transformers technologies

Upload: gnpr1010

Post on 02-Jun-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 Transformers Technologies

    1/86

    Development of New Concepts &

    Technologies - Design of Transformersfor Reliable Operation

    M. Gopal RaoM.E; F.I.E

    Former Director (Transmission),

    A.P.TRANSCO, Hyderabad

  • 8/11/2019 Transformers Technologies

    2/86

    A transformer is a static device used for transferringpower from one circuit to another without change infrequency.

    Operates on the principle of mutual induction betweentwo ckts linked by a common magnetic field.

    EMF induced in a winding is proportional to the fluxdensity in the core, cross section of the core, frequencyand no. of turns in the winding.

  • 8/11/2019 Transformers Technologies

    3/86

    H.V WindingL.V Winding

    Core

    Fundamental equation of transformer

  • 8/11/2019 Transformers Technologies

    4/86

    A transformer basically consists of:

    Magnetic Circuit comprising Limbs, yokes, clamping structures

    Electrical circuit comprising primary, secondary windings

    Insulation comprising of transformer oil and solid insulation viz.paper, pressboard, wood etc. and bracing devices

    Main tank housing all the equipment

    Radiators, conservator tank

    On or Off load tap changer

    Vent pipe, Bucholtz relay, Thermometers

    Fans, Cooling pumps connected piping

    Terminals i.e. connecting leads from windings to bushing withsupporting arrangements

  • 8/11/2019 Transformers Technologies

    5/86

  • 8/11/2019 Transformers Technologies

    6/86

    Design Parameters

    Voltage Ratio No. of phases

    Flux density Rated capacity

    Current density Insulation& cooling medium

    Insulation levels Tap changerVector group Cooling arrangement

    Percentage Impedance Oil preservation system

    Short circuit withstand

    capacity Operating conditions

  • 8/11/2019 Transformers Technologies

    7/86

    Features of Power Transformers

    Single Phase

    Three phase

    Star or Delta connected Primary

    Star or Delta connected Secondary With or without Tertiary winding

    Provided with Off-circuit tap switch or On-load TapChanger for voltage regulation

  • 8/11/2019 Transformers Technologies

    8/86

    Codes and Standards

    Codes or Regulations are mandatory requirementsstipulated to ensure the safety of the product during testingand service.

    Standards are the basis of agreement and can be used forlimited scope or even restricted. Standards also promoteinterchangeability. Standards exist for material, product,process, testing, calibration etc.

    Specifications are based on mandatory requirements of thepurchaser and agreed requirements of the standard.

  • 8/11/2019 Transformers Technologies

    9/86

    OPERATING CONDITIONS

    The environment in which a transformer works and the

    quality in design and construction play a role on its

    performance. A transformer working under normal operating

    conditions, in all probability, gives satisfactory performance

    throughout its lifeNORMALOPERATING CONDITIONS:

    1. Rated voltage and rated current with permissible margins.

    2. Temperatures of oil and windings not exceeding the

    prescribed values.3. Availability of auxiliary and control supply and proper

    functioning of accessories and protective devices.

    4. Free from external faults such as line breakdowns and

    equipment breakdowns.

  • 8/11/2019 Transformers Technologies

    10/86

    User should specify the conditions under which transformer is expected

    to work viz. quality and nature of load temperature limit, voltageconditions, short circuit withstand capacity considering present and

    expected fault levels.

    Parameters specific to locations are to be evaluated and specified to

    assess the operating requirement.

    Manufacturers should ensure that factory tests as required under

    standards and the user specifications are done to verify the quality and

    ability of the transformer to withstand all service stresses during life timeof the transformer.

  • 8/11/2019 Transformers Technologies

    11/86

    Insulation

    Major Insulation: Oil and Paper or cellulose material.

    Paper and pressboard insulation immersed in oil and subjected to

    temperature for longer periods, lose mechanical strength. Dielectric

    strength remains until paper is charred, when free carbon becomes

    conducting or too brittle to withstand mechanical shocks. De-

    polymerization of insulation takes place when deterioration starts.

    Ageing of tr. depends on the dielectric performance of the insulation

    system.

    Higher the temperature the faster is insulation deterioration.

  • 8/11/2019 Transformers Technologies

    12/86

    Transformer operates at below normal temperatureLoss of life of

    insulation is less than normal.

    Operating temp. is greater than normalloss of life is higher than

    normal.

    Transformer may be safely operated for a time at above normal

    temperature provided the loss of insulation life during this period isadequately compensated by operating for a sufficiently long time at

    temperatures below normal.

    Between 80 to 140 deg. C, the rate of loss of life due to ageing ofinsulation is doubled for every 6degrees c rise in temperature.

  • 8/11/2019 Transformers Technologies

    13/86

    Proper upkeep of solid and liquid insulation to their specified levels with

    marginal and permissible variations ensure longevity. This is possible byproper operation such as maintaining the load current and voltage and oil

    and winding temperatures at their rated levels and not exceeding these

    levels.

    Paper or oil dielectric have varying degree of sensitivity to degradation

    upon overloading, ingress of moisture, improper handling and storage

    affecting life. It is necessary that moisture ingress into oil is prevented by

    suitable oil preservation system.

  • 8/11/2019 Transformers Technologies

    14/86

    Normally flux density is chosen near knee point of magnetization curve

    leaving sufficient margin to take care of voltage and frequency variations.

    CRGO steel with silicon content of approx. 3% is used for magneticcircuit. Characteristics of good core are :

    1. Max. magnetic induction to obtain a high induction amplitude in an

    alternating field.

    2. Minimum specific core loss and low excitation current

    3. Low magnetostriction for low noise level

    4. Good mechanical processing properties.

  • 8/11/2019 Transformers Technologies

    15/86

    Magnetostriction is change in configuration ofa magnetizable body in a magnetic field whichleads to periodical changes in the length of thebody in an alternating magnetic field.

    Due to magnetostriction of laminations in analternating field core vibrates generating noisein the core.

  • 8/11/2019 Transformers Technologies

    16/86

    Current density is an important parameter to design the section of the

    conductor for a specified temperature rise, rated capacity and short

    circuit withstand capacity of the transformer.

    Different types of windings :

    Distributed crossover winding

    Spiral windingHelical winding

    Continuous disc winding

    Interleaved disc winding

    Shielded layer winding

  • 8/11/2019 Transformers Technologies

    17/86

    CHARACTERISTICS OF TRANSFORMER OIL:

    A. PHYSICAL

    Appearance

    The oil shall be clear, transparent and free from suspended

    matter

    If color of oil is

    a) Light - indicates degree of refining

    b) Cloudy or foggy - Presence of moisture

    c) Greenish tinge - Presence of copper salts

    d) Acid smell - Presence of volatile acid. Can causecorrosion

  • 8/11/2019 Transformers Technologies

    18/86

    Density: At 27deg. c is 0.89gm/cu.cm. This ensures that

    water in the form of ice present in oil remains at the bottom

    and does not float up to a temp. of about

    10 deg. c.

    Viscosity: Is a measure of oil resistance to continuous flow

    without the effect of external forces. Oil must be mobile in

    transformers to take away heat. Viscosity shall be as low as

    possible at low temperatures. Maximum value at 27deg.cshall be 27 cst

    Flashpoint: is the temperature at which oil gives so much

    vapor, which when mixed with air forms an ignitable mixtureand gives a momentary flash on application of a flame.

    Minimum flash point of a good oil shall be 140 deg. C.

  • 8/11/2019 Transformers Technologies

    19/86

    Pour point

    is the temperature at which oil will just flow under prescribed

    conditions. If oil becomes too viscous or solidifies it will hinderthe formation of convection currents, thus cooling ofequipment will be affected.

    Maximum pour point shall be -9 deg. C

    Interfacial Tension

    Is the measure of resultant molecular attractive force betweenunlike molecules like water and oil at the interface. Presence ofsoluble impurities decrease molecular attractive force between

    oil and water. This gives an indication of degree of sludging ofoil.

    Minimum value 40 dynes/M or 0.04 N/M

    .

  • 8/11/2019 Transformers Technologies

    20/86

    CHEMICAL

    Neutralization Number

    Is a measure of organic and inorganic acids present in the oil.Expressed as mg. of KOH required to neutralize the totalacids in one gm. Of oil.

    Limits for fresh oil - 0.03 mg KOH/gm - maximum

    Limits for used oil - 0.05 mg KOH/gm - maximum

    It leads to formation of sludge, metal surface corrosion andlowering of dielectric strength.

    Corrosive SulphurIt indicates the presence sulphur, sulphur compounds, whichare corrosive in nature and corrode the copper surface.

  • 8/11/2019 Transformers Technologies

    21/86

    Oxidation Stability

    This is measured by ageing the oil by simulating actualservice condition of a transformer. Covers the evaluation

    of acid and sludge forming tendency of new mineral oils.For used oil, should be minimum to minimize electricalconduction and corrosion

    Water Content: Due tomoisture entry into oil.

    a) By accidental leakage

    b) Breathing actionc) During oil filling or topping up

    d) By chemical reaction

    In unused oil - Maximum 30 ppm

    Oil in transformer 145 KV & above - Maximum 15 ppmOil in transformer below 145 KV - Maximum 25 ppm

    It reduces electrical strength and promotes degradation of

    oil as well as paper.

    ELECTRICAL

  • 8/11/2019 Transformers Technologies

    22/86

    ELECTRICAL

    Electric Strength

    Is the voltage at which arc discharge occurs between two

    electrodes when oil is subjected to an electric field under

    prescribed conditions.

    New oil unfiltered - 30 KV minimum (rms)

    New oil filtered - 60 KV minimum (rms)

    Resistivity

    It is numerically equal to the resistance between opposite facesof a centimeter cube of oil. Insulation resistance of thewindings of transformer is dependant on the resistivity of oil.A low value indicates the presence of moisture andconducting contaminants.

    Values for a new transformer are(12)

    At 27 deg. c 500x 10 ohm.cm

    (12)

    At 90 deg. c 30x 10 ohm.cm

  • 8/11/2019 Transformers Technologies

    23/86

    Dielectric Dissipation Factor (Tan Delta & Loss Tangent)

    Is measure of dielectric losses in oil & hence the amount of heat

    energy dissipated.

    It gives an indication as to the quality of insulation. A high value

    indicates presence of contaminants or deterioration products

    such as water, oxidation products, soluble varnishes, and resins.

    1) Tan delta at 90 for unused oil - maximum 0.2

    2) Tan delta at 90 oil before charging transformer -

    maximum 0.005 (1/2%)

    Low value of tan delta indicates low losses

  • 8/11/2019 Transformers Technologies

    24/86

    Vector Group and Polarity

    When induced voltages of pri . and sec. windings are in same direction, polarity

    of the two windings is same. This is called subtractive polarity. When theinduced EMFs are in opposite direction , the polarity is called additive.

    Pri. and sec. windings on any one limb have induced emfs that are in time phase.

    Different combinations of internal connections and connections to terminals

    produce different phase divergence of sec. voltage.

    Vector group or connection symbol of a transformer denotes the method of

    connection of pri. and sec. windings and the phase angle divergence of sec. with

    respect to primary.

  • 8/11/2019 Transformers Technologies

    25/86

    Vector Groups

    1

    3

    4

    U

    VW

    u

    w

    v

    u

    w

    v

    1 & 3 YNd1

    2 & 4

    YNd11

    U

    VW

    2

  • 8/11/2019 Transformers Technologies

    26/86

    U

    VW

    u

    v

    w

    u

    v

    w

    1

    2

    3

    4

    Vector Groups

    U

    VW

    1 & 3 Dyn11

    2 & 4 Dyn5

  • 8/11/2019 Transformers Technologies

    27/86

    Vector Group Test

    A

    BC

    a

    b

    c

    A

    BC

    a

    bc

    DY 11

    VAb = VAc

    VBb = VBc

    VCb > VCc

    Aa = 0

    Ab = bc = ca

    Bb = Cc

  • 8/11/2019 Transformers Technologies

    28/86

    Tap changer

    Device for regulating the voltage of transformer.

    Off circuit tap changer : Tap changing is effected when tr. is off. These

    are cheaper. They are used where frequency of tap changing is very less.

    On load tap changer : Here tap changing is effected without interruptingload. On load tap changer normally consists of transition resistors which

    bridge the circuit during tap changing operation.

    Two types of OLTCs :

    Single compartment typeIn this type selection of taps and switchingare carried out on the same contacts.

    Double compartment typeIn this tap selection is done separately and

    switching is done in a separate diverter switch.

  • 8/11/2019 Transformers Technologies

    29/86

  • 8/11/2019 Transformers Technologies

    30/86

  • 8/11/2019 Transformers Technologies

    31/86

    Externally mounted OLTC/1

    Requirements for a tap changer

  • 8/11/2019 Transformers Technologies

    32/86

    Requirements for a tap changer

    Percentage variation required for each tap

    No. of taps and step voltage

    Maximum through currentInsulation level to ground and between various contacts.

    No of steps and basic connections

    Temporary overloads and short circuit strength

    Automatic voltage regulating relays are used for automatic control of bus

    bar voltage.

    Output of voltage transformer connected to controlled voltage side of the

    tr. is used to energize AVR relay. When voltage deviation exceeds a

    preset limit, a control signal to raise or lower tap operation is given. A

    time delay unit is connected in the circuit to prevent unnecessary

    operation or hunting of tap changer during transient voltage change.

  • 8/11/2019 Transformers Technologies

    33/86

    Types of Tap Changers

    Based on function

    Constant Flux Voltage Variation (CFVV)

    Variable Flux Voltage Variation (VFVV)

    Combination of above both Based on method of tap change

    Linear

    Reversing

    CoarseFine Bridging

  • 8/11/2019 Transformers Technologies

    34/86

    Tap Changer Location

    Neutral End Middle of winding Line End

  • 8/11/2019 Transformers Technologies

    35/86

    Linear Reversing Coarse

    Fine

  • 8/11/2019 Transformers Technologies

    36/86

    Basic conditions of operation

    Load current must not be interrupted during tap

    change operation.

    Tap change must occur without short-circuiting the tap

    winding directly. Positive change of tap position.

    It means make-before-break mechanism to beused. This calls for a transition impedance.

    Also the mechanism should be fast acting typespring loaded.

  • 8/11/2019 Transformers Technologies

    37/86

    General Design considerations

    Capable to normal load/overloads on transformer.

    Maximum system voltage

    Step voltage & no. of steps

    Test voltage to earth and across tapping range

    Maximum surge voltage to earth and across range.

    Maximum test voltages between phases (whereapplicable)

    Current ratingnormal and overload

  • 8/11/2019 Transformers Technologies

    38/86

    Parts of Tap Changer

    Selector switch

    Tap selection takes place in this switch

    Diverter Switch

    Makebefore-break mechanism with transitionimpedance. Arcing takes place and hence housed ina separate compartment.

    Surge relay

    Conservator with oil level gauge.

  • 8/11/2019 Transformers Technologies

    39/86

    Transition Impedance

    Reactor type

    Resistor type

  • 8/11/2019 Transformers Technologies

    40/86

  • 8/11/2019 Transformers Technologies

    41/86

    P i i l f T h ti

  • 8/11/2019 Transformers Technologies

    42/86

    R2R1

    75

    3

    1

    8

    6

    4

    2

    N

    Principle of Tap changer operation

    M2 T2 T1 M1

  • 8/11/2019 Transformers Technologies

    43/86

    M2 T2 T1 M1 M2 T2 T1 M1 M2 T2 T1 M1

    M2 T2 T1 M1 M2 T2 T1 M1 M2 T2 T1 M1

    1 2 3

    4 5 6

  • 8/11/2019 Transformers Technologies

    44/86

    Parts of Tap Changer

    Motor drive mechanism

    Should rotate in both the directions

    Step-by-step operation

    Tap change in progress indication

    Tap change complete indication

    Sequence contact

    Remote Tap position control & indication

  • 8/11/2019 Transformers Technologies

    45/86

    Cooling Arrangement

    Controlling the temperature inside the tr. is necessary to reduce thermal

    degradation of insulation to ensure longer life. Heat generated in the tr. istransmitted to atmosphere through oil.

    Different types of cooling:

    ONAN typeOil natural and air natural. Hot oil is circulated by natural

    means dissipating heat to atmosphere by natural means.ONAF typeOil natural, air forced. Here air is blown on to the cooling

    surfaces. Forced air takes away heat at a faster rate.

    OFAF typeOil forced, air forced. If the oil is force circulated within the

    tr. and radiator by means of an oil pump, in addition to forced air, still

    better rate of heat dissipation is achieved over ONAF

  • 8/11/2019 Transformers Technologies

    46/86

    OFWF typeOil forced, water forced. Here water is employed for

    cooling oil instead of air. Ambient temp. of water is less than atmosphericair. Hence better rate of cooling is obtained. In this type oil to water heat

    exchangers are employed. Differential pressure between oil and water is

    maintained. Oil is circulated at a higher pressure.

    ODAF/ODWF typeOil directed, air/water forced. If the oil is directed

    to flow past the windings, large quantities of heat can be taken away by

    oil. Cool oil is directed to flow through the windings in predetermined

    paths. Oil is circulated by a forced oil system like oil pumps. This ensures

    faster rate of heat transfer.

  • 8/11/2019 Transformers Technologies

    47/86

    Oil Preservation System: Oil readily absorbs moisture. Presenceof moisture reduces dielectric strength of oil. Different methods are

    available to reduce contamination of oil with moisture.

    1. Silica gel Breather: It is connected to the conservator tank. It consists

    of a cartridge packed with silica gel dessicant and a small cup containing

    oil. Air is drawn into the conservator thro. oil cup and breather where

    most of the moisture is absorbed.

    2. Bellows and Diaphragm sealed conservators: A bellow type barrier or

    a diaphragm type barrier is fitted in the conservator. Air entering the

    conservator tank pushes the diaphragm downwards. As oil expands the

    diaphragm is pushed upwards. Position of diaphragm is indicated by oillevel indicator. Diaphragm acts as a barrier.

  • 8/11/2019 Transformers Technologies

    48/86

    3. Gas sealed Conservators: In this method a cushion of an inert gas like

    Nitrogen is provided over oil surface in the conservator. Gas pressure is

    always maintained higher than atmospheric pressure. Nitrogen gas

    pressure inside the conservator is regulated by nitrogen cylinder andpressure reducing valve which admit Nitrogen to the conservator when

    the pressure falls. Excessive pressure developed inside the conservator is

    relieved through a relief valve.

    4. Refrigeration Breathers: An air dryer is fitted to the conservator. Air

    breathed thro. the unit is dried in passing down a duct cooled by a series

    of thermoelectric modules based on Peltier effect. Top and bottom ends

    of the duct are terminated in the expansion space above oil level in the

    conservator and air is continuously circulated thro. the duct bythermosyphon forces.

  • 8/11/2019 Transformers Technologies

    49/86

    Short circuit withstand Capacity:

    Effects of short circuit: Energy in the system gets released in

    the form of heavy flow of current when fault occurs.

    Every fault fed by the transformer stresses the windings. The

    stress developed in the winding is related to the intensity of

    fault.

    Each fault causes sharp rise in temperature and producesmechanical forces in the winding.

    These forces act in the axial and radial directions of the

    winding, and cause compressive or tensile stresses on the

    winding and tend to deform it.

  • 8/11/2019 Transformers Technologies

    50/86

    RADIAL FORCES: ARE DUE TO FLUX IN THE SPACE

    BETWEEN COILS. TEND TO BURST COILS AND

    CRUSH ON THE CORE.

    STRENGTHENING OF WINDING

    AXIAL FORCES: ARE DUE TO RADIAL COMPONENT

    OF FLUX WHICH CROSSES THE WINDING AT THE

    ENDS AND GIVES RISE TO AXIAL COMPRESSIVE

    FORCE TENDING TO SQUEEZE THE WINDING IN

    MIDDLE.

    PROPER DRYING, COMPRESSION AND CLAMPING

  • 8/11/2019 Transformers Technologies

    51/86

    THERMAL EFFECT: RAPID RISE OF TEMPERATURE

    CAUSES

    i) MECHANICAL WEAKENING OF INSULATION DUE

    TO THERMAL AGEINGLONG TERM EFFECT.

    ii) DECOMPOSITION OF INSULATION TO PRODUCE

    GASESSHORT TERM EFFECT.

    iii) CONDUCTOR ANNEALINGBECOMES BRITTLE

    & CRACKS WILL BE FORMED.

    LIMIT OF MAX. AVERAGE TEMPERATURE AFTER

    SHORT CIRCUIT IS 2500C FOR OIL IMMERSED

    TRANSFORMER USING COPPER WINDING.

  • 8/11/2019 Transformers Technologies

    52/86

    Design Basis

    Life-time cost of transformer

    = Initial cost of transformer

    +

    Operational cost for its life period

    This is called the

    Capitalized cost of transformer.

  • 8/11/2019 Transformers Technologies

    53/86

    Design Basis -Capitalization

    Rationalized CBIP Capitalization Formula:Capitalized Cost = Initial Cost (IC) + Capitalized { No-

    load Loss (Wn) + Load Loss (Wl) + Auxiliary Losses (Wa) }

    Capitalized cost = IC + Xn.Wn +Xl.Wl +

    Xa.Wa

    Factors affecting Xn; Xl and & Xa

    Rate of Interest

    Rate of Electrical Energy

    Life of Transformer

    Design Basis

  • 8/11/2019 Transformers Technologies

    54/86

    Design Basis

    The design of a transformer aims at achievinglowest capitalized cost.

    Low No-load Loss means higher magneticmaterial cost and vice-versa

    Low Load Loss means higher copper (material)

    cost and vice-versa.

    Several iterations are made to optimize the totalcost before freezing the design and drawings aremade.

    Extensive use of CAD programs is needed forfinalizing design.

  • 8/11/2019 Transformers Technologies

    55/86

    Design Principles - Core

    Higher the number of steps in cross section, better is spaceutilization and smaller is the core diameter.

    90 to 95 % utilization factor is optimal.

    Core area (A) is determined by the Flux Density (B) whichin turn depends on many factors - like loss capitalization

    and overall design economics.

    As the no load losses attract very high capitalization,

    attempts are continuously made to reduce them.

    D i P i i l C

  • 8/11/2019 Transformers Technologies

    56/86

    Design Principles - Core

    Improved manufacturing techniques likecore building with 2-lamination packets, step-lapjoints, v-notched laminations,bolt-less cores are used.

    Hi-core steels like M0H, ZDKH, etc are availablein which the specific core losses are lower thannormal grades.

  • 8/11/2019 Transformers Technologies

    57/86

    A A

    View A-A

    Conventional Step lap

    D i P i i l

  • 8/11/2019 Transformers Technologies

    58/86

    Design Principles

    Windings- L.V winding

    L.V Windings in Transformers are either Spiral OR layer wound for low current ratings

    Helical Wound with radial cooling ductsfor higher ratings.

    Disc type wound

    Distributed Cross-over (Run-over) coils

    The conductor used is paper insulated rectangularcopper (PICC)

    For higher currents, transposed conductors are used,to uniformly distribute the current across the cross

    section of the wire of coil.

  • 8/11/2019 Transformers Technologies

    59/86

    Spiral/Layer type Winding

    Mandrel/Press-board cylinder

    Cooling Duct

    Conductor Layer 1

    Conductor

    Layer 2

    Conductor Layer 3

    Design Principles- L.V winding

  • 8/11/2019 Transformers Technologies

    60/86

    Design Principles L.V winding

    Helical Coil (Single layer) Helical coil (Double Layer)

    Start Finish

  • 8/11/2019 Transformers Technologies

    61/86

    Transposed Conductors

    Transposed conductors (CTC) are used to improve current distribution in the

    cross section of the winding wire.

    Individual cable can be coated with epoxy so that the cured and finished

    conductor is mechanically stronger and withstand short circuit forces better.

    Design Principles H V Winding

  • 8/11/2019 Transformers Technologies

    62/86

    Design Principles H.V Winding

    HV winding invariably uses PICC orCTC.

    Type of winding used is

    - Layer winding or

    - Disc winding up to 132 kV and/or- Interleaved winding or

    - Rib shielded winding

  • 8/11/2019 Transformers Technologies

    63/86

    Temporary Over-voltages Switching Over-voltages Over-voltages due to lightning.

    Power Systems Over voltages

    POWER SYSTEM OVER VOLTAGES

  • 8/11/2019 Transformers Technologies

    64/86

    Temporary Over-Voltages

    Typically due to faults < 1.2 pu

    ms to tens of second or even minutes

    Not dangerous to insulation

    S it hi O V lt

  • 8/11/2019 Transformers Technologies

    65/86

    Switching Over-Voltages

    Due to system switching operations

    1.5 pu 5 pu depends on system voltage

    mostly damped asymmetric sinusoids

    front time of first peak tens of s to a few ms.

    decides external insulation in EHV/UHV systems

  • 8/11/2019 Transformers Technologies

    66/86

    Over Voltages due to Lightning

    Due to direct or indirect lightning strokes.

    known to contribute to 50% of system outages in EHV& UHV systems

    few hundred kV to several tens of MV.

    Few kA to 200 kA

    very short duration : time to front : 1 to few tens of s

    time to tail : few tens to hundreds of s.

    Decides line insulation (BIL)

    Severely influences Transformer insulation.

  • 8/11/2019 Transformers Technologies

    67/86

    Cg

    Cs= K Cg/Cs

    Design Principles

    Impulse Voltage Distribution

  • 8/11/2019 Transformers Technologies

    68/86

    Design Principles

    Impulse Voltage Distribution

    = 0

    = 1 0

    =5

    X

    V

  • 8/11/2019 Transformers Technologies

    69/86

    Disc Type Winding

    Paper Insulated Conductor

    Press-board Cylinder

  • 8/11/2019 Transformers Technologies

    70/86

    V

  • 8/11/2019 Transformers Technologies

    71/86

    Impulse Voltage

    Distribution

    1. Plain Disc Winding

    2. Rib Shield Winding

    3. I nter-leaved Disc Winding

    Number of discs from line end

    O

    L

    T

    AG

    E

    G

    R

    A

    D

    I

    E

    N

    T

    P

    u

    D i P i i l T ti Wi di

  • 8/11/2019 Transformers Technologies

    72/86

    Design Principles Tertiary Winding

    In Star-Star Connected Transformers and Auto-

    transformers, Tertiary Winding is used-

    - to stabilize phase to phase voltages in case of

    unbalanced load

    - Suppressing third harmonic currents in earthed neutral

    - reducing zero sequence reactance

    - for supplying auxiliary load or for connecting

    capacitors.

    D i P i i l T ti Wi di

  • 8/11/2019 Transformers Technologies

    73/86

    Design Principles Tertiary Winding

    Tertiary is required to be designed for a power rating equal toone-third the rated power, it increases the cost of thetransformer by 10- 12 percent.

    Tertiary winding is known to fail due to transferred surges andShort circuits

    Present practice is to do away with tertiary up to 100 MVA for 3

    phase 3 limbed core transformers.

    CASE STUDY OF FAILED 100 MVA

    220/132 KV AUTO TRANSFORMERS

  • 8/11/2019 Transformers Technologies

    74/86

    220/132 KV AUTO TRANSFORMERSTRANSFORMER NO. 1.- DATE OF FAILURE 11.05.1992

    OBSERVATIONS: BURNING AND TWISTING OF TURNS INTHE TERTIARY WINDINGS (V&W PHASES) NEAR THE

    TOP END.

    FAILURE APPEARS TO BE MAINLY MECHANICAL.

    TYPE OF TERTIARY WINDING : SPIRAL WITHOUT ANY

    INTENTIONAL COOLING. THE AXIAL ASYMMETRY IN

    THE ASSEMBLY OF WINDINGS IS OBSERVED, AXIAL

    COMPRESSIVE FORCE IN TERTIARY IS WORKED OUT

    TO BE 133% i.e. HIGHER BY 33%.

  • 8/11/2019 Transformers Technologies

    75/86

  • 8/11/2019 Transformers Technologies

    76/86

    REASONS FOR FAILURE:

    TERTIARY WINDING USED FOR STABILIZING

    PURPOSE FAILURE ACOMPANIED BY EXTERNAL

    SINGLE LINE TO GROUND FAULT (132 KV LINE

    CONDUCTOR SNAPPING).

    DUE TO HIGH CIRCULATING CURRENTS WHEN

    TRANSFORMER FEEDS UNBALANCED SYSTEM

    (TRACTION, REROLLING, MILLS).

    TEMPERATURE RISE LEADS TO INSULATIONFAILURE.

    INCREASED SHORT CIRCUIT FORCES ON THE

    WINDING.

    THE RATING OF TERTIARY WINDING AND THE

  • 8/11/2019 Transformers Technologies

    77/86

    THE RATING OF TERTIARY WINDING AND THE

    IMPEDANCES BETWEEN HV TO TERTIARY AND IV TO

    TERTIARY IN RESPECT OF TRANSFORMERS WITH

    LOADED TERTIARY WINDING AND WITH STABILIZINGTERTIARY WINDING (NOT INTENDED FOR LOADING).

    TYPE OF %IMPEDANCE BETWEEN

    TERTIARYHV TO IV TO TRANSF.

    TERTIARY TERTIARY RATING

    LOADED 57 TO 70.5 41 TO 65.5 15MVA

    TERTIARY

    UNLOADED 28 TO 37 17 TO 22 13 TO 15

    TERTIARY MVA

    It is observed that failure of transformers particularly with tertiary

  • 8/11/2019 Transformers Technologies

    78/86

    p y y

    windings, in no. of cases occurred, where system impedance is low and

    the fault level is high.

    Impedances between pri. To tertiary and sec. to tertiary is observed to be

    low causing excessive stresses in the tertiary winding leading to its

    failure.

    It is therefore felt necessary to strengthen the tertiary winding andincrease the leakage reactance between tertiary to other windings to bear

    the stresses developed under faults.

  • 8/11/2019 Transformers Technologies

    79/86

    ADDITIONAL DESIGN CONSIDERATION FOR

    TERTIARY WINDING

    1. RAISING THE %IMPEDANCE BETWEEN HV TO

    TERTIARY & IV TO TERTIARY TO 35% & 25%

    RESPECTIVELYWITHONLYPOSITIVETOLERANCE

    OF 15%.

    2. INCREASING THE RATING OF TERTIARY

    WINDING TO 1/3 CAPACITY OF THE

    TRANSFORMER.

    3. TO PROVIDE INTENTIONAL COOLING FOR THE

    TERTIARY WINDING FOR FASTER AND LARGER

    DISSIPATION OF HEAT.

  • 8/11/2019 Transformers Technologies

    80/86

    Design Process

    Design should meet

    Requirements of customer specification

    Relevant national or international standards

    Statutory and regulatory requirements

    Manufacturers Plant Standards

    Optimized design

    O ti i ti

  • 8/11/2019 Transformers Technologies

    81/86

    Optimization

    Objective of Optimization

    To arrive at a design that yields minimum capitalized

    cost.

    It is a function of the following:

    Core diameter

    Core height

    Flux Density

    Current Density

    COMPUTER AIDED DESIGN-

  • 8/11/2019 Transformers Technologies

    82/86

    PURPOSE OF IT

    Improve productivity of design personnel

    Reduce delivery cycle

    Better analysis and arriving at a most optimum design

    To solve electro-static, electro-magnetic problems and toprovide a robust structural and thermal design.

  • 8/11/2019 Transformers Technologies

    83/86

    More precise calculations

    Tailor made designs

    No standard ratings specified above 1 MVA

    Change of specification parameter

    Relative change of material cost

    Ongoing development of technology

    Poor quality results in failures.

  • 8/11/2019 Transformers Technologies

    84/86

    q y

    Types of failures

    Infant failures: Early life failures are the result oflatent defects.

    - Latent defects are abnormalities that cause failure,depending on degree of abnormality and amount ofapplied stress.

    - Delivered defects are those that escape test /inspection within the factory

    - They are directly proportional to total defects inthe entire processes.

  • 8/11/2019 Transformers Technologies

    85/86

  • 8/11/2019 Transformers Technologies

    86/86