tm dimming and switching system - lutron electronics, inc. lcp128 setup op.pdfr lcp128 tm setup and...
TRANSCRIPT
-
R Setup and Operation Manual
D i m m i n g a n dS w i t c h i n g
SS yy ss tt ee mm
LCP128TM
LCP128TM
-
R LCP128TM Setup and Operation Manual 3
Table of Contents
PageOverview ........................................................................................................................................................ 14STEP 1: Panel Configuration ......................................................................................................................... 15STEP 2: Time Clock Configuration................................................................................................................. 22STEP 3: Scene Modification .......................................................................................................................... 27STEP 4: Control Stations .............................................................................................................................. 29STEP 5: Time Clock Events .......................................................................................................................... 44STEP 6: Panel Contact Closure Inputs .......................................................................................................... 50STEP 7: Emergency Power Mode ................................................................................................................. 54
PageReferenced FunctionsOverrides ......................................................................................................................................... 57Locking and Unlocking the Controller .............................................................................................. 61
Troubleshooting GuideTroubleshooting Guide .................................................................................................................... 63
MaintenanceMaintenance .................................................................................................................................... 68
Glossary of TermsGlossary of Terms ........................................................................................................................... 69TablesPanel Tables .................................................................................................................................... 70Module Type Table .......................................................................................................................... 74Load Type Table .............................................................................................................................. 75Control Location Table ..................................................................................................................... 76Control Station Table ....................................................................................................................... 77Time Clock Event Table ................................................................................................................... 79
Warranty .......................................................................................................................................... 80Contact Information ......................................................................................................................... 80
Reference Information
Step-by-Step Programming Instructions
Believ
eitorno
t,thisissupposedtolooklikeadictionary!
Thisicon
wascreatedby
BrentM .Nye,July6,1995.
Believ
eitorno
t,thisissupposedtolooklikeadictionary!
Thisicon
wascreatedby
BrentM .Nye,July6,1995,
under
thedirec
tionofDerekR.Thomas.
Thisicon
wascreatedby
BrentM .Nye,July6,1995.
Believ
eitorno
t,thisissupposedtolooklikeadictionary!
Thisicon
wascreatedby
BrentM .Nye,July6,1995.
Believ
eitorno
t,thisissupposedtolooklikeadictionary!
Thisicon
wascreatedby
BrentM .Nye,July6,1995.
Believ
eitorno
t,thisissupposedtolooklikeadictionary!
Thisicon
wascreatedby
BrentM .Nye,July6,1995.
under
thedirec
tionofDerekR.Thomas.
Thisicon
wascreatedby
BrentM .Nye,July6,1995.
Believ
eitorno
t,thisissupposedtolooklikeadictionary!
Thisicon
wascreatedby
BrentM .Nye,July6,1995.
PageHow to Use this Guide .........................................................................................................................................4System Specifications ...........................................................................................................................................5System Start-Up Checklist.....................................................................................................................................7Controller Overview ...............................................................................................................................................9
Introduction and System Startup
-
R4 LCP128TM Setup and Operation Manual
Introduction
How to Use this GuideThis programming guide contains three main sections:
• Introduction - Includes system specifications, electrical contractor Start-Up Checklist, and an overview of thecontroller and how to use it.
• Step by Step Programming Instructions - Walks you through each step needed to program your system.
• Reference Information - Includes additional procedures that you may need to perform after the system isprogrammed, including how to override system settings and lock/unlock the controller. This section also includestroubleshooting tips, system maintenance, a glossary of terms, and system planning tables.
When programming the LCP128 system, you will need to know the following key information:
• How many panels are in this system and how many circuits are in each panel.
• How many modules are in the system and the module types.
• What the load schedule is.
• Where each wallstation and key switch is located and what each button or key turn should do.
• What each contact closure input and output should do.
• What the time clock should do.
Please read the guide completely before attempting to program the system.
Tables are provided at the back of this guide to record the above information. Photocopy the tables asneeded, and leave them for the occupant after they are completed.
Note: For mounting and wiring information, refer to the appropriate panel installation guide.
LT-1 LT-1
Control Link 2000 ft. (600 m) maximum
LCP128 Panels
Control Stations:Wallstations, key switches, contact closure devices, andRS232 devices
System Overview Diagram
-
R LCP128TM Setup and Operation Manual 5
Introduction
System SpecificationsLCP128 is a lighting control system designed for commercial buildings. It consists of up to 8 dimming panelsand up to 32 control stations. Control stations can be wallstations, key switches, contact closure input andoutput devices (OMX-AV), contact closure output devices (OMX-CCO-8), theatrical (ODMX-512) controlinterfaces, or building management system interfaces (OMX-RS232). All panels and control stations areconnected by a digital communications link. Refer to the appropriate panel installation guide for wiring details.Other system specifications are described below.
Time Clock
• 7 weekly schedules.• Up to 40 holiday schedules.• Each holiday schedule can be 1-90 days.• Up to 500 time clock events. • Maximum of 25 time clock events per day.• Up to 32 scenes and 1 Off scene.• With each time clock event or control station input, you can select which circuits turn on or off and, for dimming
circuits, set specific dimming levels.• Time clock events can occur at a fixed time of day or at a time relative to sunrise or sunset (astronomical).• Events can be placed on either a weekly schedule (for example, occurring every Monday) or a holiday schedule
(for example, occurring only on January 1).• Holiday schedules override weekly schedules.• Time clock events can start and end afterhours mode. Afterhours is an energy saving mode where lights that
are set to be off will automatically, after a period of time, turn themselves off. Afterhours mode can betemporarily overridden by any control station action. See STEP 5 for more information.
• Time clock events can enable and disable control stations.
Control Station - Wallstation
Wallstation buttons can be individually programmed to:
• Select a scene or custom scene. A scene is a combination of preset lighting levels used to automatically turnon, off, or dim a circuit or group of circuits. Each time the wallstation button is pressed, the circuits go to theprogrammed scene settings.
• Raise or lower circuits. Dimming circuits progressively raise or lower as long as the button is pressed. Circuitsstay at this setting until another event or control station input occurs.
• Toggle circuits on and off. Each press of the button alternates between turning the circuits on and off. If thecircuits are in a mixed state (some on and some off), the lights turn on.
• Turn off with a time delay. When the button is pressed, the circuits turn off after a preset amount of time.• Enable or disable time clock.
Control Station - Key Switch
• The key switch (NTOMX-KS) can be programmed for clockwise and counterclockwise turns and with the samefunctions as a wallstation button.
-
R6 LCP128TM Setup and Operation Manual
Introduction
Control Station - Contact Closure Inputs
Two contact closure inputs are available on each LCP128 controller – more are available by purchasing a LutronOMX-AV control station (five inputs per OMX-AV that can be added anywhere on the digital control station link).Also, an OMX-WCI can provide up to seven control inputs to the lighting control system.
• The contact closure inputs can be programmed on the open and/or closure of the contact to perform the samefunctions as a wallstation button.
• SeeTouchTM wallstations have two contact closure inputs (optional version of one input and one 24 V powerfor an occupant sensor).
Control Station - Contact Closure Outputs
Contact closure outputs can be added with either a Lutron OMX-AV control station (five outputs per OMX-AV) orwith a Lutron OMX-CCO-8 (eight outputs per OMX-CCO-8). Either control station can be added anywhere onthe digital control station link.
• Each contact closure may be momentary or maintained.• Each contact closure output can be assigned to an action that is programmed to a wallstation button, key turn,
contact closure input, time clock event, or emergency state.
Integration through RS232
The LCP128 system can be integrated with a building management system through the Lutron RS232 interface(OMX-RS232, OMX-CI-NWK-E, or OMX-CI-RS232).
DMX Theatrical Integration
The LCP128 system can take up to 32 DMX inputs from a theatrical lighting console/stageboard through theLutron ODMX-512 interface.
Emergency Power Mode
When a LCP128 panel is placed into emergency power mode (loss of normal power), circuits are changed toemergency settings and remain at those settings until the controller exits emergency power mode (return ofnormal power). All control station inputs and time clock events are ignored while in emergency power mode.
Emergency power mode can be activated using:
• Panel to panel emergency sense line. This method requires that the system have at least two panels. Thesystem must have at least one normal (non-essential) feed panel and at least one emergency (essential) feedpanel. When power to the normal panel is interrupted, the emergency panel(s) will go into emergency mode.Note that the normal / emergency switches at the bottom of the controllers need to be set correctly.
• The Lutron emergency lighting interface (LUT-ELI-3PH), a UL 924 listed device, senses the normal (non-essential) line voltage on all three phases (3PH) of normal power. When one or more phases of power are lost,the LUT-ELI-3PH sends a signal to the LCP128 controller. If the LCP128 controller’s normal / emergency switchis set to emergency, the emergency lighting scene or programmed circuit levels are activated.
For more information on emergency lighting applications, refer to Application Note #106, available atwww.lutron.com.
-
LCP128TM System Start-Up Checklist for Electrical ContractorImportant Note:To ensure that the LCP128 System is ready for Start-Up, please complete the following checklist.
The LCP128 panel(s) and control station(s) have been mounted in accordance with the installation instructions.
Control stations have been wired to the panel in accordance with installation instructions.
Feed and load wiring to panel have been installed in accordance with the installation instructions.
All load circuits have been activated in bypass mode (bypass jumpers installed) and are correctly andpermanently lamped.
Bypass jumpers have been removed and all circuits activated as default Non-Dim load type.
Load schedule for each panel has been completed.
Correct load type for each circuit has been determined and recorded.
When the above checklist is completed, please fax this sheet along with the completed load schedulefor each panel to Lutron Field Service Scheduling at (610) 282-0298.
Signature: ___________________________ Job Name: _________________________________________
Today’s Date: _________________________ Lutron Job Number: _________________________________
Printed Name: _______________________ Scheduled Startup Date: _____________________________
Phone Number: _______________________ Scheduled Startup Time: _____________________________
Fax Number: _________________________ Job Site Number: ___________________________________
Bill of Material (panels, control stations, etc.):
____________________________________ Qty. ___________
____________________________________ Qty. ___________
____________________________________ Qty. ___________
Lutron Electronics Co., Inc.7200 Suter RoadCoopersburg, PA 18036-1299Telephone: In the U.S., Canada, and the Caribbean: 1.800.523.9466In Mexico: 888.235.2910In Europe: +44.207.702.0657In Asia: +65.6220.4666In Japan: +81.355.758.411In all other countries: +1.610.282.6701(Listen to menu for scheduling)
System Start-Up Checklist
R LCP128TM Setup and Operation Manual 7
-
Notes
• Use a wire connector to attachone #18 AWG (1.0 mm2) wire forCommon (terminal 1) and one#18 AWG (1.0 mm2) wire for 24V (terminal 2) from the PELV(Class 2: USA) link to the control.Two #12 AWG (4.0 mm2) wirescannot both be terminated on thecontrol station. Maximum wirelength from link to control is 8 ft.(2.4 m).
• Only connect the Drain/Shieldwire (bare copper) to terminal ‘D’in LCP128 panels. Maintain theshield throughout the link but donot allow it to touch ground(earth) or wallstation circuitry.
1
2
3,4,D
1 2 3 4 D 5
CC
I1C
OM
CC
I2C
OM
1 2 3 4 D 5
1
2
3,4,D
5
CC
I1C
OM
CC
I2C
OM
To LCP128control stations
Control Power:(2) #12 AWG (2.5 mm2)1: Common2: 24 V
Control Data:(1) twisted shielded pair#22 AWG (.625 mm2)3: MUX4: MUXD: Drain/Shield
To additionalLCP128 panels
Emergency Sense(1) #18 AWG (1.0 mm2)5: Sense Line
4321
1 2 3 4 D 5
LCP128 Controller LCP128 Controller
Control stationterminal
Drain/Shieldwire
Panel to Panel and Panel to Control Stations
PELV (Class 2: USA) Wiring
R8 LCP128TM Setup and Operation Manual
-
R LCP128TM Setup and Operation Manual 9
LCP128TM
LCP128TM Controller Layout
Digital Control Station Linkand Emergency Sense Line
Connector
Panel Contact ClosureInputs Connector
Digital Link Receive (RX) LED
Digital Link Transmit (TX) LED
24 V Power Input Connector
Normal /Emergency Switch
Module Control Harness Connectors
Help ButtonHome Button
Navigation Arrows
Right Soft Labeled Button
LCD Screen
OK Button
Power OK LED
Controller Overview
Left Soft Labeled Button
-
R10 LCP128TM Setup and Operation Manual
Main MenuOverridesTime Clock SetupControl Station SetupPanel CCI SetupBack OK
Screen TitleScroll Bar
Left Soft Label ( )*
Right Soft Label ( )
Button Function
Navigate the screen and change highlighted values
Select an item
Left Soft-Labeled – Function defined on screen
Right Soft-Labeled – Function defined on screen
Go to the Home screen
On-Screen Help?
*OK
NavigationThe LCP128 controller uses certain methods for navigating, selecting, setting values, etc. Please read thissection carefully before using the controller to program your system.
The LCP128 controller has nine buttons below the display. The table below explains their functions.
The ScreenAll screens on the LCP128 controller have asimilar look with some common elements.These are:
• A screen title
• Left and right soft button labels
• A scroll bar (only present if more information isavailable than will fit on the screen.)
The example shows the Main Menu. The scrollbar indicates that there is more information in themenu than fits on the screen. Pressing repeatedly (or press and hold) scrolls through themenu and shows other choices. The shadedslider on the scroll bar indicates what portion ofthe menu is being displayed.
HelpHelp on the current screen is always available bypressing the button. If more information isavailable than fits on the screen, use and to scroll through the text. Pressing either , or returns you to the screen you were on.
*OK
?
HelpThe home screen shows thecurrent date and time. Press *to go to the Menus, press # to goto the Status screen.Back OK
Controller Overview(continued)
-
Main MenuOverridesTime Clock SetupControl Station SetupPanel CCI SetupBack OK
Getting to the Home ScreenPress from any screen to go back to the Homescreen.
Accessing the Main MenuFrom the Home screen, press to go to the MainMenu. If a password has been set, you need toenter it before continuing (see “Locking andUnlocking the Controller” in the reference sectionlater in this guide).
*
LCP128TMby Lutron
8:00 AMWednesday, Nov 3, 2004
Menu Status
Press to Activate the Menu*
Navigating the MenusWhen in a menu, use and to change thehighlighted item and press or (OK) to selectthat item. Pressing provides help on that item.To go back to the previous screen, press (Back). *
?
OK
Entering DataOne or more screens are used to program theinformation required for each system feature.
If only one screen is required, the screen has thesoft labeled buttons “Cancel” and “Done”.
If multiple screens are required, the first screen hasthe soft labeled buttons “Cancel” and “Next”.Intermediate screens have the soft labeled buttons“Previous” and “Next”, and the last screen has thesoft Labeled buttons “Previous” and “Done”. Note: Data is not stored in the LCP128 systemdatabase until “Done” is selected.
Afterhours Setup
Warn Time: min
Cancel Next
Afterhours Setup
Flash Count: 0
Previous Next
Afterhours Setup
Off Delay: min
Previous Done
01
05
15
R LCP128TM Setup and Operation Manual 11
Controller Overview(continued)
-
R12 LCP128TM Setup and Operation Manual
Getting Started - The HomeScreen
• When the controller is first powered or is not usedfor 20 minutes, the display shows the Homescreen. Pressing (the Home button) alwaystakes you back to this screen. From the Homescreen, pressing displays the Main Menu andpressing displays the Panel Status screen.
• The Home screen shows the current day, date andtime set on the controller. If either of these areincorrect, refer to STEP 2 to set the date, time, andlocation.
• The backlight on the LCD turns off after 25 minutesof no activity. Pressing any button on the controlturns the backlight on and displays the Homescreen.
*
Unlocking the ControllerIf the controller has been locked (see “Locking theController” in the referenced function section) youare prompted to enter the password before theMain Menu is activated. Press and to selectthe digit to change. Then press and tochange each digit. When you have entered thepassword, press .
If you forget the password, contact Lutron technicalsupport at (800) 523-9466 to unlock the controller.
OK
LCP128TMby Lutron
8:00 AMWednesday, Nov 3, 2004
Menu StatusPress to Activate the Menu*
Unlock Panel
Enter Password0 0 0 0
Cancel OK
0
Controller Overview(continued)
Language Select ScreenWhen the controller is first powered, you areprompted to choose a language for the screens.Use the navigation arrows to select a language,then press or (Done).OK
Choose LanguageEnglishFrancaisEspanolItaliano Svenskt
Done
DeutschNederlandsPortugues
-
R LCP128TM Setup and Operation Manual 13
The Panel Status ScreenPressing from the Home screen displays thePanel Status screen. The Panel Status screenshows:
• Your location.• Time clock status (Enabled/Disabled).• Control station status (Enabled/Disabled).• Today’s sunrise time for the current system date
(note that the time, date, and location must beconfigured correctly).
• Today’s sunset time for the current system date(note that the time, date, and location must beconfigured correctly).
• Memory used.• Build version.
Panel Status Philadelphia, PennsylvaniaToday’s Sunrise: 05:59AMToday’s Sunset: 6:07PM
Time Clock : EnabledBack Link Detail
The Wallstation Status ScreenPressing from the Panel Status screen displaysthe Wallstation Status screen. The WallstationStatus screen shows:
• If the station is present and is recognized, thecontrol is labeled by its type (for example,“seeTouch”).
• If a station is not present, it is labeled as “NoStation”. This could also indicate a control stationaddress conflict.
• If the unit is present and is not a control that isknown to the system, the control is labeled as“???”. This could also indicate a control stationaddress conflict.
Wall Station Status
A01 - No StationA02 - seeTouchA03 - Address 3
P08 - Panel 8
Back Levels
Controller Overview(continued)
The Circuit Levels ScreenPressing from the Wallstation Status screendisplays the Circuit Levels screen. The CircuitLevels screen shows the current circuit levels onthe system.
Circuit LevelsAll Circuits - - - -001 Dim - FLASH002 Dim - 100%003 Relay - O NBack OK
-
R14 LCP128TM Setup and Operation Manual
Step by Step Programming Instructions
OverviewProgramming your LCP128 system is done in seven steps.
1. Panel ConfigurationThis step selects a language for the controller LCD and configures the load setup. For multiple panel systems,this step also assigns panel addresses and configures the number of circuits in each panel.
2. Time, Date, and LocationRequired if the time clock will be used. This step shows how to set the clock.
3. Scene ModificationRequired if changes to the default scene settings are needed.
4. Control StationsRequired if there is a remote wallstation, key switch, contact closure device, and/or RS232 device. This step isperformed to configure their function.
5. Time Clock EventsRequired if the time clock will be used. This step is used to automatically dim or turn circuits on/off at either aspecific time of day or at a time relative to sunrise or sunset.
6. Panel Contact Closure InputsRequired if the panel contact closure inputs are used. This step defines what each input will do.
7. Emergency Power ModeRequired if emergency lighting is needed when normal power is lost. Control station inputs and time clockevents are ignored while in emergency power mode. This step defines if the panel has emergency circuits andhow to configure the emergency lighting.
The following pages explain how to perform each of the programming steps.
-
R LCP128TM Setup and Operation Manual 15
PanelAddress 1
12 Circuits
SystemCircuits
1-12
PanelAddress 2
24 Circuits
SystemCircuits13-36
PanelAddress 3
16 Circuits
SystemCircuits37-52
STEP 1
Panel ConfigurationTo program a LCP128 panel, you need to:
• Choose a language for the controller LCD.
• Set the panel configuration, including:
• Panel address
• First circuit number in the panel
• Number of circuits in the panel
Each circuit in the system is identified by a system circuit number. This number will be used to identify thecircuit for programming purposes. For example, if Panel 1 has 12 circuits, the first circuit in Panel 2 will becircuit 13 on the LCP128 controller. The figure below shows a sample system.
Note: If your system has only one panel, you do not need to set the panel configuration. The panel address,first system circuit number, and number of circuits are preprogrammed. However, for multi-panel systems,you must set the panel configuration from the master panel (address 1) and then from each remote panel.
• Configure the load setup, including:
• Module type setup
• System size
• Load type
• High end trim
• Low end trim
All system programming (covered in programming STEPS 2-7) is performed at panel address 1. In a multi-panel system, panel address 1 becomes the master programming panel and all other panels are remote panels.Remote panels have limited menu options and functionality.
Before proceeding with STEP 1, complete the Panel, Module Type, Load Type, and Control StationTables located at the back of this guide.
Master Panel:All systemprogrammingmust take placeat this panel
First circuit inthis panel
First circuit inthis panel
First circuit inthis panel
-
R16 LCP128TM Setup and Operation Manual
STEP 1 (continued)
Choose a LanguageA. From the Main Menu use and to highlight
Panel Setup and press or (OK).
B. Use and to highlight Choose Language andpress or (OK).
C. Use and to set the Language and press or(Done). The default is English.
OK
OK
OK
Panel Setup
Choose Language
Load SetupEmergency SetupAfterhours Setup
Back OK
B.
Main MenuControl Station SetupPanel CCI Setup
Panel SetupScene Setup
Back OK
A.
Choose Language
Cancel Done
C.
Set System SizeYou can set the system size so that controllerscreens display only the circuits used by yoursystem. The default system size is 128 circuits.
A. From the Main Menu use and to highlightPanel Setup and press or (OK).
B. Use and to highlight Load Setup and pressor (OK).
C. Use and to highlight System Size and pressor (OK).
D. Use and to set the total number of systemcircuits and press or (Done).OK
OK
OK
OK
System SizeHow many circuitsare in this system?
Cancel Done
52
D.
Load Setup
System SizeChicago SetupLow End Trim SetupHigh End Trim Setup
Back OK
C.
EnglishFrancaisEspanolItaliano Svenskt
DeutschNederlandsPortugues
-
R LCP128TM Setup and Operation Manual 17
STEP 1 (continued)
Set Panel Configuration -Multi-Panel Systems OnlyFor multi-panel systems, you must set the addressand number of circuits for each panel, beginningwith the master panel.
A. From the Main Menu at the master panelcontroller, use and to highlight Panel Setupand press or (OK).
B. Use and to highlight Panel Addressing andpress or (OK).
C. Use and to set the Panel Address and pressor (Next).
Master panel address = 01
D. Use and to set the first system circuit numberin the panel, and press or (Next).
E. Use and to set the number of circuits in thepanel and press or (Done) to update thedatabase.
F. Repeat this procedure at each remote panel to setthe panel address and number of circuits.Panel 2 address = 02
Panel 3 address = 03
Etc.
OK
OK
OK
OK
OK
Panel SetupPanel AddressingLoad SetupEmergency SetupAfterhours SetupBack OK
Panel Addressing
Panel Address:
Master Programming Panel
Cancel Next
01
B.
C.
Circuit Offset SetupWhat is the first
system circuit numberin this panel?
Previous Next
D.
001
Circuit Offset SetupHow many circuitsare in this panel?
Previous Done
E.
36
Main MenuControl Station SetupPanel CCI Setup
Panel SetupScene Setup
Back OK
A.
-
R18 LCP128TM Setup and Operation Manual
STEP 1 (continued)
Module Type SetupYour LCP128 system contains modules configuredwith one or more outputs (circuits). The moduletypes are set by the model numbers of the panelsin the system. Complete the Module Type Table atthe back of this guide and then program themodule types for your system. The factory defaultmodule type is X (4 Switches).
A. From the Main Menu use and to highlightPanel Setup and press or (OK).
B. Use and to highlight Load Setup and pressor (OK).
C. Use and to highlight Module Type Setup andpress or (OK).
D. The Module Type Setup screen lists all the circuits.To program a module, use and to select thefirst circuit number in the module and and toset the module type.Module type options include:
X: Four-Circuit Switching (Relay) Module (XP)
S: One-output (circuit) Dimming Module (1U)
D: Two-output (circuit) Dimming Module (2U)
Q: Four-output (circuit) Dimming Module (4U)
E: Four-output (circuit) Electronic Low VoltageDimming Module (4E)
A: Four-output (circuit) Adaptive Dimming Module(4A)
M: Four-output (circuit) Motor Module (4M)
F: Four-output (circuit) Quiet Fan Speed Module(4FSQ)
G: GP panel dimmer card (G4) - assigned in groupsof four
Notes:As you set each module type, the appropriatecircuit numbers are automatically assigned to themodule.
If you set the system size earlier in STEP 1, theModule Type Setup screen lists only the circuitsused in your system.
E. When all the module types are set press or (Done).
OK
OK
OK
OKLoad Setup
Module Type Setup
Chicago SetupLow End Trim Setup
System Size
Back OK
C.
Module Type Setup001-004 - G : 4 GP Cards005-008 - G : 4 GP Cards009-012 - Q : 4 dimmers
Cancel Done
D.
013-016 - X : 4 switches
Panel Setup
Load SetupPanel Addressing
Emergency SetupAfterhours SetupBack OK
B.
-
R LCP128TM Setup and Operation Manual 19
STEP 1 (continued)
Load Type SetupComplete the Load Type Table at the back of thisguide and then program the load types for yoursystem circuits. The factory default load type foreach circuit is Non-Dim.
Note: If you are unsure of the load type for aparticular circuit, set the load type to Non-Dimuntil the correct setting is determined.
A. From the Main Menu use and to highlightPanel Setup and press or (OK).
B. Use and to highlight Load Setup and pressor (OK).
C. Use and to highlight Load Type Setup andpress or (OK).
D. The Load Type Setup screen lists all the circuits.For each circuit, use and to select the circuitand and to select the load type.Load type options depend on the module typeassigned to the circuit:
Switching: Non-dim, Tridonic DSI, 0-10 V, DALI,PWM, 10-0 V, DALI LOG, DSI LOG
Dimming: Incandescent, MLV (Magnetic LowVoltage), Tu-Wire (ballasts), Neon, ELV (ElectronicLow Voltage), Non-dim, Tridonic DSI, DSI LOG, 0-10 V, 10-0 V, DALI, DALI LOG, PWM, FDB (spec-grade only), auto detect (4A only)
Motors: Motor
Fans: Fan
NNoottee:: Switching or dimming modules controllingTridonic DSI, DSI LOG, 0-10 V, 10-0 V, DALI, DALILOG, or PWM load types require TVM(s).
E. When all the load types are set press or (Done).Load Type setup is now complete and allsettings are saved in the event of a powerfailure.
OK
OK
OK
OK
Panel Setup
Load SetupPanel Addressing
Emergency SetupAfterhours SetupBack OK
B.
Load SetupLoad Type SetupHigh End Trim SetupLow End Trim SetupChicago SetupBack OK
C.
Load Type Setup001 Dim - Incandescent002 Dim - ELV003 Relay - Non-Dim
Cancel Done
D.
004 Dim - Tu-Wire
Caution! Failure to correctly assign load typesmay damage loads, especially certainelectronic transformers, electronic ballasts,and motors. Verify with the transformer orballast manufacturer that the product can bedimmed with phase control dimming beforesetting to any load type other than Non-Dim.
-
R20 LCP128TM Setup and Operation Manual
STEP 1 (continued)
High/Low End Trim SetupHigh and low end trim settings limit the maximumand minimum output of a dimming circuit. Levelsare set automatically when the load type isassigned. You should change the high or low endtrim for a circuit only if the default setting needs tobe adjusted.
A. From the Main Menu use and to highlightPanel Setup and press or (OK).
B. Use and to highlight Load Setup and pressor (OK).
C. Use and to highlight High End Trim Setup orLow End Trim Setup and press or (OK).
D. For each dimming circuit, use and to selectthe circuit and and to set the trim level. Non-dimming, motor, and fan circuits are set to NA (notany).
E. When all the trim levels are set press or (Done).
OK
OK
OK
OK
Load Setup
High End Trim SetupLoad Type Setup
Low End Trim SetupChicago SetupBack OK
C.
High End Trim Setup
001 Dim - 90%002 Dim - 95%003 Relay - N A
Cancel Done
D.
All Circuits -
Caution! Do not reduce the low end trim on afluorescent load type. This will decrease lamplife and may damage ballasts.
-
R LCP128TM Setup and Operation Manual 21
STEP 1 (continued)
Chicago SetupThis function is used to meet electrical installationcodes in the city of Chicago, IL (USA). This settinglimits how low a light level can be, including thelevels in the “off” scene. This setting can bechanged to a value from 10% to 60%, in 1%increments.
A. From the Main Menu use and to highlightPanel Setup and press or (OK).
B. Use and to highlight Load Setup and pressor (OK).
C. Use and to highlight Chicago Setup andpress or (OK).
D. Use and to select a circuit and and toset the Chicago limit. When all the circuit limits areset press or (Done).OK
OK
OK
OK
Load Setup
Chicago Setup
Load Type Setup
Low End Trim SetupHigh End Trim Setup
Back OK
C.
Chicago Setup
Cancel Done
D.
001 Dim - OFF002 Dim - 10%003 Relay - O N
All Circuits -
-
R22 LCP128TM Setup and Operation Manual
STEP 2
Time Clock ConfigurationThe LCP128 system can be programmed to initiate scenes and other actions automatically at either a specifictime of day or at a time relative to sunrise or sunset. It is important to configure the time clock as needed foryour location.
Time clock configuration includes:
• Selecting a time format (12 or 24 hour).
• Setting the time.
• Setting the date.
• Setting the location, either by country/city or longitude/latitude.
• Adjusting sunrise and sunset times to accommodate special circumstances.
• Selecting whether to use daylight savings time and, if so, what rules to use.
-
R LCP128TM Setup and Operation Manual 23
STEP 2 (continued)
Time FormatA. From the Main Menu use and to highlight
Time Clock Setup and press or (OK).
B. Use and to highlight Setup Clock and pressor (OK).
C. Use and to highlight Time Format and pressor (OK).
D. Use and to specify 24 Hr. or AM / PM(12 Hr). Press or (Done) to save changes.OK
OK
OK
OK
TimeA. From the Setup Clock menu use and to
highlight Time and press or (OK).
B. Use and to change the current time. Use and to alternate between hours and minutes.
C. Press or (Done) to save changes.OK
OK
DateA. From the Setup Clock menu use and to
highlight Date and press or (OK).
B. Use and to change the current date. Use and to change between month, day, and year.The first 2 digits are the month, the middle 2 arethe day, and the last 4 are the year.
C. Press or (Done) to save changes.OK
OK
Time
: 35 AMHH : MM
Cancel Done
Date
/ 16 / 2004MM / DD / YYYY
Cancel Done
06
11
Setup ClockDateLocationDaylight Savings TimeTime FormatBack OK
C.
B.
B.
Time Format
Specify by:
Cancel Done
24 Hr.
D.
-
R24 LCP128TM Setup and Operation Manual
STEP 2 (continued)
LocationNote: Location must be set if using time clockevents relative to sunrise or sunset.
A. From the Setup Clock menu use and tohighlight Location and press or (OK).
B. Use and to select whether you want to setthe location by country and city (recommended) orby latitude and longitude (if there are no nearbycities listed). Press or (OK) when done.OK
OK
Set Location MethodCountry, CityLatitude, Longitude
Back OK
B.
Set Time ZoneGMT -5:00 Eastern TimeGMT -4:00 Atlantic TimeGMT -3:30 NewfoundlandGMT -3:00 Brasilia Previous Next
Set CountryUSAAustriaBelgiumChinaCancel Next
Specify Latitude, Longitude
Latitude Longitude9 . 6 N 075 . 1 W
(DEGREES) (DEGREES)
Cancel Next
3
C.
C.
D.
If Setting by Country and City
C. Use and to select the Country then press or (Next).
In the USA, use and to select the State thenpress or (Next).
D. Use and to select the City then press or (Next).
OK
OK
OK
If Setting by Latitude and Longitude
C. Use and to select the digit and use and to set the latitude and longitude of your location indegrees and press or (Next).
D. Use and to select the time zone for thislocation and press or (Next). Values are listedas an offset from Greenwich Mean Time.
Example: If your location is 39 degrees 36 minutesnorth, enter 39.6N degrees. The minutes areconverted to a decimal of a degree by dividing by60.
OK
OK
-
R LCP128TM Setup and Operation Manual 25
STEP 2 (continued)
Location (continued)
Entering Custom Country and City
E. To enter a custom country name, use and toselect each letter, then press to advance andenter the next letter. Use to go back and changeany letter. Press or (Next) to continue.
F. To enter a custom city name, use and toselect each letter, then press to advance andenter the next letter. Use to go back and changeany letter. Press or (Next) to continue.
Adjusting Sunrise and Sunset
G. If needed, use this feature to shift your location’ssunrise and sunset times by a fixed amount. Thiscan be useful if there is a geographic feature (suchas a mountain) that offsets the sunrise or sunsettime for your location by a fixed amount. This canalso be used to shift all time clock events that arerelative to sunrise and sunset after they have beenprogrammed.If no offset is required, leave the offsets at 0:00(default). Press or (Done) to save changes.
Note: Do not use this function to compensate fordaylight savings time. For procedures on how toprogram daylight savings time settings, refer tothe next page.
OK
OK
OK
Enter Country
Custom Country Name
USABack Next
E.
Enter City
Custom City Name
Coopersburg Back Next
F.
Adjust Sunrise / Sunset
Sunrise Sunset+ 00 : 00 + 00 : 00
Previous Done
+
G.
-
R26 LCP128TM Setup and Operation Manual
STEP 2 (continued)
Daylight Savings TimeUse this feature to set whether or not your locationuses daylight savings time. If it does, you canconfigure when it starts and ends. When daylightsavings time is used, the time will changeautomatically.
A. From the Setup Clock menu use and tohighlight Daylight Saving Time and press or (OK).
B. Use and to set whether or not your locationuses daylight savings time, then press or (Next).
C. If your location follows the United States rules fordaylight savings time then select United States.Otherwise select Other. Press or (Done) tosave changes.
D. If you select Other, you are prompted to enter therules. The default rules are set based on yourlocation. You will need to know:• The start month, week, and day.
• The end month, week, and day.
• The number of minutes to adjust for daylightsavings time, up to 120 minutes.
OK
OK
OK
Daylight SavingsDoes this location
use daylight savings?Yes
Cancel Next
Daylight Savings
Current SettingUnited States
Previous Done
B.
C.
Setup Clock
DateLocation
Time
Daylight Saving TimeBack OK
A.
-
R LCP128TM Setup and Operation Manual 27
STEP 3
Scene ModificationScenes are stored lighting levels for each circuit in your system. Scenes can be used to create different lightingeffects using a programmed mix of dimming and switching settings.
The LCP128 system comes with 32 pre-configured scenes and 1 Off scene (see the table below for defaultscene settings). As you program your system, you can assign these scenes to time clock events. For example,at 6 PM each evening certain dimming circuit levels rise and additional circuits turn on. You can also assignscenes to control station inputs (wallstation buttons, key switches, and contact closures). This way, any time abutton is pressed, key is turned, or contact closure is made, the system activates the desired scene.
In STEP 3, you can modify the preconfigured scenes as needed to create your own specific lightingenvironments.
Note: In STEPS 4 and 5, you can also create additional custom scenes associated with a specific timeclockevent or control station input.
SceneDefault Settings
for Dimming CircuitsDefault Settings
for Switching Circuits
Off OFF OFF
1 100% ON
2 75% ON
3 50% ON
4 25% ON
5 to 32 100% ON
-
R28 LCP128TM Setup and Operation Manual
STEP 3 (continued)
Modify ScenesA. From the Main Menu use and to highlight
Scene Setup and press or (OK).
B. The Scene Modification screen lists thepreconfigured scenes stored in your system. Use and to choose the scene you want to modifyand press or (Next).Note: Modified scenes will reflect changes in realtime.
C. The system lists each circuit and its current settingfor this scene. Use and to select a circuit and
and to change the setting for that circuit. Tosimultaneously change all circuits, select AllCircuits and use and to change the setting.Note: The All Circuits function enables you tosimultaneously adjust the percentage for alldimming circuits or to turn all circuits off or on.
Scene circuit settings depend on the circuit type:
Switching: ON, OFF, --- (unaffected)
Dimming: OFF, 1 - 100%, --- (unaffected)
Motors: Open, Close, Stop, Jog Up, Jog Down,--- (unaffected)
Fans: Low, Medium, Medium-High, High,--- (unaffected)
Note: The --- (unaffected) setting means that thecircuit is not affected by this scene.
When you are finished modifying the scene press or (Next).
D. For dimming circuits affected by the scene, use and to set a fade time and press or (Next).
E. For a combination of dimming and switchingcircuits, use and to set whether switchesreact at Start of Fade or End of Fade. Then press
or (Done).OK
OK
OK
OK
OK
Scene ModificationOff SceneScene 01Scene 02Scene 03Cancel Next
B.
Scene 02All Circuits - 001 Dim - 50%002 Dim - 75%003 Relay - O NPrevious Next
C.
Scene 02 Fade Time
Fade Time: 20 sec
Previous Next
D.
Scene 02 SwitchesWhen do
switches react?Start of Fade
Previous Done
E.
-
R LCP128TM Setup and Operation Manual 29
STEP 4
Control StationsControl stations are connected to the LCP128 panel via the digital control link. Control stations can bewallstations (with various numbers of buttons), key switches (NTOMX-KS), contact closure input and outputdevices (OMX-AV, OMX-WCI), contact closure output devices (OMX-CCO-8), OMX-RS232 interfaces, ortheatrical controls (ODMX-512). Each control station must be assigned a unique address. Addressing may befound in either the appropriate panel installation guide or installation guides for the individual devices. To set theaddress, refer to the instructions for each device.
Every wallstation button, key switch, or contact closure input can be assigned one of the following functions:
• Scene - A scene consists of a specified light level and fade time. Each time the button, key switch, or contactclosure input is activated, the assigned circuits go to the programmed scene. A scene can also be used tocontrol contact closure outputs.
• Custom Scene - A custom scene is a scene assigned to and programmed for a specific button press, keyswitch turn, or contact closure input. A custom scene may be recalled only by that single action to which it isassigned.
• Lower Circuits - Assigned dimming circuits are progressively lowered as long as input is received from thecontrol station (for example, the button is held down, key is turned, contact closure is maintained). Circuits stayat this setting until another event or control station input occurs.
• Raise Circuits - Assigned dimming circuits are progressively raised as long as input is received from the controlstation (for example, the button is held down, key is turned, contact closure is maintained). Circuits stay at thissetting until another event or control station input occurs.
• Toggle - Each time the button, key switch, or contact closure input is activated, the assigned circuits togglebetween on and off. If the assigned circuits are in a mixed state (some on and some off), the circuits turn on.
• Delay To Off - Each time the button, key switch, or contact closure input is activated, the assigned circuit(s) turnoff after the preset amount of time (1 - 90 minutes).
• Enable Time Clock - Enable the function of the time clock.
• Disable Time Clock - Disable the function of the time clock.
Before proceeding with STEP 4, complete the Control Station Table at the back of this guide. Recordwhat each input (button, key switch, or contact closure) on each control station should do.
Note: In STEP 4, you will configure contact closure inputs wired to a Lutron OMX-AV control station.Contact closure inputs wired directly to a panel are configured later in STEP 6.
Factory SettingsWhen a control station type is not programmed in the system, the LCP128 uses an algorithm to intelligentlyguess the control station type, based on the button(s) pressed. Pressing the button(s) on a control station allowsthe LCP128 to identify it; some control stations can be identified with fewer or no button presses. Once theLCP128 has identified the control station, it assigns it the following defaults (note that these can bereprogrammed as desired):
• All button actions affect all circuits, and button presses select scenes• All raise/lower actions raise and lower all circuits (non-dim loads set to 0% or 100%)• Buttons labeled OFF are assigned to the OFF scene; if there is no labeled OFF button, the last button is
assigned to OFF• Button 1 is assigned to scene 1, button 2 is assigned to scene 2, and so on until the last (OFF) button• For single-button control stations, the button toggles all circuits on and off• Once any control station is programmed by the LCP128, the default settings are bypassed• If all control station addresses are set to NO STATION, the system reverts to the factory defaults
For button numbers on various control stations, see the section that follows.
-
R30 LCP128TM Setup and Operation Manual
STEP 4 (continued)
Control Station Button Map: Factory Presets
Off
Toggle
1: Scene 12: Off
1: Scene 12: Scene 23: Off
1: Scene 12: Scene 23: Scene 34: Off
SO-1BSO-1BO
1-button control
Toggle FOMX-1BFOMX-1B-SL
1-button control
SO-2BSO-2BO
2-button control
SO-3BSO-3BO
3-button control
SO-4BSO-4BO
4-button control
Off
1: Scene 12: Scene 23: Scene 34: Scene 4
5: Off
1: Scene 12: Scene 23: Scene 34: Scene 4
5: OffLower All Raise All
SO-4NRLSO-4NRLO
5-button control
SO-4SSO-4SIRSO-4SOSO-4SIRO
5-button withraise/lower
1: Scene 12: Scene 23: Scene 34: Scene 45: Off
1: Scene 12: Scene 23: Scene 34: Scene 45: Scene 56: Off
1: Scene 12: Scene 23: Scene 34: Scene 45: Scene 56: Scene 67: Off
SO-5BSO-5BO
5-button control
SO-6BSO-6BO
6-button control
SO-7BSO-7BO
7-button control
1: Scene 12: Off
Clockwise: Scene 1Counter-clockwise: Off
NTOMX-2B
2-button control
OMX-KS
Keyswitch
Button Number/Action Model Number(s)/Program as
Button Number/Action Model Number(s)/Program as
-
R
STEP 4 (continued)
Control Station Button Map: Factory Presets
1: Scene 12: Scene 23: Scene 34: Scene 45: OffUp: RaiseDown: Lower
1: Scene 12: Off
1: Scene 12: Scene 23: Scene 34: Off
1: Scene 12: Scene 23: Scene 34: OffLower All Raise All
NTOMX-4S-NRLNTOMX-4S-IR
5-button withraise/lower
EOMX-2B
2-button control
EOMX-4B
4-button control
EOMX-4SEOMX-4S-IR
5-button withraise/lower
1-4 5-8Scene 1 Scene 5Scene 2 Scene 6Scene 3 Scene 7Scene 4 Scene 8
9: OffLower All Raise All
1: Scene 1 7: Scene 62: Scene 2 8: Scene 73: Scene 3 9: Scene 84: Scene 4 10: Scene 95: Scene 5 11: Off6: Raise 12: Lower
EOMX-8SEOMX-8S-IR
9-button withraise/lower
NTOMX-KP10
10-button withraise/lower
1: Scene 12: Scene 23: Scene 34: Scene 45: Off
7: Raise 6: Lower
NTOMX-KP5
5-button withraise/lower
1: Scene 1 7: Scene 6 12: Scene 112: Scene 2 8: Scene 7 13: Scene 123: Scene 3 9: Scene 8 14: Scene 134: Scene 4 10: Scene 9 15: Scene 145: Scene 5 11: Scene 10 16: Off6: Raise All 17: Lower All
1: Scene 1 4: Scene 42: Scene 2 5: Scene 53: Scene 3 6: Off
1: Scene 1 4: Scene 4 7: Scene 72: Scene 2 5: Scene 5 8: Scene 83: Scene 3 6: Scene 6 9: Off
NTOMX-KP15
15-button withraise/lower
NTOMX-LB6NTOMX-LB6-RL
6-button control
NTOMX-LB9NTOMX-LB9-RL
9-button control
1: Scene 12: Off
OMX-2B-DW
2-button control
1: Scene 12: Scene 23: Scene 34: Scene 45: Off6: Raise All7: Lower All
OMX-7B-DW
5-button withraise/lower
1: Scene 12: Scene 23: Scene 34: Scene 45: OffUp: Raise AllDown: Lower All
OMX-4SLB-DW
5-button withraise/lower
Button Number/Action Model Number(s)/Program as
Button Number/Action Model Number(s)/Program as
LCP128TM Setup and Operation Manual 31
-
R32 LCP128TM Setup and Operation Manual
STEP 4 (continued)
Configure the WallstationsA. From the Main Menu use and to highlight
Control Station Setup and press or (OK).
B. Use and to choose the Address of thewallstation you would like to configure and press or (Next).
Note: The wallstation Address selected mustmatch the Address switch setting on thewallstation.
C. Use and to set the Type to Wall Station andpress or (Next).
D. Use and to select whether the station hasPermanent Raise and Lower Buttons and press
or (Next).
E. Use and to set the Number of buttons andpress or (Next).Note: Do not count raise/lower buttons.
F. Use and to select the Button you want toprogram and press or (Next).Note: To configure contact closure inputs (CCI),see page 35.
G. Use and to select the type of Action for thisbutton: Lower Circuits, Raise Circuits, Scene,Custom Scene, Enable Time Clock, DisableTime Clock, Delay to Off, Toggle, or No Actionand press or (Next). Refer to the following pages to program each typeof action.
OK
OK
OK
OK
OK
OK
OK
Control Station SetupAddress 01Address 02Address 03Address 04Cancel Next
Address 03 Setup
Number of Buttons:
Previous Next
03
Address 01 SetupButton 01Button 02Button 03CCI 1Previous Next
B.
E.
F.
Address 03 Button 01
Action:
Previous Next
Lower Circuits
G.
Address 03 Setup
Type:
Previous Next
Wall Station
C.
-
R LCP128TM Setup and Operation Manual 33
STEP 4 (continued)
Select CircuitsAll Circuits - - - -001 Dim - 10%002 Dim - 20%003 Relay - O NPrevious Next
Configure the Wallstations(continued)
If Selecting a Scene Action
H. In step G, if you selected Scene, use and toselect the scene and press or (Done).OK
H.
Select CCO AddressA01 CCO1 - Maintained OpenA01 CCO2 - ---A01 CCO3 - ---A01 CCO4 - ---Previous Done
I.
Select Scene
Scene: 02
Previous Done
H.
Custom Scene Fade Time
Fade Time: 20 sec
Previous Next
J.
If Selecting a Custom Scene Action
H. In step G, if you selected Custom Scene, theSelect Circuits screen lists all the circuits. Use and to select a circuit and and to changethe setting for that circuit. Or to simultaneouslychange all circuits, select All Circuits and use and to change the setting.Note: The All Circuits function enables you tosimultaneously adjust the percentage for alldimming circuits or to turn all circuits off or on.
Circuit settings depend on the circuit type:
Switching: ON, OFF, --- (unaffected)
Dimming: OFF, 1 - 100%, --- (unaffected)
Motors: Open, Close, Stop, Jog Up, Jog Down
Fans: Low, Medium, Medium-High, High
Note: The --- (unaffected) setting means thecircuit is not affected by this scene.
When the circuits are programmed for this customscene press or (Next).
I. The Select CCO Address screen is displayed only ifcontrol station devices with contact closure outputs(OMX-AV or OMX-CCO-8) have been entered intothe system.
Use and to select the output to be associatedwith the button being programmed. Use and to change the setting for that output: maintainedopen, maintained close, momentary pulse, or--- (unaffected). When the outputs areprogrammed for this custom scene, press or (Done).
J. For dimming circuits affected by the custom scene,use and to set the Fade Time and press or .
K. For a combination of dimming and switchingcircuits, use and to set when the switchesreact (Start of Fade or End of Fade). Then press
or .OK
OK
OK
OK
Custom Scene Fade TimeWhen do
switches react?Start of Fade
Previous Done
K.
Addressnumber
Contact closureoutput number
-
R34 LCP128TM Setup and Operation Manual
STEP 4 (continued)
Configure the Wallstations(continued)
If Selecting a Delay to Off Action
H. In step G, if you selected Delay to Off, use andto set the Time to Off and press or .
I. The Assign Circuits screen lists all the circuits.Unassigned circuit numbers have hash lines goingthrough them. Move the cursor to a circuit numberand press to toggle between Assigned andUnassigned (dashed). All circuits can be toggledby selecting ALL Circuits and pressing . Whenthe circuits are programmed press .
J. For dimming circuits affected by the action, use and to set the Fade Time and press or .
K. For a combination of dimming and switchingcircuits, use and to set when the switchesreact (Start of Fade or End of Fade). Then press
or .OK
OK
OK
OK
OK
Set Delay Time
Time to Off: 10 min
Previous Next
H.
Assign CircuitsPRESS OK TO SELECT CIRCUIT
A L L C i r c u i ts0 0 1 0 0 2 0 0 3 0 0 40 0 5 0 0 6 0 0 7 0 0 8
Previous Done
I.
If Selecting a Lower Circuits, RaiseCircuits, or Toggle Action
H. In step G, if you selected Lower Circuits, RaiseCircuits, or Toggle, the Assign Circuits screen listsall the circuits. Unassigned circuits are presented asnumbers with hash lines going through them.Move the cursor to a circuit number and press totoggle between Assigned and Unassigned(dashed). All circuits can be toggled by selectingALL Circuits and pressing . When the circuitsare programmed press .
I. For dimming circuits affected by the action, use and to set the Fade Time.
J. For a combination of dimming and switchingcircuits, use and to set when the switchesreact (Start of Fade or End of Fade). Then press
or .OK
OK
OK
Assign CircuitsPRESS OK TO SELECT CIRCUIT
A L L C i r c u i ts0 0 1 0 0 2 0 0 3 0 0 40 0 5 0 0 6 0 0 7 0 0 8
Previous Done
001
H.
001
-
R LCP128TM Setup and Operation Manual 35
STEP 4 (continued)
Configure Contact ClosureInputs for seeTouchWallstations
A. From the Main Menu use and to highlightControl Station Setup and press or (OK).
B. Use and to choose the Address of thewallstation you would like to configure and press or (Next).
Note: The wallstation Address selected mustmatch the Address switch setting on thewallstation.
C. Use and to set the Type to Wall Station andpress or (Next).
D. Use and to select whether the station hasPermanent Raise and Lower Buttons and press
or (Next).
E. Use and to set the Number of buttons andpress or (Next).Note: Do not count raise/lower buttons.
F. Use and to select the Contact Closure Input(CCI) you want to program and press or (Next).
G. Use and to select whether you want to definean action for when the contact Opens or Closesand press or (Next).
H. Use and to choose the type of Action for theCCI and press or (Done).OK
OK
OK
OK
OK
OK
OK
OK
Control Station Setup
Address 03Address 02Address 01
Address 04Previous Next
B.
Address 01 Setup
Type:
Previous Next
Wall Station
C.
Address 01Button 1Button 2CCI 1CCI 2Previous Next
F.
CCI 01 SetupOpen Action
Previous Next
Closure Action
G.
Address 01 CCI 01
Action:
Previous Done
Scene
H.
-
R36 LCP128TM Setup and Operation Manual
STEP 4 (continued)
Configure the OMX-CIRA. From the Main Menu use and to highlight
Control Station Setup and press or (OK).
B. Use and to choose the Address of thewallstation you would like to configure and press or (Next).
Note: The wallstation Address selected mustmatch the Address switch setting on the OMX-CIR.
C. Use and to set the Type to Wall Station andpress or (Next).
D. Use and to select the Button you want toprogram and press or (Next).
E. Use and to select the type of Action for thisbutton: Lower Circuits, Raise Circuits, Scene,Custom Scene, Enable Time Clock, DisableTime Clock, Delay to Off, Toggle, or No Actionand press or (Next). Refer to the following pages to program each typeof action.
OK
OK
OK
OK
OK
Control Station SetupAddress 01Address 02Address 03Address 04Cancel Next
Address 01 SetupLower ButtonRaise ButtonButton 01Button 02Previous Next
B.
D.
Address 03 Button 01
Action:
Previous Next
Toggle
E.
Address 03 Setup
Type:
Previous Next
OMX-CIR
C.
-
R LCP128TM Setup and Operation Manual 37
STEP 4 (continued)
Select CircuitsAll Circuits - - - -001 Dim - 10%002 Dim - 20%003 Relay - O NPrevious Next
Configure the OMX-CIR(continued)
If Selecting a Scene Action
F. In step E, if you selected Scene, use and toselect the scene and press or (Done).OK
F.
Select CCO AddressA01 CCO1 - Maintained OpenA01 CCO2 - ---A01 CCO3 - ---A01 CCO4 - ---Previous Done
G.
Select Scene
Scene: 02
Previous Done
F.
Custom Scene Fade Time
Fade Time: 20 sec
Previous Next
H.
If Selecting a Custom Scene Action
F. In step E, if you selected Custom Scene, theSelect Circuits screen lists all the circuits. Use and to select a circuit and and to changethe setting for that circuit. Or to simultaneouslychange all circuits, select All Circuits and use and to change the setting.Note: The All Circuits function enables you tosimultaneously adjust the percentage for alldimming circuits or to turn all circuits off or on.
Circuit settings depend on the circuit type:
Switching: ON, OFF, --- (unaffected)
Dimming: OFF, 1 - 100%, --- (unaffected)
Motors: Open, Close, Stop, Jog Up, Jog Down
Fans: Low, Medium, Medium-High, High
Note: The --- (unaffected) setting means thecircuit is not affected by this scene.
When the circuits are programmed for this customscene press or (Next).
G. The Select CCO Address screen is displayed only ifcontrol station devices with contact closure outputs(OMX-AV or OMX-CCO-8) have been entered intothe system.
Use and to select the output to be associatedwith the button being programmed. Use and to change the setting for that output: maintainedopen, maintained close, momentary pulse, or--- (unaffected). When the outputs areprogrammed for this custom scene, press or (Done).
H. For dimming circuits affected by the custom scene,use and to set the Fade Time and press or .
I. For a combination of dimming and switchingcircuits, use and to set when the switchesreact (Start of Fade or End of Fade). Then press
or .OK
OK
OK
OK
Custom Scene Fade TimeWhen do
switches react?Start of Fade
Previous Done
I.
Addressnumber
Contact closureoutput number
-
R38 LCP128TM Setup and Operation Manual
STEP 4 (continued)
Configure the OMX-CIR(continued)
If Selecting a Delay to Off Action
F. In step E, if you selected Delay to Off, use andto set the Time to Off and press or .
G. The Assign Circuits screen lists all the circuits.Unassigned circuit numbers have hash lines goingthrough them. Move the cursor to a circuit numberand press to toggle between Assigned andUnassigned (dashed). All circuits can be toggledby selecting ALL Circuits and pressing . Whenthe circuits are programmed press .
H. For dimming circuits affected by the action, use and to set the Fade Time and press or .
I. For a combination of dimming and switchingcircuits, use and to set when the switchesreact (Start of Fade or End of Fade). Then press
or .OK
OK
OK
OK
OK
Set Delay Time
Time to Off: 10 min
Previous Next
F.
Assign CircuitsPRESS OK TO SELECT CIRCUIT
A L L C i r c u i ts0 0 1 0 0 2 0 0 3 0 0 40 0 5 0 0 6 0 0 7 0 0 8
Previous Done
G.
If Selecting a Lower Circuits, RaiseCircuits, or Toggle Action
F. In step E, if you selected Lower Circuits, RaiseCircuits, or Toggle, the Assign Circuits screen listsall the circuits. Unassigned circuits are presented asnumbers with hash lines going through them.Move the cursor to a circuit number and press totoggle between Assigned and Unassigned(dashed). All circuits can be toggled by selectingALL Circuits and pressing . When the circuitsare programmed press .
G. For dimming circuits affected by the action, use and to set the Fade Time.
H. For a combination of dimming and switchingcircuits, use and to set when the switchesreact (Start of Fade or End of Fade). Then press
or .OK
OK
OK
Assign CircuitsPRESS OK TO SELECT CIRCUIT
A L L C i r c u i ts0 0 1 0 0 2 0 0 3 0 0 40 0 5 0 0 6 0 0 7 0 0 8
Previous Done
001
F.
001
-
R LCP128TM Setup and Operation Manual 39
STEP 4 (continued)
Configure Key Switch(NTOMX-KS)Lutron’s NTOMX-KS key switch control station canbe programmed to initiate an action for a clockwiseand counter-clockwise turn.
A. From the Main Menu use and to highlightControl Station Setup and press or (OK).
B. Use and to highlight the address of theNTOMX-KS you would like to configure and press
or (Next).
C. Use and to change control type toKey Switch and press or (Next).
D. Use and to highlight which direction turn toprogram and press or (Next). Each keyswitch can be programmed for a clockwise orcounter-clockwise turn. Both may be programmed.
E. Use and to select the type of Action for thiskey turn: Lower Circuits, Raise Circuits, Scene,Custom Scene, Enable Time Clock, DisableTime Clock, Delay to Off, Toggle, and No Actionand press or (Next). Refer to the beginning ofSTEP 4 for an explanation of the various actiontypes.
F. Program the Lower Circuits, Raise Circuits,Scene, Custom Scene, Delay to Off, or Toggleaction using the same screen methods used toconfigure a wallstation button. Refer to “Configurethe Wallstations” earlier in STEP 4.
OK
OK
OK
OK
OK
Address 03 Setup
Type: Key Switch
Previous Next
Main MenuOverridesTime Clock SetupControl Station SetupPanel CCI SetupBack OK
Control Station SetupAddress 01Address 02Address 03Address 04Cancel Next
A.
B.
C.
Address 03 SetupClockwise TurnCounter - Clockwise Turn
Previous Next
D.
Address 03 Key Switch
Action:
Previous Next
Scene
F.
-
Configure Contact ClosureInputs on OMX-AV/OMX-WCILutron’s OMX-AV or OMX-WCI control station canbe programmed to initiate actions for up to fivecontact closure inputs.
Note: For contact closure inputs wired directly tothe LCP128 panel, refer to STEP 6.
Note: OMX-WCI has 7 contact closure inputs.
A. From the Main Menu use and to highlightControl Station Setup and press or (OK).
B. Use and to highlight the address of theOMX-AV you would like to configure and press or (Next).
C. Use and to set the control Type to OMX-AVand press or (Next).
D. Each OMX-AV provides 5 inputs. Use and tohighlight the Contact Closure Input (CCI) toprogram and press or (Next). Or selectNo CCI’s if only the contact closure outputs (CCOs)are being used.
E. Use and to select whether you want define anaction for when the contact opens or when itcloses and press or (Next). Note: If there should be an action on both, firstset up the Open Action, then follow thisprocedure again but choose Closure Action.
F. Use and to select the type of Action for thisCCI: Lower Circuits, Raise Circuits, Scene,Custom Scene, Enable Time Clock, DisableTime Clock, Delay to Off, Toggle, and No Actionand press or (Next). Refer to the beginning ofSTEP 4 for an explanation of the various actiontypes.
G. For OMX-WCI: Program the Lower Circuits,Raise Circuits, Scene, Custom Scene, Delay toOff, or Toggle action using the same screenmethods used to configure a wallstation button.Refer to “Configure the Wallstations” earlier in STEP 4.
For OMX-AV: Program the Disable Time Clock,Enable Time Clock, Scene, Custom Scene,Delay to Off, or Toggle action using the samescreen methods used to configure a wallstationbutton. Refer to “Configure the Wallstations” earlierin STEP 4.
OK
OK
OK
OK
OK
OK
Address 03 Setup
Type: OMX-AV
Previous Next
Address 03 CCI 2 SetupOpen ActionClosure Action
Previous Next
Main MenuOverridesTime Clock SetupControl Station SetupPanel CCI SetupBack OK
Control Station SetupAddress 01Address 02Address 03Address 04Previous Next
A.
B.
C.
E.
Address 03 OMX-AVNo CCI’sCCI 01CCI 02CCI 03Previous Next
D.
R40 LCP128TM Setup and Operation Manual
STEP 4 (continued)
-
R LCP128TM Setup and Operation Manual 41
STEP 4 (continued)
Configure DMX Channels toCircuits on ODMX-512Lutron’s ODMX-512 control station can beprogrammed to 32 circuits in the system. Thesystem can then take inputs from a theatrical stageconsole to assigned circuits in the system.
A. From the Main Menu use and to highlightControl Station Setup and press or (OK).
B. Use and to highlight the address of theODMX-512 you would like to configure and press
or (Next).
C. Use and to set the control Type toODMX-512 and press or (Next).
D. Use and to select the DMX Activation Modeand press or (Next).Note: The DMX can be activated either when inconnection or when the selected channel is setabove 50%.
E. Use and to assign circuits to a DMX channeland press or (Next). Note: The same DMX channel may be assignedto more than one circuit.
OK
OK
OK
OK
OK
Address 03 Setup
Type: ODMX - 512
Previous Next
Main MenuOverridesTime Clock SetupControl Station SetupPanel CCI SetupBack OK
A.
C.
Address 03 SetupWhen is the
DMX activated?
DMX 14 > 50%Previous Next
D.
Circuit to DMX AssignCircuit-001 DMX 01Circuit-002 DMX 02Circuit-003 DMX 01Circuit-004 DMX 08
Previous Next
E.
-
R42 LCP128TM Setup and Operation Manual
STEP 4 (continued)
Integration through RS232Lutron’s OMX-RS232 control station enables you tointegrate your LCP128 system with a buildingmanagement system.
A. From the Main Menu use and to highlightControl Station Setup and press or (OK).
B. Use and to highlight the address of theOMX-RS232/OMX-CI-RS232 you would like toconfigure and press or (Next).
C. Use and to change control Type to OMX-RS232 / OMX-CI-RS232 and press or (Done).
Using the GRAFIK 6000®RS232 protocol.The OMX-RS232 is packaged and shipped withcomplete instructions and a protocol that detailshow to execute each command. Only a subset ofthe commands in that document work with theLCP128 system and they are listed below:
Command LCP128 Function
Fade to Level: Sets a pattern or time delay to off
Multilevel: Flash circuits
Get Level: Request level
SimulatePress: Simulate button press
SimulateRelease: Simulate button release
EnableControlStations: Enable control stations
DisableControlStations: Disable control stations
Set Clock: Sets time and date
Time Now: Request time
Astro Times: Request sunrise / sunset times
Date: Request date
EnableTime clock: Enable time clock
DisableTime clock: Disable time clock
OK
OK
OK
Address 03 Setup
Type: OMX-RS232 / CI-RS232
Previous Done
Main MenuOverridesTime Clock SetupControl Station SetupPanel CCI SetupBack OK
Control Station SetupAddress 01Address 02Address 03Address 04Previous Next
A.
B.
C.
-
R LCP128TM Setup and Operation Manual 43
STEP 4 (continued)
Integration through EthernetLutron’s OMX-CI-NWK-E control station enablesyou to integrate your LCP128 system with abuilding management system.
A. From the Main Menu use and to highlightControl Station Setup and press or (OK).
B. Use and to highlight the address of theOMX-CI-NWK-E you would like to configure andpress or (Next).
C. Use and to change control Type to OMX-CI-NWK-E and press or (Done).
Using the GRAFIK 6000®RS232 protocol.The OMX-CI-NWK-E is packaged and shipped withcomplete instructions and a protocol that detailshow to execute each command. Only a subset ofthe commands in that document work with theLCP128 system and they are listed below:
Command LCP128 Function
Fade to Level: Sets a pattern or time delay to off
Multilevel: Flash circuits
Get Level: Request level
SimulatePress: Simulate button press
SimulateRelease: Simulate button release
EnableControlStations: Enable control stations
DisableControlStations: Disable control stations
Set Clock: Sets time and date
Time Now: Request time
Astro Times: Request sunrise / sunset times
Date: Request date
EnableTime clock: Enable time clock
DisableTime clock: Disable time clock
OK
OK
OK
Address 03 Setup
Type: OMX-CI-NWK-E
Previous Done
Main MenuOverridesTime Clock SetupControl Station SetupPanel CCI SetupBack OK
Control Station SetupAddress 01Address 02Address 03Address 04Previous Next
A.
B.
C.
-
R44 LCP128TM Setup and Operation Manual
STEP 5
Time Clock EventsTime clock events enable the system to initiate a scene or start/end afterhours mode at either a specific time ofday or at a time relative to sunrise or sunset. 47 schedules are available—one for every day of the week, and 40holiday schedules. There can be a total of up to 500 events and no more than 25 on any day / holiday. Holidayschedules always override the weekly schedule.
The options for time clock events are:
• Scene or Custom Scene - The assigned circuits go to the programmed scene/custom scene settings.
• Enable or Disable Controls - Enable or disable the function of control stations.
• Afterhours Start - Starts an energy saving mode that is used to turn lights off at the end of normal hours untilthe beginning of the next day. First, a scene or pattern of circuit levels is recalled for the space (AfterhoursStart). Circuits programmed to turn off flash to warn any occupants that they are about to go out (number offlashes specified by Flash Count). Lights remain on to allow the occupant a chance to press a button to keeplights on (length of time is programmed as Off Delay). Finally, if a button has not been pressed, lights turn offautomatically at the end of the delay period.
If a button is pressed, occupancy sensor tripped, or another timeclock event occurs while the system is inAfterhours mode or in Off Delay, lights turn on and remain on for the programmed number of minutes, (WarnTime) then flash (number specified by Flash Count) and then turn off after the Off Delay.
• Afterhours End - When afterhours ends, the circuits are returned to their programmed state.
Example Scenario for Afterhours:
A. Afterhours start event—afterhours scene is recalled. The circuits that are going to turn off start to flash and offdelay starts counting down.
B. System enters afterhours.
C. Button is pressed to turn lights on.
D. Lights flash notifying they will be turning off soon.
E. Button is pressed to keep lights on.
F. Lights flash notifying they will be turning off soon.
G. Lights turn off.
H. Afterhours end event.Before proceeding with STEP 5, complete the Time Clock Event Table located at the back of this guide.Record when each event should occur and what it should do.
OffDelay
OffDelay
OffDelay
Warn Time
Warn Time
Afterhours
A B
C D
E F
G
H
-
R LCP128TM Setup and Operation Manual 45
Adding Weekly EventsWeekly events occur each week on a specific day.
A. From the Main Menu use and to highlightTime Clock Setup and press or (OK).
B. Use and to highlight Add Event and press or (OK).
C. Use and to highlight Add Weekly Event andpress or (OK).
D. Use and to select the Day to which youwould like to add the event and press or (Next).
E. Use and to select Fixed Time or at a timerelative to Sunset or Sunrise. Press to adjustthe time or offset. Adjust the time using and and press or (Next).
F. Use and to select the desired Action for theevent: Scene, Custom Scene, Enable or DisableControls, Afterhours Start, or Afterhours Endand press or (Next). Refer to the beginning ofSTEP 5 for an explanation of the various actiontypes.Note: For Afterhours End, this step is complete.
OK
OK
OK
OK
OK
OK
Event Time
Type TimeFixed Time 08:00 AM
Previous Next
Event Time
Type TimeSunrise + 00:15
HH : MMPrevious Next
STEP 5 (continued)
Time Clock SetupSetup ClockAdd EventCopy EventsView / Modify EventsBack OK
Fixed
Sunrise
B.
E.
Add Weekly Event
Cancel Next
D.
Select Day: Sunday
Add EventAdd Weekly EventAdd Holiday Event
Back OK
C.
-
R46 LCP128TM Setup and Operation Manual
STEP 5 (continued)
Adding Weekly Events(continued)If Selecting a Scene Action
G. In step F, if you selected Scene, use and toselect the desired scene and press or (Done).To add another event to this same schedule, selectYes when prompted “Modify More Events?”
OK
Select Scene
Previous Done
G.
If Selecting an Afterhours Start Action
G. In step F, if you selected After Hours Start, chooseSelect Scene or Set Circuit Level. Then press or (Next).
H. Select the scene or set the circuit levels to be usedfor afterhours mode. Then press or (Done).Refer to the beginning of STEP 5 for a detaileddescription of how afterhours mode works.Note: Modified circuit levels will reflect changesin real time.
To add another event to this same schedule, selectYes when prompted “Modify More Events?”
Note: You will set the afterhours warn time, flashcount, and off delay later in STEP 5.
OK
OK
If Adding a Custom Scene Action
G. In step F, if you selected Custom Scene, set thecircuit settings for the custom scene. Then press or (Done).To add another event to this same schedule, selectYes when prompted “Modify More Events?”
Note: Modified scenes will reflect changes in realtime.
OK
Select CircuitsAll Circuits - - - -001 Dim - 10%002 Dim - 20%003 Relay - O NPrevious Done
G.
Scene: 03
Afterhours SetupSelect SceneSet Circuit Levels
Previous Next
G.
-
R LCP128TM Setup and Operation Manual 47
STEP 5 (continued)
Adding Holiday EventsHoliday events occur on a specific date and canlast for 1 to 90 days.
A. From the Main Menu use and to highlightTime Clock Setup and press or (OK).
B. Use and to highlight Add Event and press or (OK).
C. Use and to highlight Add Holiday Event andpress or (OK).
D. Use and to select the holiday to which youwould like to add the event and press or (Next).To define a new holiday, select New Holiday.
• Enter the start date of the holiday.
• Enter the duration of the holiday. For example,New Year’s might be defined as starting onDecember 31 and lasting 2 days (December 31and January 1).
E. Use and to select Fixed Time or at a timerelative to Sunset or Sunrise. Press to adjustthe time or offset. Adjust the time using and and press or (Next).
F. Use and to select the desired Action for theevent: Scene, Custom Scene, Enable or DisableControls, Afterhours Start, or Afterhours Endand press or (Next). Refer to the beginning ofSTEP 5 for an explanation of the various actiontypes.Program the action using the same method as for aweekly event. Refer to “Adding Weekly Events”earlier in STEP 5.
Note: For Afterhours End, this step is complete.
OK
OK
OK
OK
OK
OK
Add Holiday EventSelect Holiday:
Add New Holiday
Cancel Next
Holiday Start Date
12 / 31MM / DD
Previous Next
Holiday Duration
Number of Days:
Previous Next
02
Add EventAdd Weekly EventAdd Holiday Event
Back OK
C.
D.
-
R48 LCP128TM Setup and Operation Manual
STEP 5 (continued)
Copying EventsA. From the Main Menu use and to highlight
Time Clock Setup and press or (OK).
B. Use and to highlight Copy Events and pressor (OK).
C. Use and to highlight Copy Weekly Event orCopy Holiday Event and press or (OK).
D. Use and to select the day of the week orholiday you would like to copy from and press or
(Next).
E. Use and to select the event you would like tocopy and press or (Next). If you would like tocopy all events programmed for this day or holiday,select All Events.
F. Use and to select the day or holiday youwould like to paste to and press or (Done).Holidays appear after the weekdays in the list. Toadd a new holiday, select New Holiday at the endof the list and then modify the existing holiday’sinformation to save it as a new holiday To paste the event to another day or holiday, selectYes when prompted to “Paste Again?”.
OK
OK
OK
OK
OK
OK
Select Event to CopySun - All EventsSun - Fixed 08:00 AMSun - Sunrise +0:15Sun - Sunset -0:30Previous Next
Paste Event To
Day:
Previous Done
Deleting EventsA. From the Main Menu use and to highlight
Time Clock Setup and press .
B. Use and to highlight Delete Event.
C. Use and to highlight Delete Weekly Event orDelete Holiday Event.
D. Use and to select the day of the week orholiday you would like to delete from.
E. Use and to select the event you would like todelete. If you would like to delete all events for thatschedule, select All Events.
F. You are asked to confirm deleting the event(s).Press Yes to delete, otherwise press No.To delete another event from that day or holiday,select Yes when prompted to “Delete Another?”.
OK
Select Event to DeleteSun - All EventsSun - Fixed 08:00 AMSun - Sunrise +0:15Sun - Sunset -0:30Previous Done
Time Clock SetupAdd EventsCopy EventsView / Modify EventDelete EventBack OK
Friday
E.
F.
B.
E.
-
R LCP128TM Setup and Operation Manual 49
STEP 5 (continued)
Afterhours SetupA. From the Main Menu use and to highlight
Panel Setup and press or (OK).
B. Use and to highlight Afterhours Setup andpress or (OK).
C. Use and to set a Warn Time, from 1 to 180minutes and press or (Next).
D. Use and to set the Flash Count, from 1 to 15flashes and press or (Next).
E. Use and to set an Off Delay, from 1 to 180minutes and press or (Done).Notes:To add an afterhours start action, refer to “AddingWeekly Events” earlier in STEP 5.
120 minutes is the maximum allowable off delayin California Title 24.
OK
OK
OK
OK
OK
Panel SetupLoad SetupEmergency SetupAfterhours SetupChoose Language
Back OK
Main MenuControl Station SetupPanel CCI SetupScene SetupPanel Setup
Back OK
Viewing / Modifying EventsA. From the Main Menu use and to highlight
Time Clock Setup and press or (OK).
B. Use and to highlight View/Modify Event andpress or (OK).
C. Use and to highlight Modify Weekly Event orModify Holiday Event and press or (OK).
D. Use and to select the day or holiday youwould like to view or modify and press or (Next).
E. Use and to select the event you would like toview or modify and press or (Next).
F. You now have the opportunity to modify this event.For procedures, refer to “Adding Weekly Events” or“Adding Holiday Events” earlier in STEP 5.
OK
OK
OK
OK
OK
Select Event to ModifySun - All EventsSun - Fixed 08:00 AMSun - Sunrise +0:15Sun - Sunset -0:30Previous Next
Time Clock SetupSetup ClockAdd EventsCopy EventsView / Modify EventsBack OK
View / Modify EventModify Weekly EventModify Holiday Event
Back OK
B.
C.
E.
A.
B.
-
R50 LCP128TM Setup and Operation Manual
STEP 6
Panel Contact Closure InputsThe LCP128 controller has two contact closure inputs (see illustration below). Separate actions can be definedfor the opening and closing of the contact. The choices are:
• Scene or Custom Scene - Each time the contact closure input is activated, the assigned circuits go to theprogrammed scene. A scene can also be used to control contact closure outputs.
• Enable or Disable Time Clock - Enable or disable the function of the time clock.
• Toggle - Each time the contact closure input is activated, the assigned circuits toggle between on and off. If theassigned circuits are in a mixed state (some on and some off), the circuits turn on.
• Delay To Off - Each time the contact closure input is activated, the assigned circuit(s) turn off after the presetamount of time (1 - 90 minutes).
Before proceeding with STEP 6, complete the Control Station Table located at the back of this guide.Record how each local contact closure should function. Designate them: Panel 1 CCI 1 Opening,Panel 1 CCI 1 Closing, Panel 1 CCI 2 Opening, Panel 1 CCI 2 Closing, and continue for Panel 2 throughPanel 8 as required.
LCP128 controller Top
Panel CCI Terminal Markings1: 15 V or 24 V CCI 1
2: Common CCI 1
3: 15 V or 24 V CCI 2
4: Common CCI 2
CC
I1C
OM
CC
I2C
OM
-
R LCP128TM Setup and Operation Manual 51
Assign CircuitsPRESS OK TO SELECT CIRCUIT
A L L C i r c u i ts0 0 1 0 0 2 0 0 3 0 0 40 0 5 0 0 6 0 0 7 0 0 8
Previous Done
STEP 6 (continued)
Configure Panel ContactClosure InputsNote: For contact closure inputs wired to aLutron OMX-AV control station, refer to STEP 4.
A. From the Main Menu use and to highlightPanel CCI Setup and press or (OK).
B. Use and to choose the contact closure inputyou want to configure and press or (OK).
C. Use and to select whether you want to definean action for when the contact Opens or Closesand press or (Next).
D. Use and to choose the type of Action for theCCI: Scene, Custom Scene, Enable or DisableTime Clock, Enable or Disable Controls, Delayto Off, Toggle, or No Action.Program the desired action using the followingprocedures.
OK
OK
OK
Panel 1 CCI 1Open ActionClosure Action
Previous Next
001
E.
C.
Panel CCI SetupPanel 1 CCI 1Panel 1 CCI 2Panel 2 CCI 1Panel 2 CCI 2Back OK
B.
If Selecting a Toggle Action
E. In step D, if you selected Toggle, the AssignCircuits screen lists all the circuits. Unassignedcircuits are presented as numbers with hash linesgoing through them. Move the cursor to a circuitnumber and press to toggle between Assignedand Unassigned (dashed). All circuits can betoggled by selecting ALL Circuits and pressing .When the circuits are programmed press .
F. For dimming circuits affected by the action, use and to set the Fade Time.
G. For a combination of dimming and switchingcircuits, use and to set when the switchesreact (Start of Fade or End of Fade). Then press
or .OK
OK
OK
-
R52 LCP128TM Setup and Operation Manual
STEP 6 (continued)
Configure Contact ClosureInputs (continued)
If Selecting a Scene Action
E. In step D, if you selected Scene, use and toselect the s