Mitsubishi Programmable ControllersMELSEC-A/QnA Series Transition Guide
Aug. 2012 Edition
-
1 2
From the MELSEC-A/QnA SeriesThe MELSEC-Q Series
Network
P.4
P.7
P.11
P.13
P.15
Reuse existing 32-point I/O with Q SeriesQ Series large type base unit/Q Series large type I/O module
Upgrade A Series to Q Series while reusing existing wiringUpgrade tool
Reuse existing A Series I/O with Q SeriesQA extension base unitQA conversion adapter module
Convert existing A Series programsA/QnA Q conversion support tool
Related informationTechnical bulletinsReplacement handbooks
MELSOFT
Redundantsystem
NetworkP.19
P.22Replace Q4ARCPU redundant systems with Q SeriesQ Series redundant system
Q Series MELSECNET(), MELSECNET/B compatibilityAnS (small type) local station dedicated moduleMELSECNET()-MELSECNET/10 gateway setMELSECNET/10 network module (Production continues)
P.17Use modules that have a high rated input current and are compatible with proximity sensor inputs24 V DC input modules with a rated input current of 6 mA
P.17Avoid program changes when replacing I/O combined modules AH42 and A0J2(H)CPUI/O combined module with 64 occupied poitns
P.17Replace high-speed counter modules without restrains from specifications of the connected external devicesDedicated replacement high-speed counter modules
P.17Replace the positioning module while keeping the existing external devicesPositioning module
P.18Use existing MELSECNET/B twisted pair cables to construct MELSECNET/H network systemsMELSECNET/H network module (twisted bus type)
Mitsubishi Electric offers a carefully engineered combination of hardware, software, and support designed to allow you to upgrade legacy A and QnA Series controller systems to the current MELSEC-Q Series with minimum disruption to your plant operations.
-
1 2
From the MELSEC-A/QnA SeriesThe MELSEC-Q Series
Network
P.4
P.7
P.11
P.13
P.15
Reuse existing 32-point I/O with Q SeriesQ Series large type base unit/Q Series large type I/O module
Upgrade A Series to Q Series while reusing existing wiringUpgrade tool
Reuse existing A Series I/O with Q SeriesQA extension base unitQA conversion adapter module
Convert existing A Series programsA/QnA Q conversion support tool
Related informationTechnical bulletinsReplacement handbooks
MELSOFT
Redundantsystem
NetworkP.19
P.22Replace Q4ARCPU redundant systems with Q SeriesQ Series redundant system
Q Series MELSECNET(), MELSECNET/B compatibilityAnS (small type) local station dedicated moduleMELSECNET()-MELSECNET/10 gateway setMELSECNET/10 network module (Production continues)
P.17Use modules that have a high rated input current and are compatible with proximity sensor inputs24 V DC input modules with a rated input current of 6 mA
P.17Avoid program changes when replacing I/O combined modules AH42 and A0J2(H)CPUI/O combined module with 64 occupied poitns
P.17Replace high-speed counter modules without restrains from specifications of the connected external devicesDedicated replacement high-speed counter modules
P.17Replace the positioning module while keeping the existing external devicesPositioning module
P.18Use existing MELSECNET/B twisted pair cables to construct MELSECNET/H network systemsMELSECNET/H network module (twisted bus type)
Mitsubishi Electric offers a carefully engineered combination of hardware, software, and support designed to allow you to upgrade legacy A and QnA Series controller systems to the current MELSEC-Q Series with minimum disruption to your plant operations.
-
3 4
Large type A/QnA Series A/QnA (large type) CPU module I/O module
Special function module
Data link module (MELSECNET(), MELSECNET/B module, etc.)
PC interface boardMELSECNET(), MELSECNET(), MELSECNET/B MELSECNET/B interface board
A2C SeriesA2C CPU module A2C I/O module
Special function module etc.
A0J2(H) SeriesA0J2H CPU module Power supply module
I/O module
Special function module etc.
1 Production of AnS Series master/local station data link modules (A1SJ71AP21, A1SJ71AR21, and A1SJ71AT21B) will be continued.
Please check the Technical Bulletin "Repair acceptance of discontinued models (FA-A-0049)" for the repair acceptance period of the above discontinued products.
Small type AnS SeriesMELSECNET(), Remote I/O moduleMELSECNET/B1 MELSECNET/MINI-S3 AnS (small type) master module I/O module
Date of discontinuation Technical bulletin
End of Sep. 2006
End of Sep. 2008
End of Sep. 2008
T99-0050T99-0070
T99-0070
End of Sep. 2008 T99-0049
End of Sep. 2008 T99-0049
End of Sep. 2008
End of Sep. 2008
T99-0070
T99-0070
End of Sep. 2008
End of Sep. 2008
End of Sep. 2008
End of Sep. 2008
T99-0069
T99-0069
T99-0069
T99-0069
End of Sep. 2006
End of Sep. 2006
End of Sep. 2006
End of Sep. 2006
T99-0050
T99-0050
T99-0050
T99-0050
At-a-glance technical overviewsAt-a-glance technical overviews
Modification
CC-Link
Support
Support
P.27
P.25
P.28
P.34Support capabilitiesGlobal FA centers
Product listList of products used for upgradeModels in continuous production Discontinued productsService availability period
Replace MELSECNET/MINI-S3 with CC-LinkA2C shape CC-Link remote I/O moduleMELSECNET/MINI-S3 I/O module wiring conversion adapter
Replace A Series modules with AnS equivalentsA-A1S module conversion adapter
Technical Bulletins
P.23Replace A0J2(H) systems with Q SeriesA0J2 renewal tool
-
3 4
Large type A/QnA Series A/QnA (large type) CPU module I/O module
Special function module
Data link module (MELSECNET(), MELSECNET/B module, etc.)
PC interface boardMELSECNET(), MELSECNET(), MELSECNET/B MELSECNET/B interface board
A2C SeriesA2C CPU module A2C I/O module
Special function module etc.
A0J2(H) SeriesA0J2H CPU module Power supply module
I/O module
Special function module etc.
1 Production of AnS Series master/local station data link modules (A1SJ71AP21, A1SJ71AR21, and A1SJ71AT21B) will be continued.
Please check the Technical Bulletin "Repair acceptance of discontinued models (FA-A-0049)" for the repair acceptance period of the above discontinued products.
Small type AnS SeriesMELSECNET(), Remote I/O moduleMELSECNET/B1 MELSECNET/MINI-S3 AnS (small type) master module I/O module
Date of discontinuation Technical bulletin
End of Sep. 2006
End of Sep. 2008
End of Sep. 2008
T99-0050T99-0070
T99-0070
End of Sep. 2008 T99-0049
End of Sep. 2008 T99-0049
End of Sep. 2008
End of Sep. 2008
T99-0070
T99-0070
End of Sep. 2008
End of Sep. 2008
End of Sep. 2008
End of Sep. 2008
T99-0069
T99-0069
T99-0069
T99-0069
End of Sep. 2006
End of Sep. 2006
End of Sep. 2006
End of Sep. 2006
T99-0050
T99-0050
T99-0050
T99-0050
At-a-glance technical overviewsAt-a-glance technical overviews
Modification
CC-Link
Support
Support
P.27
P.25
P.28
P.34Support capabilitiesGlobal FA centers
Product listList of products used for upgradeModels in continuous production Discontinued productsService availability period
Replace MELSECNET/MINI-S3 with CC-LinkA2C shape CC-Link remote I/O moduleMELSECNET/MINI-S3 I/O module wiring conversion adapter
Replace A Series modules with AnS equivalentsA-A1S module conversion adapter
Technical Bulletins
P.23Replace A0J2(H) systems with Q SeriesA0J2 renewal tool
-
5 6
Fundamentals
Intelligent Function Modules
Network Modules
Communication Modules
Transition from MELSEC-A/QnA (Large Type) Series to Q Series HandbookL(NA)08043ENG
L(NA)08046ENG
L(NA)08048ENG
L(NA)08050ENG
Transition from MELSEC-A0J2H Series to Q Series HandbookL(NA)08060ENG
Transition from MELSECNET/MINI-S3, A2C (I/O) to CC-Link HandbookL(NA)08061ENG
Transition from MELSEC-I/OLINK to CC-Link/LT HandbookL(NA)08062ENG
MELSEC-A/QnA Series Transition ExamplesL(NA)08121ENG
Transition from MELSEC-A/QnA (Large Type) Series toAnS/Q2AS (Small Type) Series Handbook
L(NA)08064ENG
Transition of CPUs in MELSEC Redundant System HandbookTransition from Q4ARCPU to QnPRHCPU
L(NA)08117ENG
In-depth technical documentation resourcesIn-depth technical documentation resources
For the products shown in handbooks for transition, catalogues, and transition examples, refer to the manuals for the relevant products and check the detailed specifications, precautions for use, and restrictions before replacement.For the products manufactured by Mitsubishi Electric Engineering Co., Ltd., Mitsubishi Electric System & Service Co., Ltd., and other companies, refer to the catalogue for each product and check the detailed specifications, precautions for use, and restrictions before use.The manuals and catalogues for our products, products manufactured by Mitsubishi Electric Engineering Co., Ltd., and Mitsubishi Electric System & Service Co., Ltd., are shown in Appendix of each handbook for transtion.
Products shown in this handbook are subject to change without notice.
MEMO
-
5 6
Fundamentals
Intelligent Function Modules
Network Modules
Communication Modules
Transition from MELSEC-A/QnA (Large Type) Series to Q Series HandbookL(NA)08043ENG
L(NA)08046ENG
L(NA)08048ENG
L(NA)08050ENG
Transition from MELSEC-A0J2H Series to Q Series HandbookL(NA)08060ENG
Transition from MELSECNET/MINI-S3, A2C (I/O) to CC-Link HandbookL(NA)08061ENG
Transition from MELSEC-I/OLINK to CC-Link/LT HandbookL(NA)08062ENG
MELSEC-A/QnA Series Transition ExamplesL(NA)08121ENG
Transition from MELSEC-A/QnA (Large Type) Series toAnS/Q2AS (Small Type) Series Handbook
L(NA)08064ENG
Transition of CPUs in MELSEC Redundant System HandbookTransition from Q4ARCPU to QnPRHCPU
L(NA)08117ENG
In-depth technical documentation resourcesIn-depth technical documentation resources
For the products shown in handbooks for transition, catalogues, and transition examples, refer to the manuals for the relevant products and check the detailed specifications, precautions for use, and restrictions before replacement.For the products manufactured by Mitsubishi Electric Engineering Co., Ltd., Mitsubishi Electric System & Service Co., Ltd., and other companies, refer to the catalogue for each product and check the detailed specifications, precautions for use, and restrictions before use.The manuals and catalogues for our products, products manufactured by Mitsubishi Electric Engineering Co., Ltd., and Mitsubishi Electric System & Service Co., Ltd., are shown in Appendix of each handbook for transtion.
Products shown in this handbook are subject to change without notice.
MEMO
-
8Minimize program conversion eorts by using GX Developer'sPLC Type Change function and the Q Conversion Support Tool.
Automatic Program Conversion:GX Developer & Q Conversion Support Tool
The Q Conversion Support Tool boosts productivity by avoiding time spent consultingmanuals for guidance on nishing program conversions.
Image of dierences between the two programs
A/QnA program
Original project
Q program
Converted projectGX Developer
7
Convert A/QnA programs to Q programswith GX Developer's PLC Type Change function.
Change to Q beforehand
PLC type change
A/QnA Q conversion support tool
Dierences between the two programs
1Point
No need to manually compare the existing program with the converted program! 2
Point
A list of unconverted instructions and devices is displayed.
Information on recommended products for unconvertible special function modules is displayed.
HTML conversionguidance le
Dierences between the two programs andguidance on how to complete the
conversion are displayed.
Output
Dierencesbetween two programs
Enter the conguration information on the existing A/QnA special function modules.
Note 1: This support tool applies to ladder programs only.Note 2: Conversion from AnS/Q2AS(H) programs to Q programs is also supported.Note 3: The A/QnA Q Conversion Support Tool does not support Universal model (QnU) CPUs. To convert a CPU to a
Universal model QCPU, perform the following procedure./ Using GX Developer, change the PLC type of the original project to a PLC type which is supported by the A/QnA Q Conversion Support Tool. (Converted project 1)
0 Again using GX Developer, change the PLC type of the original project to Universal model QCPU. (Converted project 2)1 Open the original project and the converted project 1 in the A/QnA Q Conversion Support Tool.2 Reect the output result from step 3 to the converted project 2.
/ /
0
11
Can be modied directly. Prevents mistakes and improves eciency.
/Statement of unconverted devicesThe original device and the converted device are displayed as shown below. The devices contained in the circuit block are displayed one line at a time.(E.g.) #00001 ANI M9201 SM1255 ("#00001" is a search keyword in the HTML conversion guidance le.)
0Statement of unconverted instructions%The original instruction and the converted instruction are displayed as shown below. The instructions contained in the circuit block are displayed one line at a time.(E.g.) 00001 LRDP K3 D10 D100 K3 OUT SM1255 ("%00001" is a search keyword in the HTML conversion guidance le.)
1Statement of special function module processes!For the special function module instructions (FROM, DFRO, TO, DTO and instructions using X/Y devices), a message requesting review is displayed.(E.g.) !00001 Specal Function Module Process! Refer to ReviewInformation ("!00001" is a search keyword in the HTML conversion guidance le.)
Soon to be supported by Universal model QCPU (QnU)Soon to be supported by
Universal model QCPU (QnU)
-
8Minimize program conversion eorts by using GX Developer'sPLC Type Change function and the Q Conversion Support Tool.
Automatic Program Conversion:GX Developer & Q Conversion Support Tool
The Q Conversion Support Tool boosts productivity by avoiding time spent consultingmanuals for guidance on nishing program conversions.
Image of dierences between the two programs
A/QnA program
Original project
Q program
Converted projectGX Developer
7
Convert A/QnA programs to Q programswith GX Developer's PLC Type Change function.
Change to Q beforehand
PLC type change
A/QnA Q conversion support tool
Dierences between the two programs
1Point
No need to manually compare the existing program with the converted program! 2
Point
A list of unconverted instructions and devices is displayed.Information on recommended products for unconvertible special function modules is displayed.
HTML conversionguidance le
Dierences between the two programs andguidance on how to complete the
conversion are displayed.
Output
Dierencesbetween two programs
Enter the conguration information on the existing A/QnA special function modules.
Note 1: This support tool applies to ladder programs only.Note 2: Conversion from AnS/Q2AS(H) programs to Q programs is also supported.Note 3: The A/QnA Q Conversion Support Tool does not support Universal model (QnU) CPUs. To convert a CPU to a
Universal model QCPU, perform the following procedure./ Using GX Developer, change the PLC type of the original project to a PLC type which is supported by the A/QnA Q Conversion Support Tool. (Converted project 1)
0 Again using GX Developer, change the PLC type of the original project to Universal model QCPU. (Converted project 2)1 Open the original project and the converted project 1 in the A/QnA Q Conversion Support Tool.2 Reect the output result from step 3 to the converted project 2.
/ /
0
11
Can be modied directly. Prevents mistakes and improves eciency.
/Statement of unconverted devicesThe original device and the converted device are displayed as shown below. The devices contained in the circuit block are displayed one line at a time.
(E.g.) #00001 ANI M9201 SM1255 ("#00001" is a search keyword in the HTML conversion guidance le.)
0Statement of unconverted instructions%The original instruction and the converted instruction are displayed as shown below. The instructions contained in the circuit block are displayed one line at a time.
(E.g.) 00001 LRDP K3 D10 D100 K3 OUT SM1255 ("%00001" is a search keyword in the HTML conversion guidance le.)
1Statement of special function module processes!For the special function module instructions (FROM, DFRO, TO, DTO and instructions using X/Y devices), a message requesting review is displayed.
(E.g.) !00001 Specal Function Module Process! Refer to ReviewInformation ("!00001" is a search keyword in the HTML conversion guidance le.)
Soon to be supported by Universal model QCPU (QnU)Soon to be supported by
Universal model QCPU (QnU)
-
Automatic Program Conversion:GX Developer & Q Conversion Support Tool
(Example 1) Special function module processes which need to be reviewed
Click the recommended module namenext to "The recommended modulesthat can be replaced."
Click "By special function module name" in the"Programs for special function modules necessaryin review" row.
109
Detailed information is displayed hierarchically in your web browser. Information on the dierences between the two programs and the conversion guidance le are linked together.
HTML conversion guidance leEasy comparison of performance specications before and after replacement.
(Example 2) Special relays and registers which are not converted in the Q program
Click "Device no. order" in the "Special relay/special register not been converted in PLC type changing" row.
Details of unconverted special relays and registers can be displayed, improving conversioneciency.
-
Automatic Program Conversion:GX Developer & Q Conversion Support Tool
(Example 1) Special function module processes which need to be reviewed
Click the recommended module namenext to "The recommended modulesthat can be replaced."
Click "By special function module name" in the"Programs for special function modules necessaryin review" row.
109
Detailed information is displayed hierarchically in your web browser. Information on the dierences between the two programs and the conversion guidance le are linked together.
HTML conversion guidance leEasy comparison of performance specications before and after replacement.
(Example 2) Special relays and registers which are not converted in the Q program
Click "Device no. order" in the "Special relay/special register not been converted in PLC type changing" row.
Details of unconverted special relays and registers can be displayed, improving conversioneciency.
-
1211
Reduce conversion eort by using the same I/O addressingWhen reusing existing modules with a Q Series CPU, it is not required to change the I/O number of the existing modules. For new module(s) on the main base unit, assign a number after the existing modules in the I/O assignment settings. This can greatly reduce the program modication time.
Replacedmodules (A to Q)
QA6B or A6B(with QA conversion adapter module)
Q35B 0
0 1 2 3 4
1 2 3 4
5 6 7 8 9
Newly addedmodules
Note: Assign the I/O numbers in the following order: Q Series to A Series or A Series to Q Series. When the order is mixed (i.e., Q Series A Series Q Series), an error will occur in the CPU.
Example of I/O assignment
TypeModel
0
1
2
3
4
Intelli.
Intelli.
Input
Input
Output
AX41
AY41
AX41
QJ61BT11N
QJ71LP21-25
QX41
QX41
QY41P
100
120
140
160
180
5
6
7
8
9
32 points
32 points
32 points
32 points
32 points
00
20
40
60
80
Address TypeModel Point Address
Replace CPU to Q Series CPU while using existing A series modules.Use existing A Series modules when upgrading to QCPU.
QA1S65B/QA1S68B Extension Base Unit
For Large Type A/QnA Series
QA Extension Base Unit ( )
Remove the QA extension base unit (QA65B/QA68B) when all modules have been replaced with Q Series equivalents.
Existing large type A Series
Q Series
Q Seriesextension cable
Q Series
Entire replacementwith the Q Series
Existing large type A power supply,I/O modules, and other modules can beutilized; wiring is left as it is.
Step 2Step 1
Gradual transition from large type A Series to Q Series (Q mode).Construct a system that is controlled by the new Q Series CPU (Q mode) while keeping the existing large type A Series modules mounted to a QA6B extension base unit. The A Series modules can gradually be replaced to fully establish a Q Series system.
It is recommended to use QA6B extension base units to gradually upgrade from A Series system to Q Series system while using the assets of large type A series system. (The QA6B extension base units are compatible with High Performance Model QCPUs only. Basic Model QCPUs, Process CPUs, Redundant CPUs, Safety CPUs,Universal Model QCPUs, and Remote I/O Stations are not compatible.)Please refer to the "QA65B/QA68B Extension Base Unit User's Manual (IB(NA)-0800158)" for details of modules that can be mounted on the QA6B extension base units.
The small type AnS/Q2AS Series modules can also be used by connecting as a QCPU extension base.These extension base units can be used with QA65B and QA68B.
QA65BQA68B
Use existing A/QnA extension base units when upgrading to QCPU.
Mount a QA conversion adapter module to use existing A Series extension base units with a Q Series CPU.
The QA6ADP adapter cannot be connected to a QA1S extension base unit, which is used to mount small type AnS/Q2AS Series modules.The QA6ADP adapter is compatible with High Performance Model QCPUs only. Basic Model QCPUs, Process CPUs, Redundant CPUs, Safety CPUs, Universal Model QCPUs, and Remote I/O Stations are not compatible.
Modules which can be mounted on the extension base unit (A6B) are the same as when QA6B is used.An adapter module mounting bracket is required to mount the QA6ADP adapter. Follow the instructions in the user's manual when mounting.When an AC input module is mounted on the "A5B" extension base unit (without power supply) using the QA6ADP, either the "A6B with QA6ADP" or "QA6B" extension base unit (with power supply) is required in the system.
Notes
Replace the A Series CPUwith a Q Series CPU.
Replace the main baseunit (A3B) with the extensionbase unit (QA6B) andreuse existing modules.
Mount the QA conversionadapter module (QA6ADP) on theextension base unit (A6B).
Q Seriesextension cable
Q Seriesextension cable
Large type A Seriesextension cable
A3NCPU
AX41
AY41
Q06HCPU
QJ61BT11N
QJ71LP21-25
QX41
AX41
AY41
Empty
Empty
AX41
QX41
QY41P
AJ61BT11
AJ71LP21
AX41
Replace modules which cannot be mounted with Q Series modules.
QA Conversion Adapter Module (QA6ADP)
Mainbaseunit
Extensionbaseunit
32 points
32 points
32 points
32 points
32 points
Point
Input
Output
Empty
Empty
Input
QA6ADP
QA extension base(QA65B/QA68B)
-
1211
Reduce conversion eort by using the same I/O addressingWhen reusing existing modules with a Q Series CPU, it is not required to change the I/O number of the existing modules. For new module(s) on the main base unit, assign a number after the existing modules in the I/O assignment settings. This can greatly reduce the program modication time.
Replacedmodules (A to Q)
QA6B or A6B(with QA conversion adapter module)
Q35B 0
0 1 2 3 4
1 2 3 4
5 6 7 8 9
Newly addedmodules
Note: Assign the I/O numbers in the following order: Q Series to A Series or A Series to Q Series. When the order is mixed (i.e., Q Series A Series Q Series), an error will occur in the CPU.
Example of I/O assignment
TypeModel
0
1
2
3
4
Intelli.
Intelli.
Input
Input
Output
AX41
AY41
AX41
QJ61BT11N
QJ71LP21-25
QX41
QX41
QY41P
100
120
140
160
180
5
6
7
8
9
32 points
32 points
32 points
32 points
32 points
00
20
40
60
80
Address TypeModel Point Address
Replace CPU to Q Series CPU while using existing A series modules.Use existing A Series modules when upgrading to QCPU.
QA1S65B/QA1S68B Extension Base Unit
For Large Type A/QnA Series
QA Extension Base Unit ( )
Remove the QA extension base unit (QA65B/QA68B) when all modules have been replaced with Q Series equivalents.
Existing large type A Series
Q Series
Q Seriesextension cable
Q Series
Entire replacementwith the Q Series
Existing large type A power supply,I/O modules, and other modules can beutilized; wiring is left as it is.
Step 2Step 1
Gradual transition from large type A Series to Q Series (Q mode).Construct a system that is controlled by the new Q Series CPU (Q mode) while keeping the existing large type A Series modules mounted to a QA6B extension base unit. The A Series modules can gradually be replaced to fully establish a Q Series system.
It is recommended to use QA6B extension base units to gradually upgrade from A Series system to Q Series system while using the assets of large type A series system. (The QA6B extension base units are compatible with High Performance Model QCPUs only. Basic Model QCPUs, Process CPUs, Redundant CPUs, Safety CPUs,Universal Model QCPUs, and Remote I/O Stations are not compatible.)Please refer to the "QA65B/QA68B Extension Base Unit User's Manual (IB(NA)-0800158)" for details of modules that can be mounted on the QA6B extension base units.
The small type AnS/Q2AS Series modules can also be used by connecting as a QCPU extension base.These extension base units can be used with QA65B and QA68B.
QA65BQA68B
Use existing A/QnA extension base units when upgrading to QCPU.
Mount a QA conversion adapter module to use existing A Series extension base units with a Q Series CPU.
The QA6ADP adapter cannot be connected to a QA1S extension base unit, which is used to mount small type AnS/Q2AS Series modules.The QA6ADP adapter is compatible with High Performance Model QCPUs only. Basic Model QCPUs, Process CPUs, Redundant CPUs, Safety CPUs, Universal Model QCPUs, and Remote I/O Stations are not compatible.
Modules which can be mounted on the extension base unit (A6B) are the same as when QA6B is used.An adapter module mounting bracket is required to mount the QA6ADP adapter. Follow the instructions in the user's manual when mounting.When an AC input module is mounted on the "A5B" extension base unit (without power supply) using the QA6ADP, either the "A6B with QA6ADP" or "QA6B" extension base unit (with power supply) is required in the system.
Notes
Replace the A Series CPUwith a Q Series CPU.
Replace the main baseunit (A3B) with the extensionbase unit (QA6B) andreuse existing modules.
Mount the QA conversionadapter module (QA6ADP) on theextension base unit (A6B).
Q Seriesextension cable
Q Seriesextension cable
Large type A Seriesextension cable
A3NCPU
AX41
AY41
Q06HCPU
QJ61BT11N
QJ71LP21-25
QX41
AX41
AY41
Empty
Empty
AX41
QX41
QY41P
AJ61BT11
AJ71LP21
AX41
Replace modules which cannot be mounted with Q Series modules.
QA Conversion Adapter Module (QA6ADP)
Mainbaseunit
Extensionbaseunit
32 points
32 points
32 points
32 points
32 points
Point
Input
Output
Empty
Empty
Input
QA6ADP
QA extension base(QA65B/QA68B)
-
1413
Permits Q Series upgrade with existing 32-point I/O wiring.
Remove the wired terminal block from the existing I/O module.
Remove the wired terminal block from the existing I/O module.
Q Series large type blank cover (QG69L)(To mount a standard Q Series module on a large type base unit)
Q Series module
Q Series module
Mount Q Series standard power supply and CPU modules.
Mount directly.
Mount directly.
QX40
LA
FUSE
0
2
4
6
1
3
5
7
L8
A
C
E
9
B
D
F
L8
A
C
E
9
B
D
F
QY23LTRIACAC100
/240V
0.6A
LB
0
2
4
6
1
3
5
7
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
QY23L
A
0
2
4
6
1
3
5
7
COM
COM
COM
COM
8
A
C
E
9
B
D
F
8
A
C
E
9
B
D
F
QX11LAC100
V
10mA
B
0
2
4
6
1
3
5
7
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
QX11L
LA
0
2
4
6
1
3
5
7
L8
A
C
E
9
B
D
F
L8
A
C
E
9
B
D
F
+ -
QY13LRELAY
AC240V 2A
DC24V
2A
LB
0
2
4
6
1
3
5
7
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
QY13LQ12HC
PU
MODERUNERR.
USERBAT.
BOOT
PULL
USB
RS-232
Q62P
POWER
PULL
QX40
LA
FUSE
0
2
4
6
1
3
5
7
L8
A
C
E
9
B
D
F
L8
A
C
E
9
B
D
F
QY23LTRIACAC100
/240V
0.6A
LB
0
2
4
6
1
3
5
7
QY23L
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
Through the use of an upgrade tool (manufactured by Mitsubishi Electric Engineering Co., LTD., refer to page 15), terminal block modules that are not compatible with the Q Series large type I/O modules can be mounted without rewiring. For compatibility of Q Series large type base unit and upgrade tool, refer to page 16.
Notes
Q Series large type base unit(includes base adapter)
Q Series large typeI/O modules
Q Series large type I/O module
Upgrade tool (conversion adapter) manufactured by Mitsubishi Electric Engineering Co., Ltd.
Q38BLQ35BL
Q68BLQ65BLQ55BL
QX11LQX21L QG69L
QY11ALQY13LQY23LQY51PL
Q Series Large Type Base Unit,I/O Module ( )
Minimize wiring modications by reusing existing A Series 32-point I/O wiring.No need to make new mounting holes. The hole size and pitch of the Q Series large type base units are the same as those of large type A Series.
ModelProduct name
Main base unit
Q38BL
Extension base unit
Q68BL
8 slots, 1 power supply module required,Q Series large type I/O module mountable
Q35BL5 slots, 1 power supply module required, Q Series large type I/O module mountable
8 slots, 1 power supply module required, Q Series large type I/O module mountable
Q65BL5 slots, 1 power supply module required, Q Series large type I/O module mountable
Q55BL5 slots, power supply module not required,Q Series large type I/O module mountable
Q Series large type base unit optionsOutline
Model
Output module
Blank cover for mounting existing Q Series module on the Q Series large type base unit
QX11L
QY13L
QY23L
QG69L
AX11
Q Serieslarge typemodule
ExistingA Seriesmodule
AY13
AY23
N/A
32 points; 100 to 120 V AC; rated input current: 10 mA (100 V AC, 60 Hz);response time: 15 ms or less (OFF to ON), 25 ms or less (ON to OFF); 32 points/common; 38-point terminal block
QX21LAX2132 points; 200 to 240 V AC input; rated input current: 10 mA (220 V AC, 60 Hz); response time: 15 ms or less (OFF to ON), 25 ms or less (ON to OFF); 32 points/common; 38-point terminal block
QY11ALAY10AAY11A
QY51PLAY51AY51-S1
16-point contact output, 24 V DC/240 V AC, 2 A/point, 16 A/all points, all points independent common, 38-point terminal block, surge suppressor (varistor 387 to 473 V
32-point contact output, 24 V DC/240 V AC, 2 A/point, 5 A/common, 8 points/common, 38-point terminal block
32-point triac output, 100 to 240 V AC, 0.6 A/point, 2.4 A/common, 8 points/common, 38-point terminal block
32-point transistor output (Sink), 12/24 V DC, 0.5 A/point, 4 A/common, 16 points/common, 38-point terminal block
Q Series large type I/O module options
The Q Series large type base units and I/O modules are compatible with High Performance Model QCPUs, Universal Model QCPUs (except for Q00UJCPU), and MELSECNET/H Remote I/O Stations.The following CPUs and system are not compatible:Basic Model QCPUs, Process CPUs, Redundant CPUs, and Safety CPUsQ00UJCPU
Note
Product name
Input module
Large typeblank cover
Outline
Q Series power supply and CPU modules can be used without any modication (Q Series large type blank cover is not necessary).Q Series large type I/O modules can be used with Q Series modules. (Some modules, such as the ones that occupy two slots, cannot be mounted. For details, please refer to Q Series Large Type Base Unit User's Manual (IB-0800408).)
-
1413
Permits Q Series upgrade with existing 32-point I/O wiring.
Remove the wired terminal block from the existing I/O module.
Remove the wired terminal block from the existing I/O module.
Q Series large type blank cover (QG69L)(To mount a standard Q Series module on a large type base unit)
Q Series module
Q Series module
Mount Q Series standard power supply and CPU modules.
Mount directly.
Mount directly.
QX40
LA
FUSE
0
2
4
6
1
3
5
7
L8
A
C
E
9
B
D
F
L8
A
C
E
9
B
D
F
QY23LTRIACAC100
/240V
0.6A
LB
0
2
4
6
1
3
5
7
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
QY23L
A
0
2
4
6
1
3
5
7
COM
COM
COM
COM
8
A
C
E
9
B
D
F
8
A
C
E
9
B
D
F
QX11LAC100
V
10mA
B
0
2
4
6
1
3
5
7
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
QX11L
LA
0
2
4
6
1
3
5
7
L8
A
C
E
9
B
D
F
L8
A
C
E
9
B
D
F
+ -
QY13LRELAY
AC240V 2A
DC24V
2A
LB
0
2
4
6
1
3
5
7
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
QY13LQ12HC
PU
MODERUNERR.
USERBAT.
BOOT
PULL
USB
RS-232
Q62P
POWER
PULL
QX40
LA
FUSE
0
2
4
6
1
3
5
7
L8
A
C
E
9
B
D
F
L8
A
C
E
9
B
D
F
QY23LTRIACAC100
/240V
0.6A
LB
0
2
4
6
1
3
5
7
QY23L
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
Through the use of an upgrade tool (manufactured by Mitsubishi Electric Engineering Co., LTD., refer to page 15), terminal block modules that are not compatible with the Q Series large type I/O modules can be mounted without rewiring. For compatibility of Q Series large type base unit and upgrade tool, refer to page 16.
Notes
Q Series large type base unit(includes base adapter)
Q Series large typeI/O modules
Q Series large type I/O module
Upgrade tool (conversion adapter) manufactured by Mitsubishi Electric Engineering Co., Ltd.
Q38BLQ35BL
Q68BLQ65BLQ55BL
QX11LQX21L QG69L
QY11ALQY13LQY23LQY51PL
Q Series Large Type Base Unit,I/O Module ( )
Minimize wiring modications by reusing existing A Series 32-point I/O wiring.No need to make new mounting holes. The hole size and pitch of the Q Series large type base units are the same as those of large type A Series.
ModelProduct name
Main base unit
Q38BL
Extension base unit
Q68BL
8 slots, 1 power supply module required,Q Series large type I/O module mountable
Q35BL5 slots, 1 power supply module required, Q Series large type I/O module mountable
8 slots, 1 power supply module required, Q Series large type I/O module mountable
Q65BL5 slots, 1 power supply module required, Q Series large type I/O module mountable
Q55BL5 slots, power supply module not required,Q Series large type I/O module mountable
Q Series large type base unit optionsOutline
Model
Output module
Blank cover for mounting existing Q Series module on the Q Series large type base unit
QX11L
QY13L
QY23L
QG69L
AX11
Q Serieslarge typemodule
ExistingA Seriesmodule
AY13
AY23
N/A
32 points; 100 to 120 V AC; rated input current: 10 mA (100 V AC, 60 Hz);response time: 15 ms or less (OFF to ON), 25 ms or less (ON to OFF); 32 points/common; 38-point terminal block
QX21LAX2132 points; 200 to 240 V AC input; rated input current: 10 mA (220 V AC, 60 Hz); response time: 15 ms or less (OFF to ON), 25 ms or less (ON to OFF); 32 points/common; 38-point terminal block
QY11ALAY10AAY11A
QY51PLAY51AY51-S1
16-point contact output, 24 V DC/240 V AC, 2 A/point, 16 A/all points, all points independent common, 38-point terminal block, surge suppressor (varistor 387 to 473 V
32-point contact output, 24 V DC/240 V AC, 2 A/point, 5 A/common, 8 points/common, 38-point terminal block
32-point triac output, 100 to 240 V AC, 0.6 A/point, 2.4 A/common, 8 points/common, 38-point terminal block
32-point transistor output (Sink), 12/24 V DC, 0.5 A/point, 4 A/common, 16 points/common, 38-point terminal block
Q Series large type I/O module options
The Q Series large type base units and I/O modules are compatible with High Performance Model QCPUs, Universal Model QCPUs (except for Q00UJCPU), and MELSECNET/H Remote I/O Stations.The following CPUs and system are not compatible:Basic Model QCPUs, Process CPUs, Redundant CPUs, and Safety CPUsQ00UJCPU
Note
Product name
Input module
Large typeblank cover
Outline
Q Series power supply and CPU modules can be used without any modication (Q Series large type blank cover is not necessary).Q Series large type I/O modules can be used with Q Series modules. (Some modules, such as the ones that occupy two slots, cannot be mounted. For details, please refer to Q Series Large Type Base Unit User's Manual (IB-0800408).)
-
1615
Compatibility of Q Series large type base unit and base adapter/conversion adapter (upgrade tool manufactured by Mitsubishi Electric Engineering Co., Ltd.)
Compatibility of Q Series large type base unit and upgrade tool
Slot width of base unit*2
Power supply module
Same width as Q Series base unit(27.4mm)
Same width as the large type A Series base unit (37.5mm)
Item Base adapterConversion adapter(Upgrade tool)*1 Q Series large type base unit*1
Q Series standard power supply moduleBasic model QCPU
CPU moduleHigh Performance model QCPUProcess CPU*3Universal model QCPUQ Series large type I/O modules*4I/O module
Intelligent function module
*6Q Series module (occupies 1 slot)Q Series module (occupies 2 slots)
For terminal block type 16-point I/O module (occupies 1 slot) *6
For terminal block type 32-point I/O module (occupies 1 slot) *8*6
For terminal block type 32-point I/O module (occupies 2 slots) *9For high-speed counter module *8*6
For analog module (occupies 1 slot)
: Applicable (Mountable) : Applicable with restrictions (Mountable) : Not Applicable (Not mountable)
*8*6
For analog module (occupies 2 slots) *9Connection of QA/QA1S extension base unit*7
Conversion adapter
Mountable module
0 1 2 3 4 5 6 7 8
0123456789ABCDEF
37.5
0123456789ABCDEF
27.4
MELSEC-A Series module MELSEC-Q Series module
Q68ADV(I)
Conversion adapter
Existing A616AD terminal block
*1 Q Series large type base units can be used with Q Series standard base units. (The base adaptor manufactured by Mitsubishi Electric Engineering Co., Ltd. is applicable to Q Series standard base unit.)
*2 Check mounting conditions before using the upgrade tool, because wiring space is reduced due to a decrease in the module's width.
*3 Q00UJCPU is not compatible.*4 Number of common points and electrical specications are same as that of large type A Series I/O module.
*5 Since the adapters are mounted on Q Series modules, the specications and functions are same as that of the Q Series modules. (Please check the transition handbook, since the specications and functions are dierent from that of large type A Series module)
*6 Q Series large type blank cover (QG69L) is required.*7 Only High Performance Model QCPUs can be connected to the QA/QA1S extension base unit.
*8 If the size of wire connected to the terminal block is larger than 1.25mm2, ERNT-AQTX41, AQTY41, AQTX81, AQTY81, AQT68AD, AQT68ADN, AQT68DA, and AQTD61 modules may have a mounting diculty.In this case, secure wiring space by leaving empty slots in between modules. For example, mount modules on slot No. 0, 2, 4, 6, 8, and leave slot No. 1, 3, 5, 7 empty. If the number of slots is insucient, consider using the Q Series large type base unit.
*9 Can be used to replace an A616AD with two Q68ADV(I) modules and a conversion adapter. Doing so will allow the existing wired terminal blocks to be used.
0123456789ABCDEF
0123456789ABCDEF
0123456789ABCDEF
0123456789ABCDEF
0123456789ABCDEF
Replace A Series systems with Q Series withoutextensive I/O rewiring.
The upgrade tool consists of two parts: a conversion adapter that modies existing wiring of the large type A Series input/output/analog/high-speed counter modules to correspond to the Q Series modules; and a base adapter to mount Q Series base units and secure the bottom part of the conversion adapters.
Remove the large type A Series programmable controllers along with the base unit, install the base adapter in the same position, and mount Q Series modules. (New installation holes are unnecessary when mouting the base adaptor)
Attach the conversion adapters to the Q Series modules.
Remove the terminal blocks from the existing large type A Series modules and mount them on the conversion adapters. (The existing wiring can be used without modication.)
Utilize existing wiring of the I/O and other modules.
Upgrade tool(Base adapter)
Upgrade tool(Conversion adapter)
For detailed specications, precautions, and restrictions of the upgrade tool, please refer to the brochure (SAN C033E-04Z) and user's manual. For the upgrade tool, please contact your local Mitsubishi sales oce or representative.
Upgrade Tool
Upgrade tool features
*5
-
1615
Compatibility of Q Series large type base unit and base adapter/conversion adapter (upgrade tool manufactured by Mitsubishi Electric Engineering Co., Ltd.)
Compatibility of Q Series large type base unit and upgrade tool
Slot width of base unit*2
Power supply module
Same width as Q Series base unit(27.4mm)
Same width as the large type A Series base unit (37.5mm)
Item Base adapterConversion adapter(Upgrade tool)*1 Q Series large type base unit*1
Q Series standard power supply moduleBasic model QCPU
CPU moduleHigh Performance model QCPUProcess CPU*3Universal model QCPUQ Series large type I/O modules*4I/O module
Intelligent function module
*6Q Series module (occupies 1 slot)Q Series module (occupies 2 slots)
For terminal block type 16-point I/O module (occupies 1 slot) *6
For terminal block type 32-point I/O module (occupies 1 slot) *8*6
For terminal block type 32-point I/O module (occupies 2 slots) *9For high-speed counter module *8*6
For analog module (occupies 1 slot)
: Applicable (Mountable) : Applicable with restrictions (Mountable) : Not Applicable (Not mountable)
*8*6
For analog module (occupies 2 slots) *9Connection of QA/QA1S extension base unit*7
Conversion adapter
Mountable module
0 1 2 3 4 5 6 7 8
0123456789ABCDEF
37.5
0123456789ABCDEF
27.4
MELSEC-A Series module MELSEC-Q Series module
Q68ADV(I)
Conversion adapter
Existing A616AD terminal block
*1 Q Series large type base units can be used with Q Series standard base units. (The base adaptor manufactured by Mitsubishi Electric Engineering Co., Ltd. is applicable to Q Series standard base unit.)
*2 Check mounting conditions before using the upgrade tool, because wiring space is reduced due to a decrease in the module's width.
*3 Q00UJCPU is not compatible.*4 Number of common points and electrical specications are same as that of large type A Series I/O module.
*5 Since the adapters are mounted on Q Series modules, the specications and functions are same as that of the Q Series modules. (Please check the transition handbook, since the specications and functions are dierent from that of large type A Series module)
*6 Q Series large type blank cover (QG69L) is required.*7 Only High Performance Model QCPUs can be connected to the QA/QA1S extension base unit.
*8 If the size of wire connected to the terminal block is larger than 1.25mm2, ERNT-AQTX41, AQTY41, AQTX81, AQTY81, AQT68AD, AQT68ADN, AQT68DA, and AQTD61 modules may have a mounting diculty.In this case, secure wiring space by leaving empty slots in between modules. For example, mount modules on slot No. 0, 2, 4, 6, 8, and leave slot No. 1, 3, 5, 7 empty. If the number of slots is insucient, consider using the Q Series large type base unit.
*9 Can be used to replace an A616AD with two Q68ADV(I) modules and a conversion adapter. Doing so will allow the existing wired terminal blocks to be used.
0123456789ABCDEF
0123456789ABCDEF
0123456789ABCDEF
0123456789ABCDEF
0123456789ABCDEF
Replace A Series systems with Q Series withoutextensive I/O rewiring.
The upgrade tool consists of two parts: a conversion adapter that modies existing wiring of the large type A Series input/output/analog/high-speed counter modules to correspond to the Q Series modules; and a base adapter to mount Q Series base units and secure the bottom part of the conversion adapters.
Remove the large type A Series programmable controllers along with the base unit, install the base adapter in the same position, and mount Q Series modules. (New installation holes are unnecessary when mouting the base adaptor)
Attach the conversion adapters to the Q Series modules.
Remove the terminal blocks from the existing large type A Series modules and mount them on the conversion adapters. (The existing wiring can be used without modication.)
Utilize existing wiring of the I/O and other modules.
Upgrade tool(Base adapter)
Upgrade tool(Conversion adapter)
For detailed specications, precautions, and restrictions of the upgrade tool, please refer to the brochure (SAN C033E-04Z) and user's manual. For the upgrade tool, please contact your local Mitsubishi sales oce or representative.
Upgrade Tool
Upgrade tool features
*5
-
Modules for Easy Replacement
1817
High-speed counter modules(-, -)
A variety of modules are available to facilitate replacement.
These high-speed counter modules are used to replace the large type A Series high-speed countermodules (AD61 and AD61-S1) and have the same input ltering system and counting speed.Modules can be replaced without being restrained by the specications of existing pulse generators (e.g. an encoder).
DC input modules compatible with 6 mA rated input current (QX41-S2, QX81-S2)DC input modules compatible with 6 mA rated input current are available.When replacing large type A Series modules and utilizing the external devices as they are, the existing Q Series modules may not receive signals sent from external devices, such as proximity sensors, due to incompatibility with low-rated input current, and thus, external resistors need to be installed. With the QX41-S2 and QX81-S2 modules, which are compatible with 6 mA rated input current, external resistors are no longer required. (The existing external devices can be utilized when replacing modules.)
I/O combined module (QX41Y41P) * A module with sequential I/O numbersQX41Y41P's I/O assignment is same as that of large type A Series I/O combined module, AH42. This module can be used as the I/O module on the programmable controller side when using the A0J2 renewal tool (manufactured by Mitsubishi Electric System & Service Co., Ltd., refer to page 23) to replace the A0J2(H)CPUIt is not necessary to change the programs when replacing AH42 or A0J2(H)CPU. (Minimize the need to modify programs)
Input(X)
X00
X1F
00
1F32 points
Same I/O numbers are used for input and output
Y00
Y1F
Output(Y) Input(X)
Blank
X00
X1F
00
1F32 points
Sequential I/O numbers are used for input and output
(QH42P) (AH42, QX41Y41P)
Y20
Y3F
Output(Y)
Blank
20
3F32 points
Existing MELSECNET/B twisted pair cables are used to build the MELSECNET/H network system when replacing large type A Series modules (MELSECNET/B) with Q Series modules. Modules are replaced without modifying the previously laid network cables. A high-speed and large-volume network system can also be built using CC-Link cables.
MELSECNET/H network system can be built using twisted pair cables.
Utilize existing MELSECNET/B twisted pair cables
Item
32 stations (1 control station, 31 normal stations)Number of stations per network
Overall distance per network
1200 m 1200 m
600 m 900 m
400 m 600 m
200 m 400 m
200 m
(N/A) 150 m
156 k bps
312 k bps
625 k bps
1.25 M bps
2.5 M bps
5 M bps
10 M bps
Communicationspeed
100 m
Twisted pair cableCable type CC-Link Ver. 1.10 compatible cable
Twisted bus system specification
Item
32Number of input points
Rated input current
Q Series Large type A Series
Approx. 6 mA
(N/A)
24 V DC
12 V DC
QX41-S2
QX81-S2Positive common type
Negative common typeModel
Specification
Utilize the existing MELSECNET/B twisted pair cables to build MELSECNET/H network systems.
MELSECNET/H Network ModuleQJ71NT11B (twisted bus type)
32
Approx. 4 mA
(N/A)
QX41
QX81
32
Approx. 10 mA
Approx. 4 mA
AX41
AX81
64
Approx. 7 mA
Approx. 3 mA
AX42
AX82
Counting speed switch setting
AD61AD61-S1
QD62-H01QD62-H02
50 K PPS10 K PPS
A/QnA (Large Type) Series Models Q Series Replacement Models
Positioning module(QD73A1)The positioning module realizes servomotor control with a high-resolution encoder, and is compatible with a 1 Mppsmaximum input pulse (x10 conventional module). Replace the positioning module while maintaining existing external devices such as the servo ampliers.
Positioning mode
AD70 QD73A1Position control mode
Velocity/position control switchover mode
A/QnA (Large Type) Series Models Q Series Replacement Models
(Comparison of QX41-S2/QX81-S2 with large type A Series modules)
The pin arrangement is same as that of the existing A/Q Series connector type module.Use the conversion adapter manufactured by Mitsubishi Electric Engineering Co., Ltd. when replacing a large type A Series 32-point terminal block module.
Controlstation
Terminatingresistor
Normalstation
Normalstation
Normalstation
Normalstation
Normalstation
Terminatingresistor
New
-
Modules for Easy Replacement
1817
High-speed counter modules(-, -)
A variety of modules are available to facilitate replacement.
These high-speed counter modules are used to replace the large type A Series high-speed countermodules (AD61 and AD61-S1) and have the same input ltering system and counting speed.Modules can be replaced without being restrained by the specications of existing pulse generators (e.g. an encoder).
DC input modules compatible with 6 mA rated input current (QX41-S2, QX81-S2)DC input modules compatible with 6 mA rated input current are available.When replacing large type A Series modules and utilizing the external devices as they are, the existing Q Series modules may not receive signals sent from external devices, such as proximity sensors, due to incompatibility with low-rated input current, and thus, external resistors need to be installed. With the QX41-S2 and QX81-S2 modules, which are compatible with 6 mA rated input current, external resistors are no longer required. (The existing external devices can be utilized when replacing modules.)
I/O combined module (QX41Y41P) * A module with sequential I/O numbersQX41Y41P's I/O assignment is same as that of large type A Series I/O combined module, AH42. This module can be used as the I/O module on the programmable controller side when using the A0J2 renewal tool (manufactured by Mitsubishi Electric System & Service Co., Ltd., refer to page 23) to replace the A0J2(H)CPUIt is not necessary to change the programs when replacing AH42 or A0J2(H)CPU. (Minimize the need to modify programs)
Input(X)
X00
X1F
00
1F32 points
Same I/O numbers are used for input and output
Y00
Y1F
Output(Y) Input(X)
Blank
X00
X1F
00
1F32 points
Sequential I/O numbers are used for input and output
(QH42P) (AH42, QX41Y41P)
Y20
Y3F
Output(Y)
Blank
20
3F32 points
Existing MELSECNET/B twisted pair cables are used to build the MELSECNET/H network system when replacing large type A Series modules (MELSECNET/B) with Q Series modules. Modules are replaced without modifying the previously laid network cables. A high-speed and large-volume network system can also be built using CC-Link cables.
MELSECNET/H network system can be built using twisted pair cables.
Utilize existing MELSECNET/B twisted pair cables
Item
32 stations (1 control station, 31 normal stations)Number of stations per network
Overall distance per network
1200 m 1200 m
600 m 900 m
400 m 600 m
200 m 400 m
200 m
(N/A) 150 m
156 k bps
312 k bps
625 k bps
1.25 M bps
2.5 M bps
5 M bps
10 M bps
Communicationspeed
100 m
Twisted pair cableCable type CC-Link Ver. 1.10 compatible cable
Twisted bus system specification
Item
32Number of input points
Rated input current
Q Series Large type A Series
Approx. 6 mA
(N/A)
24 V DC
12 V DC
QX41-S2
QX81-S2Positive common type
Negative common typeModel
Specification
Utilize the existing MELSECNET/B twisted pair cables to build MELSECNET/H network systems.
MELSECNET/H Network ModuleQJ71NT11B (twisted bus type)
32
Approx. 4 mA
(N/A)
QX41
QX81
32
Approx. 10 mA
Approx. 4 mA
AX41
AX81
64
Approx. 7 mA
Approx. 3 mA
AX42
AX82
Counting speed switch setting
AD61AD61-S1
QD62-H01QD62-H02
50 K PPS10 K PPS
A/QnA (Large Type) Series Models Q Series Replacement Models
Positioning module(QD73A1)The positioning module realizes servomotor control with a high-resolution encoder, and is compatible with a 1 Mppsmaximum input pulse (x10 conventional module). Replace the positioning module while maintaining existing external devices such as the servo ampliers.
Positioning mode
AD70 QD73A1Position control mode
Velocity/position control switchover mode
A/QnA (Large Type) Series Models Q Series Replacement Models
(Comparison of QX41-S2/QX81-S2 with large type A Series modules)
The pin arrangement is same as that of the existing A/Q Series connector type module.Use the conversion adapter manufactured by Mitsubishi Electric Engineering Co., Ltd. when replacing a large type A Series 32-point terminal block module.
Controlstation
Terminatingresistor
Normalstation
Normalstation
Normalstation
Normalstation
Normalstation
Terminatingresistor
New
-
2019
MELSECNET(), MELSECNET/BLocal Station Data Link Module
Upgraded AnS local station data link modules permit a directQ Series connection to existing networks as local stations.
A1SJ71AP23QA1SJ71AR23QA1SJ71AT23BQ
Replace A Series MELSECNET(), MELSECNET/B stations with Q Series systems.The MELSECNET()/B local station data link modules allow a Q Series system to directly connect to existing NET()/NET/B data link system via a QA1S6B extension base unit.
MELSECNET ()
MELSECNET(), MELSECNET/BLocal station data link module
High performance model QCPU0123456789ABCDEF
0123456789ABCDEF
0123456789ABCDEF
0123456789ABCDEF
Master station
Local station
Example of a MELSECNET() conguration incorporating the Q Series
Local station
Model
A1SJ71AP23Q
A1SJ71AR23Q
A1SJ71AT23BQ
MELSECNET() local station data link module for SI optical ber cable
MELSECNET() local station data link module for coaxial cable
MELSECNET/B local station data link module for shielded twisted pair cable
Local station data link module optionsOutline
Specications
/Supported CPUsHigh Performance Model QCPUs [Q02(H), Q06H, Q12H, and Q25HCPU]0Compatible extension base unitsQA1S6B or QA6B with A-A1S module conversion adapter (A1ADP)1Number of modules per CPUSend point range can be further increased by mounting up to 6 modules per CPU.2Network parametersMinimal setup required, as network parameters settings are automatically detected by the module.3Link refresh settingLink refresh setting is not automatically detected. Hence, FROM/TO instructions within sequence program toenable send/receive cyclic data are required.
Sample programs for link refresh are provided in the "A/QnA Q Conversion Support Tool." The sample program can be used to create a QCPU program which may reduce development time.For details, please contact your local Mitsubishi sales oce or representative.
MELSECNET()-MELSECNET/10Gateway Set (Q6KT-NETGW-)
Use a Q2AS based MELSECNET()/10 gateway to gradually convert MELSECNET() stations to MELSECNET/10. MELSECNET/10 is backwards compatible with the Q Series via MELSECNET/H.
Before transition Transitional step Transition completed
Step-by-step replacement with the Q Series
Set model name
Q6KT-NETGW-SS
Q6KT-NETGW-RS
Q6KT-NETGW-RB
Q6KT-NETGW-TS
Q6KT-NETGW-TB
Q6KT-NETGW-
A1SJ71QLP21
A1SJ71QLP21
A1SJ71QBR11
A1SJ71QLP21
A1SJ71QBR11
A1SJ71AP21
A1SJ71AT21B
A1SJ71AR21A1S35B A1S61PN Q2ASCPU
Gateway set optionsMain part MELSECNET/10 partMELSECNET()/B part
Implement gradual migration from MELSECNET() to MELSECNET/10.
(Example) Partial replacement of MELSECNET(), from large type A Seriesprogrammable controllers to Q Series programmable controllers
MELSECNET()
Please check the cautions and restrictions for the gatewaystation network parameters etc. in the related manuals.
A1
A2 A5
A3 A4
A Series system Q Series systemAn Qn
A2
A3 Q4
Q5A1
MELSECNET()
MELSECNET/10
MELSECNET/H(10)
Q1
Q2 Q5
Q3 Q4Use a gateway toincorporate theQ Series systeminto the existingsystem.
Step-by-stepreplacement for theentire system conversionto the Q Series.
Readingthe modelname
/Network type MELSECNET SI optical ber cable (double loop) Coaxial cable (double loop) Twisted pair cable (bus)
/
0Network type MELSECNET/10 SI optical ber cable (double loop) Coaxial cable (bus)Gateway set 0
0123456789ABCDEF
0123456789ABCDEF
0123456789ABCDEF
MELSECNET/10
Gateway set Q Series
MELSECNET()
NET()Localstation
NET/10Controlstation
NET/10Normalstation
GatewayGateway
QA1S51BQA1S65BQA1S68B
Extension base unit with 1 slot (power supply module not required)
-
2019
MELSECNET(), MELSECNET/BLocal Station Data Link Module
Upgraded AnS local station data link modules permit a directQ Series connection to existing networks as local stations.
A1SJ71AP23QA1SJ71AR23QA1SJ71AT23BQ
Replace A Series MELSECNET(), MELSECNET/B stations with Q Series systems.The MELSECNET()/B local station data link modules allow a Q Series system to directly connect to existing NET()/NET/B data link system via a QA1S6B extension base unit.
MELSECNET ()
MELSECNET(), MELSECNET/BLocal station data link module
High performance model QCPU0123456789ABCDEF
0123456789ABCDEF
0123456789ABCDEF
0123456789ABCDEF
Master station
Local station
Example of a MELSECNET() conguration incorporating the Q Series
Local station
Model
A1SJ71AP23Q
A1SJ71AR23Q
A1SJ71AT23BQ
MELSECNET() local station data link module for SI optical ber cable
MELSECNET() local station data link module for coaxial cable
MELSECNET/B local station data link module for shielded twisted pair cable
Local station data link module optionsOutline
Specications
/Supported CPUsHigh Performance Model QCPUs [Q02(H), Q06H, Q12H, and Q25HCPU]0Compatible extension base unitsQA1S6B or QA6B with A-A1S module conversion adapter (A1ADP)1Number of modules per CPUSend point range can be further increased by mounting up to 6 modules per CPU.2Network parametersMinimal setup required, as network parameters settings are automatically detected by the module.3Link refresh settingLink refresh setting is not automatically detected. Hence, FROM/TO instructions within sequence program toenable send/receive cyclic data are required.
Sample programs for link refresh are provided in the "A/QnA Q Conversion Support Tool." The sample program can be used to create a QCPU program which may reduce development time.For details, please contact your local Mitsubishi sales oce or representative.
MELSECNET()-MELSECNET/10Gateway Set (Q6KT-NETGW-)
Use a Q2AS based MELSECNET()/10 gateway to gradually convert MELSECNET() stations to MELSECNET/10. MELSECNET/10 is backwards compatible with the Q Series via MELSECNET/H.
Before transition Transitional step Transition completed
Step-by-step replacement with the Q Series
Set model name
Q6KT-NETGW-SS
Q6KT-NETGW-RS
Q6KT-NETGW-RB
Q6KT-NETGW-TS
Q6KT-NETGW-TB
Q6KT-NETGW-
A1SJ71QLP21
A1SJ71QLP21
A1SJ71QBR11
A1SJ71QLP21
A1SJ71QBR11
A1SJ71AP21
A1SJ71AT21B
A1SJ71AR21A1S35B A1S61PN Q2ASCPU
Gateway set optionsMain part MELSECNET/10 partMELSECNET()/B part
Implement gradual migration from MELSECNET() to MELSECNET/10.
(Example) Partial replacement of MELSECNET(), from large type A Seriesprogrammable controllers to Q Series programmable controllers
MELSECNET()
Please check the cautions and restrictions for the gatewaystation network parameters etc. in the related manuals.
A1
A2 A5
A3 A4
A Series system Q Series systemAn Qn
A2
A3 Q4
Q5A1
MELSECNET()
MELSECNET/10
MELSECNET/H(10)
Q1
Q2 Q5
Q3 Q4Use a gateway toincorporate theQ Series systeminto the existingsystem.
Step-by-stepreplacement for theentire system conversionto the Q Series.
Readingthe modelname
/Network type MELSECNET SI optical ber cable (double loop) Coaxial cable (double loop) Twisted pair cable (bus)
/
0Network type MELSECNET/10 SI optical ber cable (double loop) Coaxial cable (bus)Gateway set 0
0123456789ABCDEF
0123456789ABCDEF
0123456789ABCDEF
MELSECNET/10
Gateway set Q Series
MELSECNET()
NET()Localstation
NET/10Controlstation
NET/10Normalstation
GatewayGateway
QA1S51BQA1S65BQA1S68B
Extension base unit with 1 slot (power supply module not required)
-
2221
Further network upgrade options are available because of the continued production of MELSECNET/10 modules. A complete MELSECNET() system can be replaced with MELSECNET/10 while reusing the existing cable installations. Following the network replacement, the A series stations can be replaced with Q series stations as needed in a step-by-step manner. However, the step-by-step transition is not possible if the network includes of a combination of A/QnA series and Q series stations, because the A/QnA series does not support MELSECNET/H twisted bus system.
Q Series Options with MELSECNET/10Network Modules
Complete replacement of MELSECNET() systems with MELSECNET/10 while reusing existing cable installations.
A Series system
Q Series system
An
Qn
MELSECNET
Before transition Transitional step 1(One or more AnU or QnACPU modulesare required as a control station.)
Transitional step 2
A1
A2 A5
A3 A4
MELSECNET/10
A1
A2 A5
A3 A4
MELSECNET/10
Q1
A2 A5
Q3 A4
Transition completed
MELSECNET/H(10)
Q1
Q2 Q5
Q3 Q4
Step-by-step transition from an A Series and Q Series combined system to a Q Series system.
Replace MELSECNET() data link modules at all stations with MELSECNET/10 network modules, and then switch the network system over to MELSECNET/10.
For stations that are to be changed from A Series systems to Q Series systems, replace the programmable controllers to the Q Series, and set them as MELSECNET/10 normal stations.By gradually transferring the A Series systems to the Q Series systems, you will be able to complete the transition to the Q Series system.
Change the MELSECNET() master station to the MELSECNET/10 control station.Note: For CPU modules (AnNCPU and AnACPU) that cannot be
set as the MELSECNET/10 control stations, please consider changing to the Q Series.
Set the MELSECNET() local stations to the MELSECNET/10 normal stations.
Network module options
Product name
Large type A/QnA SeriesMELSECNET/10 network module
Model
Control/normal station Remote I/O station
AJ71BR11AJ71LP21AJ71LP21GAJ71LR21AJ71QBR11AJ71QLP21AJ71QLP21GAJ71QLP21SAJ71QLR21
AJ72BR15AJ72LP25AJ72LP25GAJ72LR25AJ72QBR15AJ72QLP25AJ72QLP25GAJ72QLR25
Select the best-suited Q Series redundant systemconguration for the application.
Q Series Redundant System
Realizes local I/O system equivalent to Q4ARCPU using the redundant type extension base unit.
Up to 63 modules can be mounted using the redundant type extension base unit.Fast system switching time at (approx.) 50 ms in the redundant local I/O system, remarkable improvement compared to the Q4ARCPU redundant system (300 ms + 1 scan time).
Simple upgrades from legacy Q4AR installations to modern Q Series redundant systems.
A61RPA4UCPU
A61RPA4UCPU
Tracking cable
Remote I/O station Remote I/O station
MELSECNET/H remote I/O network
Tracking cable
Normal station Normal station
MELSECNET/H PLC to PLC network
Tracking cable
Main base unit
Redundant type extension base unit (for the rst extension base unit)
Redundant power extension base unit
Extension cable
Extension cable
Control systemRedundant CPU
Standby systemRedundant CPU
Redundant typeextension base unitQ65WRB
Q4ARCPU redundant systemConguration options
Local I/O system(with extension base unit)
MELSECNET/10PLC to PLC network
MELSECNET/10remote I/O network
Remote I/O network
Extension base unit
PLC to PLCnetwork
Control systemRedundant CPU
Standby systemRedundant CPU
Control systemRedundant CPU
Standby systemRedundant CPU
Network modules of MELSECNET/H PLC to PLC network and remote I/O network can be mounted on the Q Series redundant CPU main base. (They can be used together.)A wide variety of system is constructed to suit the needs of the control target.
-
2221
Further network upgrade options are available because of the continued production of MELSECNET/10 modules. A complete MELSECNET() system can be replaced with MELSECNET/10 while reusing the existing cable installations. Following the network replacement, the A series stations can be replaced with Q series stations as needed in a step-by-step manner. However, the step-by-step transition is not possible if the network includes of a combination of A/QnA series and Q series stations, because the A/QnA series does not support MELSECNET/H twisted bus system.
Q Series Options with MELSECNET/10Network Modules
Complete replacement of MELSECNET() systems with MELSECNET/10 while reusing existing cable installations.
A Series system
Q Series system
An
Qn
MELSECNET
Before transition Transitional step 1(One or more AnU or QnACPU modulesare required as a control station.)
Transitional step 2
A1
A2 A5
A3 A4
MELSECNET/10
A1
A2 A5
A3 A4
MELSECNET/10
Q1
A2 A5
Q3 A4
Transition completed
MELSECNET/H(10)
Q1
Q2 Q5
Q3 Q4
Step-by-step transition from an A Series and Q Series combined system to a Q Series system.
Replace MELSECNET() data link modules at all stations with MELSECNET/10 network modules, and then switch the network system over to MELSECNET/10.
For stations that are to be changed from A Series systems to Q Series systems, replace the programmable controllers to the Q Series, and set them as MELSECNET/10 normal stations.By gradually transferring the A Series systems to the Q Series systems, you will be able to complete the transition to the Q Series system.
Change the MELSECNET() master station to the MELSECNET/10 control station.Note: For CPU modules (AnNCPU and AnACPU) that cannot be
set as the MELSECNET/10 control stations, please consider changing to the Q Series.
Set the MELSECNET() local stations to the MELSECNET/10 normal stations.
Network module options
Product name
Large type A/QnA SeriesMELSECNET/10 network module
Model
Control/normal station Remote I/O station
AJ71BR11AJ71LP21AJ71LP21GAJ71LR21AJ71QBR11AJ71QLP21AJ71QLP21GAJ71QLP21SAJ71QLR21
AJ72BR15AJ72LP25AJ72LP25GAJ72LR25AJ72QBR15AJ72QLP25AJ72QLP25GAJ72QLR25
Select the best-suited Q Series redundant systemconguration for the application.
Q Series Redundant System
Realizes local I/O system equivalent to Q4ARCPU using the redundant type extension base unit.Up to 63 modules can be mounted using the redundant type extension base unit.Fast system switching time at (approx.) 50 ms in the redundant local I/O system, remarkable improvement compared to the Q4ARCPU redundant system (300 ms + 1 scan time).
Simple upgrades from legacy Q4AR installations to modern Q Series redundant systems.
A61RPA4UCPU
A61RPA4UCPU
Tracking cable
Remote I/O station Remote I/O station
MELSECNET/H remote I/O network
Tracking cable
Normal station Normal station
MELSECNET/H PLC to PLC network
Tracking cable
Main base unit
Redundant type extension base unit (for the rst extension base unit)
Redundant power extension base unit
Extension cable
Extension cable
Control systemRedundant CPU
Standby systemRedundant CPU
Redundant typeextension base unitQ65WRB
Q4ARCPU redundant systemConguration options
Local I/O system(with extension base unit)
MELSECNET/10PLC to PLC network
MELSECNET/10remote I/O network
Remote I/O network
Extension base unit
PLC to PLCnetwork
Control systemRedundant CPU
Standby systemRedundant CPU
Control systemRedundant CPU
Standby systemRedundant CPU
Network modules of MELSECNET/H PLC to PLC network and remote I/O network can be mounted on the Q Series redundant CPU main base. (They can be used together.)A wide variety of system is constructed to suit the needs of the control target.
-
2423
Before replacement
After replacement
Stackable typeSuitable when there is enoughdepth. Stack the programmablecontroller on the existing panelface.
Note: Depth of 236 mm ormore is required (whentwo interface modulesare stacked).
Flat mounting typeSuitable when there is enoughspace above existing modules.Mount the programmablecontroller above the interfacemodule(s).
Note: Space of 92 mm ormore from the top of theexisting modules isrequired.
Note: For the AnS Series,the standalone typeonly.
Standalone typeMount the programmablecontroller separately.
A0J2(H) Series I/O module
A0J2(H) CPU module
A0J2 renewal tool features
Replace A0J2(H) systems with Q Series using existing wiring.
The A0J2 renewal tool is used to replace the A0J2(H) systems with Q Series systems. It consists of an interface module to which the existing wired terminal block can be mounted, and a base adapter that can be installed using the existing installation holes.A variety of installation methods is available to t the installation space.
Interface module featuresThe interface module has DC to relay output conversion and AC to DC input conversion functions. Hence, replacement is possible together with Q Series connector type DC I/O modules. Dedicated cables are used to connect the interface module to Q Series I/O modules.
Structure
Basic conguration
(Example) 2-level stack, stackable type
Q Series programmable controller
Mounting plate To x programmable controllers: 3-slot and 5-slot
Mounting frame 2-level, for stackable type
Terminal block for 100/200 V AC relay
Base adapter for 56Large width base adaptor
Shape after assembly
indicates a part of the programmable controller xing frame set.
Before replacement
A0J2(H) Series programmable controller
CPU module
I/O module
After replacement
Q Series programmable controller
Main base unit(Q33B)Power supply module(Q62P)*1
CPU moduleI/O module
A0J2 renewal tool*3
Interface moduleProgrammable controller xing frame set*2
Programmable controller connection cable
*1: The interface modules except for some models require 24 V DC power supply. If the Q62P is not used, provide a separate external power supply.
*2: Includes a base adapter, mounting plate, mounting frame, terminal block, and power supply cable.*3: See the following list for the applicable interface module.
Interface modulefor 24/28
Interface modulefor 56
Compatible interface module list
For detailed specications, precautions, and restrictions of the A0J2 renewal tool, please refer to the brochure (X900904-165) and user's manual. For further information, For details of the A0J2 renewal tool, please contact your local Mitsubishi sales oce or representative.
1. When upgrading to the Q Series module, programs do not need to be modied if the I/O combined module "QX41Y41P (32-point input for the rst half and 32-point output for the second half)" is used. (Refer to page 17)
2. The A0J2 renewal tool can be used to replace MELSECNET/MINI compact type I/O modules (AJ35PTF- (such as 28AR and 56DR)) with CC-Link modules.
3. For products that are not described (such as connection cables for programmable controller), please contact your local Mitsubishi sales oce or representative
A0J2 Renewal Tool
Discontinued model Replacement interface module Discontinued model Replacement interface module
A0J2-E32A
A0J2-E32D
A0J2-E24R
A0J2-E24S
A0J2-E24T
A0J2-E28AR
A0J2-E28AS
A0J2-E28DR
SC-A0JQIF-32A
SC-A0JQIF-32D
SC-A0JQIF-24R
SC-A0JQIF-24S
SC-A0JQIF-24T
SC-A0JQIF-28AR
SC-A0JQIF-28AS
SC-A0JQIF-28DR
A0J2-E28DS
A0J2-E28DT
A0J2-E56AR
A0J2-E56AS
A0J2-E56DR
A0J2-E56DS
A0J2-E56DT
SC-A0JQIF-28DS
SC-A0JQIF-28DT
SC-A0JQIF-56AR
SC-A0JQIF-56AS
SC-A0JQIF-56DR
SC-A0JQIF-56DS
SC-A0JQIF-56DT
Input module
Output module
I/O module
I/O module
-
2423
Before replacement
After replacement
Stackable typeSuitable when there is enoughdepth. Stack the programmablecontroller on the existing panelface.
Note: Depth of 236 mm ormore is required (whentwo interface modulesare stacked).
Flat mounting typeSuitable when there is enoughspace above existing modules.Mount the programmablecontroller above the interfacemodule(s).
Note: Space of 92 mm ormore from the top of theexisting modules isrequired.
Note: For the AnS Series,the standalone typeonly.
Standalone typeMount the programmablecontroller separately.
A0J2(H) Series I/O module
A0J2(H) CPU module
A0J2 renewal tool features
Replace A0J2(H) systems with Q Series using existing wiring.
The A0J2 renewal tool is used to replace the A0J2(H) systems with Q Series systems. It consists of an interface module to which the existing wired terminal block can be mounted, and a base adapter that can be installed using the existing installation holes.A variety of installation methods is available to t the installation space.
Interface module featuresThe interface module has DC to relay output conversion and AC to DC input conversion functions. Hence, replacement is possible together with Q Series connector type DC I/O modules. Dedicated cables are used to connect the interface module to Q Series I/O modules.
Structure
Basic conguration
(Example) 2-level stack, stackable type
Q Series programmable controller
Mounting plate To x programmable controllers: 3-slot and 5-slot
Mounting frame 2-level, for stackable type
Terminal block for 100/200 V AC relay
Base adapter for 56Large width base adaptor
Shape after assembly
indicates a part of the programmable controller xing frame set.
Before replacement
A0J2(H) Series programmable controller
CPU module
I/O module
After replacement
Q Series programmable controller
Main base unit(Q33B)Power supply module(Q62P)*1
CPU moduleI/O module
A0J2 renewal tool*3
Interface moduleProgrammable controller xing frame set*2
Programmable controller connection cable
*1: The interface modules except for some models require 24 V DC power supply. If the Q62P is not used, provide a separate external power supply.
*2: Includes a base adapter, mounting plate, mounting frame, terminal block, and power supply cable.*3: See the following list for the applicable interface module.
Interface modulefor 24/28
Interface modulefor 56
Compatible interface module list
For detailed specications, precautions, and restrictions of the A0J2 renewal tool, please refer to the brochure (X900904-165) and user's manual. For further information, For details of the A0J2 renewal tool, please contact your local Mitsubishi sales oce or representative.
1. When upgrading to the Q Series module, programs do not need to be modied if the I/O combined module "QX41Y41P (32-point input for the rst half and 32-point output for the second half)" is used. (Refer to page 17)
2. The A0J2 renewal tool can be used to replace MELSECNET/MINI compact type I/O modules (AJ35PTF- (such as 28AR and 56DR)) with CC-Link modules.
3. For products that are not described (such as connection cables for programmable controller), please contact your local Mitsubishi sales oce or representative
A0J2 Renewal Tool
Discontinued model Replacement interface module Discontinued model Replacement interface module
A0J2-E32A
A0J2-E32D
A0J2-E24R
A0J2-E24S
A0J2-E24T
A0J2-E28AR
A0J2-E28AS
A0J2-E28DR
SC-A0JQIF-32A
SC-A0JQIF-32D
SC-A0JQIF-24R
SC-A0JQIF-24S
SC-A0JQIF-24T
SC-A0JQIF-28AR
SC-A0JQIF-28AS
SC-A0JQIF-28DR
A0J2-E28DS
A0J2-E28DT
A0J2-E56AR
A0J2-E56AS
A0J2-E56DR
A0J2-E56DS
A0J2-E56DT
SC-A0JQIF-28DS
SC-A0JQIF-28DT
SC-A0JQIF-56AR
SC-A0JQIF-56AS
SC-A0JQIF-56DR
SC-A0JQIF-56DS
SC-A0JQIF-56DT
Input module
Output module
I/O module
I/O module
-
2625
A2C Shape CC-Link Remote I/O Module
Replace A2CCPU and NET/MINI-S3 I/O modules withCC-Link using existing NET/MINI-S3 wiring.
MELSECNET/MINI-S3 I/O Module Wiring Conversion Adapter
Replace NET/MINI-S3 systems with CC-Link whilereusing existing NET/MINI-S3 wiring.
Wiring adapter terminal blocks eliminate the need to rewire.The simple replacement process helps minimize the upgrade time.The installation size is the same as that of A2C I/O modules; existing terminal block can be mounteddirectly. (Example) Replacing AJ35TB2-16D with AJ65BTB2-16D using a 34-pin conversion adapter
After replacingthe module,mount the wiredterminal block.*1
Remove the wiredterminal block fromthe existing I/Omodule.
AX41CAX81C
AX40Y50C
AX40Y10C
AY13C
AY51C
AJ65DBTB1-32D
AJ65DBTB1-32T1
AJ65DBTB1-32DT1
AJ65DBTB1-32R
AJ65DBTB1-32DR
Terminal block type, 24 V DC input, 32 points, sink/source
Terminal block type, 24 V DC input, 16 points; 0.5 A transistor output, 16 points, I/O composite module
Terminal block type, relay output, 32 points
Terminal block type, 24 V DC input, 16 points;relay output, 16 points, I/O composite module
Terminal block type, 0.5 A transistor output, 32 points, sink
Discontinued modelAlternative model
Model Outline
MELSECNET/MINI-S3 I/O module(AJ35TB2-16D)
Before replacement
*1 The communication cables and power cables need to be rewired.
Model list
After replacement
Replace with the CC-Link I/O module (AJ65BTB2-16D)
Remove the terminal block of theCC-Link I/O module, and then installthe conversion adapter.
Rewire the CC-Link cablesand power cables only.
No modication is necessary for I/O wiring since the existing terminal block of the MELSECNET/MINI-S3 I/O module can be used.
Wiringconversionadapter
Discontinued model
Alternative module Conversion adapter
Output module
AJ35TB1-16D AJ65BTB1-16DWiring conversion adapter for 26-point terminal block*1A6ADP-1MC16D
AJ35TB2-16D AJ65BTB2-16DWiring conversion adapter for 34-point terminal block*1A6ADP-2MC16D
AJ35TB1-16T
Product name Model
Alternative model
AJ65BTB1-16TWiring conversion adapter for 26-point terminal block*1, *2A6ADP-1MC16T
Model list
*1: The overall size is increased due to addition of the adapter to th