this site · 2017. 6. 20. · note: sign and seal of electrical plans is the sole authority of a...

7
A-1 SHEET NO. SUBMITTED BY: APPROVED BY: RECOMMEND APPROVAL: CHECKED BY: PREPARED BY: PROJECT TITLE: LOCATION: LOCATION: Republic of the Philippines NATIONAL POLICE COMMISSION PHILIPPINE NATIONAL POLICE Camp Quintin M Merecido, Davao City Kidalapong, Malita, Davao Occidental PROPOSED PROVINCIAL HEADQUARTERS SUPPORT GROUP ENGINEERING SERVICE REGIONAL PROJECT MANAGEMENT UNIT 11 Director, ES Police Chief Superintendent PHILIP LAWRENCE S ABAPO, III POLICE SENIOR INSPECTOR ANTONIO A TAYLAN, JR Asst. Chief, RPMU MARIA DEOVINA G SEVILLANO Police Chief Inspector Acting Chief, RPMU ABELARDO C MATILLANO Police Senior Superintendent Chief of Staff, ES MANUEL G FABROS Police Senior Superintendent Deputy Director, ES DAVAO OCCIDENTAL POLICE PROVINCIAL OFFICE Acting Chief, ID, ES HONORIO R AGNILA Police Superintendent PD's QUARTERS CHAPEL ENTRANCE GATE OUTPOST POWER MOTOR POOL OUTPOST FLAG POLE SECURITY SECURITY OUTPOST SECURITY PARADE GROUND GRANDSTAND PPSC BUILDING RANGE FIRING HPU CIDU PCLO PIU PIAS ADMIN BPO BUILDING COVERED BASKETBALL COURT PNCO FUTURE FUTURE ON-BASE HOUSING FUTURE ON-BASE HOUSING EXPANSION FUTURE CONCESSIONAIRE & OTHER FACILITIES HOUSE N S E W GATE 2 OUTPOST SECURITY PARKING AREA PARKING AREA PARKING AREA PARKING AREA PARKING PARKING BARRACKS WATER RESERVOIR CAMP DEVELOPMENT PLAN SCALE 1:1000M SIDE DEVLOPMENT PLAN SCALE 1:50M E X I S T I N G R O A D THIS SITE PERSPECTIVE VIEW SCALE NTS ENTRANCE GATE MOTOR POOL PCLO PIAS PHSG PARKING AREA E X I S T I N G R O A D

Upload: others

Post on 26-Dec-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: THIS SITE · 2017. 6. 20. · NOTE: Sign and Seal of Electrical plans is the sole authority of a PROFESSIONAL ELECTRICAL ENGINEER R.A. 7920 Section 31, 32 & 34. Field of Practice

A-1

SHEET NO.SUBMITTED BY:

APPROVED BY:

RECOMMEND APPROVAL:

CHECKED BY:PREPARED BY:PROJECT TITLE:

LOCATION: LOCATION:

Republic of the Philippines

NATIONAL POLICE COMMISSION

PHILIPPINE NATIONAL POLICE

Camp Quintin M Merecido, Davao City

Kidalapong, Malita, Davao Occidental

PROPOSED PROVINCIAL HEADQUARTERS SUPPORT GROUP

ENGINEERING SERVICE

REGIONAL PROJECT MANAGEMENT UNIT 11

Director, ES

Police Chief Superintendent

PHILIP LAWRENCE S ABAPO, III

POLICE SENIOR INSPECTOR

ANTONIO A TAYLAN, JR

Asst. Chief, RPMU

MARIA DEOVINA G SEVILLANO

Police Chief Inspector

Acting Chief, RPMU

ABELARDO C MATILLANO

Police Senior Superintendent

Chief of Staff, ES

MANUEL G FABROS

Police Senior Superintendent

Deputy Director, ES

DAVAO OCCIDENTAL POLICE PROVINCIAL OFFICE

Acting Chief, ID, ES

HONORIO R AGNILA

Police Superintendent

P

D

's

Q

U

A

R

T

E

R

S

C

H

A

P

E

L

E

N

T

R

A

N

C

E

G

A

T

E

O

U

T

P

O

S

T

P

O

W

E

R

M

O

T

O

R

P

O

O

L

O

U

T

P

O

S

T

F

L

A

G

P

O

L

E

S

E

C

U

R

IT

Y

S

E

C

U

R

IT

Y

O

U

T

P

O

S

T

S

E

C

U

R

I

T

Y

P

A

R

A

D

E

G

R

O

U

N

D

G

R

A

N

D

S

T

A

N

D

P

P

S

C

B

U

IL

D

IN

G

R

A

N

G

E

F

IR

IN

G

H

P

U

C

I

D

U

P

C

L

O

P

I

U

P

I

A

S

A

D

M

I

N

B

P

O

B

U

I

L

D

I

N

G

C

O

V

E

R

E

D

B

A

S

K

E

T

B

A

L

L

C

O

U

R

T

P

N

C

O

F

U

T

U

R

E

F

U

T

U

R

E

O

N

-

B

A

S

E

H

O

U

S

I

N

G

F

U

T

U

R

E

O

N

-B

A

S

E

H

O

U

S

IN

G

E

X

P

A

N

S

I

O

N

F

U

T

U

R

E

C

O

N

C

E

S

S

I

O

N

A

I

R

E

&

O

T

H

E

R

F

A

C

I

L

I

T

I

E

S

H

O

U

S

E

N

S

EW

G

A

T

E

2

O

U

T

P

O

S

T

S

E

C

U

R

IT

Y

P

A

R

K

I

N

G

A

R

E

A

P

A

R

K

I

N

G

A

R

E

A

P

A

R

K

I

N

G

A

R

E

A

P

A

R

K

I

N

G

A

R

E

A

P

A

R

K

I

N

G

P

A

R

K

I

N

G

B

A

R

R

A

C

K

S

W

A

T

E

R

R

E

S

E

R

V

O

I

R

CAMP DEVELOPMENT PLANSCALE 1:1000M

SIDE DEVLOPMENT PLANSCALE 1:50M

E

X

I

S

T

I

N

G

R

O

A

D

THIS SITE

PERSPECTIVE VIEWSCALE NTS

E

N

T

R

A

N

C

E

G

A

T

E

M

O

T

O

R

P

O

O

L

P

C

L

O

P

I

A

S

P

H

S

G

P

A

R

K

I

N

G

A

R

E

A

E

X

I

S

T

I

N

G

R

O

A

D

Page 2: THIS SITE · 2017. 6. 20. · NOTE: Sign and Seal of Electrical plans is the sole authority of a PROFESSIONAL ELECTRICAL ENGINEER R.A. 7920 Section 31, 32 & 34. Field of Practice

GROUND FLOOR PLAN

WORK AREA

QUARTERS

STORAGE

SUPPLY ROOM

D4

D1

D2

B

A

1 2 3

C

B

A

W1

W2W3W3

W1

RO

OF

LIN

E

ROOF LINE

ROOF LINE

RO

OF

LIN

E

FF2

UP

UP

FRONT ELEVATIONSCALE 1:100M

REAR VIEW ELEVATIONSCALE 1:100M

RIGHT SIDE ELEVATIONSCALE 1:100M

LEFT SIDE ELEVATIONSCALE 1:100M

SECTION "A"SCALE 1:100MTS

1 2 3

12

3

C B A

SEE DETAILED SECTION

CBA

1 2 3

CBA

D1

W3 W3

W2W4

D1a

W1

W1

W1

D1a D3

WF2

WF1

RF2

RF1

WF1

CHIEF

W5

TOP OF ROOF BEAM

TOP OF ROOF STEEL ROOF GIRT

F.F.L.

N.G.L.

F.F.L.

TOP OF ROOF BEAM

TOP OF ROOF STEEL ROOF GIRT

APEX OF CANOPY TRUSS

N.G.L.

F.F.L.

TOP OF ROOF BEAM

N.G.L.

N.G.L.

F.F.L.

TOP OF ROOF BEAM

TOP OF ROOF STEEL ROOF GIRT

TOP OF ROOF BEAM

TOP OF ROOF STEEL ROOF GIRT

F.F.L.

N.G.L.

SECTION "B"SCALE 1:100MTS

WORK AREAQUARTERS

W1

WORK AREA CHIEF

W1

APEX OF CANOPY TRUSS

N.G.L.

F.F.L.

TOP OF ROOF BEAM

TOP OF ROOF STEEL ROOF GIRT

SEE DETAILED SECTION

STEEL CASEMENT WINDOW

W TRANSOM

PROVIDE 3 SETS

STEEL CASEMENT WINDOW

W TRANSOM

PROVIDE 1 SET

STEEL CASEMENT WINDOW

W TRANSOM

PROVIDE 3 SETS

STEEL AWNING WINDOW

PROVIDE 1 SET

ALUMINUM FRAMED GLASS

SWING DOOR WITH TRANSOM

PROVIDE 1 SET

ALUMINUM FRAMED GLASS

SWING DOOR

PROVIDE 1 SET

PVC DOOR

SWING DOOR

PROVIDE 2 SETS

SCHEDULE OF DOORSSCALE 1:50M

SCHEDULE OF WINDOWSSCALE 1:50M

PANEL DOOR

PROVIDE 2 SETS

D3

D3

D1 D2 D3 D4

W4

STEEL AWNING WINDOW

PROVIDE 1 SET

W1 W2 W3 W4 W5

W1

W5

A-2

SHEET NO.SUBMITTED BY:

APPROVED BY:

RECOMMEND APPROVAL:

CHECKED BY:PREPARED BY:PROJECT TITLE:

LOCATION: LOCATION:

Republic of the Philippines

NATIONAL POLICE COMMISSION

PHILIPPINE NATIONAL POLICE

Camp Quintin M Merecido, Davao City

Kidalapong, Malita, Davao Occidental

ENGINEERING SERVICE

REGIONAL PROJECT MANAGEMENT UNIT 11

Director, ES

Police Chief Superintendent

PHILIP LAWRENCE S ABAPO, III

POLICE SENIOR INSPECTOR

ANTONIO A TAYLAN, JR

Asst. Chief, RPMU

MARIA DEOVINA G SEVILLANO

Police Chief Inspector

Acting Chief, RPMU

ABELARDO C MATILLANO

Police Senior Superintendent

Chief of Staff, ES

MANUEL G FABROS

Police Senior Superintendent

Deputy Director, ES

DAVAO OCCIDENTAL POLICE PROVINCIAL OFFICE

Acting Chief, ID, ES

HONORIO R AGNILA

Police Superintendent

PROPOSED PROVINCIAL HEADQUARTERS SUPPORT GROUP

Page 3: THIS SITE · 2017. 6. 20. · NOTE: Sign and Seal of Electrical plans is the sole authority of a PROFESSIONAL ELECTRICAL ENGINEER R.A. 7920 Section 31, 32 & 34. Field of Practice

GENERAL NOTES:

ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL BUILDING CODE,

PROVISIONS OF THE LATEST APPROVED PHILIPPINE ELECTRICAL CODE, THE LAWS AND ORDINANCES OF

THE LOCAL CODE ENFORCING AUTHORITIES AND REQUIREMENTS OF THE LOCAL ELECTRIC, TELEPHONE

COMPANY AND BUILDING ADMINISTRATION REQUIREMENTS.

ALL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF LICENSE DULY REGISTERED

ELECTRICAL ENGINEER OR REGISTERED MASTER ELECTRICIAN.

1. CONTRACTOR SHALL SECURE ALL WIRING PERMIT AND ALL FEES REQUIRED FOR THE WORKS AND

FURNISH THE OWNER THE CERTIFICATE OF FINAL ELECTRICAL INSPECTION,

2. CONTRACTOR SHALL CONDUCT EARTH GROUND TEST, WIRE INSULATION AND LOAD TEST UPON

COMPLETION OF WORKS,

3. INCASE OF DISCREPANCY BETWEEN PLANS AND SITE CONDITION, SPECIFICATIONS & REVISIONS

CHANGES, THE CONTRACTOR SHOULD IMMEDIATELY VERIFY & CONSULT TOWITH THE

OFFICER-IN-CHARGE OF THE CONSTRUCTION (OICC) OF THE PNP ENGINEERING SERVICE (PNPES),

4. ALL LOCATION & MOUNTING HEIGHT ARE SUBJECT TO APPROVAL OF THE OICC OF PNPES,

5. CONTRACTOR SHALL BE RESPONSIBLE IN THE PREPARATION OF AS-BUILT PLANS DULY SIGNED

AND SEALED BY PROFESSIONAL ELECTRICAL ENGINEER, AND ELECTRONIC AUTOCAD FILES,

6. FINAL LIGHTING FIXTURES AND WIRING DEVICES SHALL BE APPROVED BY PNPES,

OICCREPRESENTATIVEENGINEER,

7. CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARATION OF SHOP OR CONSTRUCTION DRAWING

REQUIRED BY OICCOWNERARCHITECHENGINEER, THIS INCLUDES DEVICES AND FIXTURES

ELEVATION,

8. CONTRACTOR SHALL VISIT SITE CONDITION AND INCLUDE ALL COST NECESSARY TO COMPLETE

THE SYSTEM AT NO COST TO OWNER, INCLUDING COST OF CORING SERVICE AND EXPENSES FOR

THE RESTORATION OF ANY DAMAGE AFFECTED CIVIL STRUCTUTAL ARCHITECTURAL FINISHES OR

RELOCATION OF EXISTING FACILITIES ON BUILDING,

9. CONTRACTOR SHALL LOCATE ALL SPLICING BOXES TO ACCESSIBLE PLACE OR WITH ACCESS

PANELS,

10. NOMINATED CONTRACTOR TO VERIFY ALL EQUIPMENTS TO BE INSTALLED OR PLACE WITHIN THE

BUILDING SITE, AND MAKE AN ADJUSTMENT WITH THE PNPES OICCENGINEER ARCHITECT

CONSENT,

11. THIS DRAWINGS ARE DIAGRAMATIC LAYOUT ONLY, ANY MATERIALS AND FITTINGS NOT SHOWN ON

THIS PLANS BUT NEEDED TO COMPLETE THE SYSTEM AND OPERATION SHALL BE INCLUDED WITH

THE CONTRACTOR'S SCOPE OF WORKS.

12. ADDITIONAL NOTES:

· USE OF MICA SHALL BE LIMITED TO 150mm MAXIMUM

· USE OF FLEXIBLE METALLIC & NON METALLIC CONDUTIT SHALL BE LIMITED TO 1m MAXIMUM

· PROVIDE PROPER CONDUIT SUPPORT, G.I. WIRES AS SUPPORT SHALL NOT BE ALLOWED

· PROVIDE DOUBLE COAT OF RUST PROTECTIVE PAINT (RED OXIDE PRIMER) ON HANGERS AND

SUPPORTS.

SPECIFICATIONS:

1. POWER SUPPLY TO THE BUILDING SHALL BE 230V, SINGLE PHASE,

2-WIRES, 60HZ.

2. ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE FOR

PURPOSE & LOCATION.

3. NORMAL AND EMERGENCY CIRCUIT SHALL NOT BE COMBINED IN ONE

RACEWAY OR CONDUIT.

4. RECEPTACLES FOR GENERAL USE SHALL BE DUPLEX 16A, 250VAC,

GROUND TYPE.

5. ALL WIRES SHOULD HAVE A MAXIMUM LOAD OF 80 OF WIRE AMPACITY.

6. LIGHT SWITCHES MINIMUM RATING SHALL BE 16A 230VAC.

7. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND SHALL HAVE THE

"P.S." MARKS.

8. MOUNTING HEIGHTS SHALL BE AS FOLLOWS:

A. LIGHT SWITCHES - 1.37m above Floor finish

B. CONVENIENCE OUTLET - 0.3m above Floor finish

C. TELEPHONE OUTLET - 0.3m above Floor finish

D. PANEL BOARD - 1.8m ABOVE FLOOR FINISH

9. CONDUIT EMBEDED WITHIN CONCRETE WALL SHALL HAVE A MINIMUM

CEMENT PLASTERED OF 20mm THICK.

10. ALL CONDUIT PIPE ABOVE CEILING SHOULD HAVE INDEPENDENT

HANGER SUPPORTS.

11. ALL LIGHTING FIXTURES SHOULD HAVE INDEPENDENT HANGER

SUPPORTS.

12. ALL BOXES SHALL BE OCCUPIED ONLY OF 50 OF WIRE VOLUME.

13. VOLTAGE DROP SHALL BE LIMITED TO 2.5 FROM SOURCE TO PANEL

BOARD AS P.E.C. REQUIREMENT OR ACCEPTABLE TO THE LABORATORY

EQUIPMENT.

14. CIRCUIT BREAKERS SERVING MOTORS AND LIGHTING SHALL BE

INDUSTRIAL AND COMMERCIAL BOLT-ON TYPE RESPECTIVELY WITH

MINIMUM OF 6kAIC.

15. ALL WIRES AND CABLES SHALL BE BRAND NEW AND APPROVED TYPE.

16. USE SOLDERLESS CONNECTOR, MECHANICAL 1 PRESSURE TYPE COPPER

LUGS FOR CONNECTION OF WIRES LARGER THAN 8mm².

17. USE FILLER COMPOUND, "SCOTCH FILL" OR APPROVED EQUAL AT SHARP

EDGES TO PROVIDE SMOOTH SURFACE BEFORE TAPING WITH

ELECTRICAL TAPE.

LED EMERGENCY LIGHT

9W LED DOWNLIGHT

1-GANG OF 3-SINGLE POLE SWITCHESSabc

DP1 DP1-DISTRIBUTION PANEL 1

LEGEND & SYMBOLS

GFCI

DUPLEX CONVENIENCE OUTLET WITH GROUND

DUPLEX CONVENIENCE OUTLET WITH GROUND, GFCI

CIRCUIT HOMERUN, A-ACU CIRCUIT HOMERUN,L-LIGHTING CIRCUIT HOMERUN, C-CONVENIENCEOUTLET CIRCUIT HOMERUN

1 x 18 LED TUBE, BOX TYPE

1-GANG OF 2-SINGLE POLE SWITCHESSab

2-WIRE SERVICE ENTRANCE

SWITCH CONDUIT RUN

LIGHTING CIRCUIT CONDUIT RUN

RECEPTACLE OUTLET CIRCUIT CONDUIT RUN

225 AT3PCIRCUIT BREAKER

1

PROFESSIONAL ELECTRICAL ENGINEER

REG NO: PTR NO: TIN:

ISS. AT: ISS. ON: TEL:

NOTE: Sign and Seal of Electrical plans is the sole authority of a PROFESSIONAL ELECTRICALENGINEERR.A. 7920 Section 31, 32 & 34. Field of Practice and Prohibition in the Practice of Electrical Engineeringand preparation of plans, supervision of installation, application of the Philippine Electrical Code.

It shall be unlawful for any person not authorized under this Act to prepare plans, electricalvaluations or specifications for any electrical wiring, equipment or system; and no installation thereofshall be undertaken unless the plans, designs, valuations and specifications have been prepared by orunder the responsible charge of, and signed and sealed by a professional electrical engineer; and theconstruction permit for the execution thereof is first secured; and unless the work is done in accordancewith the Philippine Electrical Code and is executed under the responsible charge or supervision of aPROFESSIONAL ELECTRICAL ENGINEER or REGISTERED ELECTRICAL ENGINEER or Registered MasterElectrician, as the case may be, and the routinary fiscal and ministerial requirements of the governmentagency, if any, exercising jurisdiction over the particular installation have been complied with.

TABLE OF CONTENTSSHEET

NO

SHEET CONTENTS

DRAWING

NO

E1 GENERAL NOTES & SPECIFICATIONS 1

LEGEND & SYMBOLS 2

LOCATION & SITE DEVELOPMENT PLAN 3

C

H

A

P

E

L

E

N

T

R

A

N

C

E

G

A

T

E

O

U

T

P

O

S

T

M

O

T

O

R

P

O

O

L

S

E

C

U

R

IT

Y

P

A

R

A

D

E

G

R

O

U

N

D

G

R

A

N

D

S

T

A

N

D

H

P

U

C

I

D

U

P

C

L

O

P

I

U

I

A

S

B

P

O

F

U

T

U

R

E

C

O

N

C

E

S

S

I

O

N

A

I

R

E

&

O

T

H

E

R

F

A

C

I

L

I

T

I

E

S

T-150kVAL3, P3

P1

T-250kVAL1, P4

P5

P6

P2

LOCATION AND SITE DEVELOPMENT PLAN

N

A

T

I

O

N

A

L

R

O

A

D

I

A

S

B

P

O

P1

P2

2 - 14mm² THHN/THWN Cu WireIN 25 mm dia PVC

SERVICE ENTRANCE POLE4650mm High

N

S

EW

SHEET NO.SUBMITTED BY:

APPROVED BY:

RECOMMEND APPROVAL:

CHECKED BY:PREPARED BY:PROJECT TITLE:

LOCATION: LOCATION:

Republic of the Philippines

NATIONAL POLICE COMMISSION

PHILIPPINE NATIONAL POLICE

Camp Quintin M Merecido, Davao City

Kidalapong, Malita, Davao Occidental

PROPOSED PROVINCIAL HEADQUARTERS GROUP

ENGINEERING SERVICE

REGIONAL PROJECT MANAGEMENT UNIT 11

Director, ES

Police Chief Superintendent

PHILIP LAWRENCE S ABAPO, III

POLICE SENIOR INSPECTOR

ANTONIO A TAYLAN, JR

Asst. Chief, RPMU

MARIA DEOVINA G SEVILLANO

Police Chief Inspector

Acting Chief, RPMU

ABELARDO C MATILLANO

Police Senior Superintendent

Chief of Staff, ES

MANUEL G FABROS

Police Senior Superintendent

Deputy Director, ES

DAVAO OCCIDENTAL POLICE PROVINCIAL OFFICE

Acting Chief, ID, ES

HONORIO R AGNILA

Police Superintendent

E-1

Page 4: THIS SITE · 2017. 6. 20. · NOTE: Sign and Seal of Electrical plans is the sole authority of a PROFESSIONAL ELECTRICAL ENGINEER R.A. 7920 Section 31, 32 & 34. Field of Practice

GROUND FLOOR PLANSCALE 1:100M

WORK AREA

QTRS

STORAGE

SUPPLY ROOM

1 2 3

C

A

W1

RO

OF

LIN

E

ROOF LINE

ROOF LINE

RO

OF

LIN

E

8.00

UP

UP

CHIEF

4.00 4.00

7.00

3.50

3.50

2.20

4.00 4.00

0.60

1.70

1.20

CKT

NO.

Panel Board: SCHEDULE OF LOADSOCPD

No. & Size of Wire

and Conduit

DESCRIPTION LO COSPOGFCI

Total Volts kVA Amps AT, AF, POLE,kAIC

WIRE mm²/ PVC mmØ

1 Lighting Outlet 13 13 230 1.30 5.65 15, 50, 2, 6 2-3.5 THHN 20

2 Lighting Outlet 10 10 230 1.00 4.35 15, 50, 2, 6 2-3.5 THHN 20

3 Convenience Outlet 5 1 6 230 1.08 4.70 20, 50, 2, 6 2-3.5 THHN 20

4 Convenience Outlet 4 0 4 230 0.72 3.13 20, 50, 2, 6 2-3.5 THHN 20

5 1.5HP WT ACU 1 1 230 2.30 10.00 20, 50, 2, 6 2-5.5 THHN 20

6 1HP WT ACU 1 1 230 1.84 8.00 20, 50, 2, 6 2-5.5 THHN 20

7 SPARE 0 0 230 1.84 8.00 20, 50, 2, 6 20

Sub-total 23 9 3 35 10.08 43.83

COMPUTATIONS OF LOADS: PANEL BOARD

Iw (Ampacity of Wire)= (Total current, It x Demand factor,df) + 25 of Largest motor

Iw (Wire ampacity) = 43.83 + 2.50 = 46.33 USE: 2 - 14 mm² THHN/THWN in 25 mm Ø RSC PIPE

Icb (Main Over Current Protection Device)= Iw + Largest motor

Icb (Main OCPD) = 46.33 + 10.00 = 56.33 8 Branches Panel Board, 100AF with 60 AT Main CB, Bolt-on, Center Main, 2 Pole, 240V, 60Hz withGrounding Lugs

SERVICE ENTRANCE2-WIRE, SINGLE PHASE

kWhr METERCLASS 1002-14mm² THW Cu Wire

in 25mm Ø PVC Pipe

20 A, 2P 20 A, 2P

1

3

5

2

4

6

LIGHTING OUTLET

RECEPTACLE OUTLET

1.5HP WT ACU

LIGHTING OUTLET

RECEPTACLE OUTLET

PANELBOARD

1HP WT ACU

SINGLE LINE DIAGRAM

M

15 A, 2P

20 A, 2P

15 A, 2P

20 A, 2P

2-14mm² THW Cu Wirein 25mm Ø RSC Pipe

PROFESSIONAL ELECTRICAL ENGINEER

REG NO: PTR NO: TIN:

ISS. AT: ISS. ON: TEL:

NOTE: Sign and Seal of Electrical plans is the sole authority of a PROFESSIONAL ELECTRICAL ENGINEERR.A. 7920 Section 31, 32 & 34. Field of Practice and Prohibition in the Practice of Electrical Engineering andpreparation of plans, supervision of installation, application of the Philippine Electrical Code.

It shall be unlawful for any person not authorized under this Act to prepare plans, electrical valuations orspecifications for any electrical wiring, equipment or system; and no installation thereof shall be undertakenunless the plans, designs, valuations and specifications have been prepared by or under the responsible chargeof, and signed and sealed by a professional electrical engineer; and the construction permit for the executionthereof is first secured; and unless the work is done in accordance with the Philippine Electrical Code and isexecuted under the responsible charge or supervision of a PROFESSIONAL ELECTRICAL ENGINEER orREGISTERED ELECTRICAL ENGINEER or Registered Master Electrician, as the case may be, and the routinaryfiscal and ministerial requirements of the government agency, if any, exercising jurisdiction over the particularinstallation have been complied with.

TABLE OF CONTENTSSHEET

NO

SHEET CONTENTS

DRAWING

NO

E2 LIGHTING & POWER LAYOUT 1

SCHEDULE OF LOADS & COMPUTATIONS 2

SINGLE LINE DIAGRAM 3

SERVICE ENTRANCE DETAIL 4

SERVICE ENTRANCE POLE4650mm High

SERVICE ENTRANCESINGLE PHASE, 240VAC, 60Hz2 - 14 mm² THHN/THWN Cu Wirewith Messenger

DRIP LOOPat least 1500

58" Ø EYEBOLT

GALVANIZED with SPOOL INSULATOR

KWHR METER

USE SOLDERLESSCONNECTORS

DP60 AT

25 mm Ø RSC with clamps2-14mm² THHN Cu Wire

DETAIL OF SERVICE ENTRANCE

N. G. L.

SERVICE POLE DETAILNOT TO SCALE

TOP

STEEL BARSSTIRRUPS

4 STEEL BARSBOTHWAYS

1.00M

0.30M

1.00

M

1.50

M

0.30

M

0.35

M

1.00M

0.20M

NOTE: COORDINATE TO THESTRUCTURAL ENGINEER FORTHE SIZE OF STEEL BARS

NGL

2 - 14mm² THHN/THWN Cu Wirewith Messenger SERVICE DROP LINE

2 - 14mm² THHN/THWN Cu WireIN 25 mm dia PVC

Sd

a

a

b

a

Sa

Sbc Sa

Sabc

cc

cc

a a b b

Sab

a

a

d d

d

d

Sa

Sb

b

2

1

3

5

6

4

GFCI

LIGHTING & POWER LAYOUT

2 - 14mm² THHN/THWN Cu WireIN 25 mm dia PVC

SERVICE ENTRANCE POLE4650mm High

b c

c

B

GROUND FLOOR PLANSCALE 1:100M

WORK AREA

QTRS

STORAGE

SUPPLY ROOM

1 2 3

C

A

W1

RO

OF

LIN

E

ROOF LINE

ROOF LINE

RO

OF

LIN

E

8.00

UP

UP

CHIEF

4.00 4.00

7.00

3.50

3.50

2.20

4.00 4.00

0.60

1.70

1.20

B

60 AT3P

3.5250

4.0000 7 8SPARE SPARE20 A, 2P

MAIN SERVICE EQUIPMENT60AT in NEMA 3R Enclosures

(DOUBLE THROW SWITCHBREAKER TYPE

for provision of GENSET)

MAIN SERVICE EQUIPMENT60AT in NEMA 3R Enclosures

(DOUBLE THROW SWITCHBREAKER TYPE

for provision of GENSET)

E-2

SHEET NO.SUBMITTED BY:

APPROVED BY:

RECOMMEND APPROVAL:

CHECKED BY:PREPARED BY:PROJECT TITLE:

LOCATION: LOCATION:

Republic of the Philippines

NATIONAL POLICE COMMISSION

PHILIPPINE NATIONAL POLICE

Camp Quintin M Merecido, Davao City

Kidalapong, Malita, Davao Occidental

ENGINEERING SERVICE

REGIONAL PROJECT MANAGEMENT UNIT 11

Director, ES

Police Chief Superintendent

PHILIP LAWRENCE S ABAPO, III

POLICE SENIOR INSPECTOR

ANTONIO A TAYLAN, JR

Asst. Chief, RPMU

MARIA DEOVINA G SEVILLANO

Police Chief Inspector

Acting Chief, RPMU

ABELARDO C MATILLANO

Police Senior Superintendent

Chief of Staff, ES

MANUEL G FABROS

Police Senior Superintendent

Deputy Director, ES

Acting Chief, ID, ES

HONORIO R AGNILA

Police Superintendent

PROPOSED PROVINCIAL HEADQUARTERS GROUPDAVAO OCCIDENTAL POLICE PROVINCIAL OFFICE

Page 5: THIS SITE · 2017. 6. 20. · NOTE: Sign and Seal of Electrical plans is the sole authority of a PROFESSIONAL ELECTRICAL ENGINEER R.A. 7920 Section 31, 32 & 34. Field of Practice

ALL PLUMBING WORKS SHALL BE DONE IN ACCORDANCE W THE LATEST PROVISIONS

ALL VERT SOIL & WASTE STACK PIPE SHALL BE EXTEND FULL SIZE ABOVE ROOF LINE

PROVIDE 50MM Ø P-TRAP FOR EVERY 100M M Ø X 100MM Ø FLR DRAIN

PROVIDE CLEANOUT FOR EVERY FIFTEEN METERS ( 15.00 M ) DISTANCE

ALL CHANGES IN PIPE SIZES ON SOIL WASTE LINE SHALL BE MADE W THE REDUCING

OF THE NATIONAL PLUMBING CODE

AS VENTS EXCEPT OTHERWISE SPECIFICALLY INDICATED

FITTINGS OR RECESS REDUCERS

HORIZONTAL LINE

PROVIDE STOP-COCK FOR EVERY FIXTURES

120m

m

LIFTING COVER

R.C. COVER W STL

STORM DRAINAGE

PIPE LINE

4-12Ø MM

10 MM O BARS

CHB WALL W

BARS BOTHWAYS

10 MM THK

DRAIN LINE

PLASTERED FIN.

LIFTING COVER

R.C. COVER W STL

SECTION

CO CLEAN-OUT

FD FLOOR DRAIN

SHO SHOWER

CV CHECK VALVE

GV GATE VALVE

VSTR VENT STACK THRU ROOF

M WATER METERLAV LAVATORY

WC WATER CLOSET

SV SEPTIC VAULT

URI URINAL

DS DOWNSPOUT

PVC POLYVINYL CHLORIDE

DRAINAGE PIPE LINE

LAV LAVATORY

WC WATER CLOSET

UR URINAL

COLD WATER LINE

P L A N

NOTE:

VERIFY SIZE OF SEPTIC TANK TO LOCATION

.40 X .40

6" CHB

MANHOLE

4" CHB

6" CHB

12MM∅ BARS

SPACED @ .20M

O.C BW

S E C T I O N

AIR SPACE

WATER LEVEL

CHAMBER

DIGESTIVE

.40M

WF1

∅12 LIFT BAR

AIR SPACE

WATER LEVEL

CHAMBER

LEACHING

CHAMBER

LEACHING

21

12MM∅ BARS

SPACED @ .20M

O.C BW

4" CHB

6" CHB

TO

M

AIN

SE

WE

R L

IN

E

OU

TL

ET

P

IP

E

TO

S

EP

TIC

V

AU

LT

IN

LE

T P

IP

E

TO MAIN

SEWER LINE

OUTLET PIPE

TO

SEPTIC VAULT

INLET PIPE

FAU FAUCET

PLAN

WATER LEVEL

AIR SPACE

SOIL PIPE LINE

CB CATCH BASIN

VENT PIPE LINE

PPR POLYPROPYLENE RANDOM

NOT TO SCALE

1

P1 NOT TO SCALE

1

P2

P-1

SHEET NO.SUBMITTED BY:

APPROVED BY:

RECOMMEND APPROVAL:

CHECKED BY:PREPARED BY:PROJECT TITLE:

LOCATION: LOCATION:

Republic of the Philippines

NATIONAL POLICE COMMISSION

PHILIPPINE NATIONAL POLICE

Camp Quintin M Merecido, Davao City

Kidalapong, Malita, Davao Occidental

ENGINEERING SERVICE

REGIONAL PROJECT MANAGEMENT UNIT 11

Director, ES

Police Chief Superintendent

PHILIP LAWRENCE S ABAPO, III

POLICE SENIOR INSPECTOR

ANTONIO A TAYLAN, JR

Asst. Chief, RPMU

MARIA DEOVINA G SEVILLANO

Police Chief Inspector

Acting Chief, RPMU

ABELARDO C MATILLANO

Police Senior Superintendent

Chief of Staff, ES

MANUEL G FABROS

Police Senior Superintendent

Deputy Director, ES

DAVAO OCCIDENTAL POLICE PROVINCIAL OFFICE

Acting Chief, ID, ES

HONORIO R AGNILA

Police Superintendent

PROPOSED PROVINCIAL HEADQUARTERS SUPPORT GROUP

AutoCAD SHX Text
PLUMBING NOTES:
AutoCAD SHX Text
LEGEND & SYMBOLS
AutoCAD SHX Text
SLOPE 1:10 (MIN)
AutoCAD SHX Text
SEPTIC VAULT DETAIL
AutoCAD SHX Text
DETAIL OF CATCH BASIN
Page 6: THIS SITE · 2017. 6. 20. · NOTE: Sign and Seal of Electrical plans is the sole authority of a PROFESSIONAL ELECTRICAL ENGINEER R.A. 7920 Section 31, 32 & 34. Field of Practice

2

SCALE 1:100MTS

SANITARY LINES LAYOUT

UP

WM

CV

GV

WATER LINES LAYOUTSCALE 1:100M

SCALE 1:100MTS

CB

CBCB

CB

DSDS

DS

CB

DS

STORM DRAINAGE LAYOUT

1 2 3

C

B

A

1 2 3

C

B

A

1 2 3

C

B

A

P-2

SHEET NO.SUBMITTED BY:

APPROVED BY:

RECOMMEND APPROVAL:

CHECKED BY:PREPARED BY:PROJECT TITLE:

LOCATION: LOCATION:

Republic of the Philippines

NATIONAL POLICE COMMISSION

PHILIPPINE NATIONAL POLICE

Camp Quintin M Merecido, Davao City

Kidalapong, Malita, Davao Occidental

ENGINEERING SERVICE

REGIONAL PROJECT MANAGEMENT UNIT 11

Director, ES

Police Chief Superintendent

PHILIP LAWRENCE S ABAPO, III

POLICE SENIOR INSPECTOR

ANTONIO A TAYLAN, JR

Asst. Chief, RPMU

MARIA DEOVINA G SEVILLANO

Police Chief Inspector

Acting Chief, RPMU

ABELARDO C MATILLANO

Police Senior Superintendent

Chief of Staff, ES

MANUEL G FABROS

Police Senior Superintendent

Deputy Director, ES

DAVAO OCCIDENTAL POLICE PROVINCIAL OFFICE

Acting Chief, ID, ES

HONORIO R AGNILA

Police Superintendent

PROPOSED PROVINCIAL HEADQUARTERS SUPPORT GROUP

AutoCAD SHX Text
SEPTIC VAULT
AutoCAD SHX Text
VTR
AutoCAD SHX Text
100 MM PVC PIPE
AutoCAD SHX Text
CO
AutoCAD SHX Text
LAV
AutoCAD SHX Text
WC
AutoCAD SHX Text
FD
AutoCAD SHX Text
FROM WATER UTILITY CO.
AutoCAD SHX Text
12.5mm%%CCWL PIPE
AutoCAD SHX Text
12.5mm%%CCWL PIPE
AutoCAD SHX Text
FAU
AutoCAD SHX Text
SHO
AutoCAD SHX Text
WC
AutoCAD SHX Text
LAV
AutoCAD SHX Text
TO MAIN DRAINAGE
AutoCAD SHX Text
TO MAIN DRAINAGE
AutoCAD SHX Text
150mm%%C PVC PIPE
AutoCAD SHX Text
150mm%%C PVC PIPE
AutoCAD SHX Text
150mm%%C PVC PIPE
AutoCAD SHX Text
150mm%%C PVC PIPE
AutoCAD SHX Text
150mm%%C PVC PIPE
AutoCAD SHX Text
150mm%%C PVC PIPE
AutoCAD SHX Text
20MM CWL PIPE
Page 7: THIS SITE · 2017. 6. 20. · NOTE: Sign and Seal of Electrical plans is the sole authority of a PROFESSIONAL ELECTRICAL ENGINEER R.A. 7920 Section 31, 32 & 34. Field of Practice

100MM THK. SLAB ON FILL WITH

10MM Ø BEDBARS SPACED @

0.40M O.C. B.W.

1 2 3

C

B

A

F-2C-1

F-1C-1

F-1

C-1

F-2

C-1

F-1C-1

F-2

C-1

F-1

C-1

F-2C-1

WF-1 WF-1

WF-1 WF-1

WF

-1

WF

-1

WF

-1

WF

-1

WF-2

WF-2

WF-2

WF

-2

ROOF FRAMING PLANSCALE 1:100MTS

1 2 3

C

B

A

DETAIL OF ROOF GIRT

ROOF BEAM

ROOF GIRT

ROOF BEAM

ROOF BEAM ROOF BEAM

RO

OF

B

EA

MR

OO

F B

EA

M

RO

OF

B

EA

MR

OO

F B

EA

M

RA

FT

ER

- 1

RA

FT

ER

- 1

RA

FT

ER

- 1

RA

FT

ER

- 1

RA

FT

ER

- 1

RA

FT

ER

- 1

CA

NO

PY

T

RU

SS

- 1

CA

NO

PY

T

RU

SS

- 1

CA

NO

PY

T

RU

SS

- 1

A

1 2

3

DETAILED SECTIONSCALE 1:25MTS

SCALE 1:50MTS

WF - 2

TOP OF ROOF BEAM

APEX OF STEEL ROOF GIRT

2

-2

"X

6

" C

- C

H

A

N

N

E

L

S

A

S

R

A

F

T

E

R

2-2"X

6" C

- C

H

AN

N

ELS

AS

R

AF

TE

R

2" Ø SCHED 40 G.I. PIPE TOP AND BOTTOM CHORDS

B C

R O O F B E A M R O O F B E A M

2"X4" C - PURLINS WITH 2" X 2" ANGLE BAR CLEATS

0.4MM THK RIB TYPE ROOFING

10MM Ø SOG ROD

DETAIL OF ROOF BEAMSCALE 1:25MTS

WF - 1

F - 1

F - 2

C - 2

SECTION

S-1

SHEET NO.SUBMITTED BY:

APPROVED BY:

RECOMMEND APPROVAL:

CHECKED BY:PREPARED BY:PROJECT TITLE:

LOCATION: LOCATION:

Republic of the Philippines

NATIONAL POLICE COMMISSION

PHILIPPINE NATIONAL POLICE

Camp Quintin M Merecido, Davao City

Kidalapong, Malita, Davao Occidental

ENGINEERING SERVICE

REGIONAL PROJECT MANAGEMENT UNIT 11

Director, ES

Police Chief Superintendent

PHILIP LAWRENCE S ABAPO, III

POLICE SENIOR INSPECTOR

ANTONIO A TAYLAN, JR

Asst. Chief, RPMU

MARIA DEOVINA G SEVILLANO

Police Chief Inspector

Acting Chief, RPMU

ABELARDO C MATILLANO

Police Senior Superintendent

Chief of Staff, ES

MANUEL G FABROS

Police Senior Superintendent

Deputy Director, ES

DAVAO OCCIDENTAL POLICE PROVINCIAL OFFICE

Acting Chief, ID, ES

HONORIO R AGNILA

Police Superintendent

PROPOSED PROVINCIAL HEADQUARTERS SUPPORT GROUP

AutoCAD SHX Text
10MM SOG ROD
AutoCAD SHX Text
10MM SOG ROD
AutoCAD SHX Text
0.10M THK GROUND FLOOR SLAB WITH 10mm REBARS @ 0.40 O.C. B.W.
AutoCAD SHX Text
3-12mm LONGITUDUNAL BARS WITH10MM LATERAL TIES @ 0.20 M. O.C.
AutoCAD SHX Text
0.10M THK GRAVEL BED
AutoCAD SHX Text
4" THK CHB WALL INTERIOR PARTITION WITH 10MM VERT AND HOR BARS@ 0.60 O.C.
AutoCAD SHX Text
3-12MM LONGITUDINAL BARSWITH 10MM TRANSVERSE BARS @ 0.60 O.C.
AutoCAD SHX Text
10MM VERTICAL ANDHORIZONTAL BARS @ 0.60 O.C.
AutoCAD SHX Text
6" THK CHB
AutoCAD SHX Text
3-16MM TOP BARS
AutoCAD SHX Text
2-16MM BOT BARS
AutoCAD SHX Text
2-16MM TOP BARS
AutoCAD SHX Text
3-16MM BOT BARS
AutoCAD SHX Text
@ SUPPORT
AutoCAD SHX Text
@ MID SPAN
AutoCAD SHX Text
2" SCHEDULE 40 G.I. PIPE TOP AND BOTTOM CHORDSWITH 1 " SCHEDULE 40 G.I. PIPE WEB MEMBERS12" SCHEDULE 40 G.I. PIPE WEB MEMBERS
AutoCAD SHX Text
6-16 MM DEFBARS BOTH WAYS
AutoCAD SHX Text
0.30M X 0.30M 8-16MM VERT.TIES; 4@ 0.50M, 4@ 0.10M, 4@ 0.15M, REST @ 0.20M O.C.
AutoCAD SHX Text
8-16 MM DEFBARS BOTH WAYS
AutoCAD SHX Text
8-16MM VERT BARSWITH 10MM TIES