Optical technologies in the power industry:Monitoring and diagnosis of gas-insulatedelectrical switchgear
Thomas A. Paul, ABB Corporate Research, Switzerland
-
Outline
Ø Electrical switchgear and gas insulation
Ø Insulation gas diagnostics for SF6Ø Insulation gas diagnostics for SF6-alternatives
Ø Electrical switchgear and gas insulation
Ø Insulation gas diagnostics for SF6Ø Insulation gas diagnostics for SF6-alternatives
-
Electrical SwitchgearElectrical Switchgear
Ø Essential components for energy transmission and distribution.
Ø Necessary at every switching point in the electrical power grid.
Ø Switching devices are associated with control, protection andmetering of power systems.
Ø Essential components for energy transmission and distribution.
Ø Necessary at every switching point in the electrical power grid.
Ø Switching devices are associated with control, protection andmetering of power systems.
-
Electrical SwitchgearElectrical Switchgear
Ø Air-insulatedsubstations have largespace requirement
Ø Significant reduction infootprint through use ofpotent insulation gases– the best is SF6.
Ø Air-insulatedsubstations have largespace requirement
Ø Significant reduction infootprint through use ofpotent insulation gases– the best is SF6.
380kV GIS and AIS, Pradella CHABB’s ELK-3 GIS
Air-insulated switchgear
SF6-insulated switchgear
-
SF6 as insulation gasSF6 as insulation gas
Partial discharge [image from www.think-grid.org]
Ø During operation, the gascomposition can change
Ø Humidity ingress throughseals and from outgassing
Ø Arc-induced decompositionduring switching
Ø Partial discharge induceddecomposition
Ø Decomposition products can betoxic and corrosive, and impedeoperability and safety ofswitchgear.
Ø During operation, the gascomposition can change
Ø Humidity ingress throughseals and from outgassing
Ø Arc-induced decompositionduring switching
Ø Partial discharge induceddecomposition
Ø Decomposition products can betoxic and corrosive, and impedeoperability and safety ofswitchgear.
SF6 HV circuit breaker, M. Abrahamsson, ABB
-
Insulation gas diagnosticsInsulation gas diagnostics
§ Permanent monitoring devices
Ø Density and T-compensated pressure
Ø Humidity
§ Off-line, extractive devices
Ø Humidity
Ø Complete gas composition
§ Leakage detection
§ Permanent monitoring devices
Ø Density and T-compensated pressure
Ø Humidity
§ Off-line, extractive devices
Ø Humidity
Ø Complete gas composition
§ Leakage detection
Gas analysis on a DTB, V. Williams, Company EMT
Humidity sensor on a GIS, Vaisala
SF6 sniffer, CPSOptical chilled mirror dewpoint meter, MBW
-
Abs
orba
nce
Optical instruments for switchgear diagnosisOptical instruments for switchgear diagnosis
§ SF6 and many decomposition products offer IR signatures
§ These are conveniently used for gas diagnostics
§ SF6 and many decomposition products offer IR signatures
§ These are conveniently used for gas diagnostics
Wavenumber [cm-1] F. Rager, ABB
-
Commercial optical instruments for switchgeardiagnosisCommercial optical instruments for switchgeardiagnosis
§ Multi-componentanalysis
§ Gas compositionanalysis
§ Sampling & pump-back
§ Integral leakagedetection
§ Photoacousticsensors
§ IR imaging
§ Multi-componentanalysis
§ Gas compositionanalysis
§ Sampling & pump-back
§ Integral leakagedetection
§ Photoacousticsensors
§ IR imaging
EMT IR SF6 analyzer
IR SF6 analyzers, EMT
IR photoacoustic SF6 analyzers, Innova-Lumasense
Innova-Lumasense
-
SF6-alternatives: insulation gas mixturesSF6-alternatives: insulation gas mixtures
§ Alternatives to SF6 are based ongas mixtures
§ Fluorinated organics (FOs) havehigh break-down strength
§ Performance of SF6-alternativesstrongly depends on composition
§ Composition is prone to change
ØConsumption in arc
ØCondensation
ØOther undesired processes,
§ Alternatives to SF6 are based ongas mixtures
§ Fluorinated organics (FOs) havehigh break-down strength
§ Performance of SF6-alternativesstrongly depends on composition
§ Composition is prone to change
ØConsumption in arc
ØCondensation
ØOther undesired processes,
New measurement instumentation neededNew measurement instumentation needed
-
Optical monitoring of SF6-alternatives in switchgearOptical monitoring of SF6-alternatives in switchgear
Abs
orba
nce
A. Kramer, ABB
§ Characteristic UV bandsavailable for FOs
§ UV LEDs available downto 200 nm with smallbandwidth
§ Can use straight-forwardabsorption measurement
§ Characteristic UV bandsavailable for FOs
§ UV LEDs available downto 200 nm with smallbandwidth
§ Can use straight-forwardabsorption measurement
Intensity
-
Optical monitoring of SF6-alternatives in switchgearOptical monitoring of SF6-alternatives in switchgear
§ Challengingmeasurementenvironment
ØDust
Ø Vibration
ØCorrosive gases
§ Optical absorptionmeasurementnevertheless viable
§ Accuracy betterthan 1% ofmeasuredconcentration
§ Challengingmeasurementenvironment
ØDust
Ø Vibration
ØCorrosive gases
§ Optical absorptionmeasurementnevertheless viable
§ Accuracy betterthan 1% ofmeasuredconcentration
Optical probe
A. Kramer andM. Porus, ABB
-
SummarySummary
Ø Optical technologies areused widely forinsulation gas diagnosis
Ø Diagnosisinstrumentation isestablished for mostaspects related to theuse of SF6
Ø SF6-alternatives requirenew solutions
Ø Optical technologies areused widely forinsulation gas diagnosis
Ø Diagnosisinstrumentation isestablished for mostaspects related to theuse of SF6
Ø SF6-alternatives requirenew solutions