three phase four wire kwh meter
TRANSCRIPT
OverviewActive Energy-meter for three phase four wire alternating current with a 7 digit counters (No decimals. The meter comes standard with a short terminal cover. It can be supplied with a extended cover on request.
• Load bar indication • External magnetic influence (Arrow points to number (1) on display) • Green back light display for ease of reading. • Pulse output. (SO 100 imp/kWh) • Supplied by Autometers Systems Ltd a quality assured company (IS 9001) • Solar PV generation meter
HXE34 MID Approved ( Appendix “B” and “D”) Three phase Four wire kWh meter230/400 Volt, 50 Hz, 10-100 Amp.
LED Energy Indicator
HXE34 Features
Display
Unit ID
Active Energy kWh Energy Import
Bar Indication Indicating Load
L1, L2, L3 Indicating voltage lines
Green back light LCD Display
MID Certification Number
Chart Indicating Load (Bar Indication)
Extended terminal cover fitted
L1, L2, L3 illuminating indicatingvoltage lines present
Connection Diagram
Short Terminal Cover (extended on Large Cover available)
Bar Indication
HXE34 Three phase Four wire kWh meter 230/400 Volt, 50 Hz, 10-100 Amp.
Technical Data Data in compliance with EN 62053-21, EN62053-31, EN62056-21, DIN 43857-3
Autometers Systems Limited 4B Albany Road, Chorlton-cum-Hardy, Manchester, M21 0AW Tel: +44 (0) 161 861 9056 Fax: +44 (0) 161 881 3745 www.autometers.co.uk Email: [email protected] development is continuous and Autometers Systems Ltd reserves the right to make alterations and manufacture without notice. Products as delivered may therefore differ from the descriptions and illustrations in this publication.
Supplied by Autometers Systems Ltd, a quality assured company ( IS 9001) Publication No: HXE0512
ISO 9001Registered
QualityManagement
015
Back of meter
1 3
2
4 65
17 18
15 21
17 18
15 21
13 20
235 mm
1 3
2
4 65
17 18
15 21
17 18
15 21
13 20
315 mm
Fixing Bracket
1 3
2
4 65
17 18
15 21
17 18
15 21
13 20
All Terminal diameter for cable entry: 8 mm
L1 L2
Maximum cable size: 25mm²
L3 NEUTRAL
Terminals 20-2:1 Pulse Out Put
Connection Diagram Bottom of meter 240/400v 50Hz 10-100amp
Terminals 20 and 21 Pulse Output 100imp/kWh
3 phase 4 wire 100amp direct connected kWh meter
2 5 8 11 1 3 4 6 7 9 10 12 + - 20 21
L1
L2
L3
N
L1
L2
L3
N
MAINS
LOAD
Pulse Output
Power Bar Indication
- ≥ 0.01 kw- - ≥ 0.3 kw- - - ≥ 3.0 kw- - - - ≥ 10.0 kw- - - - - ≥ 20.0 kw- - - - - - ≥ 30.0 kw- - - - - - - ≥ 40.0 kw- - - - - - - - ≥ 60.0 kw
Arrows indicate the direction of power
HXE
3419
412
Side of meter
Measuring scope Rated voltage Voltage range Rated Frequency Rate Indicator LED Communication Communication Accuracy class Basic current Maximum current Minimum current Starting current Power consumption Tamper detection Display Operating temperature range Humidity operating range Degree of protection Meter life Weight Dimensions (L x W x H) Meter cover Meter base Terminal Box cover
Active energy, MD 3x 230 v (230/400v) 0.8UN~1.2UN 50 Hz 1000 imp/k Wh Optical port, RS485 with EN 62056-21 SO Pulse Output 100imp/kWh C1.B 10 A 100A 150 mA 15 mA Voltage circuit < 0.56w Apparent Power at UN <2.361VA Current circuit <0.025VA External magnetic detection 7 digits LCD, 7 integers -40˚ + 70˚C 95% IP54 No less than 15 years Approximate 1.485KG 262 mm x 170 mm x 70 mm (Short terminal cover) Transparent PC Glass fibered PC Glass fibered PC
170 mm
262 mm
Extended Terminal Cover
Small Terminal Cover
Terminals 3 mm diameter
70 mm
150 mm