FLORIDA DEPARTMENT OF TRANSPORTATION
FDOT MODIFICATIONS TO STANDARD
SPECIFICATIONS FOR STRUCTURAL SUPPORTS
FOR HIGHWAY SIGNS, LUMINAIRES
AND TRAFFIC SIGNALS (LTS-6)
FDOT STRUCTURES MANUAL
VOLUME 9
JANUARY 2013
-
7/27/2019 transportation design manual
2/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
i
Structures Manual Home
Table of Contents
Table of Contents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 General Features of Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.1 Scope (Rev. 01/13) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.4 Functional Requirements (Rev. 01/13) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.4.2 Structural Supports for Signs and Traffic Signals . . . . . . . . . . . . . . . . . . . 1
2.4.2.2 Size, Height and Location of Signs (Rev. 01/13) . . . . . . . . . . . . . . . . . 1
Figure 1 Example: actual signs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Figure 2 Example: signs used in design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.4.2.4 Variable Message Signs (Rev. 01/13). . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.4.2.5 Horizontal Span and Cantilever Limits . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33.8 Wind Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.8.2 Basic Wind Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.8.3 Wind Importance Factor Ir(Rev. 01/13). . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FDOT Table 3-3 Minimum Design Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.8.6 Drag Coefficients Cd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.8.7 Lift Coefficient for Traffic Signals Cl . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.9 Design Wind Loads On Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.9.1 Load Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.9.3 Design Loads for Vertical Supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53.10 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5 Steel Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.5 Material - Structural Steel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.13 Cables And Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.14 Details of Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.14.3 Transverse Plate Thickness (Rev. 01/13) . . . . . . . . . . . . . . . . . . . . . . . . 6
5.15 Welded Connections (Rev. 01/13) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.15.1 Tube-to-Tube Splice Circumferential Welds (Rev. 01/13) . . . . . . . . . . . . 7
5.15.3 Tube-to-Transverse Plate Connection Welds (Rev. 01/13) . . . . . . . . . . . 75.16 Bolted Connections (Rev. 01/13) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.17 Anchor Bolt Connections (Rev. 01/13) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.17.1 Anchor Bolt Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.17.2 Anchor Bolt Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.17.3 Design Basis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.17.3.3 Use of Grout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
http://structuresmanualintroduction.pdf/http://-/?-http://structuresmanualintroduction.pdf/http://-/?- -
7/27/2019 transportation design manual
3/19
-
7/27/2019 transportation design manual
4/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
1
Structures Manual Home
1 INTRODUCTION
C 1.1Add the following:Structures Manual Introduc t ionI.6 is
updated annually to reflect the specificspecifications editions and interimsadopted by the FDOT.
1.1 Scope
Add the following:
Conform to the date specific AASHTOPublications listed in Structures ManualIntroduct ionI.6 References.
2 GENERAL FEATURES OF DESIGN
C 2.1Add the following:The FDOT Plans Preparation Manualcontains additional FDOT requirements forsign, signal and lighting structures. The
FDOT Design Standardscontainsdrawings for all typical sign, signal andlighting structures.
2.1 Scope (Rev. 01/13)
Add the following:
See Chapters 2, 7 and 29 of the FDOTPlans Preparation Manual, Volume 1
regarding the use of FDOT DesignStandards and other plans preparationrequirements.
2.4 Functional Requirements(Rev. 01/13)
2.4.2 Structural Supports for Signsand Traffic Signals
C 2.4.2.2Add the following:Minimum sign areas provide a reasonableallowance for future sign panelinstallations without the need for a newsupport structure.Minimum sign areas for overhead variablemessage sign supports are normally notrequired.
See the FDOTPPM, Volume 1,Introduction for a link to the Urban AreaBoundary Maps. See PPM, Volume 1 forcantilever and span overhead sign supportlocation criteria.
2.4.2.2 Size, Height and Location ofSigns (Rev. 01/13)
Add the following:
Span type overhead sign structures inurban locations shall be designed eitherfor the actual signs shown on the signingplans or for a minimum sign area of 120sq. ft. (12 ft. W x 10 ft. H) per lane,whichever is the greater. If the signingplans require signs for only one trafficdirection, the minimum sign area per lanerequirement applies to the traffic lanes in
this direction only.
Cantilever type overhead sign structuresin urban locations shall be designed eitherfor the actual signs shown on the signingplans or for a minimum sign area of 80 sq.ft. (8 ft. W x 10 ft. H) located at the end ofthe cantilever, whichever provides the
http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/http://www.dot.state.fl.us/rddesign/PPMManual/PPM.shtmhttp://www.dot.state.fl.us/rddesign/PPMManual/PPM.shtmhttp://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/http://www.dot.state.fl.us/rddesign/PPMManual/PPM.shtmhttp://www.dot.state.fl.us/rddesign/PPMManual/PPM.shtm -
7/27/2019 transportation design manual
5/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
2
Structures Manual Home
more stringent load or stress at thelocation under consideration.
Figures 1 and 2 show how to apply theabove minimum sign areas for span typeoverhead sign structures in urban
locations.Overhead signs in rural locations shouldbe designed for the actual sign shown onthe signing plans.
Figure 1 Example: actual signs
Figure 2 Example: signs used in design
http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/ -
7/27/2019 transportation design manual
6/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
3
Structures Manual Home
C 2.4.2.4Add the following:The minimum requirements given provideadditional measures to limit the possibilityof galloping.
Since cantilever overhead VariableMessage Sign (VMS) structures are moresusceptible to fatigue than span overheadVMS structures, span structures should beused whenever possible.
In Florida, overhead VMS structures aretypically referred to as Dynamic MessageSign (DMS) structures.
2.4.2.4 Variable Message Signs(Rev. 01/13)
Add the following:
For all overhead Variable Message Sign(VMS) structures, the horizontal membershall consist of a truss with a minimum oftwo chords with a minimum center-to-center distance between the chords of 3'-0". See FDOT section 11.8 for VMSmaximum span-to-depth ratios.
FDOT vertical clearance requirements forVMS structures are found in PPM, Volume1, Chapter 2.
C 2.4.2.5
Add the following:These limits were chosen based on pastpractice and practical experience.
A FDOT Design Variation is required whensign or signal structure limits areexceeded. The design variationdocumentation shall include the type ofstructure, height, length, discussion ofalternatives, and costs.
2.4.2.5 Horizontal Span and CantileverLimits
New Section, add the following:
Sign and signal structures shall be limited tothe following maximum horizontal lengths:
Structure Type Max Length
Span Overhead Sign 250 feet
Cantilever Overhead Sign 50 feet
Mast Arm 78 feet
Span Wire Assembly 250 feet
3 LOADS
C 3.8FDOTPPM, Volume 1, Section 25.4.27defines the structures where evaluation isnecessary.
3.8 Wind Load
Delete the last paragraph and add thefollowing:
The use of Appendix C is only permittedfor the evaluation of existing structures.
C 3.8.2Add the following:FDOT SDGTable 2.4.1-2was derivedfrom the ASCE 7-05 wind speed map.
To simplify the design process, FDOT hasdesignated one wind speed per county.
3.8.2 Basic Wind Speed
Delete the entire paragraph includingFigure 3-2, and add the following:
The wind loads shall be based on the windspeeds (mph) shown in FDOT SDGTable2.4.1-2
http://structuresmanualintroduction.pdf/http://www.dot.state.fl.us/rddesign/PPMManual/PPM.shtmhttp://www.dot.state.fl.us/rddesign/PPMManual/PPM.shtmhttp://vol1_sdg.pdf/http://vol1_sdg.pdf/http://vol1_sdg.pdf/http://vol1_sdg.pdf/http://vol1_sdg.pdf/http://structuresmanualintroduction.pdf/http://vol1_sdg.pdf/http://vol1_sdg.pdf/http://vol1_sdg.pdf/http://www.dot.state.fl.us/rddesign/PPMManual/PPM.shtmhttp://www.dot.state.fl.us/rddesign/PPMManual/PPM.shtm -
7/27/2019 transportation design manual
7/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
4
Structures Manual Home
C 3.8.3Add the following:A 1.5-year design life has been added fortemporary construction signs. Theimportance factor is calculated based on"Wind Speed for Design of TemporaryStructures" by D.W. Boggs and J.A.Peterka, Structures Congress, 1992,Compact Papers, ASCE, 1992.
Florida has traditionally designedLuminaire support structures, 50 feet inheight and less, and strain poles for a 25year design life.
Concrete strain poles are designed for
zero tension stress, therefore a twenty-fiveyear design life is appropriate.
3.8.3 Wind Importance FactorIr(Rev. 01/13)
Add the following Wind Importance Factor
to Table 3-2:
RecurrenceInterval
Years
V =85-100
mph
V > 100
mphAlaska
1.5 0.45 0.2 ---
Delete Table 3-3 and add the followingFDOT Table 3-3:
FDOT Table 3-3 Minimum Design Life
Design Life Structure Type
50-year
Overhead sign structures
Luminaire support structures>50' in height.
Mast Arms
Monotubes
Steel Strain Poles
ITS Camera Poles >50 in
height
25-year
Luminaire supports and other
structures 50' in height.
Concrete Strain Poles
10-year Roadside sign structures
1.5-year Temporary construction signsA 1.5-year design life (Ir= 0.2) for
temporary construction signs shall only beused with a 150 mph design wind speed.
C 3.8.6Add the following to note 2 at the bottomof Table 3-6:
A drag coefficient for traffic signal installedwith the ability to swing has beenestablished through research (Cook
2007). On span wire systems where signaland signs are allowed to swing, varying Cd
as a function of swing angle is allowed(Hoit and Cook 1997).
3.8.6 Drag Coefficients Cd
Replace the coefficient of drag for TrafficSignals in Table 3-6 with the following:
Traffic Signals - no ability to swing - 1.2
Traffic Signals - installed with the ability toswing on span wire systems under fullwind load - 0.7
http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/ -
7/27/2019 transportation design manual
8/19
-
7/27/2019 transportation design manual
9/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
6
Structures Manual Home
3.10 References
Add the following:
Cook, R.A. (2007). Development ofHurr icane Resistant Cable Supp orted
Traff ic Sign als(FDOT Report# BD545RPWO #57). Gainesville, Florida:University of Florida.
Hoit, M.I., Cook, R.A. (1997). ComputerAided Design Program fo r Signal Pole
and Span Wire Assemb l ies With Two
Point Connect ion System(FDOTReport# 0510653). Gainesville, Florida:University of Florida.
5 STEEL DESIGN
C 5.4Add the following:In some environmental conditions inFlorida, A588 steel has deterioratedsignificantly faster than expected.
5.5 Material - Structural Steel
Add the following:
Do not specify ASTM A588 (rustic, Corten,self-oxidizing", or "self-weathering") steelin sign, signal, or lighting structures.
C 5.13Add the followingCables used in the construction of span-
wire pole structures are listed in FDOTSpecification 634.
5.13Cables And Connections
Add the following:
Use the cable breaking strength valuesspecified in FDOT Specification 634.
5.14 Details of Design
C 5.14.3Add the following:Research has proven full-penetrationgroove welds combined with thicker baseplates increases the pole-to-base-plateconnection fatigue strength.
5.14.3 Transverse Plate Thickness(Rev. 01/13)
Add the following:
For base plate connections withoutstiffeners on 50 year recurrence interval
structures, the minimum base platethickness shall be 2 inches.
C 5.15Add the following:Section 5.15 is referenced as a requirementin FDOT Specification 460-6.4.
5.15 Welded Connections (Rev. 01/13)
http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/ -
7/27/2019 transportation design manual
10/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
7
Structures Manual Home
C 5.15.1Add the following:The Departments intent is to avoid anyunnecessary welds on sign, signal orlighting structures.
5.15.1 Tube-to-Tube SpliceCircumferential Welds(Rev. 01/13)
Add the following:
On steel sign and signal structures, nocircumferential welds are permitted on theuprights, arms or chords with theexceptions of the base plate weld, theflange plate connections on tubular trussmembers, mitered arm-to-upright angleweld on monotubes. and uprights greaterthan 40 feet in height.
C 5.15.3Add the following:Research has proven full-penetrationgroove welds combined with thicker baseplates increases the pole-to-base-plateconnection fatigue strength.
5.15.3 Tube-to-Transverse PlateConnection Welds (Rev. 01/13)
Add the following:
For base plate connections withoutstiffeners on 50 year recurrence intervalstructures, only use full-penetrationgroove welds.
C 5.16Add the following:Through bolted connections provide fullytensioned A325 bolts.
5.16 Bolted Connections (Rev. 01/13)
Add the following:
Design all pole to arm connections onMast Arm structures as "through bolted".Tapped connections are not permitted. Donot use hardened steel washers betweenthe end plate of a Mast Arm and themounting plate of the pole.
C 5.17Add the following:A minimum of eight anchor bolts providesredundancy and better distribution offorces through the base plate.
5.17 Anchor Bolt Connections(Rev. 01/13)
Add the following:
All sign, signal, and lighting structuresdesigned for a minimum service life of 50years (wind speed based on a 50-yearmean recurrence interval) shall use aminimum of eight, Grade 55, ASTM F1554anchor bolts at the pole to foundationconnection, with the exception of Mast
Arm signal structures where the minimumis six anchor bolts.
http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/ -
7/27/2019 transportation design manual
11/19
-
7/27/2019 transportation design manual
12/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
9
Structures Manual Home
6 ALUMINUM DESIGN
C 6.1Add the following:Aluminum overhead sign structures have
been prone to unacceptable levels ofvibration and fatigue cracking.
6.1 Scope
Add the following:
Do not specify aluminum overhead signstructure supports with the exception ofthe vertical sign panel hangers, which maybe aluminum or steel.
7 PRESTRESSED CONCRETE
DESIGN
7.5 Design
C 7.5.1Add the following:
FDOT uses Standard Prestressed ConcretePoles in accordance with Index 17725 andSpecification 641. After analysis of the
proposed span-wire pole structure, theDesigner selects the appropriate pole usingthe design moment values given in theInstructions for Design Standards for Index17725.
7.5.1 Method of Design
Add the following:
For Standard Prestressed Concrete PoleDesign, see Instructions for DesignStandard Index 17725, for the ServiceMoment Capacity and Ultimate Moment
Capacity. An increased percentage ofAllowable Stress for Group II loading (LTSTable 3-1) is not applicable for PrestressedConcrete Poles, since Group II loading is anultimate moment capacity calculation.
C 7.5.2Add the following:FDOT uses Class V Special, 6 ksi or ClassVI 8.5 ksi concrete in accordance withSpecification 346.
7.5.2 Concrete Strength
Replace this section with the following:
The minimum compressive concretestrength shall be 6 ksi.
7.10 Durability
C 7.10.2Add the following:FDOT requires a minimum 1 inch cover onall concrete poles in all environments.
7.10.2 Concrete Cover
Replace this section with the following:
The minimum clear concrete cover for allprestressed and non-prestressed poles is1 inch.
http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/ -
7/27/2019 transportation design manual
13/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
10
Structures Manual Home
10 SERVICEABILITY
REQUIREMENTS
C 10.5Add the following:Permanent camber equal to 1.5 times thedead load deflection provides for a better
appearance than the relatively small L/1000given in AASHTO. For mast arms, a twodegree upward angle at the arm/uprightconnection is standard industry practice.
10.5Camber
Replace this section with the following:
Provide permanent camber equal to 1.5times the dead load deflection for overheadsign structures. For span overhead signstructures, arch the horizontal memberupwards and for cantilever overhead signstructures rake the vertical supportbackwards. For mast arm signal structures,provide a two degree upward angle at thearm/upright connection.
11 FATIGUE DESIGN (Rev. 01/13)
C 11.6Add the following:Research performed at the University ofTexas (Report 0-4178) concludedincreasing "the end plate thickness for a10-inch mast arm from 1.5 inches to 2inches increased the fatigue life fromcategory E' to category D."
Since FDOT Design Standards andprograms for Mast Arm signal structures,overhead tri-chord sign trusses, and High-mast light poles use relatively thick baseplates, Fatigue Category II is appropriate.In addition, there have been no reports offatigue damage to sign, signal and lightingstructure designed using FDOT programsand built using FDOT Design Standards.
11.6 Fatigue Importance Factors(Rev. 01/13)
Add the following:
Use Fatigue Category II for all flat panelsign, traffic signal, and lighting supportstructures meeting the limits in 2.4.2.5 anddesigned using FDOT Design Standardsand Programs or designed in accordancewith Chapter 4 of NCHRP W176, "Cost-Effective Connection Details for HighwaySign, Luminaire, and Traffic SignalStructures". Use Fatigue Category I for allother sign, traffic signal, and lightingsupport structure designs including allVMS support structures.
http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/ -
7/27/2019 transportation design manual
14/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
11
Structures Manual Home
11.7 Fatigue Design Loads
C 11.7.1Add the following:Vibration mitigation devices are seldomnecessary and installed only afterexcessive vibration has been observed andthe device is approved by the Department.Cantilevered sign support structures withhorizontal three or four chord trusses havenever been reported to vibrate from vortexshedding or galloping. (ref. FHWAGuidelines for the Installation, Inspection,Maintenance and Repair of StructuralSupports for Highway Signs, Luminaries,
and Traffic Signals)
11.7.1 Galloping
Replace the 2nd, 3rd and 4th paragraphswith the following:
Vibration Mitigation devices are notallowed in lieu of designing for galloping.
Exclude galloping loads for the fatiguedesign of overhead cantilevered sign andVMS support structures with three or fourchord horizontal trusses with bolted web tochord connections.
C 11.8Add the following:The minimum requirements given provideadditional measures to limit the possibilityof galloping
11.8 Deflection
Add the following:
In addition, VMS structures shall also meetthe following maximum span-to-depthratios:
VMS Structure TypeMax.
Span-to-DepthRatio
Overhead SpanStructure
25
Overhead CantileverStructure
9
13 FOUNDATION DESIGN
C 13.6Add the following:For standard drilled shaft details, seeDesign Standard Indexes 11320, 17502,17723 and 17745 for span overhead signstructures, high mast light poles, steelstrain poles, and mast arms respectively.
13.6 Drilled Shafts (Rev. 01/13)
Add the following:
Drilled shafts are the standard foundationtype on high mast light poles, overheadsigns, mast arms and steel strain poles.
http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/ -
7/27/2019 transportation design manual
15/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
12
Structures Manual Home
13.6.1 Geotechnical Design
C 13.6.1.1Add the following:FDOT experience has established a safetyfactor of 2 produces conservative designs.
The torsion resistance equation is basedon the theory for the Beta Method (O'Neill
and Reese, 1999). A single fdot factorof 1.5 is used to adjust for the concurrentoverturning and torsional forces and tocompare with past FDOT practice. Sincethe consequence of a torsion soil-structurefailure is usually small, some rotation istypically allowable from the design wind.
Since cantilever overhead sign structurescan have significantly more torsion than aMast Arm, a higher safety factor of 1.3 isappropriate.
For soils with SPT N-values less than 5,consult the Geotechnical Engineer foradditional recommendations.
13.6.1.1 Embedment (Rev. 01/13)
Add the following:
Use a safety factor against overturning of
2 when using the Broms method.For torsion resistance in drilled shaftssupporting Mast Arm signal and cantileveroverhead sign structures, use thefollowing equations:
TuTn
SF tor--------------
Where
Tn DLFsD
2----
D
2----
2
LconcD
3----
+=
Fs vfdot=
v soilL
2---
=
soil( )tan=
Tu = Torsion force on the drilled shaft
Tn = Nominal torsion resistance of the
drilled shaft
SFtor = Safety Factor against torsion
= 1.0 for Mast Arm signal structures= 1.3 for overhead cantilever sign
structures
D = diameter of the drilled shaft
L = length of the drilled shaft
Fs = unit skin friction
v = effective vertical stress at mid-layer
fdot = load transfer ratio where theallowable shaft rotation may exceed 10
degrees= 1.5 for granular soils where SPT N-
values are 15 or greater
= 1.5N value
15---------------------------
for N-values
greater than or equal to 5 and lessthan 15.
http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/ -
7/27/2019 transportation design manual
16/19
conc
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
13
Structures Manual Home
= unit weight of concrete
soil = unit weight of soil = Coefficient of friction between the
shaft and soil
soil =soil friction angleC 13.6.2
Add the following:Using 1% steel is conservative for flexuraldesign in most cases. Additional stirrups inthe top of the shaft provides resistanceagainst shear failure in the top of the shaft.Due to torsion, additional stirrups may berequired in cantilever structures.
13.6.2 Structural Design
Add the following:
Longitudinally reinforce drilled shaftfoundations with a minimum of 1% steel.
At a minimum, place #5 stirrups at 4 inchspacing in the top two feet of shaft. Incantilever structures, design for shearresulting from the torsion loading on theanchor bolt group.
C 13.6.2.1Add the following:FDOT requires six inches of cover toensure durability in drilled shafts.
Concrete consolidation below the anchorbolts becomes more difficult withreinforcement clear spacing less than sixinches.
13.6.2.1 Details (Rev. 01/13)
Replace the second sentence with thefollowing:
A minimum concrete cover of six inchesover steel reinforcement is required.
Add the following:
The minimum diameter for drilled shafts is36 inches. A minimum main reinforcement
clear spacing of six inches is required forproper concrete consolidation. Stirrups in
drilled shafts for sign, signal and lightingstructures are exempt from this spacingrequirement.
13.10 Embedment of Lightly LoadedSmall Poles and Posts
Add the following:
When using the Broms method for groundsign foundation design, use a safety factor
against overturning of 1.3. When using theBroms method for direct burial concretepole foundation design, use a safety factoragainst overturning of 1.5.
http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/ -
7/27/2019 transportation design manual
17/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
14
Structures Manual Home
13.11 References
Add the following:
Cook, R.A. (2007). Anchor EmbedmentRequirements for Signal /Sign
Structures(FDOT Report# BD545 RPWO#54). Gainesville, Florida: University ofFlorida.
APPENDIX C
C C.1Add the following:By allowing an overstress factor of 1.4,consistent with previous editions of LTS,properly designed existing structures willbe allowed to remain in place in
accordance with thePPM.
C.1 Alternate Method (Rev. 01/13)
Add the following:
When evaluating existing structures inaccordance with PPM25.4.26, the followingdesign assumptions are permitted:
a. an allowable overstress of 1.4 isallowed for Group II loading.
b. allowances for future loads, FDOT2.4.2.2, is not required.
c. evaluation using Section 11, FatigueDesign, is not required (withoutplanned additional loading only).
d. evaluation of the foundation capacity isnot required (without plannedadditional loading only).
C C.2Add the following:To simplify the design process, FDOT hasdesignated one wind speed per county.
C.2 Wind Load
Delete the 2nd and 3rd sentence and addthe following:
The design wind pressures shall becomputed using the wind pressureformula, Eq. C-1, with the appropriatewind speed shown in FDOT Table C.2-1,Wind Speed by County.
http://structuresmanualintroduction.pdf/http://www.dot.state.fl.us/rddesign/PPMManual/PPM.shtmhttp://www.dot.state.fl.us/rddesign/PPMManual/PPM.shtmhttp://structuresmanualintroduction.pdf/http://www.dot.state.fl.us/rddesign/PPMManual/PPM.shtmhttp://www.dot.state.fl.us/rddesign/PPMManual/PPM.shtm -
7/27/2019 transportation design manual
18/19
FDOT Table C.2-1 Wind Speed by County
County (Dist)10
year25
year50
yearCounty (Dist)
10year
25year
50year
Alachua (2) 60 80 90 Lee (1) 80 90 100
Baker (2) 60 80 90 Leon (3) 60 70 80Bay (3) 70 80 90 Levy (2) 70 80 90
Bradford (2) 60 80 90 Liberty (3) 60 80 90
Brevard (5) 80 90 100 Madison (2) 60 70 80
Broward (4) 90 100 110 Manatee (1) 80 90 100
Calhoun (3) 60 80 90 Marion (5) 60 80 90
Charlotte (1) 80 90 100 Martin (4) 80 90 100
Citrus (7) 70 80 90 Miami-Dade (6) 90 100 110
Clay (2) 60 80 90 Monroe (6) 90 100 110
Collier (1) 80 90 100 Nassau (2) 70 80 90Columbia (2) 60 70 80 Okaloosa (3) 70 90 100
DeSoto (1) 70 80 90 Okeechobee (1) 70 80 90
Dixie (2) 70 80 90 Orange (5) 70 80 90
Duval (2) 70 80 90 Osceola (5) 70 80 90
Escambia (3) 70 90 100 Palm Beach (4) 80 100 110
Flagler (5) 70 80 90 Pasco (7) 70 90 100
Franklin (3) 70 90 100 Pinellas (7) 70 90 100
Gadsden (3) 60 70 80 Polk (1) 70 80 90
Gilchrist (2) 60 80 90 Putnam (2) 60 80 90Glades (1) 70 80 90 St. Johns (2) 70 80 90
Gulf (3) 70 90 100 St. Lucie (4) 80 90 100
Hamilton (2) 60 70 80 Santa Rosa (3) 70 90 100
Hardee (1) 70 80 90 Sarasota (1) 80 90 100
Hendry (1) 70 80 90 Seminole (5) 70 80 90
Hernando (7) 70 90 100 Sumter (5) 60 80 90
Highlands (1) 70 80 90 Suwannee (2) 60 70 80
Hillsborough (7) 70 80 90 Taylor (2) 70 80 90
Holmes (3) 60 70 80 Union (2) 60 80 90Indian River (4) 80 90 100 Volusia (5) 80 90 100
Jackson (3) 60 70 80 Wakulla (3) 70 80 90
Jefferson (3) 60 70 80 Walton (3) 70 80 90
Lafayette (2) 60 80 90 Washington (3) 60 80 90
Lake (5) 60 80 90
FDOT Modifications to LTS-6 Topic No. 625-020-018
January 2013
15
Structures Manual Home
http://structuresmanualintroduction.pdf/http://structuresmanualintroduction.pdf/ -
7/27/2019 transportation design manual
19/19
FDOT Modifications to LTS-6 Topic No. 625-020-018
Volume 9 - Revision History January 2013
R9-1
Structures Manual Home
VOLUME 9 - REVISION HISTORY
2.1 ................Added PPM cross reference. Revised Commentary.
2.4 ................Renumbered entire Section.
2.4.2.2 ..........Revised Commentary.
2.4.2.4 ..........Added cross reference for vertical clearance requirements.
3.8.3 .............Revised Table 3-3.
5.14.3 ...........Revised Section title.
5.15 ..............Added Commentary
5.15.1 ...........Revised Section title. Added provision for uprights > 40.
5.15.3 ...........Revised Section title.
5.16 ..............Added limitation for use of hardened steel washers.
5.17 ..............Revised minimum number of anchor bolts.
5.17.4.3 ........Revised Commentary.
11 .................Deleted Sections 11.5 Design Criteria and 11.9 Fatigue Resistance.
11.6 ..............Clarified requirements of Section 11.6.
13.6 ..............Clarified the requirements of Section 13.6.
13.6.1.1 ........Revised variable definition for load transfer ratio. Added fourth Paragraph toCommentary.
13.6.2.1 ........Added clarification for spacing requirement.C.1 ...............Revised cross reference. Added clarification.