toxic units (tu) can be tu a or tu c

2
Toxic Units (TU) can be TU a or TU c u have measured the following concentrations in the water below a series of industrial dischargers. The T d as the concentration in the water divided by the LC50. zinc, 200 ug/L lead, 60 ug/L copper, 30 ug/l silver for zinc is 200 ug/L, lead 300 ug/L, copper 80 ug/L 0 ug/L. The TU a : Zn ; 200 ug/L Pb ; 60 ug/L Cu ; 30 ug/L Ag Zn 300 ug/L Pb 80 ug/L Cu 100 ug/L Ag or zinc is 0.5 or lead is 0.67 or copper is 0.75 or silver is 0.30 f the TU a is 2.3 if you assume that the toxicity of these met ly additive, and they are bioavailable you should see acute t f the regulator is to reduce the concentrations so the sum is

Upload: abdul-gaines

Post on 30-Dec-2015

26 views

Category:

Documents


1 download

DESCRIPTION

Toxic Units (TU) can be TU a or TU c. Assume you have measured the following concentrations of metals in the water below a series of industrial dischargers. The Tu a Is defined as the concentration in the water divided by the LC50. 100 ug/L zinc, 200 ug/L lead, 60 ug/L copper, 30 ug/l silver - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Toxic Units (TU) can be TU a  or TU c

Toxic Units (TU) can be TUa or TUc

Assume you have measured the following concentrationsof metals in the water below a series of industrial dischargers. The Tua

Is defined as the concentration in the water divided by the LC50.

100 ug/L zinc, 200 ug/L lead, 60 ug/L copper, 30 ug/l silver

The LC50 for zinc is 200 ug/L, lead 300 ug/L, copper 80 ug/Lsilver 100 ug/L. The TUa:

100 ug/L Zn ; 200 ug/L Pb ; 60 ug/L Cu ; 30 ug/L Ag200 ug/L Zn 300 ug/L Pb 80 ug/L Cu 100 ug/L Ag

The TUa for zinc is 0.5 The Tua for lead is 0.67The TUa for copper is 0.75The TUa for silver is 0.30 The sum of the TUa is 2.3 if you assume that the toxicity of these metalsis strictly additive, and they are bioavailable you should see acute toxicity. The job of the regulator is to reduce the concentrations so the sum is <1.

Page 2: Toxic Units (TU) can be TU a  or TU c

Current technical guidelines recommend that no discharge should exceed 0.3 TUa at the edge of an acute mixing zoneand 1.0 TUc at the edge of a chronic mixing zone.

When a WET test is performed by a discharger it is usuallyperformed on dilutions of 100% effluent. So at the end of thepipe before the effluent is mixed with the receiving water theregulator knows what the TUa is for that effluent 100/LC50 ofthe effluent. The regulator knows that the TUc is 100/NOEC.Therefore it is the regulators job to make sure that the dilutionIn the receiving system is sufficient to meet the 0.3 TUa and the 1.0 TUc. The regulator must also be concerned with the loading(WLA) from other dischargers and non-point source pollution so that the combined effects after mixing do not exceed the established limits. If the limits are exceeded the regulator has To along with the dischargers do a total maximum daily load or TMDL to reduce the TUs to appropriate levels with a MOS that allows for future uses.