three phase inverters

Upload: srinivasrao

Post on 02-Jun-2018

225 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Three Phase Inverters

    1/36

  • 8/10/2019 Three Phase Inverters

    2/36

    Three-phase inverters are used for high-power

    applications such as ac motor drives, inductionheating, uninterruptive power supplies

    A three-phase inverter circuit changes DC inputvoltage to a three-phase variable frequency, variable

    voltage output The input DC voltage can be from a DC source or a

    rectified AC voltage

    A three-phase bridge inverter can be constructed bycombining three single-phase half-bridge inverters.

  • 8/10/2019 Three Phase Inverters

    3/36

    THREE PHASE INVERTER

  • 8/10/2019 Three Phase Inverters

    4/36

    THREE PHASE LOADS

  • 8/10/2019 Three Phase Inverters

    5/36

    It consists of six power-switches with six associatedfreewheeling diodes

    The switches are opened and closed periodically in theproper sequence to produce the desired outputwaveform

    The rate of switching determines the output frequencyof the inverter

    Basically, there are two possible schemes of gating thedevices

    In one scheme each device (switch) conducts for 180and in the other scheme, each device conducts for 120

    But in both these schemes, gating signals are appliedand removed at 60 intervals of the output voltagewaveform.

  • 8/10/2019 Three Phase Inverters

    6/36

    180-Conduction Mode with Resistive Load

    In this control scheme, each switch conducts for a period of 180or half-cycle electrical.

    Switches are triggered in sequence of their numbers with aninterval of 60.

    At a time, three switches (one from each leg) conduct. Thus, twoswitches of the same leg are prevented from conductingsimultaneously.

    One complete cycle is divided into six modes, each of 60intervals.

    Switch pair in each leg, i.e. S1 S4, S3 S6, and S5 S2 are turned-onwith a time interval of 180

    It means that switch S1 conducts for 180 and switch S4 for thenext 180 of a cycle

    Switches, in the upper group, i.e. S1, S3, S5 conduct at an intervalof 120

    It means that if S1 is fired at 0, then-S3 must be triggered at

    120 and S5 at 240. Same is true for lower group of switches.

  • 8/10/2019 Three Phase Inverters

    7/36

    Operation Table

    Sl.

    No

    Interval Incoming

    SCR

    Conducting

    Pair

    Outgoing

    SCR

    1 I T1 T5, T6, T1 T4

    2 II T2

    T6

    , T1

    , T2

    T5

    3 III T3 T1, T2, T3 T6

    4 IV T4 T2, T3, T4 T1

    5 V T5 T3, T4, T5 T2

    6 VI T6 T4, T5, T6 T3

  • 8/10/2019 Three Phase Inverters

    8/36

    GATE CURRENT WAVEFORMS

  • 8/10/2019 Three Phase Inverters

    9/36

    VOLTAGE WAVEFORMS FOR 180 MODE

  • 8/10/2019 Three Phase Inverters

    10/36

    The following points can be noted from the wave formsand the operating Table,

    Each switch conducts for a period of 180

    Switches are triggered in the sequence 1, 2, 3, 4, 5 and 6 Phase shift between triggering the two adjacent switches

    is 60.

    From table, it is observed that in every step of 60

    duration, only three switches are conducting-two fromupper group and one from the lower group and vice-versa

    The output voltage waveforms (EAB, EBC, ECA) are quasi-

    square-wave with a peak-value of Edc The three-line voltages are mutually phase-shifted by

    120.

  • 8/10/2019 Three Phase Inverters

    11/36

    The three-phase-voltages EAN,EBN, and ECNare six-stepwaves, with step heights Edc/3 and 2Edc/3.

    Line voltage EABis leading the phase-voltage EANby 30.

    Phase voltages EAN, EBNand ECNhave also been drawn forstarconnected resistive load.

    For a star-connected load, the line-to-neutral voltages must

    be determined to find the line or phase currents.

  • 8/10/2019 Three Phase Inverters

    12/36

    There are three modes of operation in a half-cycle andthe equivalent circuits are shown below for a star-connected load

  • 8/10/2019 Three Phase Inverters

    13/36

  • 8/10/2019 Three Phase Inverters

    14/36

    During interval I for

  • 8/10/2019 Three Phase Inverters

    15/36

    During interval II,

    During interval III,

  • 8/10/2019 Three Phase Inverters

    16/36

  • 8/10/2019 Three Phase Inverters

    17/36

    EBCand ECAcan be found by phase shifting EABby 120

    and 240 respectively

    The line-to-line RMS voltage can be found from

  • 8/10/2019 Three Phase Inverters

    18/36

    The RMS nth component of the line voltage is

    which, for n = 1, gives the fundamental line voltage

    The RMS value of line-to neutral voltages can be found

    from the line voltage

    8 C d i M d i h RL L d

  • 8/10/2019 Three Phase Inverters

    19/36

    180 Conduction Mode with RL-Load

    With resistive loads, the diodes across the switch haveno functions. If the load is inductive, then the current

    in each arm of the load will be delayed to its voltage asshown below

  • 8/10/2019 Three Phase Inverters

    20/36

    When switch S1 is triggered, S4 is turned-off but, because theload current cannot reverse, the only path for this current isthrough diode D1. Hence, the load phase is connected to thepositive end of the d.c. source but, until the load currentreverses at t1, switch S1 will not take up conduction

    Similar arguments apply in the reverse half-cycle at instant t2

    For a star-connected load, the phase voltage is EAN= EAB/3with a delay of 30. The line current ILfor an RL load is given by

    For a delta-connected load, the phase currents can be obtaineddirectly from the line-to-line voltages. Once the phase currentsare known, the line currents can be determined

  • 8/10/2019 Three Phase Inverters

    21/36

    O ti T bl

  • 8/10/2019 Three Phase Inverters

    22/36

    Operation Table

    Sl.

    No

    Interval Incoming

    SCR

    Conducting

    Pair

    Outgoing

    SCR

    1 I T1 T6, T1 T5

    2 II T2 T1, T2 T6

    3 III T3 T2, T3 T1

    4 IV T4 T3, T4 T2

    5 V T5 T4, T5 T3

    6 VI T6 T5, T6 T4

    GATE CURRENT WAVEFORMS

  • 8/10/2019 Three Phase Inverters

    23/36

    GATE CURRENT WAVEFORMS

    VOLTAGE WAVEFORMS FOR 120 MODE

  • 8/10/2019 Three Phase Inverters

    24/36

    VOLTAGE WAVEFORMS FOR 120 MODE

  • 8/10/2019 Three Phase Inverters

    25/36

    Following points can be noted from the waveforms and theoperating Table

    The base drives of two switches in the same-half-bridge havean inherent dead band of 60. Hence, there is no possibility ofcross conduction or shoot-through fault.

    Conduction period for each switch is 120.

    The phase-shift between the triggering of every two adjacentswitches is 60.

    Three line voltages, EABEBCand ECAare six-step waves, withstep heights Edc/2 and Edc

    The three-line voltages are mutually phase shifted by 120.

    The three-phase voltages EAN, EBNand ECNare quasi-square-

    waves with peak values of Edc/2. They are also mutually phase-shifted by 120

    The line-voltage EABis leading the phase-voltage EANby 30

    From operating table two switches conduct at a time, onefrom the upper group and the other from the lower group.

  • 8/10/2019 Three Phase Inverters

    26/36

    The equivalent circuits for a starconnected load are

  • 8/10/2019 Three Phase Inverters

    27/36

    During interval I, for

    Switches S1 and S6 conduct

    During interval II,for Switches S1 and S2 conduct

  • 8/10/2019 Three Phase Inverters

    28/36

    During interval III,for

    Switches S2 and S3 conduct

    The line-to-neutral voltages can be expressed inFourier-series as

    C i f T C d ti M d

  • 8/10/2019 Three Phase Inverters

    29/36

    Comparison of Two Conduction Modes

    In 180 mode conduction, when gate signal Ig1is removed toturn-off switch S1 at t = 180, gating signal Ig4is simultaneouslyapplied to turn-on switch S4 inthe same leg

    In practice, a commutation interval must exist between theremoval of Ig and application of Ig for proper and reliableoperation of the inverter circuit

    Since enough time may not be provided for the commutation of

    switch and two switches in series may simultaneously conduct,resulting into short circuit of the source by these switches

    This problem is overcome considerably in 120 mode inverter

    In this inverter, there is a 60 interval between the turning-off ofS1 and turning-on of S4

    During this 60 interval, switch S1 can be commutated safely.Thus, enough time is made available for the outgoing switch tocommutate before the switch in series is turned-on

    Therefore, commutation is more reliable and the possibility of

    two series switches conducting simultaneously is much less.

  • 8/10/2019 Three Phase Inverters

    30/36

    The second important difference is in terms of utility ofdevices

    The comparison of the two patterns is done using a figureof merit termed as utility factor (UF) and is defined as

    UF= Po/ PT where Pois the rated output power of the inverter and PTis

    the measure of total power handling capability of thedevices employed in the inverter, and is defined asPT= N VDRM. Irms

    where N= number of thyristors, VDRM= repetitive peak forward-voltage

    Irms = rated RMS forward current For the purpose of comparison of the two control schemes,

    it is usual to calculate the utility factor for ideal resistiveload

  • 8/10/2019 Three Phase Inverters

    31/36

    Inverter with 180 -Conduction

    For star-connected load, if R is the resistance perphase, then

    Device rating will be chosen such that the RMScurrent flowing through it will be equal to its RMScurrent rating Irms

    Therefore, under the rated conditions, the RMS valueof load phase current Ipis given by,

  • 8/10/2019 Three Phase Inverters

    32/36

    Load power Po can also be written as

    For this load, the repetitive peak forward voltage ratingof the device should be equal to Edc. Thus,

  • 8/10/2019 Three Phase Inverters

    33/36

    Inverter with 120 Conduction

    For star-connected load, with a per phase resistance ofR, output power Po will be given by

    Three-phase six-level diode-clamped inverter structure.

  • 8/10/2019 Three Phase Inverters

    34/36

    p p

  • 8/10/2019 Three Phase Inverters

    35/36

    Eleven-level wye-configured cascaded inverter.

  • 8/10/2019 Three Phase Inverters

    36/36

    y g