topic 1 psychrometry addendum
TRANSCRIPT
-
7/25/2019 Topic 1 Psychrometry Addendum
1/6
Psychrometry (addendum)
Topic 1
-
7/25/2019 Topic 1 Psychrometry Addendum
2/6
Cooling tower
! A wet cooling tower is essentially a semi enclosed evaporative cooler.
-
7/25/2019 Topic 1 Psychrometry Addendum
3/6
Cooling tower
! Induced-draft counterflow wet
cooling tower.
! Makeup water must be added to the
cycle to replace the water lost byevaporation and air draft.
! To minimize water carried away by
the air, drift eliminators are installed
in the wet cooling towers above the
spray section.
-
7/25/2019 Topic 1 Psychrometry Addendum
4/6
Cooling tower
! Natural draft cooling tower
! The air in the tower has a high water-
vapor content, and thus it is lighter
than the outside air.
! Consequently, the light air in the
tower rises, and the heavier outside
air fills the vacant space, creating an
airflow from the bottom of the tower
to the top.
-
7/25/2019 Topic 1 Psychrometry Addendum
5/6
Example 10
Cooling water leaves the condenser of a power plant and enters a wet cooling
tower at 35C at a rate of 100 kg/s. Water is cooled to 22C in the cooling
tower by air that enters the tower at 1 atm, 20C, and 60 percent relative
humidity and leaves saturated at 30C. Neglecting the power input to the fan,
determine
(a) the volume flow rate of air into the cooling tower, and(b) the mass flow rate of the required makeup water.
-
7/25/2019 Topic 1 Psychrometry Addendum
6/6
Example 10 (solution)