Bottom chord bracing and UL requirements Fact and FictionA popular sales tactic of many cold formed metal truss fabricators has been to claim that their truss system is less expensive because it does not require bottom chord bracing. This claim can be dispelled by referencing CFSEI Tech Note 551d which states that all trusses must have bottom chord bracing at 10oc maximum. Another claim made by some fabricators, one that is more difficult to dispel, is the idea that the bottom chord purlins that are typically fastened to the bottom of the bottom chord for drywall attachment can also act as the bottom chord bracing of the truss itself and no additional bracing material is required. On a 50,000 ft2 school in a low wind zone, this could amount nearly 500 pieces of hat channel and cause a difference in price of $3,500 in material alone. When communicating with your prospective truss fabricators understanding the code and the related UL listings becomes critical. A 1 hour rated ceiling can be used to eliminate the requirement of a fire sprinkler or will allow the fire sprinkler to provide a significant area increase, depending on the type of construction. In other words, for construction of types I-a, I-b, II-a or III-a a 1 hour (min) rated ceiling is a must. It is usually a safe assumption that most projects requiring cold formed steel trusses due to the non- combustibility are also projects that will require at least a 1 hour rated ceiling. A simple check to confirm this is by verifying the occupancy category calculations almost always given in the architectural drawings. Once you have verified the need for the rated ceiling assembly, you are able to consult with your fabricator based on accurate information. These two generic assemblies show the main elements of flat and sloped cold- formed steel truss assemblies Truss Notes Issue 1 10/20/2014

Upload: pete-wynnik

Post on 05-Apr-2016

215 views

Category:

Documents


0 download

DESCRIPTION

Understanding Fire Rated Cold-Formed Steel Truss Assemblies

TRANSCRIPT

Page 1: Truss Notes Issue 1 - Bottom Chord Bracing Fact & Fiction

Bottom chord bracing and UL requirements – Fact and Fiction… A popular sales tactic of many cold formed metal truss fabricators has been to claim that their truss system is less expensive because it does not require bottom chord bracing. This claim can be dispelled by referencing CFSEI Tech Note 551d which states that all trusses must have bottom chord bracing at 10’ oc maximum. Another claim made by some fabricators, one that is more difficult to dispel, is the idea that the bottom chord purlins that are typically fastened to the bottom of the bottom chord for drywall attachment can also act as the bottom chord bracing of the truss itself and no additional bracing material is required. On a 50,000 ft2 school in a low wind zone, this could amount nearly 500 pieces of hat channel and cause a difference in price of $3,500 in material alone. When communicating with your prospective truss fabricators understanding the code and the related UL listings becomes critical. A 1 hour rated ceiling can be used to eliminate the requirement of a fire sprinkler or will allow the fire sprinkler to provide a significant area increase, depending on the type of construction. In other words, for construction of types I-a, I-b, II-a or III-a a 1 hour (min) rated ceiling is a must. It is usually a safe assumption that most projects requiring cold formed steel trusses due to the non-combustibility are also projects that will require at least a 1 hour rated ceiling. A simple check to confirm this is by verifying the occupancy category calculations almost always given in the architectural drawings. Once you have verified the need for the rated ceiling assembly, you are able to consult with your fabricator based on accurate information.

These two generic assemblies show the main elements of flat and sloped

cold- formed steel truss assemblies

Truss Notes Issue 1

10/20/2014

Page 2: Truss Notes Issue 1 - Bottom Chord Bracing Fact & Fiction

Fire Rated Cold-Formed Steel Truss Assemblies

To properly design a building for fire safety, building designers must recognize and accurately follow building fire code regulations. Building codes may require construction assemblies to have a fire resistance rating such as 1 Hour, 1-½ Hour and 2 Hour in specific construction types and occupancies. The ratings represent the minimum length of time that a laboratory tested assembly maintained its structural integrity during standardized ASTM E119 fire conditions. At this point in time, Underwriters Laboratories Inc. (UL), is the only directory that lists cold-formed steel truss assemblies. The most current listings are available in UL Online Certification Directory at www.ul.com.

Typically in fire endurance assembly testing, a system is tested and then put to use in the field. The field applications must be identical to the tested assembly. Increases in the length, depth, and size of the actual structural members are allowed because they will perform better than the tested structural members. The single- most critical element in the fire endurance performance of an assembly is the protective membrane on the side of the assembly exposed to fire, which is typically fire rated gypsum board.

Restrained vs. Unrestrained Fire Rated Steel Truss Assemblies

Steel assemblies may be rated as restrained or unrestrained. These are two different test procedures to mimic two types of installations. ANSI/UL 263 defines these conditions: “Floor-ceiling and roof-ceiling assemblies and individual beams in buildings shall be considered restrained when the surrounding or supporting structure is capable of resisting substantial thermal expansion throughout the range of anticipated elevated temperatures. Constructions not complying with this definition are assumed to be free to rotate and expand and shall be therefore considered as unrestrained.” ASTM E119 Table 3.1 lists restrained and unrestrained construction systems. Note that restraint in fire testing is not the same as restraint in structural design.

Because of the more restrictive criteria, unrestrained assembly ratings may be used for floors and roofs designed for either restrained or unrestrained conditions. The decision on whether to use a restrained or unrestrained steel truss assembly will depend on what the building designer and building code requires. Only the UL “Lxxx” assemblies do not list both a restrained and unrestrained rating.

Summaries The following tables are summaries to aid in steel truss assembly selection. Always consult the full current listings for complete assembly information.

Page 3: Truss Notes Issue 1 - Bottom Chord Bracing Fact & Fiction

Rating Illustration Construction UL Report Number

FLOOR

1 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc, 12” oc with insulation Ceiling insulation optional 1x4 T&G, 15/32” panel, or 3/4” topping on 23/32”

subfloor; or mineral or fiber board on subfloor

L549, L551, L552, L553, L559, L560 L565

1 Hr Restrained 1 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc, 12” oc with insulation Ceiling insulation optional Metal lath, welded wire fabric, and normal or

lightweight concrete

G540, G542, G543, G544, G545, G546

2 Hr Restrained 2 Hr Unrestrained

Max. 48” oc truss spacing 2 layers 5/8” Type C gypsum Resilient channel 16” oc Ceiling insulation not allowed Metal lath, welded wire fabric, and normal or

lightweight concrete

G540

2 Hr Restrained 2 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc Ceiling insulation not allowed Metal lath, welded wire fabric, and normal or

lightweight concrete

G545

ROOF

1 Hr Restrained 1 Hr Unrestrained

Max. 48” oc truss spacing Min. depth 11-7/8” or 5” with a min. 3/12 slope 2 layers 5/8” Type X gypsum (Type C, if insul.

within 1” of gyp.) Resilient channel 24” oc, not req. for trusses

spaced max. 24” oc Ceiling insulation optional. Roof insulation

required Roof covering, roof membrane or metal roof deck

panel; steel roof deck; gypsum board

P515, P541

1 Hr Restrained 1 Hr Unrestrained

Max. 48” oc truss spacing Min. depth 11-7/8” or 8” with a min. 3/12 slope 2 layers 5/8” Type X gypsum Resilient channel 24” oc, not req. for trusses

spaced max. 24” oc Ceiling insulation required. Roof insulation not

allowed Roof covering, roof membrane or metal roof deck

panel; steel roof deck; gypsum board

P524

1 Hr Restrained 1 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc, 12” oc with insulation Ceiling insulation optional. Roof insulatin may be

required UL Class A, B, C roofing system or prepared roof

covering on 23/32” panel; steel roof deck, or for P523, P534, P537 only, steel floor and form units. P526, P528 and P530 allow 15/32” panel with trusses 24” oc and min. 9-½” ceiling insulation

P523, P526, P528, P530, P534, P537

Page 4: Truss Notes Issue 1 - Bottom Chord Bracing Fact & Fiction

Rating Illustration Construction UL Report Number

1-1/2 Hr Restrained 1-1/2 Hr Unrestrained

Max. 48” oc truss spacing 2 layers 5/8” Type X gypsum Resilient channel 12” oc Minimum 9-½” ceiling insulation. Roof insulation

may be required UL Class A, B, C roofing system or prepared roof

covering on 23/32” panel; steel roof deck, or for P523, P534, P537 only, steel floor and form units. P526 allows 15/32” panel with trusses 24” oc

P523, P526, P534, P537

1 Hr Unrestrained 1 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc No ceiling insulation. Roof insulation required, no

minimum thickness Steel roof deck; cementitious backer or gypsum

board; roof covering, membrane or metal deck panel

P527, P529

1-1/2 Hr Restrained 1-1/2 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc No ceiling insulation, Minimum 2” roof insulation Steel roof deck; cementitious backer or gypsum board; roof covering, membrane or metal roof deck panel

P527, P529

1 Hr Restrained 1 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc No ceiling insulation, Roof insulation minimum

thickness may be required Steel floor and form units, min. gauge varies;

cementitious backer or gypsum board; roof covering, membrane or metal roof deck panel

P521, P525, P532, P536, P540

1-1/2 Hr Restrained 1-1/2 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc No ceiling insulation, min. thickness roof

insulation required Steel floor and form units, min. 22 gauge;

cementitious backer or gypsum board; roof covering, membrane or metal roof deck panel

P521, P525, P532, P536

2 Hr Restrained 2 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc No ceiling insulation, min. thickness roof

insulation required Steel floor and form units, min. 22 gauge;

cementitious backer or gypsum board; roof covering, membrane or metal roof deck panel

P532

2 Hr Restrained 2 Hr Unrestrained

Max. 48” oc truss spacing 2 layers 5/8” Type C gypsum Resilient channel 16” oc No ceiling insulation, min. thickness roof

insulation required Steel floor and form units, min. 22 gauge;

cementitious backer or gypsum board; roof covering, membrane or metal roof deck panel

P521, P525, P536

Page 5: Truss Notes Issue 1 - Bottom Chord Bracing Fact & Fiction

Cold-formed Steel Truss Assemblies by CF Steel, LLC Floor-Ceiling: G540, L549, L565 Roof-Ceiling: P521, P523, P540

Product Substitutions Where branded products are specified in assemblies, product substitutions are not allowed. Where generic product categories are listed, substitutions of products within the category with equal or greater specifications may be allowed.

Gypsum Board Specifications “Regular” gypsum board has a naturally occurring fire resistance from the gypsum used as its core. “Type X” gypsum board has additives to the core that increase the fire resistance of regular gypsum board. “Improved Type X” (often referred to as “Type C”) has been improved with additives which further enhance the fire resistive characteristics. “Improved Type X” can be substituted for “Type X”, but not the reverse. Gypsum may be listed as generic or as proprietary.

Type X: FSW= NGC Fire-Shield SCX= USG FIRECODE Core IP-X1= USG Plaster Base (Type X)

Improved Type X (Type C or G): FSW-C= NGC FireShield C FSW-G = NGC FireShield G C= USG FIRECODE C Core IP-X2= USG Plaster Base (Type C) IPC-AR = USG Plaster Base C (Abuse Resistant)

Category (CKNX), per UL/ANSI 263, section 9. Gypsum Board: “For designs containing the statement ‘See Gypsum Board (CKNX) Category for names of Classified Companies,’ any product in the Category (CKNX) that meets the specifications (i.e. thickness, size, etc.) described in the design may be used.”

References Fire Resistance Directory, Underwriters Laboratories Inc., Northbrook, IL. www.ul.com. ASTM E119-98. “Standard Test Methods for Fire Tests of Building Construction and Materials”, American Society for

Testing and Materials (ASTM), West Conshohocken, PA. 1998. www.astm.org. SA100 Construction Selector (rev.3-02). United States Gypsum Company, Chicago, IL. www.usg.com. Gypsum Construction Guide, 7th Edition (rev. 8/2001). National Gypsum Company, Charlotte, NC. www.nationalgypsum.com

Tim Liescheidt, P.E. Mobile: (704) 516-1750

[email protected]

Pete Wynnik / Technical Services Mobile: (501) 413-6154

[email protected]

Page 6: Truss Notes Issue 1 - Bottom Chord Bracing Fact & Fiction

At CF-Steel, we offer personalized service. While we welcome phone calls and faxes regarding bids, we are making continual efforts to streamline our bid process and provide convenience to our customers. Please feel free to submit bid submissions by email to [email protected] or contact one of our representatives below: Tim Liescheidt / Managing Partner Chrissy Liescheidt / Director of Sales [email protected] [email protected] Mobile: (704) 516-1750 Direct: (704) 737-8023 Scott Dickson / Sales Representative Adrian Kennedy / Sales Representative Mobile: (704) 340-7724 Mobile: (704) 322-9270 [email protected] [email protected]

Head Quarters &

Primary Manufacturing Facility 152 American Drive Oakboro, NC 28129 Ph: (704) 485-2234 Fax: (704) 485-5750 www.cf-steel.com

Arkansas Sales Office & Manufacturing Facility 23389 Hwy 64

Knoxville, AR 72485

NY Design & Technical Sales Office 28 Champlain St.

Rouses Point, NY 12979 Ph: (518) 206-4075