PRINCIPAIS PONTOS NORMAS TRANSFORMADORES SECO IEEE C57.12.01-1989 (trecho citado no item 7.2 da norma IEEE C57.12.91-1995) 9. Tolerances 9.1 Ratio. With rated voltage impressed on one winding of a transformer, all other rated voltages at no load shall be correct within 0,5% of the name plate markings. Rated tap voltages shall correspond to the voltage of the nearest turn if the voltage per turn exceeds 0,5% of the desired voltage. 9.2 Impedance. The tolerances for impedance shall be as follows: (1) The impedance of a two-winding transformer shall have a tolerance of +/- 7,5% of the specified value. Differences of impedance between two duplicate two-winding transformers, when two or more units of a given rating are produced by one manufacturer at the same time, shall not exceed 7,5% of the specified value. (2) The impedance of transformers having three or more windings or having three or more windings or having zigzag windings shall have a tolerance of +/-10% of the specified value. Differences of impedance between duplicate three-winding or zigzag transformers, when two or more units of a given rating are produced by one manufacturer at the same time, shall not exceed 10% of the specified value. (3) The impedance of an autotransformer shall have a tolerance of +/-10% of the specified value. Differences of impedance between duplicate autotransformer, when two or more units of a given rating are produced by one manufacturer at the same time, shall not exceed 10% of the specified value. (4) Transformers shall be considered suitable for operation in parallel if their resistance and reactances come within the limitations of 9.2 (1) through 9.2 (3), provided turn ratios and other controlling characteristics are suitable for such operation.

Upload: diego-andrade

Post on 18-Aug-2015

216 views

Category:

Documents


0 download

DESCRIPTION

Principais trechos da norma IEEE de transformadores a seco.

TRANSCRIPT

PRINCIPAIS PONTOS NORMAS TRANSFORMADORES SECOIEEE C57.12.01-1989 (trecho citado no item 7.2 da norma IEEE C57.12.91-1995)9. Tolerances 9.1 Ratio. ith rated !olta"e im#ressed on one $indin" o% a trans%ormer& all other rated !olta"es at no load shall 'e correct $ithin 0&5( o% the name #late mar)in"s. Rated ta# !olta"es shall corres#ond to the !olta"e o% the nearest t*rn i% the !olta"e #er t*rn e+ceeds 0&5( o% the desired !olta"e.9.2 Im#edance. The tolerances %or im#edance shall 'e as %ollo$s,(1) The im#edance o% a t$o-$indin" trans%ormer shall ha!e a tolerance o% -.- 7&5( o% the s#eci/ed !al*e. 0i1erences o% im#edance 'et$een t$o d*#licate t$o-$indin" trans%ormers& $hen t$o or more *nits o% a "i!en ratin" are #rod*ced '2 one man*%act*rer at the same time& shall not e+ceed7&5( o% the s#eci/ed !al*e.(2) The im#edance o% trans%ormers ha!in" three or more $indin"s or ha!in" three or more $indin"s or ha!in" 3i"3a" $indin"s shall ha!e a tolerance o% -.-10( o% the s#eci/ed !al*e. 0i1erences o% im#edance 'et$een d*#licate three-$indin" or 3i"3a" trans%ormers& $hen t$o or more *nits o% a "i!en ratin" are #rod*ced '2 one man*%act*rer at the same time& shall not e+ceed10( o% the s#eci/ed !al*e.(4) The im#edance o% an a*totrans%ormer shall ha!e a tolerance o% -.-10( o% the s#eci/ed !al*e. 0i1erences o% im#edance 'et$een d*#licate a*totrans%ormer& $hen t$o or more *nits o% a "i!en ratin" are #rod*ced '2 one man*%act*rer at the same time& shall not e+ceed 10( o% the s#eci/ed !al*e.(5) Trans%ormers shall 'e considered s*ita'le %or o#eration in #arallel i% their resistance and reactances come $ithin the limitations o% 9.2 (1) thro*"h 9.2 (4)& #ro!ided t*rn ratios and other controllin" characteristics are s*ita'le %or s*ch o#eration.9.4 6osses. the losses re#resented '2 testin" a trans%ormer& or trans%ormers&on a "i!en order shall not e+ceed the s#eci/ed losses '2 more than the #ercenta"es "i!en in Ta'le 8.IEEE C57.12.91-1995...10.9 Ins*lation-resistance testsIns*lation-resistance tests are made to determine the ins*lation resistance %rom indi!id*al $indin"s to "ro*nd& or 'et$een indi!id*al $indin"s. The ins*lation resistance in s*ch tests is commonl2 meas*red in me"ohms '*t ma2 'e calc*lated %rom meas*rements o% a##lied !olta"e and lea)a"e c*rrent.Ins*lation-resistance tests shall 'e made $hen s#eci/ed. The ins*lation resistance o% electrical a##arat*s is o% do*'t%*l si"ni/cance as com#ared $ith the dielectric stren"th. It is s*'7ect to $ide !ariation $ith desi"n& tem#erat*re& dr2ness& and cleanliness o% the #arts. hen the ins*lation resistance %alls 'elo$ #rescri'ed !al*es& it can& in most cases& i% it is o% "ood desi"n and has no de%ect& 'e 'ro*"ht *# to the #rescri'ed !al*e '2 cleanin"and dr2in" the a##arat*s. The ins*lation resistance& there%ore& ma2 a1ord a *se%*l indication as to $hether the a##arat*s is in s*ita'le condition %or a##lication o% the dielectric test.89TE:,1 ; The si"ni/cance o% !al*es o% ins*lation-resistance tests "enerall2 rell $indin"s short-circ*itedc) >ll '*shin"s or terminals in #laced) Trans%ormer tem#erat*re a##ro+imatel2 20 ?C10.9.2 Instr*mentationIns*lation resistance ma2 'e meas*red *sin" either o% the %ollo$in",a) > !aria'le-!olta"e dc #o$er s*##l2 $ith means to meas*re !olta"e and c*rrent ("enerall2 in micro-am#eres or milliam#eres)') > me"ohmmeter 89TE ; @e"ohmmeter are commonl2 a!aila'le $ith nominal !olta"es o% 500 A& 1000 A& and 2500 A. 0C a##lied test ell connections shall ma)e"ood mechanical 7oints $itho*t %ormin" shar# corners or #oints. :mall 'are $ire ma2 'e *sed in connectin" the res#ecti!e ta#s and line terminals to"ether& '*t care shall 'e ta)en to )ee# the $ire on the hi"h-!olta"e side $ell a$a2 %rom the "ro*nd. 8o a##recia'le resistance sho*ld 'e #laced 'et$een the testin" trans%ormer and the one *nder test. It is #ermissi'le& ho$e!er& to *se reacti!e coils at or near the terminals o% the testin" trans%ormer. > relie% "a# set at a !olta"e 10( or more in e+cess o% the s#eci/ed test !olta"e ma2 'e connected d*rin" the a##lied-!olta"e test.10.4.5 Aolta"e rate o% riseThe !olta"e sho*ld 'e started at one-%ter 'ein" held %or the time s#eci/ed& it sho*ld 'e red*ced "rad*all2 (in not more than 5 s) to one