TRANSFORMER SPECIFICATIONS

1.The Transformers shall be supply ,commission and make them to parallel. The transformersshall be made on both the side Terminal Boxes(HV side and LV side)

1 Name of Manufacturer Kirloskar Electric Co. Ltd., Mysore, India.

2 Reference Standard IS 2026

3 KVA rating 1500

4 Type of cooling ONAN

5 Number of phases & rated frequency 3 & 50Hz

6 Rated voltage at no load HV/LV (in kV) 33-11/ 0.433

7 Connection (HV/LV) & Vector group Delta/Star & Dyn11

8 Insulation level- HV- HVN/LV LI 170 AC 70 / AC 3

9 Type of Tap changer- Off circuit / On load Off Circuit Tap Changer

10 Tap range, Number of steps, Step size & Location +5% to –10% @ 2.5% in 6 Steps For 33KV

11 Temperature rise of top oil / winding (degree C) 50/55

12 No load loss at rated voltage & rated frequency(in kW) 2.0 IS Tol.

13 Load loss at 75 0C and rated current (in kW) 14 IS Tol. For 33KV

14 % Impedance volts at 750C, rated current & frequency 6.25% +/- Sub to IS Tol.

15 % Efficiency @ UPF & 0.8 PF Lag

a. 100% Load

b. 75% Load

c. 50% Load

d. 25% Load

@ UPF

98.94

99.13

99.27

99.24

@ 0.8 PF Lag

98.68

98.91

99.09

99.05

16 % Regulation at Full load and at UPF / at 0.8 pF Lag 1.12/4.55

17 Approx. weights in kgs

a. Core & winding

b. Tank & Fittings

c. Oil

d. Total weight

2750

2600

2200

7550

18 Approx.overall dimensions in mm (L x B x H) 2900 x 3100 x 3150

19 Approx.Transport dimensions in mm (L x B x H) 2900 x 1900 x 2850

20 Approx.Transport Weight in kgs 6500

21 Terminations HV / LV HV

Cable Box

L V

Bus Duct

Page 3: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

Sr no Description1 Rating & diagram plate 1

2 Earthing terminals 2

3 Inspection covers As required

4 Air release plug As required

5 Lifting lugs 4

6 Drain Valve 1

7 Top & Bottom filter valve 2

8 Silica gel breather 1

9 Magnetic Oil level guage 1

10 Pressure Relief Valve 1

11 Conservator with oil filling hole, drain valve and accessories 1 standard

12 Thermometer pocket 4

13 Double float Buchholz relay for main transformer with A/T Contacts 1

14 Shut-off valve for Buchholz relay 215 150 mm Dial OTI 116 150 mm Dial WTI 117 Top, middle & bottom sampling valves 3

18 Bi-directional rollers 4

19 Radiators Capacity 1 x 100%

20 Jacking lugs 4

21 Marshalling box 1

22 Tap Changer Off circuit

23 HV Bushings 3

24 LV bushings + LVN Bushing 3 + 1

25 Terminal Boxe HV side

26 Terminal Boxe LV side

TRANSFORMER FITTINGS & ACCESSORIES - I

Page 4: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

ANNEXUREBOM

SRI VIJAYA VISAKHA MILK PRODUCERS COMPANY LIMITED

S.No Dicription Make Qty UnitsEB Incomer ACBs

1

3200A,4P,70Ka,EDO ACB – with microprocessor based LSING protection Basedcurrent display relay and having the following protections. SIEMENS/L&T 3 Nos

2

Feeder Protection Relay having with (ANSI Code - 50: Instantaneous/Definite TimePhase Over current Protection, 51:Inverse Time Phase Over currentProtection,50N: Instantaneous/Definite Time Ground Over currentProtection,51N:Inverse Time Ground Over current Protection) ASHIDA 3 Nos

3 Reverse Power Relay (device code-32) SIEMENS/L&T 3 Nos

4Line monitoring relay with Over and Under Voltage, Phase failure , Phase SequenceProtection relay (device code-27) ASHIDA 3 Nos

5 Master Trip Relay With HR Contacts (High Speed) ASHIDA 3 Nos6 Protection CT's 3000-1, 15VA, Cl:0.5 resin cast Kappa/Reshab 9 Nos7 10A,2NO+2NC Aux cantactor SIEMENS/L&T 12 Nos8 Metering CT's 3000-5, 15VA, Cl:1.0 resin cast Kappa/Reshab 9 Nos9 3P MFM meter EM 8400 with RS-485 com.port ELMEASURE 3 Nos

10 Digital type Amp Cl:1.0 with auto selector ELMEASURE 3 Nos11 Digital type Volt meter Cl:1.0 with selector switch ELMEASURE 3 Nos12 Indicating Lamps (RYB) & (CKT) SIEMENS/L&T 27 Nos13 6Control MCB SIEMENS/L&T 18 Nos

DG Incomer ACBs

14

3200A,4P,70Ka,EDO ACB – with microprocessor based LSING protection currentdisplay relay and having the following protections. SIEMENS/L&T 3 Nos

15

Generator Protection Relay (ANSI Code - 50: Instantaneous/Definite Time PhaseOver current Protection, 51:Inverse Time Phase Over current Protection,50N:Instantaneous/Definite Time Ground Over current Protection,51N:Inverse TimeGround Over current Protection) ASHIDA 3 Nos

16 Reverse Power Relay (device code-32) SIEMENS/L&T 3 Nos

17Line monitoring relay with Over and Under Voltage, Phase failure , Phase SequenceProtection relay (device code-27) ASHIDA 3 Nos

18 Master Trip Relay With HR Contacts (High Speed) ASHIDA 3 Nos19 Protection CT's 3000-1, 15VA, Cl:0.5 resin cast Kappa/Reshab 9 Nos20 10A,2NO+2NC Aux cantactor SIEMENS/L&T 12 Nos21 Metering CT's 3000-5, 15VA, Cl:1.0 resin cast Kappa/Reshab 9 Nos22 3P MFM meter EM 8400 with RS-485 com.port ELMEASURE 3 Nos23 Digital type Amp Cl:1.0 with auto selector ELMEASURE 3 Nos24 Digital type Volt meter Cl:1.0 with selector switch ELMEASURE 3 Nos25 Indicating Lamps (RYB) & (CKT) SIEMENS/L&T 27 Nos26 6Control MCB SIEMENS/L&T 18 Nos

BUS COUPLER ACBs

27

3200A,4P,70Ka,EDO ACB – with microprocessor based LSING protection Basedcurrent display relay and having the following protections. SIEMENS/L&T 2 Nos

27A Reverse Power Relay (device code-32) SIEMENS/L&T 3 Nos27B Master Trip Relay With HR Contacts (High Speed) ASHIDA 3 Nos30 10A,2NO+2NC Aux cantactor SIEMENS/L&T 12 Nos31 Indicating Lamps (RYB) & (CKT) SIEMENS/L&T 27 Nos32 6Control MCB SIEMENS/L&T 18 Nos

OUT GOING FEEDERS (1250A ACB)

33

1250A,4P,50Ka,MDO ACB – with microprocessor based LSING protection Basedcurrent display relay and having the following protections with Shunt Trip Coil. SIEMENS/L&T 3 Nos

36 Earth Fault relay with CBCT SIEMENS/L&T 3 Nos

Page 5: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

37 3P MFM meter EM 8400 with RS-485 com.port ELMEASURE 3 Nos38 Metering CT's 1000-5, 15VA, Cl:1.0 resin cast Kappa/Reshab 9 Nos39 Indicating Lamps (on/off/trip) SIEMENS/L&T 9 Nos40 6Control MCB SIEMENS/L&T 12 Nos

OUT GOING FEEDERS (630A MCCB)

33

630A,4P,65Ka,MCCB – with microprocessor based LSIG protection Based Trip Unitand having with 1NO+1NC Aux Switch, 1NO+1NC alaram switch, Shunt Trip Coil,RHOM and Extended Spreder links setrelay and having the following protectionswith Shunt Trip Coil. SIEMENS/L&T 24 Nos

36 Earth Fault relay with CBCT SIEMENS/L&T 24 Nos37 3P MFM meter EM 8400 with RS-485 com.port ELMEASURE 24 Nos38 Metering CT's 600-5, 15VA, Cl:1.0 resin cast Kappa/Reshab 72 Nos39 Indicating Lamps (on/off/trip) SIEMENS/L&T 72 Nos40 6Control MCB SIEMENS/L&T 96 Nos

Other Feature41 1.5KVA, 20Mints Back-up ONLINE UPS Emerson/APC 1 Nos42 250mmX250mm Cooling Fans entire the panel board doors. Rexonald 30 Nos

43

Supply, install, commissioning and testing of PLC with SCADA System for main PCC panelwith complete automatic operating system with necessary protections and display ofoutgoing feeder’s status and monitoring. The PLC shall be supplied sitable digitalINPUTs/OUTPUTs & Anloge INPUTs/OUTPUTs with suitable SCADA System also allnecessary relevant components as SMPS, Relay cards and Windos.8.1 PC with 22 InchesLED monitor. ( The detailed Scheme shall be impliments as per requirements has beensubmited along with offer)

Mitsubishi Electric 1 Set

S.No Dicription Make Qty UnitsKIOSK PANEL BOQ (3Panle)

13200A,4P,70Ka,EDO ACB – with microprocessor based LSING protection Basedcurrent display relay and having the following protections. SIEMENS/L&T 3 Nos

2 Reverse Power Relay (device code-32) SIEMENS/L&T 3 Nos3 Master Trip Relay With HR Contacts (High Speed) ASHIDA 3 Nos4 Protection CT's 3000-1, 15VA, Cl:0.5 resin cast Kappa/Reshab 9 Nos5 10A,2NO+2NC Aux cantactor SIEMENS/L&T 12 Nos6 Metering CT's 3000-5, 15VA, Cl:1.0 resin cast Kappa/Reshab 9 Nos7 3P MFM meter EM 8400 with RS-485 com.port ELMEASURE 3 Nos8 Digital type Amp Cl:1.0 with auto selector ELMEASURE 3 Nos9 Digital type Volt meter Cl:1.0 with selector switch ELMEASURE 3 Nos

10 Indicating Lamps (RYB) & (CKT) SIEMENS/L&T 27 Nos11 6Control MCB SIEMENS/L&T 18 Nos

Page 6: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

ANNEXUREScope of work

SRI VIJAYA VISAKHA MILK PRODUCERS COMPANY LIMITEDPCC & KIOSK PANELs ,EARTH PITS , BUS DUCT AND ERRECTION & COMMISSIONING TECHNICAL SPECIFICATIONS

1

Installation, testing and commissioning of 1500 KVA, 11KV / 415V, 'oilcooled outdoor transformer with all necessary arrangements, and filtrationthe the oil before charge the load as per required BDV test requirements(The transformer shall be supplied by Sri vijaya visakha milk producerscompany)

3 No's

2

laying, connecting and commissioning of 11.kv, 3Cx185Sqmm & 12 core 2.5 sqmm(T/f Control cable)Standerd Power Cables,Solid Aluminum/copper conductor ,XLPEInsulated,cores laid up, PVC tape innersheathed,INSULATION SCREENING WITHEXTRUDED SEMI CONDUCTING COMPOUND IN COMBINATION WITH COPPER TAPE( 0.3kA FOR 1 SEC) , AL ROUND WIRE ARMOURED , AND OVERALL PVC FRLCSHEATHED CABLE CONFORMING TO IS 7098 / PART-II) 1985 - From our existing HTVCB panel to new 1500Kvar transformer (The Cable shall be supplied by Srivijaya visakha milk producers company)

200 Mtrs each

3Supply, laying, connecting and commissioning 11 KV (E) 3 core 185Sq.mm. XLPEScreene Indoor Terminetion Kit with long barulle Al lugs and other associatedaccessories.

raychem rpg / 3M 6 no's

4

Supplying, installing and connecting of 2.5 Mtr.long 75mmX8mm. dia Cast Iron(C.I) Earth Pipe with in an earth pit of 380 x380 x 3000mm.filled with salt andcharcoal mixed with sand in alternate layers 150 mm.each up to a height of2500mm. From bottom. The pipe shall have provision for watering through afunnel. It shall also have provision for connecting the copper and GA flats asrequired on two sides. (The earth pipe should be supply with moulded flangtype and not less the 8mmm wall thickness )

CAST IRON 20 No's

5Supply, laying and connecting EC grade 75 x 10 mm. Copper Flat laid for T/FNeutral connecting with necessary clamps, screws, interlinks and Hardwareetc.,

EC91 Grade 50 Mtrs

6Supply, laying and connecting 75x10mm GA Flat laid for T/F Body earthconnecting with necessary clamps, screws, interlinks and Hardwareetc.,

100 Mtrs

7Supply, laying and connecting 50x6mm GA Flat laid for PCC panle,Outdoorkiosk,Busduct and all eletrical metal parts Body earth connecting with necessaryclamps, screws, interlinks and Hardwareetc.,

200 Mtrs

8

Supplying, installing and Testing of 3200A IP65 rated Out Door kiosk withinput Bus duct arrangement and output Cable termination as panel size of :1000mmX2000mmX1200mm (L.H.W) The complete BOM and technicaldetails shall be follow as enclosed

IP 65 3 No's

9

Manufacturing, Supplying, laying, and connecting of 3Ph 4wire, [email protected] Al non-segregated Outdoor type Busduct having with 150mmX12mmX3Runsand 150mmX12mmX2Runs for nutaral.The complete BOM and technical detailsshall be follow as enclosed

IP 65 15 Mtrs

10

Manufacturing, Supplying, laying, and connecting of 100x10mm with 450mmlength EC grade 0.2mm Tinned copper flexible for connecting transformer LTTerminal to Al busduct The complete BOM and technical details shall be followas enclosed

EC91 Grade 33 No's

Page 7: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

11

Manufacturing, Supplying, installing and Testing of 3200A IP52 rated LT PCCPanel with 3EB Incomers, 3DG incommers and 2 Bus coupler14500mmX2000mmX1100mm/1500mm (L.H.W) with SCADA operatedthrough PLC. The complete BOM and technical details shall be follow asenclosed

IP 52 1 No's

12

laying, connecting and commissioning of 1Cx400 sqmm Standerd PowerCables,Solid Aluminum conductor ,XLPE Insulated,cores laid up, FRLS PVC tapeinners & outer heathed with Round Armour Type ST2 sheathed,650/1100V gradeas per IS 7098(Part 1) 1988 or updated amendment ( from Transformers KisokPanel to New PCC

Poly cab/Universal 3500 Mtrs

13

Supplying, terminating, connecting of 1x400sqmm armoured cables Doublecompression type Cable glands . and The cables shall be terminated with heavyduty long barrel Aluminium lugs after crimping. With necessary high tensile nutbolt and accessorise,etc,.

HMI/Dowells 450No's

14 laying, connecting and testig of 11.kv, 31/2Cx240Sqmm Aluminum Armoured ,XLPE Insulated cacble - From our New PCC to Biproduction section (The Cableshall be supplied by Sri vijaya visakha milk producers company)

2800 Mtrs

15

Supplying, installing and connecting Hot dip galvanized (IS:2629&IS:4759) laddertype cable tray in the standards length of 2.5 meter each complete with 2Nos of“C” Type Coupler plates and required electroplated hardware of the followingsizes. As per 65 microns Zinc coating Thickness (IS:4759) with Purity of Zinc(IS:209) Size Of tray : 600mm Wide 90x20x2mm Runner and 30x15x2mm rungs

200 mtrs

16 Liasioning of Transfromers ,PCC panel, all installed equipments connectedto this project and Proposed to install 2000KVA DG sets by APCEIG 1 No's

Note: 1.If any alteration is required during project execution in the way of civil as wellas Electrical side work will be contractor scope for which no price enhancement.Hence please make sure that before quote the price, the contractor should have visit the site and know the exact requirement.2.The civi work related transformers Plinth ,PCC panel and Cable trench is supplier scope3.The dimension and sizes for the PCC panel ,Kiosk and busbars mentioned in GA dwawings and scope workis the fianl.4.If any doubts regarding the project feel free to contact to below mobile number

9959499895

Page 8: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

3200A OUT DOOR KIOSK AND BUSDUCTThis specification covers the design, procurement, fabrication, assembly, testing atmanufacturer's works, loading at works and transportation to site in a properly packedcondition, erection, testing and commissioning of 415 V LT Scope consisting of LTKIOSK with all accessories for efficient and trouble-free operation of the Panel for mainelectrical system.

DESIGN CRITERIA

The 3200A PCC Panel having with 3200A,4P ACB with necessary Axillaryprotection and located at nearest transformer. The Kiosk shall be made with suitable ofinput supply from T/F Al bus duct and Outgoing Cable termination.

a) 3200A Kiosk - 3 Nosb) BUSDUCT - 15 Mtrs

Construction of OUT DOOT PANELThe PANEL shall be self standing, floor mounted, compartmentalized, made of minimum2 mm thick CRCA sheet steel cubicle with metal / insulating partitions and the thicknessof doors / covers also shall not be less than 2 mm.

The enclosure shall conform to IP-65 degree of protection.

The panels shall be rigid, vibration proof and free from bends and twists. Panel door andside doors shall have self-locking screws and locks.

The Panel shall have provision for bottom cable entry, and Removable gland platesshall be not less than 2.5 mm thick.

Foundation rolled channels (ISMC 100 or 75), cadmium plated / zinc passivated boltsand nuts and other necessary items shall be supplied along with the respectiveequipment.

Suitable lifting hooks shall be provided on each transport section for ease of lifting ofswitchboard.

SEVEN TANK TREATMENT INCLUDE FOLLOWING STAGES:

After complete the fabrication and before going to paint shop the Panel and all metalpart should be clean as per proper 7tank Chemical treatment relevant standards.

PaintingAfter Complete 7 tank process chemical treatment the PCC panel

Apply the powder coated paint as per approved shade shall be applied. Before makingpaint vendor shall confirm the shade.

The final thickness of paint film or steel shall not be less than 100 microns and shall notbe greater than 150 microns. Touch up quantity shall be supplied

Page 9: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

Bus Bar for Kiosk BreakerBus bar material shall be aluminum of EC91 electrolytic grade as per Indian standardcode. Aluminum Used for the the bus bar is” Jindal” make only.

All bus bars, bus taps shall be insulated with close fitting sleeves of heat shrinkabletype.

Buses shall be fully insulated for working voltage, spaced with adequate clearance of atleast 35 mm between phases and 25 mm between phase and ground.

Size of Bus Bar: Use bus bar size 100x12x4Runs for RYB and 100x12x2Run forneutral from ACB to Main Bus bar and ACB to Cable termination point. The busbar shallbe use suitable support nearest at ACB and proper clearance shall be provide for CTcoil inset and also other relevant components.

consider at KIOSK ACB out going bus bar is to be extended and made enoughclearance to connecting 1 core , 400 sqmm size of runs not less than 10 no’s foreach phase.The gland holes are made (14mm) size for above quantity .

ACBs.All the incoming & Bus coupler 3200A ACB fully draw out, 4 pole, electrically drawout(EDO) type ,ACB with inbuilt LSIGN protection and LCD display microprocessorbased trip Unit .

Reverse power relay shall be in corporate for additional protection.

Also provide required quantity of control MCBs, terminals Relay cards, Aux. contactorsand LED indications with MFM meter and control gears.

All the current transformers (CTs) shall be cast resin insulated type, with Secondarycurrent of all CTs shall be 1 A for protection and 5A for metering with short linkedterminals and 4sqmm Cu. Cable for CT wiring

Earthing Connections

The Entire panel shall be connected to a 60x10mm Aluminum earth bus bar and32x6mm Al Bus bar for ACBs and all doors and movable parts shall be connected to theearth bus with flexible copper connections. Provisions shall be made to connect theearthing bus bar to the plant earthing grids at two ends. All non-current carrying metallicparts of the mounted equipment shall be earthed.BUS DUCT:

Supply of 3 No of 415 Volts , 50 HZ, 6300 Amps, 3 Phase , 4 Wire Non – Segregatedinterleaved BUS – DUCT as per the following specifications.

The equipment shall be designed and manufactured in full accordance with relevant codes andregulations and shall be capable of safe and continuous operation under all conditions withoutstrain, vibration and other operational difficulties. The equipment shall be suitable for operation

Page 10: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

under hot and humid tropical conditions.

The enclosure for 415 V busduct shall be of non – segregated enclosure made of sheet steelrectangular totally enclosed type of 2.0 mm thickness. The bus enclosure shall be ventilated andprotected with IP 65 degree of protection.

Adjacent enclosure section shall be jointed together by means of bolted flanges with nitrilegaskets in between to ensure a weather tight joint. Bolts and nuts and all other necessaryhardware shall be cadmium coated. Suitable flexible bellows shall be provided near thetransformer end connection to arrest vibration emanating from transformer.

The busbar shall be designed to keep enclosure losses to a minimum due to temperature rise.Provision shall be made for an expansion and contraction due to temperature variations andfaults. Bolted covers with gaskets for easy inspection and access to busbars /bus joints,Inspection opening of sufficient size shall be provided on the enclosure to facilitate inspection /maintenance of busbars, joints , insulators at any point without disconnectionThe busbars shall be in the form of straight extruded lengths of liberal sections rigidly supported/ braced with FRP HEAVY DUTY SUPPORTS conforming to IS 10912 UP1 grade to providethrough fault withstand capacity.Buses shall be air insulated with clearances as per BS between phases and between phasesand ground. Busbars shall be colour coded with Red , Yellow, Blue for easy identification ofphases and neutral with black colour.The busbar and bus connections shall be designed not to exceed a maximum temperature of 85degrees centigrade during continuous operation at rated current and at ambient temperature of50 degree centigrade. Under normal operating conditions ,the hot spot temperature of theenclosure shall not exceed 70 degree centigrade at the ambient temperature of 50 degreecentigrade.

Busbar joints bolted with high tensile cadmium plated bolts ,nuts and washers. Termination attransformer where the equipment terminals are of copper shall be made of laminated copperflexibles. The cross section of copper provided shall be adequate for continuous as well as shorttime ratings of busduct without exceeding the specified temperature rise valuesAll transformers shall have terminal bushings with flanged enclosure to receive the busduct.Supplier shall make necessary arrangements to match the busduct with the equipment terminalflanges. The flanges shall be provided with gaskets, nuts,bolts etc.

Page 11: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

3200A PCC PANEL SpecificationsThis specification covers the design, procurement, fabrication, assembly, testing atmanufacturer's works, loading at works and transportation to site in a properly packedcondition, erection, testing and commissioning of 415 V LT Scope consisting of LT PCC panelwith all accessories for efficient and trouble-free operation of the Panel for main electricalsystem.

DESIGN CRITERIA

The 3200A PCC Panel consisting with 3x3200A ACBs for 1500KVA EB load and3x3200A ACBs for 2000KVA (2DG present connected and 1 is future DG) DGs sourcereceived and distributed to entire plant with 2Nos of 3200A Bus coupler for load balancingeither EB or DG source.

The PCC system operated with complete automation mode with SCADA through PLCwith all necessary back-end protection of reverse power, IDMT, line monitoring protection andother features. All the EB & DG incomers and Bus couplers should be operated through PLCwith necessary digital I/O’s and analogue Inputs to satisfy the complete scheme.

Also incorporated all output feeders on/off/trip feedbacks and Amperes taken feederwise in the SCADA for monitoring.

The scope of supply shall consist of the following, a)

3200A PCC Panel - 1 No’sb) Required PLC & SCAD with accessoriesc) 1.5KVA Online UPS for PCC Control System.

Construction

1.The PCC shall be self standing, floor mounted, compartmentalised, made of minimum 2 mmthick CRCA sheet steel cubicle with metal / insulating partitions between compartments. Thethickness of doors / covers also shall not be less than 2 mm.

2.The enclosure shall conform to IP-52 degree of protection.3.The operating height of the operating handle / switches shall be limited to a maximum of1800 mm and a minimum of 300 mm. Minimum compartment / module size shall be 400 x500 (H.W)

4.The panels shall be extendible at both ends for the additions of vertical sections either by abreaker panel or a fuse switch panel. Ends of the bus bars shall be suitably drilled for thispurpose.

5.The panels shall be rigid, vibration proof and free from bends and twists. Panel door and sidedoors shall have self-locking screws and locks.

6.The PCC shall have provision for bottom cable entry and gland plate shall be design foreasily cable removable and insert without any damage to the cable . The thickness of theRemovable gland plates shall be not less than 2.5 mm.Foundation rolled channels (ISMC 100 or 75), cadmium plated / zinc passivated bolts andnuts and other necessary items shall be supplied along with the respective equipment.

7.Suitable lifting hooks shall be provided on each transport section for easy lifting .

Page 12: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

8.The PCC MCCB modules shall be arranged in vertical sections with barriers between eachmodule. The bus chambers as well as the breaker cubicles shall have provide thebarrier/partition as required to avoid the fair failures. A liberally sized (Please Check the GA)vertical cable alley shall be provided to accommodate all cables as per rating of the breaker asaccommodate 240sqmm, 31/2 core Al.Armored cable.

SEVEN TANK TREATMENT INCLUDE FOLLOWING STAGES:

After complete the fabrication of the PCC panel and before going to paint, the Panel andall metal part should be clean as on following methods.

1. The PCC should be treated to Degreased/ Surface cleaned in 20-30 minutes. Here you usemetrite SAG-HD Chemical at 10%. Which removes quickly Grease, Oils, carbonaceousdeposits, Paints?

2. Clean with water3. Next 20-30 minutes keep the panel in AP-H at 40% filled Tank. Which helps to removes rust

and etches and also helps good powder coating finish uniformly to base metal.4. Clean with water5. Clean with DSM at 2%.6. Clean with water7. Immersed for 20 minutes duration with ZLP-COLD-LP at 6%. For formation of Zincphosphate confirming to class “B” & class “C” IS: 3618. And passivate at 0.1%. This chemicalhelps in preventing corrosion and best Powder Coating finish. The Item is then taken out andair dried for five minutes and then taken to powder Coating booth.

Painting

After Complete 7 tank process chemical treatment for the PCC panel

Apply the powder coated paint as per approved shade by the developer.The final thickness of paint film or steel shall not be less than 100 microns and shall not begreater than 150 microns. Touch up quantity shall be supplied.

Bus BarBus bar material shall be aluminium of EC91 electrolytic grade as per Indian standard code.Aluminium material used for the bus bar “ Jindal” make only.

All bus bars, bus taps shall be insulated with close fitting sleeves of heat shrinkable type.

Buses shall be fully insulated for working voltage, spaced with adequate clearance of at least35 mm between phase to phase and 25 mm between phase to neutral.

Main Horizontal Bus bar :

The main bus bar should provide wholly end to end in addition with Bus coupler is to be laid150x12x3Runs for RYB and 150x12x2Runs for Neutral .the bus bar mount with finger typeCMC/SMC insulators. And covered with heat shrinkable red, yellow, blue, black sleeves foreasy identifying the phases and 12mm high-tension suitable heavy duty nut & bolts, springwashers are to be used for entire horizontal bus bar.

Page 13: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

Vertical Bus bar: use bus bar size 100x10x2Runs for RYB and 100x10x1Run for neutral. thebus bar mount with “L” CMC/SMC insulators. And covered with heat shrinkable red, yellow,blue, black sleeve to easy identify the phase and entire horizontal bus bar should be use 12mmhigh-tension nut bolt with suitable heavy duty washer and spring washers.

EB & DG Incomer: 1.use bus bar size 100x10x4Runs for RYB and 100x12x2Run for neutralfrom ACB to Main Bus bar and ACB to Cable termination point. The bus bar shall be usesuitable support nearest at ACB and proper clearance shall be provide for CT coil insert andalso other relevant components.

2. Consider at ACB incoming bus bar extensions for EB & DG shall be suitable holes (14mm)and have a enough clearance for connecting not less than 10Nos of 400sqmm Single corearmoured Al cables for each phase.

3.The Extended the bus bars of the EB and DG out going for all three sections in the New PCCpanel bus bar size 100X10X2 runs for each phase for connecting to old existing PCC from NewPCC.

Bus coupler: use bus bar size 100x10x4Runs for RYB and 100x12x2Run for neutral from ACBto Main Bus bar and ACB to Main Bus bar. The bus bar shall be use suitable support nearest atACB and proper clearance shall be provide for CT coil insert and also other relevantcomponents.

1250A ACB : use bus bar size 75x12x2Runs for RYB and 75x12x2Run for neutral from ACB toMain Bus bar and ACB to Cable termination point. The bus bar shall be use suitable supportnearest at ACB and proper clearance shall be provide for CT coil insert and also other relevantcomponents. (the size of bus bar shall be support future upgrade the ACB up to 1600A)

630A MCCB : use bus bar size 40x10x2Runs for RYB and 40x10x2Run for neutral from ACBto Main Bus bar and ACB to Cable termination point. The bus bar shall be use suitable supportnearest at ACB and proper clearance shall be provide for CT coil insert and also other relevantcomponents .The extended bus bar shall be made enough clearance and current rating forcable termination of size of 240 sqmm 31/2 core for 3 runs for each MCCB.

1. ACBs.All the incoming & Bus coupler 3200A ACB , 4 pole, electrically draw out(EDO) typeACB with inbuilt LSIGN protection and LCD display microprocessor based trip Unit .

Reverse power relay and IDMT relay, SPP and Earth/ground fault relay shall be incorporatedfor additional protection for transformer and equipment.

Also required quantity of control MCBs, terminals Relay cards, Aux. contactors and LEDindications with MFM meter and control gears.

All the current transformers (CTs) shall be cast resin insulated type, with Secondarycurrent of all CTs shall be 1 A for protection and 5A for metering with short linkedterminals and 4sqmm Cu. Cable for CT wiring.

Outgoing ACBs protected with inbuilt LSIGN protection and LCD displaymicroprocessor based trip Unit, adjustable over load current and remainingstandard as above.

Page 14: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

2. MCCBs.

630A, 4P, 65KA, 4P MCCB with inbuilt LS protection microprocessor based trip Unit withAdjustable Overload, Adj. Short circuit and Earth fault

The MCCB Shall be supplied as follow Specifications.a) Speeder link & extended rotary handle.b) Aux.NO+NC Switch & Trip Alarm Contact.c) Shunt trip Coil.

Also required quantity of control MCBs, terminals Relay cards, Aux. contactors and LEDindications with MFM meter and control gears.All the current transformers (CTs) shall be cast resin insulated type, with Secondary current ofall CTs shall be 5A for metering with short linked terminals and 2.5 sqmm Cu. Cable for CTwiring.

Earthing Connections.

The Entire panel shall be connected to a 60x10mm Aluminium earth bus bar runningthroughout the length Panel and 32x6mm Al Bus bar for All ACBs and all doors andmovable parts shall be connected to the earth bus with flexible copper connections.Provisions shall be made to connect the earthing bus bar to the plant earthing grids at twoends. All non-current carrying metallic parts of the mounted equipment shall be earthed.

PLC.

64Inputs and 32outputs PLC with CPU and suitable rating of SCADA system and allnecessary equipment,SMPS Relay cards, terminal, wiring and all accessories will be required as per system.

.

Page 15: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

VISAKHA DAIRY

DOCUMENT NO.

DRAWING NAME

CHECKEDREVISIONSDRAWN BYDATE

PANEL

NTS

SCALE:

1 OF 1

Sht. No.

REFERENCE NO: --

MILK PRODUCERS COMPANY LIMITEDVISAKHAPATNAM-530012

SRI VIJAYA VISAKHA

Page 16: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

0 OFF DISCHARGED

3200 A ACB

V

R Y B

EB INCOMER

3200A,4P,EDO,ACB

onoff

trip

MFM

A

TNC

0 OFF DISCHARGED

3200 A ACB

V

R Y B

DG INCOMER

3200A,4P,EDO,ACB

onoff

trip

MFM

A

TNC

0 OFF DISCHARGED

3200 A ACB

R Y B

BUS COUPLER

3200A,4P,EDO,ACB

onoff

trip

TNC

0 OFF DISCHARGED

1250 A ACB

O/G - FEEDER-1

1250,4,MDO,ACB

onoff

trip

MFM

BUS BAR

CHAMBER

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

on off

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

on off

trip

MFM

0 OFF DISCHARGED

3200 A ACB

V

R Y B

EB INCOMER

3200A,4P,EDO,ACB

onoff

trip

MFM

A

TNC

0 OFF DISCHARGED

3200 A ACB

V

R Y B

DG INCOMER

3200A,4P,EDO,ACB

onoff

trip

MFM

A

TNC

0 OFF DISCHARGED

3200 A ACB

R Y B

BUS COUPLER

3200A,4P,EDO,ACB

onoff

trip

TNC

0 OFF DISCHARGED

onoff

trip

MFM

BUS BAR

CHAMBER

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

on off

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

on off

trip

MFM

150mmX12mmX3Runs Al.BUSBAR Chamber

3780A @ 0.7 Density

150mmX12mmX3Runs Al.BUSBAR Chamber

3780A @ 0.7 Density

150mmX12mmX3Runs Al.BUSBAR Chamber

3780A @ 0.7 Density

BUS BAR

CHAMBER

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

on off

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

onoff

trip

MFM

630A,4P,50ka

MCCB

on off

trip

MFM

150mmX12mmX3Runs Al.BUSBAR Chamber

3780A @ 0.7 Density

0 OFF DISCHARGED

3200 A ACB

V

R Y B

EB INCOMER

3200A,4P,EDO,ACB

onoff

trip

MFM

A

TNC

0 OFF DISCHARGED

3200 A ACB

V

R Y B

DG INCOMER

3200A,4P,EDO,ACB

onoff

trip

MFM

A

TNC

0 OFF DISCHARGED

onoff

trip

MFM

150mmX12mmX3Runs Al.BUSBAR Chamber

3780A @ 0.7 Density

14799

14800mm

EB INCOMER

CABLE

CHAMBER

150mmX12mmX3Runs Al.BUSBAR Chamber

3780A @ 0.7 Density

150mmX12mmX3Runs Al.BUSBAR Chamber

3780A @ 0.7 Density

630A x 4nos

OUT GOING

CABLE

CHAMBER

150mmX12mmX3Runs Al.BUSBAR Chamber

3780A @ 0.7 Density

150mmX12mmX3Runs Al.BUSBAR Chamber

3780A @ 0.7 Density

14787

14800mm

630A x 4nos

OUT GOING

CABLE

CHAMBER

1250A ACB

OUT GOING

CABLE

CHAMBER

DG INCOMER

CABLE

CHAMBER

BUS COUPLER

CHAMBER

EB INCOMER

CABLE

CHAMBER

630A x 4nos

OUT GOING

CABLE

CHAMBER

630A x 4nos

OUT GOING

CABLE

CHAMBER

1250A ACB

OUT GOING

CABLE

CHAMBER

DG INCOMER

CABLE

CHAMBER

BUS COUPLER

CHAMBER

EB INCOMER

CABLE

CHAMBER

630A x 4nos

OUT GOING

CABLE

CHAMBER

630A x 4nos

OUT GOING

CABLE

CHAMBER

1250A ACB

OUT GOING

CABLE

CHAMBER

DG INCOMER

CABLE

CHAMBER

630A x 4nos

FEEDER LANE

630A x 4nos

FEEDER LANE

2000A

Al

BUSBAR

CHAMBER

630A x 8nos,OUT GOING

CABLE CHAMBER

650mmX1450mm

size widest cable chamber

1250A

ACB

OUTGOING

CABLE CHAMBER

EB INCOMER

CABLE CHAMBER

EB INCOMER

CABLE CHAMBER

BUSCOUPLER

630A x 4nos

FEEDER LANE

630A x 4nos

FEEDER LANE

2000A

Al

BUSBAR

CHAMBER

630A x 8nos,OUT GOING

CABLE CHAMBER

650mmX1450mm

size widest cable chamber

1250A

ACB

OUTGOING

CABLE CHAMBER

EB INCOMER

CABLE CHAMBER

EB INCOMER

CABLE CHAMBER

BUSCOUPLER

630A x 4nos

FEEDER LANE

630A x 4nos

FEEDER LANE

2000A

Al

BUSBAR

CHAMBER

630A x 8nos,OUT GOING

CABLE CHAMBER

650mmX1450mm

size widest cable chamber

1250A

ACB

OUTGOING

CABLE CHAMBER

EB INCOMER

CABLE CHAMBER

EB INCOMER

CABLE CHAMBER

1050

1500

3200A ACB - 8 NoEB INCOMERS (3 Nos),DG INCOMER (3Nos), BUS COUPLER (2 Nos)

1250A ACB - 3 NoZONE-1 (1 No),ZONE-2 (1No), ZONE-3 (1 No)

630A MCCB -24 No ZONE-1 (8 No),ZONE-2 (8No), ZONE-3 (8 No)

1250 A ACB

O/G - FEEDER-1

1250,4,MDO,ACB

1250 A ACB

O/G - FEEDER-1

1250,4,MDO,ACB

150mmX12mmX3Runs Al.BUSBAR Chamber

3780A @ 0.7 Density

SRI VIJAY VISAKHA MILK PRODUCERS COM.

KEY BOARD RACK

150mmX12mmX3Runs Al.BUSBAR Chamber

3780A @ 0.7 Density

150mmX12mmX3Runs Al.BUSBAR Chamber

3780A @ 0.7 Density

PCL

COMPARTMENT

SURYANARAYANA GARU

SRN ORIGINAL ISSUE SURESH ANAND

DOCUMENT NO.

DRAWING NAME

APPROVEDCHECKEDREVISIONSDRAWN BYDATE

PANEL

NTS

SCALE:

1 OF 1

Sht. No.

REFERENCE NO: --

Page 17: TRANSFORMER SPECIFICATIONS - Visakha · PDF fileTRANSFORMER SPECIFICATIONS ... KIOSK PANEL BOQ (3Panle) 1 ... 11KV / 415V, 'oil cooled outdoor transformer with all necessary arrangements,

0 OFF DISCHARGED

3200 A ACB

V

R Y B

LT KIOSK

3200A,4P,EDO,ACB

onoff

trip

MFMA

TNC

900

2001

900

2001

1200

INSIDE VIEW OUTSIDE VIEW SIDE VIEW

SURYANARAYANA GARU

SRN ORIGINAL ISSUE SURESH ANAND

DOCUMENT NO.

DRAWING NAME

APPROVEDCHECKEDREVISIONSDRAWN BYDATE

PANEL

NTS

SCALE:

1 OF 1

Sht. No.

REFERENCE NO: --