treasurer agenda.pdf · protecto 401 shall not be applied over protecto 401 joint compound. joint...

36
THE REGIONAL BUILDING . 723 WOODLAKE DRIVE . CHESAPEAKE, VIRGINIA 23320 . (757) 420-8300 The next Full Committee meeting for the Regional Construction Standards is scheduled for March 27, 2018 at 9:30 A.M. in the HRPDC Board Room D/E, The Regional Building, 723 Woodlake Drive, Chesapeake. The agenda for the Full Committee meeting will include: 1. Welcome 2. Historical Usage/Locality Feedback 3. Training Program Update 4. Request for Locality Special Provisions 5. VDOT Initiative 6. Video Conferencing 7. Approval of Proposed Revisions PR 6.1 – Ductile Iron Pipe Protections PR 6.2 – Concrete Curb Sliplining PR 6.3 – Pipe Bursting PR 6.4 – Fusible PVC Pipe PR 6.5 – Storm Sewer Joint Wrap PR 6.6 – ASTM Reference for Hydrophilic Lateral Seals 8. New Business 9. Adjournment Please make arrangements for you or your designated alternate to attend. Copy: Whitney Katchmark - HRPDC Robert Sciacchitano – CDM Smith Date: February 27, 2018 To: Regional Construction Standards - Full Committee From: Richard Nettleton, Full Committee Chairman Subject: Full Committee Meeting ROBERT A. CRUM, JR., EXECUTIVE DIRECTOR/SECRETARY ELLA P. WARD, CHAIR . MICHAEL J. HIPPLE, VICE-CHAIR .R. RANDY MARTIN, TREASURER

Upload: others

Post on 12-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

THE REGIONAL BUILDING . 723 WOODLAKE DRIVE . CHESAPEAKE, VIRGINIA 23320 . (757) 420-8300

The next Full Committee meeting for the Regional Construction Standards is scheduled for March 27, 2018 at 9:30 A.M. in the HRPDC Board Room D/E, The Regional Building, 723 Woodlake Drive, Chesapeake.

The agenda for the Full Committee meeting will include:

1. Welcome 2. Historical Usage/Locality Feedback 3. Training Program Update 4. Request for Locality Special Provisions 5. VDOT Initiative 6. Video Conferencing 7. Approval of Proposed Revisions

• PR 6.1 – Ductile Iron Pipe Protections • PR 6.2 – Concrete Curb Sliplining • PR 6.3 – Pipe Bursting • PR 6.4 – Fusible PVC Pipe • PR 6.5 – Storm Sewer Joint Wrap • PR 6.6 – ASTM Reference for Hydrophilic Lateral Seals

8. New Business 9. Adjournment

Please make arrangements for you or your designated alternate to attend. Copy: Whitney Katchmark - HRPDC

Robert Sciacchitano – CDM Smith

Date: February 27, 2018 To:

Regional Construction Standards - Full Committee

From:

Richard Nettleton, Full Committee Chairman

Subject:

Full Committee Meeting

ROBERT A. CRUM, JR., EXECUTIVE DIRECTOR/SECRETARY

ELLA P. WARD, CHAIR . MICHAEL J. HIPPLE, VICE-CHAIR .R. RANDY MARTIN, TREASURER

Page 2: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision Form

March 22, 2012

Proposed Revision To:

General Provisions (Division 1)

Technical Specifications (Divisions 2-8)

Standard Details

Change No.

6.1

(ASSIGNED BY TECHNICAL REVIEW COMMITTEE)

Hampton Roads Planning District Commission

723 Woodlake Drive

Chesapeake, VA 23320 (Phone: 757-420-8300)

Date Proposal Received

October 16, 2017

(ASSIGNED BY TECHNICAL REVIEW COMMITTEE)

Subsection or Standard Detail to be Revised: 200.5.10. A.11 On page(s): 200-14

Proposed Revision:

Replace, “Section 200.5.10.A.11 - Corrosion Resistant Linings” with the following:

11. Corrosion Resistant Linings

a. Ductile iron pipe and fittings shall be lined with ceramic epoxy coating, as specified

below. Acceptable products shall be Protecto 401, Permox CTF, or approved equal.

(i) The corrosion resistant linings shall be a ceramic-filled amine-cured novalac

epoxy lining containing at least 20% by volume of ceramic quartz pigment.

(ii) The lining shall be shop applied to bare metal in strict accordance with the

manufacturer’s recommendations to cover the inner surface of the pipe and

fittings. The lining shall be a nominal thickness of 40 mils and a minimum

thickness of 35 mils.

(iii) Due to the tolerances involved, the gasket groove and spigot end, up to 6

inches back from the end of the spigot end, must be coated with 6 mils

nominal, 10 mils maximum dry film thickness of the lining manufacturer’s

un-reduced Joint Compound. The Joint Compound shall be applied by brush

and care shall be taken to ensure the coating is smooth and without excess

buildup in the gasket seat/groove and on the spigot end. Coating of the gasket

seat/groove and spigot ends shall be done after the application of the lining of

the pipe barrel.

(iv) The gasket area and spigot end up to 6-inches back from the end of the spigot on

the outside of the pipe shall be coated with 6 mils nominal, and 10 mils

maximum. The following tests must be run on coupons from factory lined

ductile iron:

1.) ASTM G-95 Cathodic Disbondment 1.5 volts @ 77°F. Results to

equal no more than 0.5 mm undercutting and/or disbondment after

30 days.

2.) Immersion testing rated using ASTM D-714-87

i. 20% Sulfuric acid—No effect after two years.

ii. 140° F 25% Sodium Hydroxide—No effect after two years.

iii. 160° F Distilled Water—No effect after two years.

3.) ASTM D-4060 Abrasion Resistance shall not exceed a weight loss of

more than 0.30 grams (CS17 Wheel, 1000- gram load, 1000 cycles).

4.) ASTM B-117 Salt Spray (scribed panel) – Results to equal 0.0

Page 3: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision Form

March 22, 2012

undercutting after two years.

(v) Surface Preparation:

All pipe and fittings shall be delivered to the application facility without

cement or asphalt lining or any other lining on the interior surface. Because

total removal of old linings is generally not possible nor cost effective, the

intent of this specification is that the entire interior of the DIP and fittings

shall be as cast without any lining material prior to application of the

specified lining.

(vi) Applicator Requirements

a) The application shall be performed by an applicator and/or certified

firm approved by the coating manufacturer, in accordance with the

manufacturer’s instructions and under controlled conditions at the

applicator’s shop or pipe manufacturer’s plant. The lining shall be

applied by a certified applicator and/or firm with a successful history

of applying linings to the interior of ductile iron pipe and fittings.

b) All applicators must be independently inspected at least two times per

year to insure compliance with the requirements of this specification.

This inspection must be coordinated and reviewed by the

manufacturer of the lining material and any deviation from the

application and/or quality requirements shall be corrected by the

applicator. All inspections shall be in writing and a permanent

record maintained.

(vii) Lining

(1) Upon completion of the blast cleaning operation, the lining material

should be applied to the interior of the pipe within 12 hours in order

to avoid any possible post blast surface contamination. Any area

found to have rust bloom prior to application must be reblasted.

(2) Where field touch up is required to seal cut ends and repair damaged

areas, Joint Compound shall be applied by brush to ensure complete

coverage in accordance with the manufacturer’s recommendations. Joint

Compound may be used over lined pipe and fittings, or on bare substrate.

Care must be taken that the joint compound is applied smooth, without

excessive buildup in the gasket seat or on the spigot ends and allowed to

cure for 24 hours in accordance with the manufacturer’s

recommendations. At least 1-inch of overlap shall be applied to the area

being repaired. The ceramic-filled amine-cured novalac epoxy lining

Protecto 401 shall not be applied over Protecto 401 Joint Compound.

Joint Compound shall not be applied over wet or frozen surfaces.

(viii) Factory Inspection and Certification

(1) The lining in each joint of pipe and fittings shall be tested for pin

holes and pass a non-destructive 2,500-volt pin hole/holiday test. The

pin hole/holiday detection testing shall be conducted over 100% of all

lined surfaces for the ductile iron pipe and fittings. All holidays shall

be repaired in accordance with the manufacturer’s instructions and

tested again to ensure a pinhole free lining. Short lengths of pipe

required to accommodate the pipeline geometry shall be furnished

Page 4: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision Form

March 22, 2012

factory-lined.

(2) Dry film thickness determination for the interior lining of all pipe

and fittings shall be checked for thickness using a properly calibrated

magnetic film thickness gauge. The thickness testing shall be done

using the method outlined in SSPC PA-2 Film Thickness Rating.

(3) The pipe or fitting manufacturer must supply a written certificate

attesting to the fact that the applicator met the requirements of this

specification, that the material used was as specified, and that the

material was applied as required by the specification.

The lining in each joint of pipe and fitting shall pass a 2,500 volt pin

hole/holiday test. The pin hole/holiday detection testing shall be

conducted over 100% of all lined surfaces for the ductile iron pipe and

fittings. All holidays shall be repaired in accordance with the

manufacturer’s instructions and tested again to ensure a pinhole free

lining. Short lengths of pipe required to accommodate the pipeline

geometry shall be furnished factory-lined. All outlets shall be tapped by

the pipe manufacturer at the factory prior to applying the pipe lining.

Also,

Modify 5.10.A. as follows:

8. AWWA C105 – Polyethylene Encasement and V-Bio Enhanced Polyethylene Encasement for

Ductile-Iron Pipe Systems.

9. Coatings shall be provided on the exterior of all pipe, joints and fittings as required by AWWA/ANSI

C110/A21.10, C111/A21.11, C115/A21.15, C116/A21.16, C151/A21.51, or C153/A21.53 as

applicable. All pipes, joints, and fittings shall be examined after laying to determine if the coating was

damaged during installation. Any damaged areas shall be coated with an Owner-approved coating in

accordance with the manufacturer’s recommendations. with a minimum of 2 mils of an approved

bituminous coating

If required in the Contract Documents, the exterior of the pipe shall be coated with a layer of

arc-sprayed zinc in accordance with ISO 8179. The mass of zinc applied shall be 200 g/m2 of pipe

surface area. A finishing layer topcoat shall be applied to the zinc. The mean dry film thickness

of the finishing layer shall not be less than 3 mils with a local minimum not less than 2 mils. The

zinc coating system shall conform to ISO 8179-1 “Ductile iron pipes – External zinc-based

coating – Part 1: Metallic zinc with finishing layer (Second Edition 2004-06-01)

Modify 5.10. G. as follows:

a. Push-on Joints

For push–on joint type pipe, the restrained joint system shall be a manufacturer’s standard

restrained joint system SnapLock (U.S.Pipe), Lok Ring (American Pipe), TR Flex (U.S. Pipe),

FlexRing (American Pipe), or approved equal.

Modify 5.19 A. as follows:

6. Coatings shall be provided on the exterior of all pipe, joints and fittings as required by AWWA/ANSI

C110/A21.10, C111/A21.11, C115/A21.15, C116/A21.16, C151/A21.51, or C153/A21.53 as

applicable. All pipes, joints, and fittings shall be examined after laying to determine if the coating

was damaged during installation. Any damaged areas shall be coated with an Owner-approved

coating in accordance with the manufacturer’s recommendations. with a minimum of 2mils of an

Page 5: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision Form

March 22, 2012

approved bituminous coating

If required in the Contract Documents, the exterior of the pipe shall be coated with a layer of

arc-sprayed zinc in accordance with ISO 8179. The mass of zinc applied shall be 200 g/m2 of pipe

surface area. A finishing layer topcoat shall be applied to the zinc. The mean dry film thickness

of the finishing layer shall not be less than 3 mils with a local minimum not less than 2 mils. The

zinc coating system shall conform to ISO 8179-1 “Ductile iron pipes – External zinc-based

coating – Part 1: Metallic zinc with finishing layer (Second Edition 2004-06-01)

12. AWWA C105 – Polyethylene Encasement and V-Bio Enhanced Polyethylene Encasement for

Ductile-Iron Pipe Systems

Modify 5.19.K.2 as follows:

a. Push-on Joints

For push–on joint type pipe, the restrained joint system shall be a manufacturer’s standard

restrained joint system SnapLock (U.S.Pipe), Lok Ring (American Pipe), TR Flex (U.S. Pipe),

FlexRing (American Pipe), Series 3000 Stargrip wedge action restraint (Star Pipe Products) or

approved equal.

Modify 801. 2.2.E (Page 801-6) as follows:

E. Polyethylene Encasement:

1. Pipe shall be encased with polyethylene or V-Bio Enhanced polyethylene where specified in the

Contract Documents.

2. In the event that corrosive soils (as defined by Appendix “A” of ANSI/AWWA C105/A21.5) are

encountered during excavation (and have not been identified as such in the Contract Documents),

the Owner may direct that all, or a portion, of the pipeline be encased.

3. Materials and methods of installation shall be in accordance with ANSI/AWWA C105; Method A,

B, or C may be used unless otherwise specified in the Contract Documents. Polyethylene shall be

at least 4 mils thick, cross laminated, and shall conform to the requirements of ANSI/AWWA

C105/A21.5. V-Bio Enhanced polyethylene shall be at least 8 mils thick.

Modify 803. 2.2.E (Page 803-5 and 803-6) as follows:

E. Polyethylene Encasement:

1. Pipe shall be encased with polyethylene or V-Bio Enhanced polyethylene where specified in the

Contract Documents.

2. In the event that corrosive soils (as defined by Appendix “A” of ANSI/AWWA C105/A21.5) are

encountered during excavation (and have not been identified as such in the Contract Documents),

the Owner may direct that all, or a portion, of the pipeline be encased.

3. Materials and methods of installation shall be in accordance with ANSI/AWWA C105; Method A,

B, or C may be used unless otherwise specified in the Contract Documents. Polyethylene shall be

at least 4 mils thick, cross laminated, and shall conform to the requirements of ANSI/AWWA

C105/A21.5. V-Bio Enhanced polyethylene shall be at least 8 mils thick.

Page 6: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision Form

March 22, 2012

Reason for Revision:

To allow Permox CTF as an alternate lining product to Protecto 401 (by Induron) for sanitary sewer force main pipe. Also, included

updated technology for ductile iron pressure pipes.

Special Considerations or Restrictions in Usage/Construction: Yes No (If yes, explain below)

Performance History: List at least five locations where the material or procedure has been used successfully. Include

contact individuals and phone numbers.

Location Contact Phone No

HRSD – Coatings Ann Copeland 833-7472

Norfolk DU - Coatings Selo Qejvani 664-6773

Submitted By: HRPDC Regional Construction Standards Address:

Agency: Technical Review Committee

Phone No:

Instructions: Use a separate form for each revision. Provide exact wording. Cite applicable Standards and Test Designations

(ASTM, AWWA, AASHTO, etc.) For minor changes, copy present wording using strike through for words to be

deleted and bold new text. For major changes, rewrite or add paragraphs/sections. Attach plain paper to this form if

more space is needed. Reason for change MUST be given.

TRC Action: February 7, 2018 (Date)

Recommended for:

Approval as submitted

Approval as modified by TRC

Denial

Page 7: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 14

Proposed Revision 6.1

7. ASTM A674 – Standard Practice for Polyethylene Encasement for Ductile Iron Pipe

for Water or Other Liquids.

8. AWWA C105 - Polyethylene Encasement and V-Bio Enhanced Polyethylene

Encasement for Ductile-Iron Pipe Systems

9. Coatings shall be provided on the exterior of all pipe, joints and fittings as required by

AWWA/ANSI C110/A21.10, C111/A21.11, C115/A21.15, C116/A21.16,

C151/A21.51, or C153/A21.53 as applicable. All pipes, joints, and fittings shall be

examined after laying to determine if the coating was damaged during installation.

Any damaged areas shall be coated with an Owner-approved coating in accordance

with the manufacturer’s recommendations a minimum of 2 mils of an approved

bituminous coating.. If required in the Contract Documents, the exterior of the

pipe shall be coated with a layer of arc-sprayed zinc in accordance with ISO 8179.

The mass of zinc applied shall be 200 g/m2 of pipe surface area. A finishing layer

topcoat shall be applied to the zinc. The mean dry film thickness of the finishing

layer shall not be less than 3 mils with a local minimum not less than 2 mils. The

zinc coating system shall conform to ISO 8179-1 “Ductile iron pipes – External

zinc-based coating – Part 1: Metallic zinc with finishing layer (Second Edition

2004-06-01)

10. Pipe diameters 12-inches and smaller shall be gaged and delivered round and true

throughout its entire length. Pipe diameters over 12-inches shall have one piece of

gaged pipe delivered for each fitting and at connections to existing pipelines. Gaged

pieces shall be marked on the pipe with markings indicated in the shop drawings.

11. Corrosion Resistant Linings

a. All ductile iron pipe and fittings shall be seal coated in accordance with

ANSI/AWWA C104/A21.4.

a. Ductile iron pipe and fittings shall be lined with ceramic epoxy coating as

specified below. Acceptable products shall be Protecto 401, Permox CTF,

or approved equal.

(i) The corrosion resistant linings shall be a ceramic-filled amine-

cured novalac epoxy lining containing at least 20% by volume of

ceramic quartz pigment.

(ii) The lining shall be shop applied to bare metal in strict accordance with

the manufacturer’s recommendations to cover the inner surface of the

pipe and fittings. The lining shall be a nominal thickness of 40 mils

and a minimum thickness of 35 mils.

(iii) Due to the tolerances involved, the gasket groove and spigot end,

up to 6 inches back from the end of the spigot end, must be coated

with 6 mils nominal, 10 mils maximum dry film thickness of the

lining manufacturer’s un-reduced Joint Compound. The Joint

Compound shall be applied by brush and care shall be taken to

ensure the coating is smooth and without excess buildup in the

gasket seat/groove and on the spigot end. Coating of the gasket

Page 8: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 15

Proposed Revision 6.1

seat/groove and spigot ends shall be done after the application of

the lining of the pipe barrel.

(iv) The gasket area and spigot end up to 6-inches back from the end of

the spigot on the outside of the pipe shall be coated with 6 mils

nominal, and 10 mils maximum.The following tests must be run on

coupons from factory lined ductile iron:

a) ASTM G-95 Cathodic Disbondment 1.5 volts @ 77°F.

Results to equal no more than 0.5 mm undercutting

and/or disbondment after 30 days.

b) Immersion testing rated using ASTM D-714-87

i. 20% Sulfuric acid—No effect after two years.

ii. 140° F 25% Sodium Hydroxide—No effect after

two years.

iii. 160° F Distilled Water—No effect after two years.

c) ASTM D-4060 Abrasion Resistance shall not exceed a

weight loss of more than 0.30 grams (CS17 Wheel, 1000-

gram load, 1000 cycles).

d) ASTM B-117 Salt Spray (scribed panel) – Results to equal

0.0 undercutting after two years.

(v) Surface Preparation:

All pipe and fittings shall be delivered to the application facility

without cement or asphalt lining or any other lining on the

interior surface. Because total removal of old linings is generally

not possible nor cost effective, the intent of this specification is

that the entire interior of the DIP and fittings shall be as cast

without any lining material prior to application of the specified

lining.

(vi) Applicator Requirements

a) The application shall be performed by an applicator

and/or certified firm approved by the coating

manufacturer, in accordance with the manufacturer’s

instructions and under controlled conditions at the

applicator’s shop or pipe manufacturer’s plant. The

lining shall be applied by a certified applicator and/or

firm with a successful history of applying linings to the

interior of ductile iron pipe and fittings.

b) All applicators must be independently inspected at least

two times per year to insure compliance with the

requirements of this specification. This inspection must be

coordinated and reviewed by the manufacturer of the

lining material and any deviation from the application

Page 9: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 16

Proposed Revision 6.1

and/or quality requirements shall be corrected by the

applicator. All inspections shall be in writing and a

permanent record maintained.

(vii) Lining

a) Upon completion of the blast cleaning operation, the

lining material should be applied to the interior of the

pipe within 12 hours in order to avoid any possible post

blast surface contamination. Any area found to have rust

bloom prior to application must be reblasted.

b) Where field touch up is required to seal cut ends and repair

damaged areas, Joint Compound shall be applied by brush to

ensure complete coverage in accordance with the

manufacturer’s recommendations. Joint Compound may be

used over lined pipe and fittings, or on bare substrate. Care

must be taken that the joint compound is applied smooth,

without excessive buildup in the gasket seat or on the spigot

ends and allowed to cure for 24 hours in accordance with the

manufacturer’s recommendations. At least 1-inch of overlap

shall be applied to the area being repaired. Protecto 401The

ceramic-filled amine-cured novalac epoxy lining shall not

be applied over Protecto 401 Joint Compound. Joint

Compound shall not be applied over wet or frozen surfaces.

(viii) Factory Inspection and Certification

a) The lining in each joint of pipe and fittings shall be tested

for pin holes and pass a non-destructive 2,500-volt pin

hole/holiday test. The pin hole/holiday detection testing

shall be conducted over 100% of all lined surfaces for the

ductile iron pipe and fittings. All holidays shall be

repaired in accordance with the manufacturer’s

instructions and tested again to ensure a pinhole free

lining. Short lengths of pipe required to accommodate the

pipeline geometry shall be furnished factory-lined.

b) Dry film thickness determination for the interior lining of

all pipe and fittings shall be checked for thickness using a

properly calibrated magnetic film thickness gauge. The

thickness testing shall be done using the method outlined

in SSPC PA-2 Film Thickness Rating.

c) The pipe or fitting manufacturer must supply a written

certificate attesting to the fact that the applicator met the

requirements of this specification, that the material used

was as specified, and that the material was applied as

required by the specification.

Page 10: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 17

Proposed Revision 6.1

The lining in each joint of pipe and fitting shall pass a 2,500 volt pin

hole/holiday test. The pin hole/holiday detection testing shall be conducted

over 100% of all lined surfaces for the ductile iron pipe and fittings. All

holidays shall be repaired in accordance with the manufacturer’s instructions

and tested again to ensure a pinhole free lining. Short lengths of pipe required

to accommodate the pipeline geometry shall be furnished factory-lined. All

outlets shall be tapped by the pipe manufacturer at the factory prior to applying

the pipe lining.

12. Each length of ductile iron pipe shall be hydrostatically tested at the point of

manufacture to 500 psi for a duration of 10 seconds per AWWA C151. Testing may

be performed prior to machining bell and spigot. Failure of ductile iron pipe shall be

defined as any leak or rupture of the pipe wall.

13. For ductile iron pipe diameters 16-inches and greater:

a. All pipe and fittings to be installed under this Contract may be inspected at

the plant for compliance with this Section by an independent testing laboratory

selected by the Owner at the Owner's expense.

b. A manufacturer's representative shall be made available when requested by

the Owner during the manufacturing furnishing, transporting, and unloading

of the pipe and during installation and testing to assist in confirming that the

pipe is properly fabricated, transported, unloaded, stored in the field, joined

and tested.

c. The manufacturer’s representative shall be made available a minimum of 2

working days (time on site) during the project when requested by the Owner,

including the first 2 Days of pipeline installation.

d. The cost for the services of the manufacturer’s representative, including

expenses, shall be considered incidental to the project and will not be paid

separately.

B. Polyvinyl Chloride (PVC) Pipe

1. PVC pipe shall be furnished in 20-foot laying lengths, with push-on joints. Pipe shall

be restrained joint where shown in the Contract Documents.

2. PVC pipe, 4 to 12-inches in diameter, shall conform to the requirements of AWWA

C900 - Class 150 (DR-18), unless otherwise indicated in the Contract Documents.

PVC pipe greater than 12-inches in diameter shall be AWWA C-905 - Class 235 (DR

18) or Class 165 (DR 25), as specified in the Contract Documents.

a. The pipe, shall be made from virgin polyvinyl chloride resin or clean rework

materials generated from the manufacturer’s own pipe production that equals

or exceeds cell class 12454-B as defined by ASTM D 1784, and shall bear

the seal of approval by the NSF. The pipe shall be unplasticized polyvinyl

chloride plastic pressure pipe with integral wall bell and spigot joints.

b. Joints shall be push-on type with a flexible factory assembled elastomeric

ring in the integral bell-end. O-ring gaskets shall conform to ASTM F 477.

Page 11: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 23

Proposed Revision 6.1

2. Brass Pipe shall be red brass pipe meeting the requirements of ASTM B 43. Pipe sizes,

wall thickness and dimensions shall meet the requirements of ASTM B 251 Table I

for regular pipe. Brass pipe fittings shall be screwed end malleable iron pattern

meeting the requirements of ANSI B16.15. They shall be finished rough, unless

otherwise specified. Unions shall be of all brass or bronze with ground joints and shall

be left semi-finished. Fittings shall be rated for steam working pressures up to 125 psi.

Joints shall be screwed type with threads clean cut, tapered and smooth, meeting the

requirements of ANSI B2.1.

3. Service Saddle - Shall be designed and sized for the force main on which the saddle is

to be installed. The service saddle shall also meet the following requirements:

a. Stainless steel saddle bodies shall be 18-8, Type 304, stainless steel with all

welds fully passivated to restore stainless steel characteristics.

b. Ductile iron saddle bodies shall conform to ASTM A-536 and have a fusion

applied epoxy coating 12-mils dry thickness (D.T.). Straps shall be stainless

steel, 18-8, Type 304 fully passivated for corrosion resistance.

c. Threads shall be AWWA C-800 CC/Taper.

d. The saddle band shall be a minimum of 2-inches in width.

e. The saddle shall be provided with a Buna-N rubber gasket meeting ASTM

D2000 to seal the saddle and the main pipe.

f. The nuts, washers, bands, and bolts shall be 18-8 stainless steel.

g. Acceptable manufacturers are The Ford Meter Box Co., Inc., Model

FS202/FS303/FRS202, JCM Model 406, Romac Industries Inc., Style 202N,

Cascade Products Style CNS2, or approved equal.

G. Joint Restraint Devices

1. Joint restraints shall be provided where indicated in the Contract Documents.

2. The restrained joint system shall have a pressure rating equal to or greater than that of

the pipe on which it is used. Restrained joint devices shall be installed in strict

accordance with the manufacturer’s recommendations.

3. Ductile Iron Pipe

a. Push-on Joints

For push–on joint type pipe, the restrained joint system shall be a

manufacturer’s standard restrained joint system, SnapLock (U.S.Pipe)- Lok

Ring (American Pipe), HP Lok (U.S. Pipe), TR Flex (U.S. Pipe), FlexRing

(American Pipe), or approved equal.

b. Mechanical Joints

Page 12: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 40

Proposed Revision 6.1

2. DI pipe shall conform to the requirements of ANSI/AWWA C151/A21.51.

3. DI pipe shall be Class 52 for all pipe diameters; or, Class 350 minimum pressure

classification for diameters 24-inch and smaller and 250 psi for diameters larger than

24-inches; or, the thickness classification indicated in the Contract Documents. The

manufacturer’s mark, country where cast, year the pipe was produced, and the letters

“DI” or “Ductile Iron” shall be cast or stamped on the pipe.

4. Joints and gaskets shall conform to ANSI/AWWA C111/A21.11 or ANSI/AWWA

C115/A21.15 as applicable. The minimum acceptable pressure rating for all joints is

250 psi. All flanges and glands for pipes shall be made of ductile iron.

5. Fittings shall be manufactured in accordance with ANSI/AWWA C110/A21.10 or

ANSI/AWWA C153/A21.53, as applicable, and shall be ductile iron. Compact fittings

are required, and shall have a minimum acceptable pressure rating of 350 psi for 24-

inch and smaller piping and 250 psi for larger than 24-inch piping. Fittings shall have

the same pressure rating, as a minimum, of the connecting pipe.

6. Coatings shall be provided on the exterior of all pipe, joints and fittings as required by

ANSI/AWWA C110/A21.10, C111/A21.11, C115/A21.15, C151/A21.51,

C116/A21.16, or C153/A21.53 as applicable. All pipes, joints, and fittings shall be

examined after laying to determine if the coating was damaged during installation.

Any damaged areas shall be coated with an Owner-approved coating in accordance

with the manufacturer’s recommendations with a minimum of 2 mil of an approved

bituminous coating.. If required in the Contract Documents, the exterior of the

pipe shall be coated with a layer of arc-sprayed zinc in accordance with ISO 8179.

The mass of zinc applied shall be 200 g/m2 of pipe surface area. A finishing layer

topcoat shall be applied to the zinc. The mean dry film thickness of the finishing

layer shall not be less than 3 mils with a local minimum not less than 2 mils. The

zinc coating system shall conform to ISO 8179-1 “Ductile iron pipes – External

zinc-based coating – Part 1: Metallic zinc with finishing layer (Second Edition

2004-06-01)

7. All ductile iron pipe and fittings shall be double thickness cement lined for diameters

up to 30-inch, with single thickness for diameters above 30-inches, and seal coated

in accordance with ANSI/AWWA C104/A21.4.

8. Pipe diameters 12-inch and smaller shall be gaged and delivered round and true

throughout its entire length. Pipe over 12-inches in diameter shall have one piece of

gaged pipe delivered for each fitting. Gaged pieces shall be marked as such on the pipe

and shall be accompanied by the manufacturer's certification. Manufacturer's

certification of inspection and testing shall accompany each delivery.

9. ASTM A242 – Standard Specification for High-Strength Low-Alloy Structural Steel

10. ASTM A307 – Standard Specification for Carbon Steel Bolts and Studs, 60,000 PSI

Tensile Strength.

11. ASTM A674 – Standard Practice for Polyethylene Encasement for Ductile Iron Pipe

for Water or Other Liquids.

Page 13: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 41

Proposed Revision 6.1

12. AWWA C105 – Polyethylene Encasement and V-Bio Enhanced Polyethylene

Encasement for Ductile-Iron Pipe Systems.

13. For pipe diameters 16-inches and greater:

a. Each length of ductile iron pipe shall be hydrostatically tested at the point of

manufacture to 500 psi for a duration of 10 seconds per AWWA C151. Testing

may be performed prior to machining bell and spigot. Failure of ductile iron

pipe shall be defined as any leak or rupture of the pipe wall.

b. All pipe and fittings to be installed under this Contract may be inspected at

the plant for compliance with this Section by an independent testing laboratory

selected by the Owner at the Owner's expense.

c. A manufacturer's representative shall be made available to the Owner during

the manufacturing furnishing, transporting, and unloading of the pipe during

installation and testing of the pipe to assist in insuring that the pipe is properly

fabricated, transported, unloaded, stored in the field, joined and tested.

Manufacturer's responsibilities relate only to the proper care and treatment of

the pipe during these procedures and not the techniques or procedures used

during installation and testing.

d. The manufacturer’s representative shall be made available a minimum of 2

working days (time on site) during the project when requested by the Owner,

including the first 2 Days of pipeline installation.

e. The cost for the services of the manufacturer’s representative, including

expenses, shall be considered incidental to the project and will not be paid

separately.

B. Polyvinyl Chloride (PVC) Pipe

1. PVC pipe shall be furnished in 20-foot laying lengths, with push-on joints. Restrained

joints shall be provided where shown in the Contract Documents.

2. PVC pipe, 4- to 12-inches in diameter, shall conform to the requirements of AWWA

C900 - Class 150 (DR-18), unless otherwise indicated in the Contract Documents.

PVC pipe greater than 12-inches in diameter shall be AWWA C-905 - Class 235 (DR

18) or Class 165 (DR 25), as specified in the Contract Documents.

3. The pipe, shall be made from virgin polyvinyl chloride resin or clean rework materials

generated from the manufacturer’s own pipe production that equals or exceeds cell

class 12454-B as defined by ASTM D 1784, and shall bear the seal of approval by the

NSF. The pipe shall be unplasticized polyvinyl chloride plastic pressure pipe with

integral wall bell and spigot joints.

4. Joints shall be push-on type with a flexible factory assembled elastomeric ring in the

integral bell-end. Joint material including gaskets and lubricants shall conform to

AWWA C900.

5. Fittings shall be manufactured in accordance with ANSI/AWWA C110/A21.10 or

ANSI/AWWA C153/A21.53, and shall be ductile iron. The minimum acceptable

Page 14: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 48

Proposed Revision 6.1

Meter settings shall include meter setter, meter box, water meter, and all appurtenances

necessary for providing customer water service at the location designated in the Contract

Documents. See the Special Provisions for additional information.

K. Joint Restraint Devices

1. Joint restraints shall be provided where indicated in the Contract Documents.

2. Ductile Iron Pipe

The restrained joint system shall have a pressure rating equal to or greater than that of

the pipe on which it is used. Restrained joint devices shall be installed in strict

accordance with the manufacturer’s recommendations.

a. Push-On Joints

For push–on joint type pipe, the restrained joint system shall be a

manufacturer’s standard restrained joint system, SnapLock (U.S.Pipe), TR

Flex (U.S. Pipe), Lok-Ring (American Pipe), HP Lok (U.S. Pipe), FlexRing

(American Pipe), Series 3000 Stargrip wedge action restraint (Star Pipe

Products), or approved equal.

b. Mechanical Joints

For mechanical joint type pipe, the restrained joint system shall be a

manufacturer’s standard restrained joint system, Series 1100 Megalug ductile

iron glands (EBBA iron, Inc.), Series 1400 retainer glands (Ford Meter Box

Company, Inc.), Series 3000 Stargrip wedge action restraint (Star Pipe

Products), or approved equal.

3. PVC Pipe (4-inch and larger)

The restrained joint system shall have a pressure rating equal to or greater than that of

the pipe on which it is used. Restrained joint devices shall be installed in strict

accordance with the manufacturer’s recommendations.

a. Bell and Spigot PVC Joints

The restraint system for bell and spigot PVC joints shall be Series 1600/2800

ductile iron retainers as manufactured by EBAA Iron, Inc, Series 1390

retainers as manufactured by Ford Meter Box Company, Inc., or approved

equal.

b. PVC to Mechanical Joint Fittings

The restraint system for restraining PVC pipe to ductile iron mechanical joint

fittings shall be Series 2000 PV ductile iron retainers as manufactured by

EBAA Iron, Inc., Series 1500 retainers as manufactured by the Ford Meter

Box Company, Inc., Series 4000 Stargrip wedge action restraint (Star Pipe

Products),or approved equal.

4. Concrete Reaction Blocking

Page 15: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision FormProposed Revision To:

General Provisions (Division 1) Technical Specifications (Divisions 2-8) Standard Details

Change No.

     

(ASSIGNED BY TECHNICAL REVIEW COMMITTEE)

Hampton Roads Planning District Commission723 Woodlake DriveChesapeake, VA 23320(Phone: 757-420-8300)

Date Proposal Received

     

(ASSIGNED BY TECHNICAL REVIEW COMMITTEE)

Subsection or Standard Detail to be Revised: CI_03 On page(s):      

Proposed Revision:Add the following note as extracted from the VDOT CG-2 Parkway Curb Detail: “The depth of the curb may be reduced as much as 3” (15” Depth) or increased as much 3” (21” depth) in order that the bottom of curbwill coincide with the top of a pavement substructure. Otherwise, the depth is to be 18” as shown. No adjustment in the price bid is to be made for a decrease or an increase in depth.”

Reason for Revision:This will allow the use of slip-form machinery (Curb Machine). The current CI_03 detail can only be accomplished with hand forms. This means that sometimes we have to ask the architect or engineer to allow a substitution with the VDOT CG-2, which is essentially the same detail as CI_03, except for the provision for slip-forming. (See attached VDOT CG-2 detail). Thank you.

Special Considerations or Restrictions in Usage/Construction: Yes No (If yes, explain below)

     

Performance History: List at least five locations where the material or procedure has been used successfully. Include contact individuals and phone numbers.

Location Contact Phone No

                 

                 

                 

                 

                 

Submitted By: Jim Grantz Address: 3716 Shoreline Drive Portsmouth, VA 23703

Agency: Hampton Roads Concrete Contractors      

Phone No: 757-435-3139      

Instructions: Use a separate form for each revision. Provide exact wording. Cite applicable Standards and Test Designations (ASTM, AWWA, AASHTO, etc.) For minor changes, copy present wording using strike through for words to be deleted and bold new text. For major changes, rewrite or add paragraphs/sections. Attach plain paper to this form if more space is needed. Reason for change MUST be given.

TRC Action:       (Date)

Recommended for:

Approval as submitted Approval as modified by TRC Denial

March 22, 2012

SCIACCHITANOR
Typewritten Text
6.2
SCIACCHITANOR
Text Box
October 30, 2017
SCIACCHITANOR
Text Box
November 30, 2017
Page 16: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision Form

March 22, 2012

Page 17: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection
Page 18: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision Form

March 22, 2012

Proposed Revision To:

General Provisions (Division 1)

Technical Specifications (Divisions 2-8)

Standard Details

Change No.

6.3

(ASSIGNED BY TECHNICAL REVIEW COMMITTEE)

Hampton Roads Planning District Commission

723 Woodlake Drive

Chesapeake, VA 23320 (Phone: 757-420-8300)

Date Proposal Received

11/30/17

(ASSIGNED BY TECHNICAL REVIEW COMMITTEE)

Subsection or Standard Detail to be Revised: 815.1.1, 815.2.2. B.4, and 815.2.2. D.2 On page(s): 1, 6, and 7

Proposed Revision:

• Paragraph 815.1.1 – Add at the end of the paragraph: “Under favorable conditions upsizing to 150% of the

existing diameter may be permitted upon submittal and Owner approval of supporting calculations from the

Contractor.”

• Paragraph 815.2.2.B.4 - Replace: “…be threaded…” with “…extend…”

• Paragraph 815.2.2.D.2 – Add after “lateral reconnection” : “in accordance with the manufacturer’s written

recommendations. A strain gage shall be used to verify that pipe strain does not exceed the manufacturer’s

recommendations, unless deemed unnecessary by the Owner.”

Reason for Revision:

Clarifications

Special Considerations or Restrictions in Usage/Construction: Yes No (If yes, explain below)

Performance History: List at least five locations where the material or procedure has been used successfully. Include

contact individuals and phone numbers.

Location Contact Phone No

Submitted By: TRC Address:

Agency:

Phone No:

Instructions: Use a separate form for each revision. Provide exact wording. Cite applicable Standards and Test Designations

(ASTM, AWWA, AASHTO, etc.) For minor changes, copy present wording using strike through for words to be

deleted and bold new text. For major changes, rewrite or add paragraphs/sections. Attach plain paper to this form if

more space is needed. Reason for change MUST be given.

TRC Action: February 7, 2018 (Date)

Recommended for:

Approval as submitted

Approval as modified by TRC

Denial

Page 19: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 815 - 1

Proposed Revision 6.3

SECTION 815

PIPE BURSTING

I. GENERAL

1.1 DESCRIPTION OF WORK

The Work covered in this section specifies the method or process to include all labor, materials, tools,

equipment and incidentals necessary to provide for the complete rehabilitation of deteriorated sanitary

gravity sewer by pipe bursting, connect new pipe to existing manholes, modify existing manholes bases as

needed, reconnect existing sewer lateral connections, perform pre- and post-rehabilitation television

inspection, and other Work as shown in the Contract Documents and as specified herein..

Pipe bursting is the construction technique of replacing an existing, underground pipe system in situ by

fracturing a pipe and displacing the fragments outwards into the surrounding soil while a new HDPE or

fPVC pipe is drawn in to the annulus left by the expanding operation to replace the old pipe. The process

can be either by pneumatic, hydraulic or static pull methods, using a conically shaped bursting head to

break out the old pipe. The rear of the bursting head is connected to the new pipe, while its front is

connected to a cable or pulling rod. The bursting head and the new pipe are launched from the insertion

pit, and the cable or pulling rod is pulled from the reception pit. The replacement pipe is either pulled or

pushed into the bore. The replacement pipe shall not be greater than 25% larger in diameter than the

existing pipe. Under favorable conditions upsizing to 150% of the existing diameter may be

permitted upon submittal and Owner approval of supporting calculations from the Contractor.

1.2 SUBMITTALS

The Contractor shall provide qualifications to the Owner as evidence of competency and authority to

perform the method of pipe bursting to be utilized and restoration of existing services. The qualifications

and submittals shall include the following:

A. The Contractor shall be trained by the pipe bursting equipment manufacturer in the use of the

equipment for pipe bursting. The Contractor shall submit a letter from the manufacturer stating

that they provided training to contractor staff on the use, operation and maintenance of the

equipment. The Contractor shall hold the Owner and its agents harmless in any legal action

resulting from patent infringement.

B. The Contractor shall be trained by the thermal fusion equipment manufacturer in the use of the

equipment for thermal butt-fusion of high density polyethylene (HDPE) pipe. The butt-fusion

method for pipe jointing shall be carried out in the field by certified operators with prior

experience in fusing HDPE pipe with similar equipment using proper jigs and tools per standard

procedures outlined by the pipe manufacturer. HDPE pipe shall conform to the requirements of

Section 200.

C. All pipe bursting Contractors shall have at least two (2) years continuous experience in pipe

bursting and shall have completed at least three projects in the last five (5) years involving pipe

bursting installations of a combined total of 25,000 feet of pipe bursting experience as a

prequalification for this project. Documentation to substantiate the Contractor’s experience shall

be provided.

Page 20: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 815 - 6

Proposed Revision 6.3

2. The insertion pit must be large enough to allow the pipe to be inserted without

overstressing the new pipe in bending. Pipe manufacturer’s bending radius limitations

must be adhered to.

3. When the winch and pulling cables are used to pull the bursting tool through the pipe,

place the winch into the reception pit and pull the cable through the existing pipe and

attach to the front of the bursting unit in the insertion pit.

4. When rigid pulling rods are useused, the rods shall be threaded extend from the

reception pit through the existing pipe to the pipe insertion pit and attach to the bursting

head.

C. Bursting Operation

1. The upsizing method shall not cause excessive disruption or heaving to the above ground

terrain or improvements except for at the launching and receiving pits.

2. Upon commencement of the bursting process, pipe insertion shall be continuous and

without interruption from one entry point to another, except as approved by the Owner.

3. Bursting head shall be remotely controlled. The bursting head shall be sized such that the

maximum diameter of the temporary void created by the bursting operation shall not

exceed the maximum outside diameter of the replacement pipe by greater than 20%. The

new sewer shall be installed straight along the centerline of the existing pipeline

following the same line and grade.

4. Due to the presence of existing utilities adjacent to the sewer to be replaced, the pipe

bursting method shall limit vibrations transmitted to the surrounding soils. The peak

velocity shall be limited to 0.5-inches per second.

5. In the event a section of pipe is damaged during the bursting operation, or joint failure

occurs, as evidenced by inspection, visible groundwater inflow, or other observations, the

Contractor shall submit to the Owner for approval his methods for repair or replacement

of the pipe.

6. Winch and Cable Method

a. Bursting of the old pipe shall be performed as a continuous action providing

constant tension to the bursting head when the winch and cable method is used.

b. The Contractor shall provide a system of guide pulleys and bracing at the exit pit

to minimize cable contact with the existing pipeline between the insertion and

reception pits.

c. Trench shoring supports in the insertion pits shall remain completely separate

from the winch boom support system and shall be designed that neither the

winch support cable shall be in contact with therm.

7. Rigid Rod Method

Page 21: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 815 - 7

Proposed Revision 6.3

When rigid rods are used as a pulling unit, the bursting operation may be temporarily

halted to unthread and remove each rod section from the pit.

8. Continue this process until the bursting head is pulled completely back into the reception

pit.

9. Do not drag the replacement pipe over the ground surface. Pipe shall move over rollers or

slings for insertion and transportation. Pipe ends shall be capped.

10. If any obstruction is encountered that can not be burst through, the Contractor shall

immediately excavate the location of the obstruction to allow the bursting to continue

with the Owner’s approval. This Work shall be performed in accordance with Section

818 – Point Repair by Excavation.

11. If the Contractor damages any existing utility, the Contractor shall immediately inform

the utility owner of the location and the nature of the damage. The Contractor shall allow

the utility owner time to conduct the necessary repairs prior to continuing the bursting

operation. Damages to properly marked utilities will be the financial responsibility of the

Contractor.

12. If surface heave or subsidence occurs, the Contractor shall repair the impacted area(s) to

the satisfaction of VDOT or the locality, as appropriate.

D. Sewer Service Laterals and Reconnections

1. The Contractor shall be responsible for continuity of sanitary sewer service to each

customer connected to the section of sewer being replaced or rehabilitated during the

execution of the work. If sewage backup occurs and enters buildings, the Contractor shall

be fully responsible for clean-up, repair, property damage costs and claims.

2. Existing service connections shall be located before initiating sewer main replacement

operations. Service laterals shall not be reconnected to the new sewer line until

replacement and testing are completed, and not less than 4 hours after completion of the

pipe bursting procedure. If the bursting is done with HDPE pipe, there shall be a

minimum 12- hour relaxation period before permanent lateral reconnection., in

accordance with the manufacturer’s written recommendations. A strain gage shall

be used to verify that pipe strain does not exceed the manufacturer’s

recommendations, unless deemed unnecessary by the Owner. Any services

remaining off line for an extended period of time, or any connections as deemed

necessary by the Owner to protect the customer, shall be bypass pumped until such time

that they can be reconnected.

3. Connection of the new service lateral (ASTM D-3034 SDR 26 PVC Pipe) to the new

sewer main shall be accomplished by use of the watertight compression –fit service

connection. The service connection shall be specifically designed for connection to the

fPVC or HDPE sewer main being installed, and shall be INSERTA TEE as

manufactured by Insert Tee Fittings, Inc., or approved equal.

2.3 SEALING AND BENCHES IN MANHOLES

A. Following the minimum relaxation period identified above, the annular space in the manhole wall

Page 22: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision Form

March 22, 2012

Proposed Revision To:

General Provisions (Division 1)

Technical Specifications (Divisions 2-8)

Standard Details

Change No.

6.4

(ASSIGNED BY TECHNICAL REVIEW COMMITTEE)

Hampton Roads Planning District Commission

723 Woodlake Drive

Chesapeake, VA 23320 (Phone: 757-420-8300)

Date Proposal Received

November 30, 2017

(ASSIGNED BY TECHNICAL REVIEW COMMITTEE)

Subsection or Standard Detail to be Revised: 200.5.19 On page(s): 200-41

Proposed Revision:

Add Paragraph D to Section 200.5.19:

D. Fusible Polyvinylchloride (fPVC) Pipe

1. Pipe Supplier shall furnish fPVC pipe conforming to all standards and procedures, and meeting all

testing and material properties as described in this specification. Pipe, 4 to 12 inches in diameter,

shall conform to AWWA C900 – Class 150 (DR 18), unless otherwise indicated in the Contract

Documents. Pipe greater than 12 inch shall conform to AWWA C905 – Class 235 (DR 18) or Class

150 (DR25), as specified in the Contract Documents.

2. fPVC pipe shall be tested at the extrusion facility for properties required to meet all applicable

parameters as outlined in AWWA C900 or C905, as appropriate. Rework material shall be allowed

per AWWA C900 and AWWA C905 standards. All piping shall be made from a PVC compound

conforming to cell classification 12454 per ASTM D1784.

3. fPVC pipe shall be extruded with plain ends and shall normally be supplied in standard 40 foot

lengths. The ends shall be square to the pipe and free of any bevel or chamfer. There shall be no bell

or gasket of any kind incorporated into the pipe. fPVC pipe shall be blue in color for potable water

use or green for wastewater.

4. Acceptable fittings for use with fPVC pipe shall include standard ductile iron fittings conforming to

AWWA/ANSI C110/A21.10 and AWWA/ANSI C153/A21.53.

5. Connections to fPVC pipe may be made using a restrained or non-restrained retainer gland product

for PVC pipe, as well as for MJ or flanged fittings.

6. Bends, tees and other ductile iron fittings shall be restrained as indicated in the Contract Documents.

7. Ductile iron fittings and glands must be installed per the manufacturer’s guidelines.

8. Pipe generally shall be marked per AWWA C900 or AWWA C905, and shall include as a minimum:

a. Nominal pipe size

b. PVC

c. Dimension Ratio, Standard Dimension Ratio or Schedule

d. AWWA pressure class and Standard number

e. Extrusion production-record code

f. Trademark or trade name

g. Cell Classification 12454 and/or PVC material code 1120 may also be included.

h. NSF-61 mark, if for potable water service.

9. The manufacturer’s representative shall be made available a minimum of 2 working days (time on

site) during the project when requested by the Owner, including the first 2 Days of pipeline

installation.

10. The cost for the services of the manufacturer’s representative, including expenses, shall be considered

incidental to the project and will not be paid separately.

Page 23: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision Form

March 22, 2012

Reason for Revision:

Inadvertently omitted from 6th Edition

Special Considerations or Restrictions in Usage/Construction: Yes No (If yes, explain below)

Performance History: List at least five locations where the material or procedure has been used successfully. Include

contact individuals and phone numbers.

Location Contact Phone No

Submitted By: TRC Address:

Agency:

Phone No:

Instructions: Use a separate form for each revision. Provide exact wording. Cite applicable Standards and Test Designations

(ASTM, AWWA, AASHTO, etc.) For minor changes, copy present wording using strike through for words to be

deleted and bold new text. For major changes, rewrite or add paragraphs/sections. Attach plain paper to this form if

more space is needed. Reason for change MUST be given.

TRC Action: February 7, 2018 (Date)

Recommended for:

Approval as submitted

Approval as modified by TRC

Denial

Page 24: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 41

Proposed Revision 6.4

7. Pipe sections shall be joined on the job site above ground into continuous lengths by

the thermal butt-fusion or electrofusion method, which shall be performed in strict

accordance with the manufacturer’s recommendations. The butt-fusion equipment

used in the joining procedures shall be capable of meeting all conditions recommended

by the pipe manufacturer, including, but not limited to, temperature requirements of

400 °F, alignment, and 75 psi interfacial fusion pressure. Butt-fusion joining shall be

100% efficient and shall provide a joint weld strength equal to or greater than the

tensile strength of the pipe. Socket-fusion, extrusion welding or hot gas welding of

HDPE shall not be used for pressure pipe applications. Flanges, unions, grooved-

couplers, transition fittings, and some mechanical couplers may be used to

mechanically connect HDPE pipe without butt-fusion, if specified in the Contract

Documents and approved by the manufacturer.

8. The manufacturer’s representative shall be made available a minimum of 2 working

days (time on site) during the project when requested by the Owner, including the first

2 Days of pipeline installation.

9. The cost for the services of the manufacturer’s representative, including expenses,

shall be considered incidental to the project and will not be paid separately.

10. Transition couplings from HDPE to other pipe materials, shall be as indicated in the

Contract Documents.

D. Fusible Polyvinylchloride (fPVC) Pipe

1. Pipe Supplier shall furnish fPVC pipe conforming to all standards and

procedures, and meeting all testing and material properties as described in this

specification. Pipe, 4 to 12 inches in diameter, shall conform to AWWA C900 –

Class 150 (DR 18), unless otherwise indicated in the Contract Documents. Pipe

greater than 12 inch shall conform to AWWA C905 – Class 235 (DR 18) or Class

150 (DR25), as specified in the Contract Documents.

2. fPVC pipe shall be tested at the extrusion facility for properties required to meet

all applicable parameters as outlined in AWWA C900 or C905, as appropriate.

Rework material shall be allowed per AWWA C900 and AWWA C905

standards. All piping shall be made from a PVC compound conforming to cell

classification 12454 per ASTM D1784.

3. fPVC pipe shall be extruded with plain ends and shall normally be supplied in

standard 40 foot lengths. The ends shall be square to the pipe and free of any

bevel or chamfer. There shall be no bell or gasket of any kind incorporated into

the pipe. fPVC pipe shall be blue in color for potable water use or green for

wastewater.

4. Acceptable fittings for use with fPVC pipe shall include standard ductile iron

fittings conforming to AWWA/ANSI C110/A21.10 and AWWA/ANSI

C153/A21.53.

5. Connections to fPVC pipe may be made using a restrained or non-restrained

retainer gland product for PVC pipe, as well as for MJ or flanged fittings.

6. Bends, tees and other ductile iron fittings shall be restrained as indicated in the

Page 25: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 42

Proposed Revision 6.4

Contract Documents.

7. Ductile iron fittings and glands must be installed per the manufacturer’s

guidelines.

8. Pipe generally shall be marked per AWWA C900 or AWWA C905, and shall

include as a minimum:

a. Nominal pipe size

b. PVC

c. Dimension Ratio, Standard Dimension Ratio or Schedule

d. AWWA pressure class and Standard number

e. Extrusion production-record code

f. Trademark or trade name

g. Cell Classification 12454 and/or PVC material code 1120 may also be

included.

h. NSF-61 mark, if for potable water service.

9. The manufacturer’s representative shall be made available a minimum of 2

working days (time on site) during the project when requested by the Owner,

including the first 2 Days of pipeline installation.

10. The cost for the services of the manufacturer’s representative, including

expenses, shall be considered incidental to the project and will not be paid

separately.

E. Copper Water Pipe

Pipe shall be seamless copper tubing conforming to ASTM B 88, Type K, Temper 060, and

shall be of the coiled type. Fittings shall be wrought copper solder-joint pressure fittings

conforming to ASME B16.22. Copper tube and fittings shall be rated for a working pressure

of 150 psi. Joints shall be compression style.

F. Valves

1. Gate Valves

a. Resilient-seated gate valves shall be used on pipelines 3-inches in diameter up

to and including 12-inches in diameter. Resilient-seated gate valves shall be

in accordance with AWWA C509 or AWWA C515 and shall be supplied with

an interior epoxy coating in accordance with AWWA C550. Resilient-seated

gate valves shall be iron body, non-rising bronze or stainless steel stem, rubber

encapsulated iron disc, o-ring seals, and suitable for buried service. Valve

ends shall be flanged, mechanical joint, or mechanical joint by flange to suit

the pipe or fittings as indicated in the Contract Documents.

Gate valves shall be manufactured by Kennedy Valve Company, Mueller

Company, or approved equal, or as specified in the Special Provisions.

b. Gate valves smaller than 3-inches in diameter shall be cast bronze, solid-

wedge disc, screwed bonnet, inside screw, non-rising stem valves with

threaded connections. Valves shall conform to Standard SP-80, Type 2, Class

SCIACCHITANOR
Text Box
D
SCIACCHITANOR
Line
SCIACCHITANOR
Text Box
E
SCIACCHITANOR
Line
Page 26: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 43

Proposed Revision 6.4

150, Manufacturer's Standardization Society of the Valve and Fitting Industry,

Inc.

c. Gate valves larger than 16-inches in diameter shall meet the requirements of

AWWA C500, except Section 4.4.8.1.1 will not be allowed. Valves shall be

rated for 150 psi working pressure and a minimum 300 psi test pressure.

Valves shall be iron body, bronze-mounted, double disc, parallel seat, non-

rising stem type fitted with O-Ring seals. Valves shall be capable of drip tight,

bi-directional shut off and operate in the horizontal position. The operating

nuts shall be 2-in square. Valves shall open counter clockwise. Seats in the

body shall be replaceable without removing the valve from the pipeline. Discs

shall be cast iron and bronze faced and shall be free to revolve 360 degrees.

Valves to be furnished with bronze rollers, bronze tracks and bronze scrapers.

d. Valve Operators

Buried valves shall have a 2-inch square operating nut conforming to AWWA

C509, and shall open in a counterclockwise direction, unless otherwise noted.

A valve key wrench of adequate length and of each type required shall be

provided for each buried valve; however, not more than three of each type are

required for each project. Valves in vaults shall have a hand wheel of cast iron

conforming to ASTM A126, Class B.

2. Ball Valves

Owner-approved ball valves smaller than 3-inches in diameter shall be:

a. Brass with threaded connections, O-ring seals, and a coated ball conforming

to AWWA C800 and Standard SP-80, Type 2, Class 150 Manufacturer’s

Standard Society of the Valve and Fittings Industry, Inc. Valves shall be

manufactured by the Ford Meter Box Company B11, Mueller Company 300

Ball Curb Valve, B-20283, or approved equal.

b. PVC True Union Standards ball valve with steel reinforced threaded-end

connectors, with a minimum pressure rating of 230 psi at 70°F, conforming to

ASTM D1784, Cell Classification 12454, as manufactured by Asahi, Spears,

or approved equal.

c. NSF approved.

3. Butterfly Valves

a. Butterfly valves may be used on pipelines 16-inches in diameter and larger

and shall be Pressure Class 150B in accordance with the latest revision of

AWWA C504. Butterfly valves and operators shall be suitable for buried

service. Valve seats shall be of synthetic rubber compound and tested in

accordance with ASTM D-429. The valve shall be operable with a maximum

input of 150 foot-pounds on the operating nut, and be able to withstand an

overload input torque of 150 foot-pounds at full open and full closed positions

without damage to the operator nut. Actuator components shall be designed

to withstand, without damage, a rim pull of 200 pounds for the hand wheel,

and an input torque of 300 Ft-Lbs for wrench nuts, in accordance with AWWA

Page 27: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 44

Proposed Revision 6.4

C504.The disc shall be capable of holding in any intermediate position

without creep or flutter.

b. Butterfly valve operators may be side-mounted, shall meet the requirements

of AWWA C504, pressure class 150B, shall be capable of seating and

unseating the discs against the full design pressure and velocity, and shall

transmit sufficient torque to the valve to accomplish this. Buried valves shall

contain permanently lubricated operators. Valve operators shall be suitable for

a minimum of 10,000 cycles of operations at its rated torque.

4. Coatings

All interior ferrous surfaces of all valves shall be coated in accordance with

ANSI/AWWA C550 using a coating approved by the Virginia Department of Health

for contact with potable water and shall not contain lead, coal tar resins, lampblack,

carbon black or bituminous materials. The exterior surfaces shall receive a factory

applied fusion bonded epoxy coating.

5. Valve Stem Extensions

Valve stem extensions, when allowed by the locality, shall be furnished when the

distance from the operating nut to the top of the valve box frame is greater than 36-

inches. Extension stems shall have a 2-inch square wrench nut on the top end and shall

be at least as strong as the valve stem. Extension stems shall be coated in accordance

with above.

6. Valve Markings

Valve markings shall be cast on the bonnet or body of each valve and shall show the

manufacturer’s name or mark, the year the valve casting was made, the size of the

valve, and the designation of working pressure.

H. G. Valve Boxes

Valve boxes shall be as indicated in the Standard Details.

I.H. Fire Hydrants

1. Fire hydrants shall be of the dry-barrel type and shall conform to AWWA C502.

2. The hydrant base shall have a 6-inch mechanical joint bell, designed for connection to

a horizontal 6-inch ductile iron hydrant branch with retainer glands. The traffic

coupling shall allow for 360-degree adjustment of the upper standpipe. The fire

hydrant shall be painted with a high gloss, alkyd industrial enamel (colors shall be

selected by the Owner). Extension spools shall be available from 6-inches to at least

48-inches, in 6-inch increments. Normal bury depth shall be 3.5 feet.

3. The flow rate shall be a minimum of 1000 gallons per minute with not more than 5-

psi pressure drop through the steamer nozzle, per AWWA C502.

4. The internal valve shall be no smaller than 4½-inches in diameter and have bronze-to-

bronze seating.

Page 28: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 200 - 45

Proposed Revision 6.4

5. Hydrants shall include two (2) 2 1/2-inch hose nozzles placed 180 degrees apart;

National Standard (American) fire hose coupling screw threads; and one steamer

nozzle with 4 1/2-inch National Standard (American) fire hose coupling screw threads

(unless specified otherwise by the Owner).

6. Fire Hydrants shall conform to Mueller Super Centurion 250 Model A421 or A-423,

Kennedy Guardian K-81D, or Owner-approved equal.

H. I. Appurtenances

1. Air Vent and Blow Off Assemblies

a. Air Vent and Blow Off Assemblies shall be as indicated in the Standard

Details.

b. Brass Pipe shall be red brass pipe meeting the requirements of ASTM B 43.

Pipe sizes, wall thickness and dimensions shall meet the requirements of

ASTM B 251, Table I for regular pipe. Brass pipe fittings shall be screwed

end malleable iron pattern meeting the requirements of ANSI B16.15. They

shall be finished rough, unless otherwise specified. Unions shall be of all brass

or bronze with ground joints and shall be left semi-finished. Fittings shall be

rated for steam working pressures up to 125 psi. Joints shall be screwed type

with threads clean cut, tapered and smooth, meeting the requirements of ANSI

B2.1.

2. Water Sampling Stations

Water sampling stations shall conform to Eclipse Model 88 as manufactured by the

Kupferle Corporation, or approved equal, in accordance with the Special Provisions.

Housing shall be either aluminum or plastic as approved by the Owner. If aluminum,

housing shall be painted in a color approved by the Owner. If housing is plastic, the

color shall be impregnated in the plastic and approved by the Owner.

3. Corporation Stops

Corporation Stops shall be manufactured to meet or exceed the AWWA C-800 latest

revision. The corporation stops shall also meet the following requirements:

a. The valve shall be of the ball type construction. A plug valve is not approved.

b. The corporation stops shall be designed to withstand working pressures up to

300 psi.

c. The corporation stops shall be manufactured with AWWA/CC tapered

threads.

d. Corporation stops joining to copper and plastic tubing shall have pack joint

compression couplings.

e. Corporation stops joining to existing galvanized piping shall have female iron

pipe threads.

Page 29: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision Form

March 22, 2012

Proposed Revision To:

General Provisions (Division 1)

Technical Specifications (Divisions 2-8)

Standard Details

Change No.

6.5

Hampton Roads Planning District Commission

723 Woodlake Drive

Chesapeake, VA 23320 (Phone: 757-420-8300)

Date Proposal Received

November 30, 2017

Subsection or Standard Detail to be Revised: Section 302.2.1.B and E On page(s): 302-1 and 302-7

Add to 302.2.1.B:

B. When geotextile filter fabric is required to wrap joints of rigid pipe, the installation shall be in accordance with

302.2.1.E below.

Add 302.2.1.E:

E. Joining rigid pipe:

1. The method of joining rigid pipe sections shall be such that ends are fully entered and inner surfaces are

flush and even.

2. Joints shall be sealed with any one or combination of the following to form a leak-resistant joint; rubber,

preformed plastic, mastic gaskets, and concrete pipe joint wrapping; or cold-applied pipe joint sealer

wrapped with filter fabric.

3. Rubber ring gaskets shall be installed to form a flexible, leak-resistant seal.

4. The Contractor shall double wrap each pipe joint with non-woven geotextile fabric strip and attach the

fabric to the pipe with a minimum of two (2) non-metallic straps. The width of the fabric strip shall be at

least two (2) feet wide and centered over the joint. The fabric shall be laid transversely in the trench of

each joint prior to laying pipe and shall be centered over the joint. The inside of all concrete pipes shall be

mortared to the spring line of the pipe. When pipes enter structures, the inside of the pipe/structure joint

shall be fully mortared.

Non-Woven geotextile filter fabric shall meet the following requirements:

• 90 lbs. Tensile Strength (ASTM D4632),

• 50% Tensile Elongation (ASTM D4632)

• 250 lbs. CBR puncture (ASTM D6241),

• 40 lb. Trapezoidal Tear Strength (ASTM D4533),

• 70% UV resistance at 500 hours (ASTM D4355),

• 50 US Sieve Apparent Opening Size (AOS) (ASTM D4751),

• 150 gpm/ft2 Water Flow Rate (ASTM D4491).

Acceptable non-woven geotextile product manufacturers are ACF Environmental 35, US Fabrics 90NW,

or approved equal.

5. Permissible construction tolerances between the proposed inverts as shown on the Drawings as the as-

built condition:

a. Maximum deviation of any invert from plan grade: +/-0.05'.

b. Total deviation of both inverts at each end of a particular line: +/-0.08'.

c. Maximum slope deviation +/- 0.02% between any two points in the line from the plan slope.

d. The strictest of the above shall apply. Any lines not properly installed in compliance with the

above shall be removed and reinstalled to the proper alignment and in accordance with all other

specification requirements, by the Contractor at no additional expense to the Owner.

Page 30: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision Form

March 22, 2012

Reason for Revision:

Most of these specifications were included in the 5th Edition and were inadvertently omitted from the 6th Edition. Specification for Non-

Woven geotextile fabric is updated.

Special Considerations or Restrictions in Usage/Construction: Yes No (If yes, explain below)

Performance History: List at least five locations where the material or procedure has been used successfully. Include

contact individuals and phone numbers.

Location Contact Phone No

Submitted By: HRPDC Regional Construction Standards Address:

Agency: Technical Review Committee

Phone No:

Instructions: Use a separate form for each revision. Provide exact wording. Cite applicable Standards and Test Designations

(ASTM, AWWA, AASHTO, etc.) For minor changes, copy present wording using strike through for words to be

deleted and bold new text. For major changes, rewrite or add paragraphs/sections. Attach plain paper to this form if

more space is needed. Reason for change MUST be given.

TRC Action: February 7, 2018 (Date)

Recommended for:

Approval as submitted

Approval as modified by TRC

Denial

Page 31: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 302 - 1

Proposed Revision 6.5

SECTION 302

DRAINAGE STRUCTURES

I. GENERAL

1.1. DESCRIPTION OF WORK

The Contractor shall furnish all labor, supervision, material (except as herein provided), tools, equipment,

supplies, and services; and, shall perform all Work necessary for the installation and construction of pipe

culverts, endwalls, box culverts, precast concrete and metal arches, storm drains, drop inlets, manholes,

spring boxes, junction boxes, and intake boxes and removing and replacing existing structures in

accordance with these specifications and in conformity to the lines and grades shown in the Contract

Documents or as designated by the Owner.

1.2. MATERIALS

Materials shall be furnished by the Contractor in accordance with Section 200.

1.3. SUBMITTALS

A. Submittals shall be made by the Contractor in accordance with the procedures set forth in Section

105 and as described below.

B. The Contractor shall furnish copies of the manufacturer’s specifications and details for cast in

place installations indicated in the Contract Documents, Standard Details, and the VDOT Road

and Bridge Standards, latest edition, listing specific materials proposed.

C. Submittal of designs for precast items included in the Contract Documents will not be required

provided fabrication is in accordance with the VDOT Road and Bridge Standards, latest edition.

Submittal of designs for precast structures on VDOT’s approved list will not be required provided

the Contractor submits a certification that the item will be fabricated in accordance with the pre-

approved design Drawings.

D. The Contractor shall furnish the Owner with an affidavit stating that products to be installed on

this project comply with specification requirements.

E. The “Acceptance Procedures for Aggregates” shall be in accordance with Section 200.

II. EXECUTION

2.1. PROCEDURES

A. Trenching, excavation, bedding and backfill operations shall be performed in accordance with the

requirements of Section 303.

B. The Contractor shall execute the Work in accordance with the latest edition of the VDOT Road

and Bridge Specifications, Section 302.03, Procedures, however, Post Installation Inspection of

Storm Sewer Pipes and Culverts shall be performed in accordance with 302.2.1.C below. Any

references to “Engineer” or VDOT personnel shall mean the “Owner”. When geotextile filter

Page 32: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 302 - 2

Proposed Revision 6.5

fabric is required to wrap joints of rigid pipe, the installation shall be in accordance with

302.2.1.E below.

C. Post Installation Inspection of Storm Sewer Pipes and Culverts

In addition to the visual inspection if performed by the Owner during the initial installation of

storm sewer pipes and pipe culverts, a post installation visual/video camera inspection shall be

conducted by the Contractor in accordance with the requirements of this specification and VDOT

VTM 123 on all pipes identified in the Contract Documents as storm sewer pipe and a selected

number of pipe culverts. For the purposes of this Section all pipe installations not identified in

the Contract Documents as storm sewer pipe are considered pipe culverts. Post installation

Inspections shall be performed on straight line and radial installations.

For pipe culverts, a minimum of one pipe installation for each size of each material type utilized

on the project will be randomly selected by the Owner for inspection, however, in no case will the

amount of pipe subject to inspection be less than ten percent of the total contract amount for the

size and material type indicated. Where possible, for all installations in which the pipe or

culvert’s size, orientation, or location permit deflection to be easily visually identified, (as verified

with the Owner) the Contractor may perform visual inspections in lieu of video inspections. If

defects as described herein are noted during the inspection, the Owner may require additional

pipe installations of that size and/or material be inspected. The Contractor shall coordinate and

schedule all post installation inspections so that these are made in the presence of the Owner. The

post installation inspection shall be performed no sooner than 30 days after completion of the pipe

installation and placement of final cover (except for pavement structure). The Contractor shall

issue a report detailing all issues or deficiencies noted during the inspection (including a

remediation plan for each deficiency noted where applicable) no later than 5 days after

completion of the inspection.

While the intent of this requirement is to perform the post installation inspection prior to paving,

project scheduling may dictate that a particular site be paved before the end of the 30 day period.

In such cases, a preliminary inspection of the pipe shall be made, prior to paving over it, to insure

that the pipe has been properly installed and is performing well. Performing such a preliminary

inspection prior to paving will not relieve the Contractor from the requirement to perform the post

installation inspection after the 30 day period.

The Contractor’s inspection report shall identify and address any of the following items observed

during the post installation inspection including identifying any proposed remediation measures

the Contractor plans to perform where applicable. Remediation measures may consist of

repairing or replacing the defective pipe section(s) or a combination of the two where differing

conditions exist within the same run of pipe. Where permitted as an option, remediation methods

for the various installation defects shall be proposed by the Contractor, reviewed with the Owner

and must have the Owner’s approval prior to implementation of the corrective action.

Remediation shall be the sole responsibility of the Contractor. Further, if remediation measures

are shown to be necessary, any time associated with such measures shall be reflected in the

impact to the Contractor’s progress schedule (may take the form of a time impact analysis, where

required by the scheduling requirements) and will not relieve the Contractor of his responsibilities

to finish the work required by the contract within the contract time limits or form the basis for any

claim of delay where such remediation measures are determined to be a result of the Contractor’s

fault, omission or negligence.

Page 33: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 302 - 6

Proposed Revision 6.5

a. original diameter, the pipe shall be replaced by the Contractor at his expense to

the satisfaction of the Owner

Remediation efforts and percentage of payment shall apply to the entire

section(s) of the deflected pipe or culvert, joint to joint. The cost of the remedial

measures (including removal and replacement of the pipe, if necessary) and the

re-inspection of the remediated pipe necessitated as a result of the Contractor’s

negligence, omission or fault shall be the contractual and financial responsibility

of the Contractor. D. Cleaning

Upon completion, each pipe and structure shall be cleaned of silt, debris, and foreign matter and

shall be kept clear of such accumulation until final acceptance.

E. Joining rigid pipe:

1. The method of joining rigid pipe sections shall be such that ends are fully entered and

inner surfaces are flush and even.

2. Joints shall be sealed with any one or combination of the following to form a leak-

resistant joint; rubber, preformed plastic, mastic gaskets, and concrete pipe joint

wrapping; or cold-applied pipe joint sealer wrapped with filter fabric.

3. Rubber ring gaskets shall be installed to form a flexible, leak-resistant seal.

4. The Contractor shall double wrap each pipe joint with non-woven geotextile fabric

strip and attach the fabric to the pipe with a minimum of two (2) non-metallic straps.

The width of the fabric strip shall be at least two (2) feet wide and centered over the

joint. The fabric shall be laid transversely in the trench of each joint prior to laying

pipe and shall be centered over the joint. The inside of all concrete pipes shall be

mortared to the spring line of the pipe. When pipes enter structures, the inside of the

pipe/structure joint shall be fully mortared.

Non-Woven geotextile filter fabric shall meet the following requirements:

• 90 lbs. Tensile Strength (ASTM D4632),

• 50% Tensile Elongation (ASTM D4632)

• 250 lbs. CBR puncture (ASTM D6241),

• 40 lb. Trapezoidal Tear Strength (ASTM D4533),

• 70% UV resistance at 500 hours (ASTM D4355),

• 50 US Sieve Apparent Opening Size (AOS) (ASTM D4751),

• 150 gpm/ft2 Water Flow Rate (ASTM D4491).

Acceptable non-woven geotextile product manufacturers are ACF Environmental 35,

US Fabrics 90NW, or approved equal.

5. Permissible construction tolerances between the proposed inverts as shown on the

Drawings and the as-built condition:

a. Maximum deviation of any invert from plan grade: +/-0.05'.

Page 34: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 302 - 7

Proposed Revision 6.5

b. Total deviation of both inverts at each end of a particular line: +/-0.08'.

c. Maximum slope deviation +/- 0.02% between any two points in the line

from the plan slope.

d. The strictest of the above shall apply. Any lines not properly installed in

compliance with the above shall be removed and reinstalled to the proper

alignment and in accordance with all other specification requirements, by

the Contractor at no additional expense to the Owner.

III. MEASUREMENT FOR PAYMENT

A. The cost of excavation, backfill, and disposal of surplus material for drop inlets, intake boxes,

manholes both new and reconstructed, spring boxes, junction boxes, and base sections of pipe tee

units used as drop inlets and manholes shall be included in the bid price for such items. No

additional or separate payment will be made. In the event steps or invert shaping are required, the

cost thereof shall also be included in the price for such items.

B. Bedding stone depth shall be 6-inches and shall be considered incidental to the pipe and

structures.

C. Undercut excavation and the replacement of excavated undercut material shall be as specified in

Section 303.

D. Pipe will be measured in linear feet of each size pipe and material type installed. Pipe will be

measured through the fittings from center of the structure to center of structure or to the terminal

end. When a partial section is required, the actual length of the partial section will be measured in

place. Pipe shall be paid for at the contract unit price per linear foot, complete in place. Payment

will include the cost of the following:

1. Backfilling, compacting, and compaction testing

2. Bedding

3. Cleaning prior to acceptance, as required

4. Dewatering

5. Disposal of surplus material

6. Excavation

7. Joint Wrapping & Sealing, including geotextile fabric

8. Main line fittings

9. Pipe anchor blocks

10. Restoration in right-of-way and shoulders and easements (including curb and gutter

restoration), unless otherwise specified in the Contract Documents.

11. Storm sewer and appurtenances

12. Stripping and stockpiling topsoil

13. Temporary seeding and stabilization

14. Temporary sheeting and bracing.

E. Pipe culverts will be measured and paid in linear feet. Pipe will be measured through the fittings

from center of the structure to center of structure or to the terminal end. When a partial section is

required, the actual length of the partial section will be measured in place.

F. Pipe tees and elbows will not be measured separately.

Page 35: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

REGIONAL CONSTRUCTION STANDARDS

Proposed Revision Form

March 22, 2012

Proposed Revision To:

General Provisions (Division 1)

Technical Specifications (Divisions 2-8)

Standard Details

Change No.

6.6

(ASSIGNED BY TECHNICAL REVIEW COMMITTEE)

Hampton Roads Planning District Commission

723 Woodlake Drive

Chesapeake, VA 23320 (Phone: 757-420-8300)

Date Proposal Received

November 30, 2017

(ASSIGNED BY TECHNICAL REVIEW COMMITTEE)

Subsection or Standard Detail to be Revised: 824.1.2 On page(s): 824-2

Proposed Revision:

Add ASTM F2561-16 reference for: “Rehabilitation of a Sewer Service Lateral and Its Connection to the Main Using a One Piece

Main and Lateral Cured in Place Liner

Reason for Revision:

Provides ASTM reference for hydrophilic seals called for in the specifications under Section 824.

Special Considerations or Restrictions in Usage/Construction: Yes No (If yes, explain below)

Performance History: List at least five locations where the material or procedure has been used successfully. Include

contact individuals and phone numbers.

Location Contact Phone No

Submitted By: TRC Address:

Agency:

Phone No:

Instructions: Use a separate form for each revision. Provide exact wording. Cite applicable Standards and Test Designations

(ASTM, AWWA, AASHTO, etc.) For minor changes, copy present wording using strike through for words to be

deleted and bold new text. For major changes, rewrite or add paragraphs/sections. Attach plain paper to this form if

more space is needed. Reason for change MUST be given.

TRC Action: February 7, 2018 (Date)

Recommended for:

Approval as submitted

Approval as modified by TRC

Denial

Page 36: TREASURER Agenda.pdf · Protecto 401 shall not be applied over Protecto 401 Joint Compound. Joint Compound shall not be applied over wet or frozen surfaces. (viii) Factory Inspection

June 2016 824 - 2

Proposed Revision 6.6

installation of the lateral liner the contractor shall verbally notify the resident(s) that their sewer

service will be temporarily interrupted and then notify the resident(s) again once sewer service

is reestablished.

D. If the Contractor damages the sewer main or lateral during construction and is unable to

complete the lining in a manner that is satisfactory to the Owner, the Contractor shall submit

method of repairs to the Owner. Upon approval by the Owner, the Contractor shall make repairs

at no additional cost the Owner and complete the CIPP installation.

E. The Contractor shall perform all required permanent landscape restoration of disturbed areas on

private property and within the locality or VDOT right-of-way upon completion of the Work to

the satisfaction of the Owner and/or VDOT.

F. The Contractor shall comply with the Contract Documents for erosion and sediment control and

other applicable requirements to protect drainage structures, systems, and waters of the

Commonwealth.

G. It shall be the responsibility of the Contractor to schedule and perform his Work in a manner

that does not cause or contribute to incidence of overflows or spills of sewage from the sewer

system. In the event Contractor’s Work activities contribute to overflows or spills, the Contractor

shall immediately take appropriate action to contain and stop the overflow, clean up the spillage,

disinfect the area affected by the spill, and notify the Owner in a timely manner.

1.2 RELATED DOCUMENTS

This Section references ASTM, NASSCO, and AWWA standards that are made part hereof by

reference, and shall be the latest edition and revision thereof. If there is a conflict between these

standards and this Section, this Section will govern. The testing specifications include but are not

limited to the following:

A. ASTM D543 – Standard Practices for Evaluating the Resistance of Plastics to Chemical

Reagents.

B. ASTM D790 – Standard Test Methods for Flexural Properties of Unreinforced and Reinforced

Plastics and Electrical Insulating Materials.

C. ASTM D2990 – Standard Test Methods for Tensile, Compressive, and Flexural Creep and

Creep-Rupture of Plastics.

D. ASTM D5813 – Standard Specification for Cured-In-Place Thermosetting Resin Sewer Pipe.

E. ASTM F1216 – Standard Practice for Rehabilitation of Existing Pipelines and Conduits by the

Inversion and Curing of a Resin-Impregnated Tube.

E.F. ASTM F2561 – Standard Practice for Rehabilitation of a Sewer Service Lateral and Its

Connection to the Main Using a One Piece Main and Lateral Cured-in-Place Liner

F.G. Products shall conform to Section 200

1.3 SUBMITTALS

A. Design Calculations