must they be used in systems containing liquids or solutions other than water. The onlyexception is the addition of a proprietary central heating corrosion inhibitor, cleaner or anti-freeze to the systemwater in accordance with the manufacturer's instructions.

Terrier heating controls are manufactured to a strict quality assurance system in accordance with ISO 9000:2001.

Page 3: TRV - mkmbs.co.uk · PDF fileTerrier thermostatic radiator valves are approved to EN 215. ... the manual shut off cap may be used for added security instead of the TRV head. In this

GUARANTEE

Thermostatic and Manual Radiator Valves

Pegler Yorkshire Customcare 5 Year Guarantee - Terms & Conditions

Products are subject to a 5 year guarantee that is between Pegler Yorkshire and the final purchaser of theproduct.

The guarantee is subject to proof of purchase being supplied.

This guarantee does not affect any statutory rights the consumer may have in law.

The guarantee covers manufacturing or material defects and is not applicable where the product is fitted contraryto conditions of use in our literature.

The guarantee is subject to the following limitations:

1. The valves are designed for use only in an indirect open-vented or sealed water-filled central heating and/orindirect hot water system and for no other purpose.

2. They must be used within the pressure and temperature limits stated in the technical information table below.

Operating Conditions (Maximum) System Water Temperature (at 5bar) : 120 °C Operating pressure (at 65 oC) :10 bar

3. Under no circumstances must they be used to in systems containing liquids or solutions other than water. Theonly exception is the addition of a proprietary central heating corrosion inhibitor, cleaner or anti-freeze to thesystem water in accordance with the manufacturer’s instructions. 

4. Damage caused by abusive behaviour and accidental damage to the product are not covered by thisguarantee

The extent of Pegler Yorkshire liability is limited to the cost of the replacement of the defective item and not tofitting or consequential damages.

APPROVALS

Keymark License EN215

Page 4: TRV - mkmbs.co.uk · PDF fileTerrier thermostatic radiator valves are approved to EN 215. ... the manual shut off cap may be used for added security instead of the TRV head. In this
Page 5: TRV - mkmbs.co.uk · PDF fileTerrier thermostatic radiator valves are approved to EN 215. ... the manual shut off cap may be used for added security instead of the TRV head. In this

4. Range Limiting or Fixed Set Tem

peratureThe terrier TRV has the facility for fixing the thermal head at a set tem

pera-ture or to lim

it the range of operation. This is achieved by using the twopegs provided with the product.

To obtain a fixed set point, locate a peg in the slot either side of theselected setting and push hom

e.

To set a limited range for tem

perature control, first locate a peg in theslot to the right of the viewing window for the lowest tem

perature settingrequired. Adjust the valve head to display the m

aximum

temperature

desired. Locate a peg in the slot to the left side of the viewing window.Push both pegs hom

e. The head will now be adjustable between theselected range of tem

perature.

5. Frost ProtectionIf you plan to be away from

home for any length of tim

e the TRV can beturned to the frost protection setting “�

“. If the temperature falls below

7°C the valve will automatically open giving protection against freezing.

(Provided that the boiler remains in operation via a frost stat.)

6. Removal of Radiator

The “0” Setting on the TRV is a positive “Off” position. This will enable aradiator to be rem

oved for maintenance purposes.

To avoid accidental operating of the valve or damage whilst decorating

the manual shut off cap m

ay be used for added security instead of theTRV head. In this case, rem

ove the TRV sensor head by unscrewing thesecuring ring and replacing with the m

anual cap BEFORE removing the

radiator.

TW

OW

AYT

HERM

OSTAT

ICRA

DIAT

OR

VALVE

TW

OW

AYT

HERM

OSTAT

ICRA

DIAT

OR

VALVE

TEC

HN

ICA

L DATA

Temperature range

7°C - 28°CMaxim

um Test Pressure

20barMaxim

um Static Pressure

10bar at 120°CMaxim

um Differential Pressure

0.6barMaxim

um Water Flow Tem

perature120°C

Installation and User Guide

SENSOR HEAD

MANUAL SHUTOFF CAP

1/2” BSPTAIL

VALVE BODY STRAIGHTPegler Lim

ited, St. Catherines Avenue, Doncaster DN4 8DF.Telephone: 01302 560560 Fax: 01302 367661

VALVE BODY

terrier trv 8/9/04 2:25 pm Page 1

Page 6: TRV - mkmbs.co.uk · PDF fileTerrier thermostatic radiator valves are approved to EN 215. ... the manual shut off cap may be used for added security instead of the TRV head. In this

INSTA

LLATIO

ND

irections for use:A

ngle TRV

The universal terrier TRV is designed to operate with water flow in eitherdirection. The 15m

m size m

ay be fitted in either the horizontal OR verti-cal position. The m

ost effective position is to have the head in a horizon-tal position where the greatest efficiency will be obtained. Straight T

RVStraight bodied valves should not be used in the top connection of a radiator as heat from

the radiator will affect the sensor.C

orrect installationsCorrect installation and m

aximum

performance will be achieved if:

The thermostatic head is not concealed behind furniture, curtains or

drapes, hidden under shelves, panelling or in a recess where air pocketscan occur.The therm

ostatic head is not exposed to direct sunlight or draughts.

Fitting1. Thoroughly clean any pipe work to be connected to the valve.

2. Drain down existing system, connecting a hosepipe to the lowest drain

off point available.

3. Screw 1/2” BSP tail into radiator tapping, using suitable jointingm

aterial e.g. PTFE tape.

4. Connect valve body to tail and tighten nut.

5. Cut and fit copper tube to valve body - tightening nut and cone.

6. Remove m

anual shut off cap and store safely.

7. Turn Sensor head to indicate “5” in setting window.

8. Position sensor head so that setting window can be viewed and handtighten securing ring to valve body.

9. Set sensor head to required temperature setting.

10. When fitting a lock shield valve, this m

ust be set to control the waterflow through the radiator to the correct level.

PLEASENOTE: To avoid the problem

of hydronic (water flow) noise it is recomm

endedthat the differential pressure does not exceed 0.2 bar. It is stronglyrecom

meded that a differential pressure valve should be fitted to any sys-

tem with TRV’s (Pegler order code for differential pressure valve

678021/22mm

) will be suitable for most dom

estic installations. Largersizes are available if required.

USER IN

STRU

CT

ION

S1. O

perating Description

The influence of uncontrolled heat gains from cooking, lighting and sunshineetc., can lead to wasteful overheating. The terrier TRV is designed to react totemperature fluctuations and allow you to control individual room tempera-ture.

The sensor head contains a powerful wax-filled sensor which senses tempera-ture changes. These variations cause expansion and contraction of the ther-mal element which is transmitted to a valve seat which regulates the waterflow to the radiator

2. Setting the TRV

Initially set the TRV to the required room temperature from the table belowe.g. Position 3/ 20°C. The TRV should be left for at least 1 hour to allow thetemperature to stabilise. If a higher or lower room temperature is requiredsimply adjust the setting accordingly and repeat the process.

3. Temperature Settings

The TRV settings are factory calibrated as indicated in the table below.

0�

12

34

5Shut Off

7°C11-13°C

15-17°C19-21°C

23-25°C27-29°C

Note: These temperatures m

ay vary slightly, depending upon the natureof the installation

xStraight TRV

Angle TRV

terrier trv 8/9/04 2:25 pm Page 2