to perform parallel operation and polarity test of two single phase transformer

4
 PRACTICAL NO: 4 AIM: To perform parallel operation and polarity test o f two single phase transformer. APPARATURS: Sr. No. Apparatus Range Quantity 1 Wattmeter 300V, 10A 01 2 Voltmeter 0-300 Volt 02 4 Ammeter 05 A 02 5 Ammeter 10 A 01 6 Lamp load 1phase 5KW,230V 01 THEORY: The two transformers to be connected in parallel should be connected in a manner that their  primary and secondary have the same polarities. This can be accomplished by conducting a  polarity test. PROCEDURE: 1. Polarity check: The two transformers to be connected in parallel should be connected in a manner that their  primary and secondary have the same polarities. This can be accomplished by conducting a  polarity test -for which the transfor mers should be connected as shown in Fig.:1 The test is conducted as follows: 1. Connect the circuit as shown in Fig.:1 2. Switch on the supply. 3.  Note the reading in the v oltmeter connected on th e secondar y side. It may be either zero or twice the secondary terminal voltage. 4. If the volt meter reads double the secondary voltage, then in the secondary opposite  polarities have been connected. Then the terminal S 1  should be connected to S' 2  and S' 1  should be connected to S 2 .

Upload: thomas-allen

Post on 07-Oct-2015

14 views

Category:

Documents


0 download

DESCRIPTION

perform parallel operation and polarity test of two single phase transformer

TRANSCRIPT

  • PRACTICAL NO: 4

    AIM: To perform parallel operation and polarity test of two single phase transformer.

    APPARATURS:

    Sr.

    No. Apparatus Range Quantity

    1 Wattmeter 300V, 10A 01

    2 Voltmeter 0-300 Volt 02

    4 Ammeter 05 A 02

    5 Ammeter 10 A 01

    6 Lamp load 1phase 5KW,230V 01

    THEORY:

    The two transformers to be connected in parallel should be connected in a manner that their

    primary and secondary have the same polarities. This can be accomplished by conducting a

    polarity test.

    PROCEDURE:

    1. Polarity check:

    The two transformers to be connected in parallel should be connected in a manner that their

    primary and secondary have the same polarities. This can be accomplished by conducting a

    polarity test -for which the transformers should be connected as shown in Fig.:1

    The test is conducted as follows:

    1. Connect the circuit as shown in Fig.:1

    2. Switch on the supply.

    3. Note the reading in the voltmeter connected on the secondary side. It may be either zero

    or twice the secondary terminal voltage.

    4. If the volt meter reads double the secondary voltage, then in the secondary opposite

    polarities have been connected. Then the terminal S1 should be connected to S'2 and S'1

    should be connected to S2.

  • CIRCUIT DIAGRAM:

    Fig.:-1

    Fig.:-2

  • 2. PARALLEL OPERATION OF TWO SINGLE PHASE TRANSFORMERS FOR

    EQUALVOLTAGE RATIO:

    1. Connect the circuit as per the circuit diagram shown in fig.:-2. Ensure that the two

    secondary have been connected properly as per polarity determined in part (1).

    2. With S2open, close the switch S1. If the voltage ratio of the two transformers is same no

    circulating current would be observed. But, if some circulating current is observed,

    means that the voltage ratio is not equal. Record the reading of this circulating current.

    3. Next, switch S2, on the secondary side should be closed.

    4. Change the position of load. For various positions of the load, note the readings of all the

    instruments connected.

    5. Switch off the load in steps. Open the switch S2 and then open the switch Sl.

    OBSERVATIONS:

    The observations made above should be recorded in a tabular form as shown below:

    Sr.

    No.

    VL

    Volt

    IL

    Ampere

    Measured Values Calculated Values

    I1 (Amp.) I2 (Amp.) I1 (Amp.) I2 (Amp.)

    1.

    2.

    3.

    4.

    5.

    CALCULATION:

    21

    1 2

    *lZ

    I IZ Z

    12

    1 2

    *lZ

    I IZ Z

    Here,

    Z1&Z2 are the secondary impedances of the two transformers.

  • Load shared by 1st transformer is

    21

    1 2

    *lZ

    S SZ Z

    Load shared by 2nd

    transformer is

    12

    1 2

    *lZ

    S SZ Z

    Where lS is load rating i.e 2l lS V I

    GRAPH:

    Plot the graph of IL versus I1 and I2.

    Conclusion: