transformer trouble , test , drying , parallel operation

Upload: mohammad-ibnul-hossain

Post on 02-Jun-2018

232 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    1/35

    Transformer Troubles

    a)

    Star-siar

    transformers.

    -

    It should

    first

    be

    noted

    that

    in

    the

    case

    of three-phase

    transformers,

    ofnecesiit),.

    in

    ph4ge

    in

    alllblgg_lh3 9s

    at

    the same

    time,

    and

    hence

    in

    the

    case ofstar

    connected

    windings

    no third

    harmonic

    voltage

    can

    exist

    between

    lines,

    although

    they

    are

    present between

    each terminal

    and

    the

    neutral

    point.

    Similarly,

    the

    third

    harmonic

    components

    of

    current

    can

    only

    exist

    if

    a ieturn

    path

    is

    providdvia

    the

    neutral

    point. Thus

    if a star-star

    connected

    transformer

    has

    both

    the

    primary

    and

    secondary

    neutral

    points insulated,

    no

    third

    harmonic

    currqntf

    san

    flaf

    L

    rr:sultirrg

    in

    the

    presence

    of

    triple

    frequency

    voltage

    between

    the

    secondary

    terminals

    and

    the

    secondary

    neutral

    point. The

    line voltages

    will

    be sinusoidal,

    but

    the

    neutral

    point

    wi11, instead

    of

    being

    at zero

    potential, osciilate

    by

    an amount

    equal

    to

    the

    third

    harmonic

    component.

    If,

    however,

    the

    primary neutral

    point is connected

    to

    the

    generator

    neutral,

    a

    path

    for

    the

    flow of

    the third

    harmonic

    component

    of the

    magnetizing

    current

    will

    be

    provided

    and

    the wave

    of

    flux

    and induced

    voltages

    on

    the

    secondary

    side

    will

    be

    fiee

    from

    harmonics.

    Similarly,

    if the

    secondary

    side is

    used

    as

    a

    three-phase

    four-wir::

    s,rzstem,

    a path

    for

    the

    flow of

    a

    third

    harmonic current

    will

    be

    provided

    via

    the

    load,

    and

    in

    this case

    both

    third

    harmonic

    currents

    and

    voltages

    exist

    on

    the seconciary

    side.

    Because

    ofthis

    objective

    feature

    star-star

    connected

    transformers

    are seldom

    used.

    If,

    however,

    connected

    in

    a

    tertiary,

    or

    stabilizin.g

    winding

    is

    provided on

    the

    delta,

    a

    local circuit

    i

    Such an

    auxiliary winding

    can also be

    used

    to

    supply power

    for

    local

    putposes

    at

    a

    voitage other

    than that

    of the

    primary

    or

    secondary

    windings.

    The

    minimum

    capacity

    of the stabilishing

    winding,

    apart

    liom

    any

    consideration

    of

    the supply

    of

    external

    load

    currents,

    is determined

    by

    the third

    harmonic

    compQnqnl-oflhe

    -qlaglslzi]u

    current required.

    A stabilishing

    winding

    also introduces

    additional

    reactance

    eflect

    between

    the

    incclming

    and

    outgoing

    lines,

    and serves

    as a leactor

    on

    the

    system.

    Star-interconnected

    star

    transformers.

    -

    This

    is a

    useful

    type

    of

    winding

    as,

    due

    to

    the

    interconnection

    between

    the

    two

    halves

    of

    each

    phase winding

    on

    the

    secondary

    side,

    the

    third

    harmonics

    ofthe

    voltage

    cancel

    out,

    so

    that

    no

    third

    harmonic

    components

    of

    (b)

    {"'dgx-:*

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    2/35

    (c)

    voltage

    can

    exist between

    the

    terminals

    and

    the

    secondary

    neutral

    point. This

    allows

    three-phase,

    four-wire

    unbalanced loads to be supplied

    without the

    objectionable

    presence

    of

    circulating

    currents. In spite

    of this, however,

    the

    possibility

    of

    neutral

    inversion still

    exists

    with

    this type of

    comection.

    Delta

    connected

    transformers.

    -

    Transformers

    which

    have

    a delta connected

    winding

    on

    either the

    primary or the secondary side or both,

    provide

    a

    path

    for

    the

    flovv

    of

    the

    requisite

    third

    harmonic

    component of

    the magnetizing

    current,

    thus relieving

    the

    supply no-load

    current of

    the

    necessity

    of supplying

    this.

    Delta-star

    connected

    transformers are the

    most common,

    as

    the secondary

    will

    provide

    a three

    phase, four-

    wire system

    free

    from third

    harmopic

    voltages

    between

    line

    and neutral.

    Star-delta

    transformers

    are

    only

    suitable

    for balanced

    loads.

    The

    primary

    current

    is sinusoidal,

    and a third harmonic

    circulating current

    flows in the secondary

    delta

    connection

    without

    appearing

    in

    the secondary

    lines.

    The

    presence

    of

    this

    third

    harmonic

    circulating

    current

    coffects

    the flux

    curve

    to an approximately

    sine shape,

    and thus

    suppresses

    the

    third

    harmonic

    induced

    e.m.f.

    A condition

    of

    balance

    between

    third

    harmonic magnetizing

    current, and an

    approximately

    sine

    shaped flux

    wave

    is

    thus

    established.

    In the

    case

    of

    a

    delta-delta connected

    transformer,

    the

    third

    harmonic

    component

    of

    the no-load magnetizing current

    is

    shared between

    the

    two

    windings

    depending

    on

    their

    respective impedances.

    If

    third

    harmonic

    currents

    are

    present

    in an

    abnormal degree,

    they

    may

    prove

    objectionable,

    due

    to the

    increase

    in

    transformer

    or cable

    losses. W}'ere

    third

    harmonic voltage exist

    on

    the

    secondary side,

    they may result

    in

    heavy cable

    charging

    currents,

    due

    to

    the reduced

    triple

    frequency

    capacitive reactance

    of

    the

    cables,

    while

    in the

    case

    of condensers

    for

    power

    factor improvement

    excessive

    currents

    may

    be

    taken

    with

    resultant

    overheating,

    which

    has been

    known to

    cause eventual

    breakdown

    of

    the

    insulation.

    Some

    telephonic

    disturbances are also traceable

    to

    third

    harmonic

    pressures

    in transformers. It

    is also interesting

    to

    note that

    third

    harmonic

    components

    will be

    prominent in switching in current rushes, where

    paths

    for their:

    flow

    are

    provided,

    due

    to

    the

    saturation

    of

    the

    iron

    circuits

    during this transient

    period.

    t.

    dfu*--=y

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    3/35

    Sglg

    lntp15[4

    rlspects

    of

    -

    :,-:

    ,,..,

    Il44lformers

    .

    ,,,.,.

    What

    is

    transformer

    Noise?

    'i.he

    main

    source

    of

    sound in

    a

    transformcr

    is

    a

    magneto-strictiorr. Tliis

    is thc

    properly

    of

    eiectr.ical sheet steel

    whicir oi lrses

    it to

    elongate and

    contract

    in

    the

    preselce

    ol

    the

    n.ragnetic

    field. These

    periodic

    mechanjcal nlovements produce

    sound

    vibrations

    in the

    core,

    having

    a

    ftindamental freciuency

    equu) to

    twice the

    flux

    frequency.

    l)ue

    to

    a non-linear

    relationship

    between n.ragneto-striction

    and

    llux

    ciensity a

    number 1b harmonically

    related

    irigher

    frequency

    are also

    produc.':d.

    This results

    in

    a

    noise

    spectrum,

    composed

    of fr"tndamental

    frequencies

    of

    120 cycles

    per

    second and

    harmonics

    of

    240,360,480,600 etc.

    The

    pulsations

    of

    the

    core also

    travel

    through other

    parts

    of

    the transformer,

    which have a

    tendency

    to vibrate

    at one or other

    ofthese

    same

    frequencies.

    These

    add

    to

    the

    overall

    sound

    level

    in

    the forrr:

    of

    interlaminar core and

    coil

    vibrations,

    enclosure,

    and

    sub-asscmbly

    vibrations.

    The

    amount

    of

    thi'r

    rLddition

    is dependent

    upon the surfaoe

    area and resonant

    frcquency

    of

    eac,h componeni

    part.

    Holir to control

    transformer

    sound and

    minimize

    its transmission

    -

    As

    outUned

    above, there

    are four main sources

    of

    sound

    in

    a

    transformer:

    i.

    Core

    vibrations

    2.

    Interlarninar

    core anci

    gap

    vibrati,rns

    and coil vibrations

    3.

    Subassembly

    vibrations

    4.

    Enclosurevibrations

    I,Iever

    Make Megger

    Tests

    uuder Vacuum

    or Without

    Oil

    The

    great

    the vacuum

    (r'nless

    it's

    perfect)

    the

    Iower the spark-over level. At

    tlre vacuum

    values

    normally

    reached in

    li:r: fi.:ld,

    it

    is

    very likely the

    megger

    learlings

    .,vi11

    L;e

    zero;

    in

    other u,urds,

    rreeping

    or

    flashitg to

    gouncl

    will occur.

    Breakdown strength

    under vacuuur is ir

    function

    of both

    pressure

    and distance.

    It

    is not

    our intent at

    this poirt

    to

    go

    into

    a

    long discourse

    on the

    phenomenon

    of

    voltage

    Lreakdown

    but

    simply to

    CAUT-IO|'I

    yott

    not

    Io

    megger

    a

    unit

    while

    under

    vac;uum.

    It

    is

    also

    recommended

    that you

    do

    nct

    rnegger

    a

    unit in

    air

    because

    the values

    may

    lead

    to

    wrong

    conclusions and will not

    agree

    with

    readings

    taken

    at

    a later

    date

    when they

    are

    taken

    under

    oil.

    Readings taken

    in oil

    are

    about ll2to

    ll4

    that of the insulation resistance in

    air.

    Evaiuation

    of

    Insulation

    Megger

    readings,

    power

    factor

    readings,

    and

    oil dielectric

    breakdown values are

    inlpofiant

    indicators

    as to

    whether

    or not

    a

    traxsformer

    is wet.

    The

    dielectric

    strength o{

    oil

    for high

    voltage

    oorver transfonrers musi

    be 30kv

    or belter before it

    is

    put

    into

    a

    new

    unit

    in

    the ficid.

    The megger

    readings on high voltage power

    tlansformers,

    when corrected

    Io

    20"C, should be

    1

    megohm

    per

    kv

    or higher.

    .'

    Whal is traflsfor

    er Noise.doc

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    4/35

    o

    On

    EHV

    transformers

    a

    minimum value

    of 3 megohms

    per kv is

    required.

    Several

    one

    minutes

    readings

    should be taken

    with

    a

    motor

    driven

    megger

    and

    the

    megohm

    results

    oornpared

    rvith factory

    data. Power

    factor

    should be

    less than

    2% on

    oil-filled

    transformers

    q,itl.r

    two

    windings

    and

    less lhan

    2-1l2lo

    on

    units

    with load

    tap

    changers when

    corrected

    to

    20"c

    In

    sul ation

    There

    is not

    much

    that

    can be done

    in

    the

    way of

    maintenance

    of

    the solid insulation

    of oil-

    insulated

    transformers

    and regulators,

    but

    correct

    load and

    temperature

    control can

    do much

    to keep insulation

    aging

    within normal limits. Aging of insulation

    is

    affected

    by

    the operating

    temperature

    of the

    windings and

    the

    condition

    of the oil

    in which

    it

    is submerged.

    Oil

    of high

    acidity

    will

    accelerate

    again

    of

    the

    solid

    insulation.

    The

    aging

    rate

    of

    organic

    insulation

    doublre.for approximately

    cach

    8"C increase in its

    temperaturejthe

    lower

    the

    operating

    temperature,

    the longer

    the insulation life.

    Since

    aging

    is

    so much

    more

    rapid at

    the higher range

    of temperature,

    excessively

    high

    temperatures

    should

    be

    avoiJed as

    much as

    possible.

    On

    the

    other

    hand,

    little

    is

    gained

    by

    having

    insulation

    life

    exceed the obsolescence life ofthe

    apparatus.

    Maximum

    life is assured

    only

    under

    uniform,

    normal loading. Therefore, loading

    should

    be controlled

    as much

    as

    possible to

    obtain

    that

    objcctivc.

    1'he Secondary

    of

    a

    current transformer (CT)

    should not

    be

    open-circuited

    under:rny

    circumstances.

    Why?

    If

    the

    CT secondary

    becomes

    open

    circuited,

    a

    high voltage

    will

    exit

    across the

    secondary

    because

    the large

    ratio

    of se,,ondary to

    primary

    turn causes the

    transforrter

    to act

    as a step-up

    transformer.

    Also,

    since thc

    counter ampere-tums

    ofthe

    secondary

    no longer

    exist,

    the flux in

    the

    core, instead

    of

    being

    due

    to the

    difference of the

    primary and

    secondary

    ampere-turns,

    will

    now

    be due

    to

    the total

    primary

    ampere-turns

    acting

    alone.

    This

    causes a large

    increase

    in

    the

    flux,

    producing

    excessive core

    loss

    and heating,

    as well as

    a

    high

    voltage across

    the

    secondary

    termjnals.

    Ovei-excitatioir

    Capacity

    and

    Inrush Current

    The

    extent of

    which

    the transformer can be overexcited

    is

    determine

    by the highest

    permissible

    flux

    density.

    With

    the

    increase of flux

    density

    the

    no-load

    current and

    its

    harmonics

    rise,

    and

    also

    the

    losses

    in

    the

    in

    the

    iron

    cor:e,

    the

    windings

    and

    the

    structural

    parts.

    The

    flux density

    is

    proporlional to

    the Voltage

    applied

    and

    inversely

    proportion

    to the

    frequency

    of

    that voltage.

    The applied Voltage may

    deviate

    permanently by

    J:5%

    from

    the

    rated

    voltage

    and

    the frequency

    may deviate permanently by

    +2.5'y.

    from

    the

    rated frequency.

    When

    transformers

    are

    switched

    on, an increased

    current of

    exponentially

    decreasing

    amplitude

    may

    appear.

    The magnitude

    of

    this inrush

    current

    depends

    on the

    instantaneous

    value

    of

    the

    voltage

    and

    the

    residual

    magnetism

    of

    the

    transformer

    at

    the

    moment

    of

    switching

    on.

    what is transformer Noise-doc

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    5/35

    *a-

    #l

    In

    the

    500

    to

    1,000

    kvA range,

    the

    amplitudes

    of

    the

    inrush

    curents

    decay

    to

    half

    their

    original

    vaiue

    after

    8

    to

    10

    cycles.

    With

    units

    of

    1,000

    to 10.000

    kVA

    this

    decay

    takes

    10 to

    60

    cycles

    and

    with

    larger

    powers 60

    to

    3,600

    cycles

    Overload

    Capacity

    Transformers

    can

    be

    temporarily

    or

    pelm',nently

    overload,

    depending

    on

    the

    initial

    ioading,

    the temperatures

    of

    the

    cooling

    media

    and

    the

    permissib:e

    maximum

    values

    of the

    winding

    temperatures.

    If

    the

    permissible

    windings

    temperatures

    are exceedecl,

    the

    normal

    lile

    of

    the

    transformer

    is

    shofiened,

    unless

    the oveiloading

    is

    compensated

    by

    periods

    of

    lower

    load.

    If

    transformers

    are

    to

    be

    overload,

    it is

    important

    to

    check in

    advance

    whether

    all

    parts

    of

    the

    transformer

    and

    the

    equipment

    are capable

    of

    meeting

    the

    demands.

    made

    on

    them

    (for

    instance,

    bushings,

    tap-changers

    and

    cable end-boxes).

    Table

    below

    contains

    representative

    values

    for

    the period

    of

    overloading

    of

    oil-immersed

    transformers

    in relalion

    to

    the

    previous load

    and

    the

    oil temperature

    at

    the

    beginning

    of

    overloading.

    The

    averago

    winding

    temperatures

    do not

    exceed

    105"c

    if

    the

    average

    temperaturE

    of the

    cooling

    medium

    during

    the

    period

    in

    question

    is

    25oC.

    If

    transformers

    with

    F-cooling

    are

    operat-d without

    fans,

    the

    overloads

    and

    the

    previous

    permanent

    loads

    should

    be relatedlo

    600/o

    ofthe rated

    power

    ofthe

    transformer.

    Transformer

    Noise

    The transformer

    noise

    is

    majnly

    genelated by the

    magnetostriction

    qf

    the

    iron

    core.

    It is

    dependent

    on

    flux

    density.

    changes

    of 10%

    in

    flux

    density

    cause

    of

    change

    of2_to

    3

    dB

    (A)

    in

    the noise

    level within

    the

    12

    to

    16

    kGs

    range.

    The radiated

    sound

    spectrum

    is between

    100

    and

    500H2.

    Table:

    Duration

    of Overloading

    of

    Oil-immersed

    Transformers

    Previous

    continuous

    loading

    as

    Yo of

    rxled

    power

    Oil t

    nr

    p

    c ralLr re at the

    L,.ginning

    of the overload

    in

    'C

    for

    cooling

    medlod

    tlrrratirin ofovcrload

    lor an overload,as

    oZ

    of

    raied

    Po\Yer,

    ol

    SC, FC, WC

    10%

    200/. 30%

    40%

    5OVr

    h

    h

    mtn

    mln

    mln

    50

    55

    49 3

    1.5

    60 30

    l5

    75

    68

    60 2

    1.0

    l0

    t5

    90 78

    68 I

    0.5

    15

    8

    4

    I

    VN|L"'

    V{% Vt t

    Y

    {r:t

    what

    is

    transforner Noise.doc

    (f

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    6/35

    No

    -Load

    Losses of

    Transformers

    The noload

    losses

    is the

    loss measured

    by a wattmeter

    when rated

    voltage at rated

    frequen^cy

    is applied

    to either

    winding, the

    other winding

    being open-circuited.

    It includes core

    loss, I2R

    loss

    in

    the

    winding

    due

    to exciting current,

    and

    the dielectric

    loss in

    the

    insulation. TlTis

    no-

    load loss

    appears in

    the transflormer,

    independent

    olthe

    load and

    for

    all

    practical

    purposes

    is

    independent of

    temperature.

    The

    core

    loss

    consists

    of hysteresis

    loss and

    eddy-current

    loss.

    The hysteresis

    loss

    is thc

    energy

    required to

    magnetize

    the core

    first in one

    direction

    and then

    in

    the

    other.

    It increase

    directly

    with

    the

    frequency

    and

    depends on

    the maximum

    flux

    density

    and

    the

    quality

    ofthe

    core

    steel.

    The

    eddy-current

    losses

    are

    produced by eddy

    currents

    which are

    set-up

    in the core

    in that

    iron

    is

    a

    conductor

    ol

    current as-well-as

    magnetic

    flux.

    The change offlux

    in the core

    induces

    a

    voltage

    in

    the core

    which

    causes

    eddy current

    to flow.

    This

    loss is

    proportional

    to

    the

    square

    of

    the

    eddy current

    or

    the

    square of the

    induced

    voltage and

    is

    therefore

    proportional

    to the

    square

    of the

    flux

    density

    and

    the frequency.

    Exciting

    Current and

    Flux

    of

    Transformer

    The current

    which flows

    under no-load

    conditions

    is called

    the exciting

    current.

    'fhe

    exciting

    current

    is

    actually

    made

    up

    of

    two

    components.

    One component

    supplies the

    losses

    in

    the

    core caused

    by hysteresis

    and

    eddy

    curents,

    and

    the other

    component

    produces

    the

    magnetizing

    force

    in

    the core.

    The

    alternating

    current voltage

    in the

    primary winding

    of

    a

    transformer

    produces

    a

    quantity

    termed

    "FIux"

    in

    the

    core.

    This oscillating

    llux

    is

    what

    causes the

    voltage to

    be

    produced

    on

    the secondary

    winding

    ofthe transformer.

    Load

    Losses oI

    Transformer

    'fhe

    load losses are

    the

    losses measured

    by

    a

    wattmeter

    when sufhcient

    voltage

    is

    applied to

    one

    winding to

    produce full-load

    current

    in

    the

    other winding

    which

    is short circuited.

    The

    load loss consists

    of

    the

    I2R

    loss

    in

    the

    winding

    due

    to full-load

    current

    passing through

    the

    windings

    and a

    stray

    loss

    which

    is produced by

    stray

    flux

    inducing

    currents in

    the winding.

    The

    stray

    losses can

    be reduced

    by

    )aminating

    and

    transposing

    the copper

    in the

    windings.

    The stray loss

    may vary

    lrom 10 to

    20

    percent of the

    I'R

    loss at

    full-load

    current.

    Both losses

    are affected

    by

    changes

    in

    temperature.

    The I2R

    loss increases

    with

    temperature,

    while

    the

    stray

    loss decrease

    with temperature.

    The load

    losses of a transl'ormer

    ate

    guaranteed

    on the

    basis of

    an average

    winding

    temperature.

    All losses

    are dissipated

    in

    the

    form of

    heat and

    must

    be

    controlled

    if

    the

    transformer

    is

    to

    be efficient

    and

    practical

    in

    design.

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    7/35

    DIELEC

    TRIC

    ABSO

    *--li;

    ?i

    i,.(haoral

    A2LI

    'fhllo

    an

    lnsuLatlon

    noggor hae

    boon

    used

    for

    many

    yoars,

    thero aro

    stlII

    nany uE-

    bqn

    faotore

    1n ltg

    use

    for

    moasurlng

    the

    quallty

    of

    lnsulation,

    espaolally

    that

    @

    h.rgo

    genorators.

    Thoro

    aro

    somo

    quostlong as to tho

    bsst voltage

    to

    bo usod;

    tho

    offoot

    of

    tho

    tomperature

    of

    tho

    wlndlngs,

    tho

    longth

    of tlne

    roadlnge

    should

    bo

    takon

    and

    tho froquonoy of

    tho

    roadlngs,

    to what

    oitant

    duat aBd

    dirt

    on

    the

    vladtags

    ntght

    affoot

    tho roadlngs,

    and

    flnally,

    Yhat

    should

    bs

    coasldorod

    tho

    lcnror ihfts

    of usofulness

    rond.o .lng

    tho replaco:nont

    of insulrtlon

    advtsablo"

    Yftrilo

    thors

    le Do

    cLear-cut

    agroomont

    on how

    to interprot spot

    neggior roadlngs,

    tho ln-

    dratry ic la

    egreement

    that

    perlodlc

    roadlngs,

    tekon ovsr

    a courso

    of

    yoars

    uuder

    :

    rldlar

    couditions,

    will

    give

    a

    truo

    plcture of tho dotorlorablon

    of the lneulatlon

    ;f;.ud

    oau

    bs used

    to forotell

    whsn rewlnding

    or

    re-lnsulatlon

    w111

    be noaded.

    Ths

    t,l*ro

    o" loso

    aocepted

    nsthod

    of

    rooording

    thls

    porlodio

    Lrformattou

    1g

    in tho fono

    ,'lr.o

    a dlolectrlc

    absorption

    curveo

    Jlhs rords

    rdielectric

    aloorptionrt rofor

    tq-t-h9,.abq-o1p o3

    o

    f shargo

    ls.

    tho.lnsula--

    ho rords

    "d1e

    Ioctric

    a_b

    s_o_ fllo-n-

    _"

    ral ar

    -l_q_l-_hg,

    -aD

    q-ofPllofl

    -9-r

    snar8o I'u.

    troe

    -

    r.nEurn--

    193.

    bu_t__ sjLeloc.ldq.gb-s-o-qp-t-l.o-n-o-urve

    is

    u

    aually-plcbted..wlth

    lnsulatlon

    valuea,

    ia..Sad

    fion

    a

    mo,ggor,-.p1otto

    d

    aga{,11g --tlne.-

    T-h-l-s-is-.rqq,-b1- ,i1.s--Lrye.r

    se-qt-c-{l-

    ..road

    fron

    a_ms-Bgorr_

    Plo_ttod_aga1:l1s -_ 1nlg.-

    :t-t1-1_8_r8-

    {oa,r_ly

    _ ,n-_Llry9.r

    80-ql-q-ql:-

    fLt-qqtr:g_a

    sof

    p-t

    io:e.-curvelt-n

    th;t it

    will

    have

    a

    gradually lacroaslng charaoterlstlo

    lOotrlo

    abi-orpt

    1o]1 curve.r, -n

    that it

    wlll

    have

    a

    Bradually

    lncroaslnB

    charaotgrl.s

    ,

    Gh-".rp";f

    to

    trru r""toh*

    3f

    u.

    gradually

    decroaslng.lrrlact3rrltlo

    which

    would

    bo

    tho

    case

    lf

    oharging

    or'rrabsorbodrr

    current

    were

    plottod

    agalnst

    tlme"

    tAbrgllggl-gg5rglt

    lg-y,g

    curront

    whlch

    flows

    whon

    a constant

    poJenttal

    ilLtnpr9ls

    B9l

    u

    tho

    Instran

    or Yolra

    Eqr\aPPl

    lcallou

    at a-varfabG-

    ra{e

    ,

    -Adiffi[.fae--on=._

    ffd-"66rAEE

    eE

    o?6F a

    c

    on

    siadtatfe-Ten

    ati on

    i-varlab1e

    factors" Ij_:_q_lr*P_91."d

    -

    Although,

    as

    statod

    ProviouslY,

    roDt

    ney

    peroist

    for

    hours,

    tho

    a

    nuoh

    ehortar

    tims.

    Tho sloPe

    tbo

    roslatanco

    at 10

    nlnutos

    to

    fitraffi

    ti-mila

    c

    to

    r s

    r

    -cE-pa

    cf tanc e

    cur re

    nt

    .

    die

    I

    o

    ot

    r I

    c

    ab

    s

    orp-

    t@apaElEin6i--curro{rstnstrgouirej-t-o-ShaTEo

    fEiipliltanoe

    of iho

    maETno

    r,rfnding

    to tho

    core.

    Dloloctrlo

    absorptlon

    or

    polari;lng

    current

    ls

    a curront

    caused

    -by

    tho absorption.of

    e]

    ectr

    lcal.

    -

    charge

    tn

    ibo

    dinl"it"t",

    in

    thc

    forrns

    of

    tho oI{igning

    of dipolos

    or

    charged

    polar

    molocules

    throughout

    the lnsulatlnS.rnatorial and

    the

    ptllng of

    froe

    oloctrons

    on

    the

    lnter-

    facosi Loakago

    ourront

    is oompoood

    of

    the currant

    that

    pasies

    lnternally

    through

    tho lnsuLatloi

    and

    that whioh

    passeo

    or

    loaks

    along

    the outsldo

    .of

    ths

    insulatLon.

    0f

    these

    dlfforont curronts,

    the capacitanco

    curront

    ls

    of

    appreoiablo

    valus

    for

    .

    oEly

    a

    fsw

    seconds

    after

    the voltags

    ls

    appllod,

    and

    tho Loakago

    curreDt

    remalns

    .oou;tant

    as

    long

    as the voltage

    is applled"

    Tho

    shapo

    of

    tho

    dioloctrlc

    absorptlon

    ./our"g"

    thorsfore. ia Indicative

    of

    tho rats

    of flov

    of diolectrlo

    absorptlon our-

    Y

    ront.

    whloh

    hae a

    docroasi.ng

    oharacterlstic

    but with

    a much lonor

    rats

    of

    chango

    than

    has

    tlio

    capacltancs

    current"

    In

    faot,

    in a

    good,

    dry lnsulatlon

    thls

    currsnt

    nay

    docroaso

    gradua).Iy

    over

    a

    por.lod

    of

    ssvsral

    hours"

    The

    rate

    of

    docreaso

    of thls

    ourrent

    anC,

    Joo"uqrr"r,tly,

    tho

    shapa

    of

    the

    disloctrlc

    absorptlon

    curvo

    ls

    usuolly

    nors

    lndlcatlvo

    of

    tho

    quallty

    of the

    lnsulatlon

    thau

    tho

    actual valus

    of

    oirmrg

    aoacurod

    for

    th6 varlous

    polnte on

    tho ourvo.

    For

    th18

    roason

    lt

    18

    excoedingLy

    lnportant

    for

    the

    data

    for

    tho

    curve

    to

    be obtatnod

    under

    alnllar

    oonditlons

    oach

    tlno

    a

    partlcular

    pleoe

    of

    equlprnont

    ls tosted.

    tho

    gradual

    decrsaso

    of

    dloleotrlc

    absorptlon

    cur-

    charactoristic

    of

    ths curvo

    becomeg

    eetabllshod

    in

    of tho

    ourve, orprossed

    1:r

    ths

    form

    of

    a ratlo of

    .

    ..

    tho

    rasistanco

    at oD

    rainute,

    is

    called the

    polariza-

    tloqlndox

    (P.

    ,-)-

    and

    ls ueod

    ln

    comparing

    and

    aualyzlng

    tho

    curvos"

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    8/35

    fl

    I

    LZ-2

    P"I"

    =

    lnsulation

    rssistanco

    8.t I0

    minutos

    Insulatlon

    rosistanco

    at

    1

    ninute

    A do-pclarizsrtion

    or

    diachargo

    cur.ve

    for

    a

    liivon

    pioco

    of

    oqutpment

    would

    rese

    tho aLoorptlon curve

    in

    revorseo so

    to

    speak"

    Consoquontly

    an,oqual-

    amount

    of

    1e

    roqulrid

    to d18char6o

    a

    glvon

    pleco of

    equipmont

    &ftor

    a

    voltago

    has

    booa

    appl

    a"

    *a,

    corsu*sd

    in

    building

    up

    tho charge.

    Thls

    is

    an

    oxooodlEgly

    lmPortant

    oo[.

    sldsratlon

    ln

    tostlng

    oqui-pnent.

    llfhan

    severaf

    tosts

    qrs

    mado

    at

    dlf,feront

    ture.s

    e.nd voltagoo

    as requlrod

    for

    our standard

    testa it-ig

    aliolutely

    osasntlal

    that

    the

    wi.ndln[s

    bolng

    testod

    bo

    grounded

    botwoon.runs

    for

    F

    at loa

    I

    Slnoe

    ths

    dogroo

    of

    polarizatton

    of

    the ineul.atlon

    of

    equipnent

    imodiatoly'aftei

    ehut-down

    and

    Just

    procedlng

    a tost

    cannot

    bo

    known,

    it

    18

    advlsabls

    that

    to

    bo

    teetod ohould

    be

    grounded aa

    soon

    as

    praotloabls

    and

    tho

    ground.

    bo

    loft

    u.

    touohod

    througilout

    the

    porlod

    of

    proparation"

    If

    thts

    porlod

    18

    ahort,

    lt

    1o

    to

    ths timo

    through

    whioh tho volta6o

    wa; apPllsd

    in

    the

    provious ruu'

    procautlon

    io

    tak6n,

    the

    fo1).owlng

    tost

    will

    havo

    no valuo,

    beoau6s tho

    dls

    ,rLtt

    lo

    partlally polarlzod st

    ths

    boginnlng

    of

    the toot"

    advlgable

    to

    oheck the

    wlndlng

    to dstormlne

    whsthsr

    the

    groundlng

    timo

    hae

    bsoa

    sufflc 6nt

    to drain ths

    lnsulatlon

    oomplotely.

    Th18

    cal1 bo

    dons

    by

    oonnocttaS

    tho

    wlnclLtg

    under

    to8t to

    tho

    nogger

    Lnstrumont

    wlth

    the

    motor ds-onorglzed

    aud

    notlng

    if

    iho

    lnetrumont

    pointor dsflocte

    up-scalo

    boyond

    lnflnlty"

    Another factor

    which he,s eonslderablo

    effoct

    upon

    tho

    dteloctrlc

    aboorptlon

    chargo

    on

    the

    windlng,i

    to touch

    the

    wladln6;l

    oircuits

    whi1o.

    tho

    to

    If

    the

    gonorator.

    or

    soon

    aa

    1t

    ls

    shut

    and

    any

    spot

    mogg;or

    readlng

    ls

    tho

    tomperature

    rjf

    the

    dielectric"

    Fornulas

    havc

    boen

    dove-loped,

    -iowever,

    *it},

    *tioh

    fairlyaccurate

    tamperaturo

    coofflcients

    of

    reslstancc

    can

    be

    developod

    for

    insulations

    providing

    tost data

    aro avallable,

    takon

    at

    two

    differeni

    tomporatures"

    I

    .Jtn

    matrng

    dlElectric

    absorptlon

    tosts

    any

    abnormality

    tn readln6s

    should

    bs

    ln-

    -vestigatid,

    for

    a

    serious

    break-down

    of

    insulation

    may

    havo

    takon

    P1aco.

    Safoty_

    Pi

    ocayt]ons

    Tho

    2,500-volt

    moggor

    builds

    up

    a relativoly

    high etatic

    this

    chargs

    should

    bo dischargod

    before

    anyono

    is

    aLlowod

    Likowise,

    no

    one

    should

    bo

    allowod

    to

    work

    oa

    tho

    excitor

    is

    in

    pr ogr"o i; ri

    "

    Pre

    l ini

    rnar-y

    Opcrations

    Tho

    follovring

    Proli-r:lina::y

    operations

    should

    be

    performed"

    othor

    eqlripmJ,li

    iu

    i., sorvico

    they

    should

    bo

    porformod

    as

    1.

    Havo

    tirc

    grounci

    switch

    closed

    to

    drain

    off

    any

    -chargo

    on

    tho.

    Btator

    wlndlngi

    It

    is

    goo d

    prlctico

    to

    loavo

    tho

    noutral

    OCB

    cLosod

    throughout.

    the

    ehut-down

    poriod

    and

    to

    maintain

    a

    Eround

    on

    all

    windings

    to

    bo tostod

    throughout

    the

    pror

    P0r1(Ju

    urru

    parato.y

    poriod

    boforo

    tefts

    aro

    mado.

    hrrthormoro,.if.thore

    t:."1{

    P::ilti^-

    ivhsther-

    tho

    dlainage

    tj"ms

    hus'boen

    sufficient,

    tho

    winding

    should

    bo

    tesl:9

    {9tif

    rosidual

    ehargo.

    This

    is

    dono

    by

    connecting

    iho

    windlng

    to

    tho

    mogEor

    rrlth

    tho

    ^oiot

    a"-or',u. trua.

    If

    the

    inst;mont

    polnier

    deflocts

    up-scalo

    boyonil

    i:cflnlty'

    tho

    winding

    should

    bo grounded

    for

    additiona]

    tirno

    '

    2"

    Remove

    gonoro.tor.fieId

    slip-ring

    bruEhos

    the

    main

    exciter

    armatur

    and

    plIot

    exciter

    on

    the

    stator"

    .

    Jfti

    and

    ground

    this

    fleld.

    AIeo

    and

    keop

    all

    g.roundod

    during

    ground

    tho

    to

    )

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    9/35

    _ _ .

    .

    ,tktzhl/5)+)

    r2-1

    .

    :

    t

    s,

    J

    ;

    f,

    ).

    Ctuo"

    tho

    stator

    and

    its connecting

    vrindin8s

    of all lightning

    arrostors and

    :

    potonti.al

    transforners,

    and

    disco:rnoct

    tho pc,ror cable

    as near to

    tho

    generator

    as

    poso1b1e.

    If

    ar.y appreciabls omount

    of cablo ls lofb

    connocted

    in

    the circuitl

    the

    nogger

    roadlnga

    v"l"II

    bo

    influoncocl

    by

    thj-s cable,

    r"..td thelr

    5611

    not

    be trus

    roslstivity

    reaclings of

    tho

    stotor.

    Tho

    length,

    size,

    and

    type of oable

    should

    be

    rocorded

    on

    the data

    sheets.

    Also,

    if

    tho cablos

    termlnato

    outslde

    ths

    bu11d1n8,

    rot-I'and

    dry-bulb

    temperahrres

    must

    be oltained.

    tl.r

    [.

    flIpe

    all

    p]aces

    n'hore

    coblos

    ter:rLj-nate

    and cond.uctors

    go

    to open

    rviring.

    .t

    :,i,

    lhars

    is

    ahvays moro

    or J,oss loaka5e

    ovor the

    end.s of

    the

    cables

    to

    the

    shoaths

    at

    l,:,il

    ruoir

    placos,

    and

    wiping

    the dust

    cieposi.ts

    will

    reduce

    tho nurnber

    of

    ).oakago

    patho.

    []['

    Cto*ing

    the

    wlndings

    befcro tho tost is

    of

    qusstionablo value,

    but

    it is

    deslrablo

    ili:

    to

    iroo. all

    porcelain

    insulators

    wipud off

    that aro

    on

    the circuit

    being

    moggered.

    [it

    fi,ft

    includes

    tho noutral onrl

    as

    weIl as

    the

    lino

    ond

    of

    the

    winding.

    Tho

    fact

    $Ij:

    tU"t tho

    windings woro or wore not cleanod

    should

    be rocord.ed.'

    If

    the

    vri:rdlngs

    [l]:

    aro

    cleanea,

    rnake

    tests

    al'i;or cleaning

    only.

    ),.

    i

    Test

    Procsd.rrro

    .,/.

    i,.,

    ---

    \l1?-

    t..

    i...

    0onorator Stator

    h:'

    --

    iii'

    .&to

    negger

    reacllngs

    at

    [O'

    C.

    or

    as

    near

    this

    tomperaturo

    as

    practicable.

    Two

    il.

    rota of

    ieadings

    aio

    to

    bo

    rnader

    tho first

    at

    lOO

    volts;'(62J

    '6]-ta

    if

    that

    is

    the

    Ni

    rrtiug of

    tho

    megger),

    and the

    second.sot

    ab

    2 00 volts. Tho

    :notor

    on

    tho mogger

    [r':

    rhould be

    allowed

    to c

    on,:,

    up

    to

    fuI]

    spoed beforo

    tho

    ground

    on

    tho

    st&tor

    is rs-

    li:ll

    rcvoa.

    Reaclings

    should

    i;o

    rnads

    at I -soconrl

    intorva-]s

    for

    tho first

    minuts

    and

    at

    fii;

    r;:;ir";; iilEi"ui.'r",

    tho next r minutos

    for

    a iotal

    tims

    of

    16

    minutes. Thuo

    i'

    '

    ttroro

    are

    two seriss

    of

    tests

    and two curvos

    should

    be dra'an.

    It

    1s

    essontial that

    thr-,

    rvindinns

    irnder

    test

    bo

    grounded

    ).on6

    enough

    botween

    tosts

    ii':

    6-difrn-olr-TE6-iTdt1c

    ti o.

    -Sec

    tho

    f

    j-rst

    two

    paragraphs

    on

    pag

    Az-z

    undor

    i,r;,

    "

    rrorrllrtl.r.1r

    J

    uPtJ

    a\"r

    .|.,

    l.i.

    Ilolds

    and

    Exc

    ltor

    s

    t'i,-

    ll,

    thko

    suro thB.t the

    vrindiugs

    have

    been

    groundor).

    for

    a

    len5th

    ol

    time suff:ciont

    to

    j

    draln

    all charp-e fron

    t'J

    dtelectrli.

    Th.r

    lcst

    flivon

    in Proliminary

    Oporatic::s

    ;

    (poragraph 1) should

    bc rnadc if

    there

    is

    any

    rluestion.

    llll(e

    only

    one

    sot of

    retldings, usin6

    tho

    625-?o1t

    or

    lOO-volt

    mog6or

    at

    l4Oo

    C'

    lho

    roading

    intorvais

    strould be

    the

    s8.rTro as

    on

    tho

    stator,

    but

    they

    should

    oniy

    be

    ocotlnued. until

    tho

    curvc

    flattens

    out

    vrhioh

    is

    usu811y

    less

    than.ten

    minutos.

    111

    voltnoter

    and

    instrlmont

    wiring

    shou]J

    be

    disoonneoted.

    while

    megSering

    ls

    In

    Progr88s.

    ,/ ,,

    Y[6lviu

    Bridgo

    Tests

    .-:-

    .i

    ,

    trdlo

    bridgo

    testo aro

    not

    . "i"'

    Stator

    or arnature

    trind:ing

    ,,,i

    : ftor

    tho absorpti"on

    tcsts.

    part of

    the

    absorption

    tosts,

    the rosistanco

    of

    tho

    ihould

    be

    rnoasured

    with

    a

    Kolvin

    bridge

    immedlatoly

    rations

    I'or

    .

    indic

    ati

    ons and a

    test

    1or

    prosence

    or'&

    c

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    10/35

    A2-4

    CaDacitanco

    Bridge

    Te

    st

    Uslng

    a

    capacitancc

    bridge,

    rloasure

    in66

    and

    giound.

    Alsol

    record

    t)re

    the

    capacitance

    botive

    en

    dissipation

    factor

    vrhich

    .

    ij

    the

    stator

    wind-

    I

    i-s

    also

    read

    on

    ..

    tilo

    capacitance

    bri"d

    go

    .

    *0uardini'.

    of

    Cablos

    '

    hiold

    of

    col'laj'n

    Ssrorator'

    r

    '

    It

    has

    bcen

    founct

    possiblo

    to

    Suard

    the

    tround,:

    ,,-

    ^^Lr^d

    +n^h

    *ha.,..

    ih'ili."iirl;;";;.";;"uiiu3t

    or

    tno

    insriration

    on

    the

    cabros

    fro4.tho

    ,,,,

    megger

    readings

    on

    the

    ;;';;-;;;

    siator'

    "llt'^l:

    ::::''nl:':::":'"tlllli*""1

    Ii '[i"lll'';:li"]tt"""

    ;;";i';-;;";;;

    shio-Iis,

    ancr-:I:.::".:'::i.:::::il

    *"-

    tho,nesser

    is

    connecte

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    11/35

    DRYING

    F

    TRANSF

    .fhere

    are

    a

    number

    of

    ipprbved

    methods

    for

    dry'in

    z

    out

    the transformer

    core

    and

    coils'

    Gencrally

    ,lr.

    i;;;'oitn-.-*-urr.rurer

    should

    be

    foLlorved.

    If

    the

    drying

    out

    process

    is

    carelessty

    or

    ***.4,

    performei,

    great

    damage

    may

    -result.to

    the.

    transformff

    insulation

    through

    over

    hcaring_

    Drying

    out

    of

    pcrver

    r-.fir

    rrr

    .tl,ruld

    be carried

    out

    ur,der

    the

    personal

    sup,'nision

    ;;;:-;;-;ed

    officcr.

    ,re

    following

    gcnci.lr

    insrrucrioos

    are

    grr'q

    for

    carr)'ing

    out

    rli'ing

    opcrelic.:n.

    .l

    hc

    transformer

    must

    b

    suppled

    during

    the

    drying

    operatron

    with

    a

    quantit]. o1'hcat

    equivalenl

    tothclatenlh.utofv,porisaionfor-tlremoisrurctot,cremol'cd.Atnormalaln]ospheric

    prcssure

    watcr

    *.ill

    onry,rfiir.-,,piary'

    it"*

    insulation

    aI tempsrarurc

    aho.c

    E00C.

    J'ct

    the

    insulation

    is

    litely

    to

    b"

    badll:Lmag"4

    ii

    t"-'''-

    part of

    it

    is

    heatcd

    to

    more

    than

    100"C'

    evcn

    for

    quite a sltort

    timc.

    U'the

    on

    it

    o"ttt'"'i,

    it

    wi

    also

    bc

    damaged'

    The

    orer-heading

    nill

    cause

    Jrarti""

    and

    products

    of

    oxjdation

    will

    promote

    fuiher

    dcterioration

    of

    the

    oil

    evsn

    at

    lorvcr

    ;;il.

    fi

    .ry

    ,tro-inlure

    thc

    jnsulatjon.

    i'hc

    rarge

    of

    tempcr,arure

    ^within

    n'hich

    a

    transformcr

    can

    be

    effccti ,cly

    Ji"d

    i.

    thus

    vcrl'

    narro \,

    the

    morc

    so,

    zs

    ferv

    of

    thE

    mcthods

    by

    *,hich

    it

    can

    be heated

    gr.,.

    oJo*

    distributitn

    of

    teinperature.

    it

    is

    for

    tlds reason

    that

    the

    operation

    is

    so

    critical.

    a

    .rrying

    t

    "n.r,rrmr:r

    sloul,J

    ne'er

    be le{1

    unattended.

    I-l

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    12/35

    The

    temperature

    limits

    and

    Ioads

    should

    be

    strictly

    adhered

    in

    ordcr

    to

    obtain

    desired

    results

    *

    ithout

    dimage

    to

    translormers'

    NOTE:

    It

    m-ay

    be

    nqled

    that

    highcr

    the

    prescribed

    oil.

    temperature'

    the

    smaller

    the

    load;

    which

    means

    trrat

    additional

    blrrk.i;*g;f;."oJ

    i"

    required

    for sim

    ar

    currsnts

    th,n

    for

    higher

    currents,

    in

    order

    to

    bring

    the

    ;rr

    ",."rp;;;;p

    to

    rh.

    varues

    shown

    in

    rhc

    above

    table.

    itisalsoessentialthatplentyofr.err(ilationbcprolide

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    13/35

    /'z

    I

    )re

    Megohms

    v&1

    dpproxima

    tely

    n

    ,ersl}ry

    with

    temp"raturc

    and

    for

    a

    l00C

    change

    of

    tenrpcrature

    the

    Megohms

    ttt-gt

    'i"i"i"

    ofipproximately

    2

    :

    I

    for

    example'

    :

    Megohnis

    at

    "at

    '"

    at

    (

    .1

    850C

    750C

    650C

    -

    -o^

    ))

    (-

    300

    600

    1200

    2400

    r

    ror

    oir

    circur^rri"1i,

    d?.:

    ,?J;ff,JI'l-Jj;TJffi1l;ilT.:"#F'J':T,l^:i

    iffi

    ti

    hottom

    of

    rhe

    ta*

    and

    wtthi

    hcatcrs

    llncd

    to

    filttt

    app'oxil'la'iiiit:

    "lrtt't"n

    wilt

    ut-'"'luirtd

    fo'

    C\tr'

    1io0

    g'rllons

    of

    oil. Local

    r..rverltceling

    or

    'r'"""i"i*'u"

    ^"iita

    so

    'thrt

    loaiing

    on

    lhc

    h:rl'r'

    sltoulJ

    nut

    crcced

    3

    \\,/Sq.

    cm.

    no.

    rt

    oula"fi.

    tii""*tt

    "rtr"

    "lr

    "t"tJJ

    gi%

    "t

    the

    ltcatcrs

    or

    750(l

    ncar

    rlre

    rr

    indurSs.

    Prcc:tutiotrs:

    -

    i)

    Vent Dipc

    with

    single

    diapfuagrn

    should

    bc

    rcmo'u'cd

    and

    thc

    h

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    14/35

    Hence

    or

    y lop

    valve

    should

    bc

    'iosed

    leaving

    the

    botlom

    damage

    the

    ratliators'

    one

    opened.

    ,'

    tiii\

    Normallv

    the

    dclivery

    pipe

    of the

    frlter

    should

    be

    connecled

    to

    lhe

    bofiom

    valve

    i\r,'/

    ;r

    th;i;

    i";.aintaining

    "'ironn

    tcmperaturc

    in

    he

    tansformer'

    xi\)

    ttire

    extinguishers

    mar

    be

    prorided

    for

    conibatirg

    accidental

    fir':s'

    sr')

    The

    tap

    should

    b

    so

    set

    for

    passing

    short

    circuit

    currsnt

    tlut

    all

    the

    wirdirg

    is

    in

    ':''l

    ;;,ri,",,

    rlrat

    the

    entte

    siilding

    mly

    bc

    dried'

    rri)

    lf

    mcrcwy

    thermometers

    are

    used

    special

    care

    should

    be

    taken

    o

    prerent

    thc

    bulb

    l-,rcakhg

    oa

    .o*.qr*f

    'ntt"a'"1

    ltlcury

    into

    the

    transformcr

    winding'

    \Iercury

    rt

    "r*ottttt]-'iottiJ

    intUutt-'

    be

    used

    rvith

    thc

    meul

    shiclding

    Ibr

    pr.r."iittg

    .r.fl

    utcidtntt

    lt

    is normally

    ricsirable

    to

    usc

    dial

    lwc

    therlnometcrs

    or

    '\lcohol

    thermometers

    as

    far

    as

    possible

    r:rii)

    Rciorc

    rccording

    insulation

    rcsistancc

    valucs'

    thc suppl)

    to

    the

    rrindurgs

    slro'uld

    ,''\rr./

    ir"."i.i,.a

    "n-La,fr.

    i..a.

    discorur,.ctctl

    sircc

    []rc

    leads

    mar

    c,'ntrihutc

    to

    ]orr

    t*0.g.

    obtaincd'

    duc

    to

    their

    inhcrcnt

    characteristic

    Drl

    ing

    undcr

    \

    acuunl:

    :iismcthodcoruistsolheatingupthetranslbrrtsr.bl'shortcircuituntleroilandapplyinga

    rcuum

    10 removc

    the

    ntni't*?

    ;i+'it

    ^ttttoa

    can

    be

    cnlplol

    cd

    lbr

    translt-rnncrs

    ntounted

    in

    :ong

    steel

    tanl:s

    suirb)y

    dtt;gt";';;;li:i

    ttl

    s:tc))'

    xitir-srand

    erlcmal

    prcssure

    rcsulting

    cm

    a

    vacuum

    of

    27

    inches

    i' 'ott

    lr4oJem

    transformers

    are

    gcncral11'

    strong

    cnough

    to

    idrsland

    this

    Pressure

    llowevJ'

    i'

    J"'U'f

    i

    cascs'

    this

    me

    thod

    shoulcl

    r'-ot

    bc

    emplol

    cd rvithout

    -*iots

    approvat

    of

    nlunuf"ru'io

    ;-"'*"

    punrp

    should

    be

    connectcd

    to

    thc

    top

    of

    lilc

    anslbrmer

    ank.

    ..r:

    should

    bc

    LrI:en

    to

    see

    tllrt

    thc

    diaplLr:rgm

    on

    tl:c

    c-rplosion

    \cnt

    of

    thc

    tlattslormer

    is

    mo'cd

    and

    thc

    opsning

    tt'rtilp

    *itft

    u'uf^iltg

    platc'

    lhc

    transformcr

    tan-L

    sidcs

    should

    be

    .soed

    *'ith

    some

    covcring

    "ti

    "j'"tp'J"

    fttt

    oi

    iimil-',nalcrial

    to

    prevent

    unnecessary

    loss

    i

    *;

    'ii;;

    ;;;;,

    ;,;;"ili"g-;;

    ,adiarors

    should

    be

    closcd

    to obtair

    the

    deslred

    tsmpsrature'

    hetrarsformershouldbefieldwitlroilsuchthatthecoilsandirsulationarecompletelycovered

    v

    oil.

    Onc

    oi

    thc

    n'indings

    ftl'V

    lt f-

    V

    l

    should

    bc

    short

    circuited

    and

    3

    phase

    supply

    ncithcr

    rcater

    nor

    apprcciably

    ""'Utt'tft*

    1fl"

    ;*fta'ntt

    voltage

    of

    the

    transformer applied

    to

    the'

    ther

    n inding

    to

    enable

    " "t

    f'flf"'i-"'*"nt

    as

    possible

    but not

    larger

    than

    full

    load

    currenf

    obtaurcrj.

    'fl)c

    tcrnperatuc

    ;;;;;;t'i;

    shoultl

    bc

    ti"J

    tio*ty

    t"o

    approximat"ly'550C

    in

    ::

    lir.

    r

    8 ho*'s;

    ro

    o:oc

    ;n

    *',.

    :';;J;;

    ,

    ;i

    u..,

    zs'c

    i'"t'"

    tt'il0

    a

    noun

    'tJl.,

    tre

    7s0c

    imperatlrlc

    is

    reached

    tf"

    t"*io"tt'

    should

    be

    disconnected

    from

    the

    source

    of

    power

    and ilie

    il

    draincd

    out

    and

    rr;u'rm

    'rifi

    tJ"i"t'^"tf

    itte

    ll

    'lhc.racuum

    should

    bc

    a

    mjnimum

    of

    25" but

    ,referably

    28'.

    '1hc

    tutu*''

    should

    be

    maintained

    until

    rempclarurc

    drops

    to 50'C'

    lhc

    raruformer

    should

    again

    bt

    l'x;;;i;

    r.I"t

    ();r

    "

    600C

    atul

    tlte

    short

    circuit

    switchcd

    on

    and

    the

    ycle rcpcated.

    Temperaure

    -JLt'f"i""

    resistance

    of

    the

    windings

    should

    be

    laken

    evcry

    tryo

    rou.rs

    and

    the

    drying

    process

    conthued

    Lntil

    ihe

    mcgger:iadings

    risc

    ovgr

    the

    minimum

    and

    are

    ,tcadily

    rising.

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    15/35

    Thc

    tabl,r

    below

    shows

    the

    relation

    behl'een

    vacuunl

    and

    volatilisatio[

    tcmperatule

    of the

    water

    contained

    in

    Lhe

    oil:-

    .

    1''i:"

    .Jil:H*

    Y#*:*:"

    degrees

    Centigrade

    oo ?a

    '99.15

    98.60

    97.71

    9s.85

    e?.77

    87.89

    80.42

    69.21

    53.31

    . ?I)O?'

    0

    75.54

    7

    5.35

    7 5.01

    71.26

    i2.85

    70.5

    I

    56.80

    61.12

    52.60

    .10.54

    23.50

    0

    0

    5

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    From

    the

    dbo.",e

    it

    can

    be

    clearly

    secn

    thrt

    the

    eraporation

    temperaturc

    of

    moisture

    dcpends

    ^.iriv

    ,p""-,fie

    degleo

    of

    ,acuum.

    If

    l'acuum

    is

    mai,taincd

    the

    moisture

    in

    thc

    core

    and

    lvinding

    evaporatcs

    even

    at

    very

    low

    lemporaturc-s.

    the

    tcmpcraturc

    ol

    thc

    translbrmcr

    -is

    raised

    t

    l,

    ,Alfo.rour

    short

    circuit

    oi

    the

    ri'i-ndings

    and

    oil

    circulatign

    tlrrough

    strcant

    linc

    llltcr.

    'l'hc

    oil

    medium

    is

    used

    mainly

    for

    distributing

    the

    heat

    uniforml'

    throughout

    thc

    core-

    and

    rvinding'

    It

    l,

    ""..,'",v

    tlrat

    tlrc

    oi]

    should

    be

    pu,.

    -d

    hot

    while

    iI is

    bcing

    field

    in.

    For

    this

    purpose

    it is

    aduar..,tag"ous

    to

    usc

    a

    largc

    tank

    oi

    suitrbl"

    capacity

    wlcre

    the oil

    is

    circulared

    tl,ough

    strearn

    line filrer

    to

    naintain

    high

    temperaturc

    bc,forc

    lilling

    in.

    Onl}'aftcr

    thc

    transfonncr

    is

    complctcll'

    fillcd

    n.ith oil

    the

    shortlircuii

    should

    bc sn'itchcd

    on.

    l-lnder

    rto

    circumstan::s

    the

    short

    circuit

    should

    be ,*,it.h"d

    on i;ither

    during

    thc

    pcriod

    rvhen

    tlte

    vacuum

    is

    being

    appLcd

    or

    during

    fillinginoperation

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    16/35

    Raise

    the

    temperah-Ee

    of

    thc

    core

    and

    windings

    gradually'

    Before'applying

    vacuum

    make

    sure

    that

    the

    tank is

    designed

    for this

    purpose'

    :

    I)recautions:-

    i)

    ii)

    iii)

    i1)

    Vent

    lpe

    diaphragrn

    rnust

    be

    removed

    and

    plate.

    the hole

    blan-ked

    off

    with

    a

    sturdY

    Ilrecautions

    regarding

    simultaneous

    short

    circuit

    and

    oi1

    circulation

    have

    already

    ;;;;

    unier

    fialheadtng

    a:rd

    the

    sarnc

    m-ay

    be

    complied'

    Drling

    bY

    Hot

    Arr

    Circulation:

    ln

    tiris

    method

    tle

    hot

    air from

    elcctric

    healcr

    is

    blorm

    to utc

    Lranslbrm0r

    rvindings

    tluough

    art

    ;;;il;;

    towcr

    part of

    the

    tank

    and

    is

    allowed

    to

    escape

    ttubugh

    an opel

    ng

    in

    the

    top

    cover. The

    oil from

    tlte

    core

    -a

    *inairg.

    should

    be completely

    rcmoved

    before

    starting

    the

    a.yng*.toperation.Thtrarsformershoul-ldbeloggedwithtarpauLinorothersirni]armateri3lto

    pr'",',:iito*

    of

    tcat

    and

    to

    assist

    in kcepi-ng

    t1e

    whole

    of

    the

    intcrior

    tanl

    at s

    ch

    a

    temprafure

    ;-;;;,;;

    ;ndensation.

    Thermu*.teri

    should

    be

    fixed

    in

    suitable

    places

    to i.dicate

    the

    ".pri"*.

    ,f

    ij

    the

    int.t

    ,it

    iiij

    tf"

    outgoing

    air'

    'lhe

    hot

    air

    should

    bc

    supplied

    by

    mcans

    of

    a

    nf"*:*

    -a

    electric

    heaters

    *hi.'h

    rrlry

    be"controllcd

    so

    as lo

    regulate

    thc

    temperaturc

    'lhe

    mouth

    of

    the blower

    at

    rvhich

    the

    cool

    air

    cnten

    should

    bc

    cor''erod

    rvith

    onc

    or two

    lal

    ers

    o{

    clea:r

    .,"",.r".ntopleventdrrstbeingdraw,niltothcrvindings.Itisncccssan,toforccasmuchofthc

    ;;u.d;;;r;;rsible

    through

    th"e

    ducrs

    olrhc

    rransformcr

    rvinding

    lor

    accomplishing

    d{ing

    to

    ".u""",r-ri.,

    LaJIles

    should

    be

    placcd bernecn

    core

    and

    tenk

    closing

    inlen'ening

    spacc

    as

    Inu ll

    as

    pcrssible.

    .Ihe

    remDeraluc

    of

    thc

    tncorning

    air should

    bc raiscd

    gradualll'

    from

    55cC

    to

    850C

    in

    about

    24

    ;il;ffi;;i.,.i

    r,

    ss'C

    ut;r11ct

    till

    the

    end

    of

    d4'ing

    'l

    o

    ersure

    uniform

    drying

    the

    volume

    ,i

    fra"r.a

    air

    should

    be

    such

    that

    the

    outlet

    temperaturc

    an

    inlct

    temperalure

    are

    as

    near

    as

    f".riur".

    During

    drl,ing

    out

    operation,

    the

    insulating

    material

    loses

    the

    nroisture

    contcnt

    prescnt

    i,,

    i1'

    *a

    Lpr"""".-

    iJ

    di"l""t

    i"

    characte

    ristio.

    Ar

    thc

    samc

    time,

    the

    mechanical

    strcngth

    is

    corsiderably

    decrcase

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    17/35

    -

    .

    .

    jjifi;H"dilr;,G]fi'iio'

    n**'"*;

    of

    the

    airblast

    exceeds

    presetvalue'

    nsliouldbemadeforfacilitalingautomaticcutoflofheatersincasethc

    blorvcr

    stoPs.

    Suitable

    baIflcs

    may

    be

    p'rovided

    1o

    disperse

    the

    tsmPcrafure

    inside

    the

    tank'

    Trarsformer

    may

    be

    propcrly

    lagged

    to

    rnaintain

    unifonn

    inlct

    and

    outlet

    temperature'

    to

    prev 'nt

    condensation

    undemiath

    the

    top

    cover'

    The

    temDeranfe

    of

    the

    incoming

    air

    may

    be

    gradually

    raised

    so

    that

    the

    maximum

    *d"*.;id

    be

    reached

    in

    about

    24

    hours'

    OiI

    should

    5e

    completely

    drained

    offbefore

    commencing

    the

    drying

    opcration'

    6,

    ,,^

    4,

    '-

    _

    7

    hot blast

    lo

    maintain

    uniform

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    18/35

    .'-4.,.,,

    h-Y

    PARALI,EL

    OPERATIOI\I

    OF

    TRANSFORMERS

    General

    conditions

    for

    the

    satlsfactory

    operation

    of

    Transformers

    in

    Parallel.

    SINGLE

    trarsformcr

    may

    bc

    said

    to

    opcrate

    satisfactorily

    if it

    carries

    its

    rated

    ioad

    without

    "it

    Be

    dr9P, but-where

    two oi

    more

    tsansformers

    are to

    operate

    in

    parallel

    on

    the

    prt".ry

    id

    secondary

    bul bars,

    several

    othsr

    conditions

    must

    also

    be futfilled-

    Under

    this

    saiisfactory

    opcration

    also

    implies

    equafity

    ofload

    sharing

    in

    proportion

    b

    rhe

    rating

    each trarsformer,

    absence

    of circulating

    currents

    and apgoximately

    similar

    internal

    power

    in

    each

    transilomrcr.

    In

    order

    to

    satiiff

    these latter

    requiremcnts,

    the

    following

    conditions

    bc met:

    (a)

    The

    phase sequence

    or order

    of

    voltage

    rise

    on

    the

    termirals

    of

    the

    two tansformers

    which

    are

    to operate

    in

    parallel

    must

    be the same.

    (b)

    The

    potarity

    of

    thc two

    tansformers

    must be

    thc

    same.

    Two

    trarsformers

    might

    havc

    '

    .

    O," r-"-"

    pi,..

    rrqu*""

    voltagc

    risc

    but on tcsting

    out

    it

    might

    bc

    fo,nd

    that

    zcro

    voltage was not

    obtained

    between

    similarly

    marked

    terminals

    on

    the

    to

    units

    due

    to

    oe

    pota;ty

    being

    incorrecg

    which

    would

    cause

    the- furstantaneous

    terminal

    PrSssures

    to

    be 18O

    degrees

    out

    of

    phase.

    If

    zero

    voltagc is

    obtained

    between

    ail

    pairs

    of

    similarly

    maried

    termhals

    on

    the

    two

    transformers

    then it

    is

    an indication

    that

    the

    phase

    sequencc

    as

    well

    as the

    polarity

    are

    identical

    in

    each case'

    (c)

    The

    two

    tarsformers

    must

    have

    the s:rme

    p(essure

    ratio

    so

    that

    on

    ope,r

    ckcuit

    the

    ' '

    s"cond".1,

    'iottages

    are

    eqnal.

    When

    installing

    npw

    kansformcrs

    the

    position

    of

    the

    tapping

    swilches

    should

    be examined.

    (d)

    The

    angle

    of

    phase displacemcnt

    between

    the

    primary

    aod

    secondary

    vectors

    mlst

    be

    '

    '

    thc

    samc

    for

    cach

    transformcr.

    This

    phase angle

    differerice

    is

    a fixed

    inhef

    snt

    (e)

    For satisfactory

    sharing

    of the

    load

    cunent

    the impedance

    voltage

    drop

    at firll

    load

    should

    be

    the same

    for

    both

    transformsrs.

    This

    :necessitates

    the

    transformers

    having

    the same

    values

    of

    pe.rcentage

    impedance

    voltage drop,

    but

    not

    necessarily

    the

    same

    valuc of

    ohmic

    impcdan""f

    fiir

    latter

    value dcpending

    on

    thc

    KVA

    rating

    of

    the

    tansformer,

    (f;

    In

    addition

    to

    having

    equal

    pcrcentage

    impedance

    voltage

    &ops

    it

    is advisable

    that

    the

    two transformsrs

    iaVc-

    nearly

    the

    same

    ratios

    of

    percentage resistance

    to

    psrcentage

    reactance

    pressure

    drops,

    which

    necessitates

    similar

    ratios

    of

    resistance

    to

    icactance in

    each

    casc.

    If

    this condition

    is

    not

    met

    there will

    be a

    phase displacernent

    between

    the

    tsansformer

    and the

    total

    toad

    currents

    resulting

    in

    different

    power

    factors

    for each

    bansformer

    and necessitatin

    E

    a

    grcatet KVA

    output

    than

    is

    acnully

    required,

    with

    accompanying

    additional

    heating losses

    and

    Poorer

    voltage

    regulation.

    2.

    Loa'd

    Sharing

    under

    Normal

    Conditions

    The

    noltage

    chaacteristic

    of

    a tansforma,

    connecling

    terminal voltage

    with

    load

    curreng

    will

    usual-ty

    bc

    a

    &ooping

    curvc somewhat

    similar

    to

    that

    of a dircct

    current

    shut-wound

    gcnerator'

    Howevcf,

    the

    actual

    value of

    the

    terminal

    voltage

    at

    any

    Particular

    load

    wiil

    depend not

    only

    on

    the

    value'of

    the imlrcdancc

    voltage &op

    but

    the

    phase

    relation

    of

    thie

    &op

    to

    the

    apptied

    voltage,

    *ft.t

    io

    tum

    will

    iepcnd

    on

    ttre

    power

    factor

    of

    the

    load. Two

    transformers

    which

    are

    to

    operate

    irt

    prt.U"f

    shotld hlve

    ,i-rtu.f,"

    '

    s:uLp'd

    crment-voltage characteristics,

    so

    that thc

    *op

    in

    terminal

    pressure betweefl no

    load

    an{

    iiU

    Ioarl is

    the

    sa.:ne in

    each. |1i

    otiier

    words,

    tiiey

    shouici

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    19/35

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    20/35

    ft

    .i"

    a-s

    usua

    howcver,

    for

    Ere

    traosformer

    rr-rne-a1gc

    to

    b

    cxpressed

    as

    I'crcntage

    drops

    at

    firll

    load

    -t

    ,g

    *#frai"Itt

    the

    "qui*r*t

    tnnedance

    of

    the

    traosformcr'

    l*t

    ,4:pcrcentage

    impedance

    of

    transformer

    No'

    1

    and

    17;

    perc*fiageimpedance

    of

    rransfomra

    No'

    2

    Thenassumingforthcprese,rtthatlrand12arethefullloadcrrrerrtsofthctransformen,Zland

    ;J;;hti";;pedanLs

    maY

    bc

    exPressed

    as

    .-

    "Y

    'r

    -

    Il'1oo'

    Thus

    from

    which

    11

    then

    bccomes

    and

    similarlY

    --

    zzY

    .t7-

    Ir.lffi'

    Zz

    -TT

    lz=It

    z2

    VI1

    +

    z1VI2

    zzVIt

    lkVA

    )

    x

    zz

    r,=r,

    @iTT;E6jT;

    Theaboveisvalidforbottrsingle.phasearrdthree.phasetransformers.

    The

    correct

    Pairing

    of

    Transformers

    Thecorrectpairingoftraruformersislargely.

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    21/35

    :#, .?iffih:

    :ffi

    I',*"Ty

    ;:g- r:

    bue

    bar,ettering

    -h

    ffi*T,:f**;

    ;;il

    ;,Ja;X

    i:ffi*t

    H,J:,,,ffi.ffi

    ,r,

    Ph

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    22/35

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    23/35

    R'

    -

    R'

    =

    iz

    -

    iir

    = tt*icc

    phase voltage,

    Y'

    -

    Y'

    =bz

    -

    br

    =

    twice'phasc

    voltage,

    B'

    -

    B'

    =

    cz

    -

    Gr

    =

    twice

    phasc

    voltage,

    whilc

    readings betwecn other

    pairs

    of

    tcrminals

    will

    give

    indications

    of

    phase

    volts.

    Similar results

    are

    obtained

    for delta{elta connected

    tansformer, this

    case bcing

    shown

    in

    Fig.l

    .

    The

    secondaqr

    of

    the second transformer

    is shown

    with

    each

    phase

    .

    rwersed

    with respect

    to

    the fst

    kansformer.

    the

    result

    is

    :

    complete

    rewrsal

    of

    the

    veotors

    of

    induced

    terminal

    e.m.f.s,

    and

    giving

    180

    degrees

    phase

    displaccrnent

    between the similarly

    te

    nuedbus

    b3rs-L',.Y', B',

    as

    in

    the case of

    ttre

    star'star

    ,.

    rl

    ^

    x

    r

    t

    n'

    Ftc,

    5

    -Eff.4t

    of intcrchanging

    two

    cxrcrnal conncctions

    on

    primary

    sidc

    of

    della-star

    transformcr

    .

    connectcd transformers.

    If

    voltagc ri,adings

    behreefl

    the

    secondaries

    are

    to

    be

    made, one

    phase must

    first

    bc

    conncctd

    as

    thsre

    is

    no

    cornmon neutral point

    availablc. If

    R',

    R'

    are

    commoned,

    thcn reading

    between

    Y'

    -

    Y'

    and

    B' -

    B'

    will

    givc

    twicc

    normal

    lino

    volts, as

    can

    bc

    seen

    &om

    tho vcctor

    diagpms'

    (c)

    Phase

    sequence,

    and

    the

    interaction

    between

    this

    and

    polarity.

    - Phase

    scquence

    is ody

    a

    iactor

    of

    importance

    in

    ths

    parallel

    opcration

    of threo

    phasc

    tansformers'

    * ofballk"

    of

    three single_ptnse

    units

    opsratod

    as

    a

    three-pharc

    group-.

    It

    has

    besn shown

    in

    the

    precrding scction

    in

    the case

    of

    tansformn

    with

    eimilarly

    connected

    primary

    ina r""ondrry

    windings

    such

    as star-star

    tarsformers,

    that

    a

    rgvcfsal

    ofttr.

    poturity on one

    sidc,

    although

    it

    will

    rsnder

    parallel-opcration

    impossiblg

    will

    not

    alier

    ths

    phasc sequance

    of

    thc

    se&ndary

    induccd

    volages,

    Conracrscly

    a

    pair oi star-star

    or dclta{clta

    transformers

    which

    haw

    thc

    sarnc

    relative

    polarifu,

    but

    whose

    secondaries

    have

    oppositc

    phase sequencel

    'ay

    F

    operated

    in

    parauet by

    rcconnecting

    the

    cxtamal

    connections

    oo

    cither

    thc

    6

    4

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    24/35

    primrry or thc

    socoodary

    sides so

    as

    to

    produce

    similar

    phase

    5

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    25/35

    /\

    -,\

    8r

    R

    Y

    E

    B,

    B,

    Y,

    f

    .....-E

    4

    1;";8,'1,:,"n"i\".11i,.lli

    o1';''llEl'X'i"if

    lil'

    lLil3l""fl$"3i"o'""

    this

    property

    pf

    star-delta

    and

    delta-star

    transformers

    -also

    makes

    it

    possible

    to

    cnrrect

    rhs

    cffect

    of

    *""*';";;;"[surtine

    from

    a

    rcvcrsal

    of

    rtre

    intcmal

    connections

    on

    the

    primary

    lti"il'J;

    ti;es'

    by

    a

    change

    in

    the

    ext'rnai

    conncctions,

    and

    thus

    '"'*";

    ;Ji;.iiiu"i

    "pi'"ii"''

    *ithout

    alteration

    to

    the

    intemal

    connectiors'

    Fig'

    "

    f,;;;t#J'1":'i*

    ITj""#IL.I";3,*il'i

    H:

    #*x:6:l'g*;,15{i;13*ff"1**;e*,;1[

    ffffi.j'HIffi-T"ffi'?,"J#;i

    **",

    "f

    d'

    X:

    ".,HlHf,'#:

    ;;;"

    ;h*"

    ,Jqt'*"'

    o-f

    the

    secondary

    t*-

    IT

    "I

    I

    made

    the

    sarne

    as

    o*.

    ,",

    *".

    iiitire

    additional_

    reversal

    of

    thc

    secondary

    ext

    nal

    comection

    ',

    ^"J:i"i"

    tr"t

    **naitr

    tY

    tff*1|,*

    trJ";

    ffiil;.",

    then

    be

    paralleled'

    Two

    other

    sets

    io*".

    t"

    *otttd

    out

    in

    a

    similar

    manner'

    rhe

    case

    of

    a

    delta-star

    transformcr

    -*

    *U'l

    r:

    ::ffiLH"::"I"#t:l1l

    i*.?tr^*

    on

    the

    delta

    side

    of.one

    ol

    1"',:nu

    ..ftom

    which

    it

    will

    be

    Iffi"i-th*'gi"ing

    reverse

    pol"rity'

    is

    shown

    T-tl?

    ""##J'".

    .i"'*"""a'"v

    Hi#;imift

    Poiarity

    ancl

    phase

    sequonce

    of

    *-

    sidc

    bus

    bars

    by

    suitabty

    rlJi'ittttir'*

    t"

    "*t"-"r

    connections

    as

    in

    tho

    Provrous

    case

    r:::11:1fii'::"'""ff'

    T;ffi{;if

    H;#i"q,Wrtr,*"n*ffi;.ffi

    ::

    "*Tfi'..1a"^rlri"i6ov in

    parallel

    unless

    m--ca"u

    ;;r;

    -plmary-

    ana

    [:[r]m'

    mex'

    ;:"[f"'

    ';r[+&l5'

    ffi

    '*m;:

    tris ohase

    displacrrnent

    depends

    primarily'

    on

    the

    typ^

    primary

    and

    secondary

    i"riii"tt'*a

    "

    tl*

    ""p'bl"

    of

    variation

    by

    alteration

    ot

    ilti-.v

    orth"

    wioil[l:f#;.t'.f,,i.;

    or

    ssoondaf,v

    sidss'

    In

    cadam

    di--

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    26/35

    q.pes

    of

    tansforf,cr

    aho,

    the

    nhase

    rlisnflmcnl-'

    rraY

    bc

    altcred

    by

    a-

    rErrmgcme'[t

    of

    trc

    cxrerral

    -c;;cctionr'

    which

    prowides

    a

    vahublc

    means

    ol

    suirabty

    pairing

    trmsform;;ffi;;i

    u" ioi-o--to

    hrw

    differcnt

    phasc

    disolaccmcnl

    In

    othcr

    t**

    ;'o.J;;-.,d

    Ph*t

    displacernent

    b"*alt"

    "ri"-v

    and

    secondary

    ioat'Ja

    "tft'g"t

    "'n

    otity

    bc

    changed

    by

    'reconnechon

    or

    #;#;;.;;;;

    ;;

    ;

    io"r

    m"in

    i*f

    F

    consider

    sfrich

    can

    be

    ":*-"rfii

    W

    a""rr"g;t

    "

    t1p"

    ot

    tt*"rormer

    applicable

    to

    each

    case'

    l

    :

    2.

    Y

    ,

    Y

    I

    '.''

    F,6.

    9

    -srar.srar

    rransrormer,.shorrhjjI?.ili;:,tJ'jl:::mcnt

    tcr*ccr rri'r:::)

    and s"ooaJr]

    9

    ^1

    L\ c,t

    Jt"]

    ,J

    al

    cl

    ,'-Lfl

    Y'--+_+

    l--

    rl

    ^

    /Y

    ,,H,

    .,'

    R'

    FlG. I

    -D:a8ram

    shoqing

    how-

    incortc'l

    .Polarity

    of

    delta sidc

    of

    delta'star

    ''-'

    ir"nsfo.m-cr

    m"i'ii

    ii'iiita

    ui

    iiicratibn

    of

    thc

    crrcmal

    conncctions

    s

    having

    zero

    phase

    displacement

    berween

    primary

    and

    '-'

    s."ond"ry

    induced

    lerminal

    vologes'

    Transformer

    under

    this

    headings

    consist^

    of

    slar-star'

    delta-deh4

    and

    delta-

    intsrconnected

    "t"

    ""*fttrnt.'"fne

    case

    for

    a

    star-star

    connected

    unit

    is

    shown

    in

    Fig.

    s

    .

    and

    from

    ilU;;t';Garns

    it

    will

    be

    noted

    that

    the

    secondarv

    vector

    of induc'ed

    tj'"

    ;L;;i;

    *"t

    prt""

    does

    not

    differ

    in

    angular

    position

    &om the

    .*."p*aiog

    ffi""""-

    --J

    trt'

    th:

    enmary

    and

    secondary

    line

    ;J;;";;'f'B,

    *i;

    -

    b2

    are

    prallel

    and

    have

    the

    same

    sense'

    &

    Y

    D

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    27/35

    (2)

    Threc-phasc

    hansformen

    having

    lg0 degrees

    phase

    dilplacemcat

    betwecn

    pdmary

    and

    secandry

    incladed

    tirminol

    vitog"s.

    -

    ,

    The

    tansfomrem

    belonging

    to

    this

    class

    havc

    similar

    typcs

    of

    windings

    to

    those

    considcred

    in

    the

    abo.ne

    section,

    but

    in

    cach

    case

    '

    \1;

    FtO.

    lO

    -Sur.rcvcrsc

    srar lransforocr-

    showing

    lg0 d.8rc.s

    ph.se

    disolaccmcnr

    bcrwccn

    primary

    and

    s

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    28/35

    rcs

    and

    that

    the

    PrimarY

    and

    ffi;#*T.Hry,H"TH#:St#ffi1ffi

    ffiI#:'*

    Hcpcndent

    '

    mH :ffi#Hr,

    ::,fffi;":;x*s

    e

    phasc

    dispracomcnt

    bctwc

    c'n

    m*f:*r:****1

    il",il'il".;;;ry::f

    ;ili::f

    f; ,i',H.T:"HXffi

    ,;;-;-"","."i1a"r'"+

    terminal

    vollagc

    on

    eacn

    and

    ttrat

    the

    vectors

    or

    the

    ilfi;;;;i;

    I

    u'

    P9 ?

    ;"*

    T*H:1"J.t#"iJi;

    *:"#L'":iitrr*.*;i:ffi

    . 1'lf"ffl;t""*a

    6''r'

    Figs

    z

    and

    'I3

    show

    the

    corrcsponoing

    iiigr"

    t

    for

    star-delta

    and

    star-interconnected

    star

    transformers

    which

    have

    a

    similar

    phasc

    displaccrnent

    characteristic.

    (4

    )'11ree-phase

    . IT*Tfi

    ^rHX?

    "

    "?,2iif;2""

    r,?#;.*;Xff

    ':

    "

    phase

    displacement

    betweerl

    ['flmary

    drrs

    Jvvvri*r

    z

    D

    .l

    I

    I

    I

    I

    tl

    l.

    v

    ,

    11

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    29/35

  • 8/11/2019 Transformer Trouble , Test , Drying , Parallel operation

    30/35

    The

    Bridsh

    Stendard

    Specilicetion

    for Power

    Transformer'

    No'

    171

    (1959)

    (a) Need

    for

    uni{ormity.

    -

    Transform.ers

    which

    1nay

    have.

    to

    bo

    paralleled

    rc

    not

    ;fi;)i-;,fi&ia

    w

    o"

    ,"*"

    ir*

    -a

    o"rri"re

    it

    is

    ar

    obvious

    advantage

    if

    il#n

    '*

    .gr*a

    -"rt

    od

    "f-";G

    i*'l"als

    a1t

    rnakine

    internal

    connections'

    which

    can

    bc

    artopted

    tty

    "U

    ffi"f..t**.

    B.S.

    1?1

    (1959)

    providcs

    the

    ;;;;;;,-darfiLtior,

    ;

    futd

    -q

    *Tdi"qT-ections

    this

    information

    bcing

    given

    in

    section

    14';;Iht

    "tdification

    lach

    tlpe

    of

    taruformcr

    has

    dcsigrratcd

    to

    it

    three

    tV

    U"f"

    *i'i"f

    chssiS

    it

    according

    to

    its

    intcrnal

    connections

    and

    phase

    Otpi.."t*t

    betwesn

    pti*"r'

    and

    secondary

    induced

    voltages.

    Thephase

    di.pl"J;;;;;J;il

    bv;"1""]-face

    number

    so

    that

    0u

    is

    indicated

    by 0.0

    o'clock

    aJ;;-t

    by;0

    "ti*f.

    etc'

    In

    this

    chapter

    the

    wind-ing

    and

    vector

    diagrams

    frr""

    U"*

    ituJted

    in

    accordancc

    with

    B'S'

    No'

    171

    (1959)'

    For

    threc-ptraso

    ruosfor-o,

    ther"

    tt"

    fo*

    main

    groups

    arranged

    according

    to

    the

    phase

    displacem"rrt

    U"rw"*-tt'"-ptl"'*y

    '1a

    *gt"i'*

    induced

    voltages'

    The

    reference

    Ddo,

    for

    "-"-pfi'-iiai""tit 'h-"t

    F:

    transformer'

    is

    delta-delta

    ".*""i"4

    ""ties

    uflder

    rn"'io'g*p

    l,

    and

    tlut

    it

    hal

    zero

    phase

    displacernent'

    This

    tansformer

    may

    ut-ti't"ti'a'i"

    paralleJ

    with

    a transformo

    whose

    charactsristics

    are

    dcfioea

    -Uy-ti,

    reference'Yyo,

    because

    although

    rhis-is a

    star-

    star

    transformer

    it

    rru,

    "tro

    ,lnaer

    main

    group

    I

    and

    has zcro

    phase displacernent

    Similarly,

    a

    bansformcr

    of

    "ft"n"t

    yJf

    refcrs

    to

    a star-delta

    unit

    belonging

    to

    main

    group 3

    ancl

    has

    "

    PhJ;;i;;"*ent

    corresponding

    to I'0

    o'clock

    or

    -

    30"'

    The

    enginecr

    who

    is

    resporsible

    for

    the

    commissioning

    or

    connecting

    up

    of

    .t

    "*i"il*,

    ir

    well

    aalvised

    to

    obtain

    a copy

    of

    the

    abovc

    specification'

    Marking

    of

    terminals

    and

    windings

    '

    - Capitel

    l"I"'=.

    -"

    used

    to

    indicatc

    the

    H'V'

    and

    small

    lettsrs

    thc

    L.v.

    #;;;;

    *rutt'

    i"

    *tit

    book

    have

    besn

    refsrred

    to

    as

    thc

    pdmary

    and

    secondary

    ;;G'

    The

    corresPonding

    primary

    and

    secondary

    winding

    of

    each

    phase

    ",,

    A'o

    fr"*

    suffx

    n''

    inberg.as

    Ar'

    Az'