Transformer Overloading and Assessment of Loss-of-Life
for Liquid-Filled Transformers
P.K. Sen, PhD, PE, Fellow IEEE Professor of Engineering Colorado School of Mines
PSERC Project Webinar, April 19, 2011
![Page 2: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/2.jpg)
Presentation Outline
• Introduction and Motivations • Remaining Transformer (Insulation) Life,
Transformer Thermal Model, IEEE Loading Guides
• Modeling and Economic Evaluation • Simulation and Results • Conclusions
2
![Page 3: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/3.jpg)
• Oil-Filled Transformer - <500 kVA (distribution, OA)
- 500 kVA - 100 MVA (distribution power) (OA, OA/FA, OA/FA/FA)
- >100 MVA (transmission power) (OA/FA/FA and OA/FA/FOA)
Transformer Type and Nameplate Rating
• 65°C average winding temperature rise (thermally-upgraded paper insulation)
• 55°C average winding temperature rise (not thermally-upgraded paper, kraft)
• 30/40/50/56 MVA @55o / 65o C TR (OA/FA/FA)
@55°C TR 3
![Page 4: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/4.jpg)
• Thermal Model - Design Consideration (Losses & Cooling) - Temperature (Top & Bottom Oil, Winding Hottest-Spot Temp.)
- Insulation Degradation
- Estimation of Transformer Remaining Life from Its Insulation
• Economic Model - Total Owning Cost (TOC) - Revenue Requirement
- Other Models!!
Issues and Considerations
4
![Page 5: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/5.jpg)
Thermal Model • Design •Temperature • Insulation • Life
Economical Model Revenue Requirement
Optimization (Minimum Cost & Optimum Sizing) • New Design • Retrofit Design
- Replace now - Replace later - Add a second transf. - ??
Uncertainties & Probability Approach • Future load growth projection •Ambient temp. •Transformer Failure
5
![Page 6: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/6.jpg)
Loading Guide Standards
• IEEE Std. C57.91-1995 (USA) – Clause 7 (Classical Model) – Annex G (Detailed Model)
• IEC 354-1991 (EUROPE, CANADA and Others)
• IEEE & IEC Comparisons
IEC is somewhat similar to IEEE Clause 7
6
![Page 7: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/7.jpg)
• Long-term Failure Mode – Mechanical and chemical properties of insulation
deterioration – Dielectric strength reduction (approx. 10% over
the transformer life)
• Short-term Failure Mode – Bubble formation (gassing), temporally dielectric
strength reduction (30% impulse strength reduction @ 180 °C )
Transformer Failure Modes
7
![Page 8: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/8.jpg)
• The Tensile Strength (Mechanical) of cellulose insulation is used as a criteria for loss-of-life estimation.
• Recently, the Degree of Polymerization (DP)
(Chemical) has also become a popular measurement of insulation life.
• If a sample of insulation near hot spot location is
made available, the remaining life of the transformer could be approximately predicted based on specific criteria.
Remaining Transformer (Insulation) Life
8
![Page 9: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/9.jpg)
0
20
40
60
80
100
120
1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 -0.1 -0.2
Remaining Life (per unit)
% T
ensi
le S
tren
gth
The normalized remaining life by tensile strength method based on 20% remaining tensile strength (RTS) as end-of-life criteria, created by least square method
Remaining Life by Tensile Strength Method
97.05ln633.01Life Remaining TSR
9
![Page 10: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/10.jpg)
Remaining Life by DP Method
0
100
200
300
400
500
600
700
1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 -0.1 -0.2
Remaining Life (per unit)
Deg
ree
of
Po
lym
eriz
atio
n
The normalized remaining life by DP method based on remaining DP of 200 as end-of-life criteria, created by least square method
622ln881.01Life Remaining RDP
10
![Page 11: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/11.jpg)
IEEE Std. C 57.91-1995, Per-Unit Life
• Per-Unit Life
• Relative Aging Factor
• Equivalent Aging
• % Loss-of-Life
273
000,151810 x 80.9 HST
eL
273
000,15 39.164HST
AA edt
dLF
1
0
dtFT
F
T
AAEQA
100 × Life Insulation Normal
Tx F= EQA
• Normal Insulation Life
• Hottest-Spot Temperature (THS) 11
![Page 12: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/12.jpg)
THERMAL MODEL
Hottest-Spot Temperature (T ) HS
Hottest-spot temperature = ambient temperature (TA) + top oil rise over ambient + hot spot rise over top oil (DTG)
(DT TO)
12
![Page 13: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/13.jpg)
GTOA TTTT DDHS
Steady-State Equations
n
TORTOR
RKTT
DD
112
mGRG KTT 2DD
Thermal Model (IEEE Clause 7)
K = Per-Unit Loading (Actual Load/Rated (max) Load)
R = Loss Ratio (Load Loss @ Rated Load/No-Load Loss)
Exponent „n‟ and „m‟ depends on “Cooling” 13
![Page 14: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/14.jpg)
Thermal Model (IEEE Clause 7) Transient Equations
uTOTOTO
TO TTdt
Td,DD
D
n
TORuTOR
RKTT
DD
112
,
,uGGG
G TTdt
TdDD
D
m
uGRuG KTT )( 2, DD
Oil
Winding
14
![Page 15: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/15.jpg)
Modified Transient Equations
AuTOTOTO
TO TTTdt
TdDDD
D,
)(1
1)(1
1)( , sTs
sTs
sT A
TO
uTO
TO
TO D
D
D
15
![Page 16: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/16.jpg)
Thermal Block Diagram (IEEE Clause 7)
16
![Page 17: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/17.jpg)
• Loading cycle, Complex load growth
• Ambient temperature variation Thermal Model
Aging rate, %Loss-of-life
273
000,15383
000,15
HSTeRateAging
LifeNormal
telifeofloss
HST
100* %
273000,15
383000,15
D
Aging Rate and % Loss-of-Life
17
![Page 18: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/18.jpg)
• “Clause 7” thermal model: Simple, Requires minimum information, uses top-oil temperature
• “Annex G” thermal model: More complex, Requires
more information, Focus on duct oil temperature change, uses bottom-oil temperature
IEEE “Clause 7” & “Annex G” Comparisons
18
![Page 19: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/19.jpg)
IEEE Classical Model (Clause 7) IEEE Detailed Model (Annex G)
1. Top oil temperature rise at rated load2. Hot spot temperature rise over top oil at
rated load3. Loss ratio at rated load4. Winding time constant5. Oil time constant or6. Type of cooling system
1 Top oil temperature rise at rated load2 Hot spot temperature rise at rated load3 Average winding temperature rise at rated
load4 Bottom oil temperature rise at rated load5 Losses data from test report6. Weight of Core & coil7. Weight of tank & fittings8. Gallons of fluid9. Type of cooling system10. Type of cooling fluid11. Type of winding material12. Winding time constant13. Location of hot spot14. Per unit eddy current losses at hot spot location
“Clause 7” and “Annex G” Data Requirements
19
![Page 20: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/20.jpg)
H o t s p o t
To p o il
L o a d in g
Te m p e r a tu r e Pr o f ile Plo ts ( IEEE A n n e x G Th e r m a l M o d e l)
T im e ( h r )
1 21 086420
Tem
pera
ture
(C
)
1 2 0
1 0 0
8 0
6 0
4 0
2 0
0
Loading (Per unit)
5
4 .5
4
3 .5
3
2 .5
2
1 .5
1
0 .5
0
IEEE Annex G & Clause 7 Thermal Model (Step Load Response)
20
![Page 21: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/21.jpg)
Economic Evaluation (Total Owning Cost)
Buying a New Transformer
Simplified Practice,
TOC = IPP + A * NLL + B * LL
• Size (MVA) • A & B Factors
Owner Specifies: • Initial purchase price (IPP) • Losses (Winding & Core)
Manufacturer Specifies:
21
![Page 22: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/22.jpg)
Revenue Requirement • Daily load curves • Daily ambient temp. variations • Overloading & end-of-life • Accurate energy loss • Transformer replacement • Refined & flexible method • Detailed economic analysis
Applicable for Investor Owned Utilities
(IOU)
Economic Evaluation (Revenue Requirement)
22
![Page 23: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/23.jpg)
OPTIMIZATION • NEW DESIGN • RETROFIT APPLICATIONS
THERMAL MODEL
ECONOMIC MODEL
23
![Page 24: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/24.jpg)
Daily load curve, Complex load growth
Ambient temperature variation
Economic data - discount rate, tax, - energy cost, etc.
Transformer Data
Thermal Model
Economic Model
Life Expectancy
TOC
Optimization (New Procurement)
24
![Page 25: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/25.jpg)
Existing system
Estimate Remaining Life
Remaining Life Expectancy
Historical load and ambient temp. data
Present load Load growth Load shape Ambient temp. Economic data etc.
Replace with new transformer now
Add a 2nd transformer
Overload existing transf. and replace with new one later
Optimization (Retrofit Design)
25
![Page 26: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/26.jpg)
Probability Tree Structure
ProbabilityDistribution
Path Levelized Probability Revenue Requirement
1 $134,000 0.0016
81 $101,000 0.0016
Probability
Equivalent LevelizedRevenue Requirement (ERR)
Utility’sFinancial
Model
Debt RatioEquity ReturnBorrowed Money RateTax Rate
Depreciation MethodBook Life
HistoricalData
Transformer ThermalModel
Transformer DataSize, Losses, Cost
New TransformerSizing Criteria
Cost of Transformer Cost of Losses
End-of-Life
Load
Ambient Temperature andLoad Profiles
Economic Data
Energy and Demand ChargeEscalation Rate
Estimated Remaining Life
Random Failure ModelThermal Data, Electrical Losses
Cost of Failure
Complete Method Block Diagram
26
![Page 27: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/27.jpg)
SIMULATION CASE STUDIES
AND RESULT
• Case #1 - New Design • Case #2 - Retrofit Applications
27
![Page 28: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/28.jpg)
• Buy new transformer for a new project
• Initial peak load = 20 MVA
• Load growth in first 4 years (Probability)
- High growth = 2.00%
- Moderate growth = 1.75%
- Low growth = 1.00%
• Load growth after the 4th year is 2.00%
Case #1: New Design Example Data
28
![Page 29: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/29.jpg)
Hot SpotTop Oil
Hot Spot and Top Oil Temperature
Year203020282026202420222020201820162014201220102008200620042002
Tem
pera
ture
(Deg
ree
C)
160
150
140
130
120
110
100
90
80
70
60
50
40
Case #1: Hot-Spot & Top-Oil Temperature Plots
29
![Page 30: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/30.jpg)
• Existing transformer rating = 18 MVA
• In service for 25 years
• Estimated remaining life = 0.25 pu.
• Initial peak load = 20 MVA
• Load growth in first 4 year (Probability) - High growth = 2.00% - Moderate growth = 1.75% - Low growth = 1.00%
• Load growth after 4th year is 2.00%
• Replace with new unit now or continue overload ..and replace later ?
Case #2: Retrofit Design Example Data
30
![Page 31: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/31.jpg)
• Graphic interface, Load, Save, Print, and Copy • Transient Loading Analysis (Daily load) • Life Cycle Study (with load growth from table) • Optimize Transformer Size
• Delay Replacement or Replace now Analysis
Windows Based Computer Program
31
![Page 32: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/32.jpg)
Screen Shot (1), Main Menu
32
![Page 33: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/33.jpg)
Screen Shot (2), Annex G Input
33
![Page 34: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/34.jpg)
Screen Shot (3), Load Profile Input
34
![Page 35: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/35.jpg)
Screen Shot (4), Load Growth Input
35
![Page 36: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/36.jpg)
Screen Shot (5), Temperatures Plot
36
![Page 37: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/37.jpg)
Screen Shot (6), Life Cycle Charts
37
![Page 38: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/38.jpg)
Screen Shot (8), Economic Data Input
38
![Page 39: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/39.jpg)
• Developed an Optimization Model for the
“Best Utilization” of a transformer: – Transformer replacement strategy (retrofit
design) – Optimum transformer sizing (new design)
• Computer program is written to facilitate long and complex calculations
• Windows based computer program
• Asset management tools
Conclusions
39
![Page 40: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/40.jpg)
• New programming is required for faster optimization computation
• The different depreciation method (economic
model) shall be explored
• Loss-of-life and hottest-spot calculation shall be updated when more real data is made available
• Other financial model shall be explored
• Sensitivity analysis on Loss Ratio (R)
Future Work
40
![Page 41: Transformer Overloading and Assessment of Loss-of-Life for](https://reader031.vdocuments.us/reader031/viewer/2022012503/617d0ce0940ee554e414b99d/html5/thumbnails/41.jpg)
Now publicly available on the PSERC Website
PSERC Project Report: Transformer Overloading and Assessment of Loss-of-Life
for Liquid-Filled Transformers
Project Leader: P.K. Sen Professor of Engineering Colorado School of Mines
Golden, CO 80401 [email protected], (303) 384-2020