TB/TS/KE, /KEF Sensors Installation Instructions TG200605 Issue 3, 26-Aug-2014 1
Installation Instructions
TB/TS/KE, /KEFThermistor Room Temperature Sensors
Important: Retain these instructions
These instructions shall be used by trained service personnel onlyIf the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired.
1 Dimensions
2 Mounting Requirements
3 InSTallaTIon
1 Box ConTEnTS 2 SToRIng
It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).
- +
85 mm (3.35”)
26 mm (1.02”)
85 m
m (3
.35”
)
6 mm (0.24”)
- +
> 50 cm (20”)
1.5 m(5 ft)
TB/TS/KE, /KEF Installation Instructions (TG200605)
H O2
+50 °C(122 °F)
0-10 °C(14 °F)
90 %RH
2 TB/TS/KE, /KEF Sensors Installation Instructions TG200605 Issue 3, 26-Aug-2014
TB/TS/KE, /KEF Installation Instructions
3 Requirements (continued)
3 Remove backplate Mount backplate 4
5 Remove Cutout(s) 6 Route cables
3 InSTallaTIon (continued)
H O2
- +
-10 °C(14 °F)
+50 °C(122 °F)
0 %RH 90 %RH
or wall
BESA box
35 mm (1.38”)
60 mm (2.36”)wall box
as required
0 °C(32 °F)
+40 °C measurment(104 °F)
35 mm (1.38”)
35 mm (1.38”)
35 mm (1.38”)
- +
-+
-+
-+
FR
ABS
TB/TS/KE, /KEF Sensors Installation Instructions TG200605 Issue 3, 26-Aug-2014 3
Installation Instructions TB/TS/KE, /KEF
9 Set up strategies 8 assemble unit
3 InSTallaTIon (continued)
Wire to controller7
TB/TS Data Sheet (TA200603)
or
A strategy should be created to cover the TB/TS options required. The function of the options and strategy requirements are described in the data sheet.
1 2 3 4 5 6 Note that these options (TB/TS/KE, or TB/TS/KEF) cannot be used with IQs (except they can be used with IQecos); use options TB/TS, TB/TS/K, /KO, /OS, /KOF, or /KOSF with IQs.
Terminal size 0.5 to 2.5 mm2 (20 to 14 AWG)
‘click’
SENSOR IQ
1
2 IN
TB/TS
analogue input
(thermistor T)
COM (0V)0V
Temperature
5
4
IN
/EC
Overridedigital input
3 IN
COM (0 V)
/Kanalogue input
(thermistor T)
Knob
1
6 IN
COM (0 V)
/F
analogue input
(voltage V)
Fan
1
polarity
independent
IQLs and IQecos with fixed strategies must be connected as described in the relevant strategy data sheet or installation instructions.
For IQLs and IQecos with fixed strategies ignore steps (9) and (10) and proceed to step (11).
option Connect TerminalsTB/TS 1, 2TB/TS/K 1, 2, 3TB/TS/KE 1, 2, 3, 4, 5,TB/TS/KEF 1, 2, 3, 4, 5, 6
Note that screened cable is not required for sensor wiring to IQLs. If screened cable is used, the screen must be terminated at the controller to its supply cable earth.
4 TB/TS/KE, /KEF Sensors Installation Instructions TG200605 Issue 3, 26-Aug-2014
TB/TS/KE, /KEF Installation Instructions
Please send any comments about this or any other Trend technical publication to [email protected]
© 2014 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control Systems limitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.comTrend Control Systems USa6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 897-3900 Fax:(425) 869-8445 www.trend-americas.com
11 Test system
10 Set up IQ Sensor Types
4 DISpoSal
WEEE Directive:At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.Do not dispose of with normal household waste.Do not burn.
The recommended method of setting the sensor scaling is to use the ‘Unique Sensor Reference’ provided in SET, see below for details.The scaling parameters used by SET can be seen when the sensor type is configured. If these are not suitable these scaling parameters can be used as a guide to create your own sensor scaling using SET.
The input channel must be set to the appropriate input type (see controller documentation for details) and the sensor type module must be set up with the correct scaling.
� �
/K /E /F∆ T
∆ SP ∆
3 InSTallaTIon (continued)
Knob: The input channel used should be set for thermistor (T), and sensor scaling set as below.
Controller Unique Sensor Reference notesIQeco (Knob TB 05 deg trim)
Type 102 - Potentiometer-0.5 to + 0.5 deg trim
Thermistor: The input channel used should be set for thermistor (T), and sensor scaling set as below.
Controller Unique Sensor Reference notesIQeco (10k Therm DegC TBTS)
Type 101 - Thermistor °CValue in °C
(10k Therm DegC TBTS)Type 108 - Thermistor °F
Value in °F
Fan Control: The input channel should be set for voltage (V), and sensor scaling set as below.
Controller Unique Sensor Reference notesIQeco (Fan TBTS KEF)
Type 103 - Fan Speed SwitchFor TBTS KEF
(Fan TBTS KOF)Type 111 - TBTS Fan Speed Control
For TBTS KOF, KOSF