thermal comfort in a room with exposed roof using evaporative cooling in delhi

9
Building and Environment 38 (2003) 185 – 193 www.elsevier.com/locate/buildenv Thermal comfort in a room with exposed roof using evaporative cooling in Delhi Krishan Kant, S.C. Mullick Centre for Energy Studies, Indian Institute of Technology, New Delhi 110016, India Received 9 April 2001; received in revised form 25 October 2001; accepted 8 November 2001 Abstract In this study, diurnal hourly values of temperature and humidity in a room, with its roof exposed to the solar radiation in the summer months of April, May and June in Delhi, and having a direct evaporative cooler, have been computed and compared with the values obtained if the roof is unexposed. It is seen that additional heat load due to exposure of the roof to the solar radiation can be taken care of by slightly increasing the ow rate of the evaporatively cooled supply air. For April and May, the resulting conditions of the room air can be brought within an extended comfort zone (ECZ) by selecting an appropriate air change rate (ACH) giving due consideration to the bypass factor (BPF) of the cooler. During the month of June, the ambient air is very hot and its humidity rises; the conditions of the room are not within the ECZ, although the discomfort is mitigated. The levels of thermal sensation, which may be obtained with a direct evaporative cooler, have been computed on a numerical scale (S ) which is pertinent to hot-dry and warm-humid climatic zones in India. ? 2002 Elsevier Science Ltd. All rights reserved. Keywords: Evaporative cooling; Exposed roof; Summer of Delhi 1. Introduction The main purpose of a building is to provide shelter from the vagaries of nature. The roof protects us from the intense heat from above. It causes a decrement in the amplitude and a time lag between the temperature uctuations that are transmitted through it. The hot quartet of April–June is a trying period for the people who live in places such as Delhi and more so for those whose oces are located on the top oors of the multi-storied buildings. The indoor temperature is higher in case of a room with its roof exposed to the solar radiation as compared to a similar room on a lower oor wherein the roof is a partition. Under such conditions, a direct-evaporative cooler oers an inexpensive and eco-friendly way to achieve thermal comfort. It can provide large amounts of cool air to sweep away the room heat loads. The advantages of the evaporative air cooler over the halogen-based air conditioners are beautifully brought out by Mathews et al. [1]. Corresponding author. Tel.: 0091-11-659-1251,1254; fax: 0091-11-686-2208. E-mail address: [email protected] (S.C. Mullick). The evaporative cooling process is based on evaporation of water directly into the supply air lowering the sensible heat of the air and water vapour mixture but raising its hu- midity. A suitable combination of air change rate (ACH) and bypass factor (BPF) can be selected to achieve comfort con- ditions or to mitigate discomfort in a room depending on the outdoor temperature and humidity as discussed by the au- thors [2]. The walls of the room (Appendix A) were modeled using the ASHRAE transfer function approach [3] and sim- ulations were carried out with a computer program, TRN- SYS [4], for computing the hourly values of room air tem- perature and humidity. In the present study, the room with its roof exposed to the solar radiation has been considered and compared with a similar room with its roof unexposed. 2. Results and discussions The diurnal hourly values of the room air dry bulb tem- perature (DBT) and relative humidity (RH) in the month of April in Delhi, for an air change rate (ACH = 3:5 ac= h) and a bypass factor (BPF = 10%) are plotted in Fig. 1. The 0360-1323/03/$ - see front matter ? 2002 Elsevier Science Ltd. All rights reserved. PII:S0360-1323(02)00012-4

Upload: krishan-kant

Post on 03-Jul-2016

219 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Thermal comfort in a room with exposed roof using evaporative cooling in Delhi

Building and Environment 38 (2003) 185–193www.elsevier.com/locate/buildenv

Thermal comfort in a room with exposed roof using evaporative coolingin Delhi

Krishan Kant, S.C. Mullick ∗

Centre for Energy Studies, Indian Institute of Technology, New Delhi 110016, India

Received 9 April 2001; received in revised form 25 October 2001; accepted 8 November 2001

Abstract

In this study, diurnal hourly values of temperature and humidity in a room, with its roof exposed to the solar radiation in the summermonths of April, May and June in Delhi, and having a direct evaporative cooler, have been computed and compared with the valuesobtained if the roof is unexposed. It is seen that additional heat load due to exposure of the roof to the solar radiation can be taken careof by slightly increasing the 4ow rate of the evaporatively cooled supply air. For April and May, the resulting conditions of the room aircan be brought within an extended comfort zone (ECZ) by selecting an appropriate air change rate (ACH) giving due consideration tothe bypass factor (BPF) of the cooler. During the month of June, the ambient air is very hot and its humidity rises; the conditions of theroom are not within the ECZ, although the discomfort is mitigated. The levels of thermal sensation, which may be obtained with a directevaporative cooler, have been computed on a numerical scale (S) which is pertinent to hot-dry and warm-humid climatic zones in India.? 2002 Elsevier Science Ltd. All rights reserved.

Keywords: Evaporative cooling; Exposed roof; Summer of Delhi

1. Introduction

The main purpose of a building is to provide shelter fromthe vagaries of nature. The roof protects us from the intenseheat from above. It causes a decrement in the amplitudeand a time lag between the temperature 4uctuations thatare transmitted through it. The hot quartet of April–Juneis a trying period for the people who live in places suchas Delhi and more so for those whose o=ces are locatedon the top 4oors of the multi-storied buildings. The indoortemperature is higher in case of a room with its roof exposedto the solar radiation as compared to a similar room ona lower 4oor wherein the roof is a partition. Under suchconditions, a direct-evaporative cooler o?ers an inexpensiveand eco-friendly way to achieve thermal comfort. It canprovide large amounts of cool air to sweep away the roomheat loads. The advantages of the evaporative air cooler overthe halogen-based air conditioners are beautifully broughtout by Mathews et al. [1].

∗ Corresponding author. Tel.: 0091-11-659-1251,1254; fax:0091-11-686-2208.E-mail address: [email protected] (S.C. Mullick).

The evaporative cooling process is based on evaporationof water directly into the supply air lowering the sensibleheat of the air and water vapour mixture but raising its hu-midity. A suitable combination of air change rate (ACH) andbypass factor (BPF) can be selected to achieve comfort con-ditions or to mitigate discomfort in a room depending on theoutdoor temperature and humidity as discussed by the au-thors [2]. The walls of the room (Appendix A) were modeledusing the ASHRAE transfer function approach [3] and sim-ulations were carried out with a computer program, TRN-SYS [4], for computing the hourly values of room air tem-perature and humidity. In the present study, the room withits roof exposed to the solar radiation has been consideredand compared with a similar room with its roof unexposed.

2. Results and discussions

The diurnal hourly values of the room air dry bulb tem-perature (DBT) and relative humidity (RH) in the monthof April in Delhi, for an air change rate (ACH = 3:5 ac=h)and a bypass factor (BPF= 10%) are plotted in Fig. 1. The

0360-1323/03/$ - see front matter ? 2002 Elsevier Science Ltd. All rights reserved.PII: S0360 -1323(02)00012 -4

Page 2: Thermal comfort in a room with exposed roof using evaporative cooling in Delhi

186 K. Kant, S.C. Mullick / Building and Environment 38 (2003) 185–193

Nomenclature

ACH number of air changes (ac=h)BPF bypass factor (%)DBT dry bulb temperature (◦C)rh relative humidity (%)S thermal sensation numberTSI tropical summer index (◦C)

numbers 9–17 marked in the diagram represent the usualo=ce hours in Delhi. An extended comfort zone (ECZ) assuggested by Watt [5] (Appendix B) is also shown in thediagram. It is seen that if the room has a partition-roof, theroom air conditions are within the ECZ, whereas if the roofis exposed to the solar radiation the conditions are outsidethe comfort zone for a substantial part of the day. However,the additional heat load due to the radiations incident onthe roof can be absorbed by increasing the ACH slightly.Fig. 2 shows that the room air conditions are brought withinthe ECZ when the ACH is increased from 3.5 to 4 ac=h forthe BPF = 10%.Figs. 3–5 show the results for di?erent combinations of

ACH (2, 5 and 10 ac=h) and BPF (10%, 20% and 40%) inApril (Table 1). An air change rate of 2 ac=h cannot providecomfort conditions in the room for exposed or unexposedroof. The air change rate of 5 ac=h provides comfort condi-tions when BPF is 10–20%. However, the air change ratehas to be increased to 10 ac=h to obtain comfort conditionswhen the BPF is 40% for either type of the roofs. Hourly val-ues of water consumption for three of the above mentionedcombinations of ACH and BPF viz. (4,10), (5,20), (10,40)which give comfort conditions in the room are shown inFig. 6. Although each one of them lies within the ECZ, thesecond combination (5 ac=h 20% BPF) may be preferred, asthe Lrst requires a quite low BPF = 10% whereas the third,requiring an air change rate of 10 ac=h implies considerablygreater water consumption.

APRIL, ACH=3.5 ac/h, BPF=10%

20

30

40

50

60

70

80

90

20 22 24 26 28 30 32 34 36 38 40

TEMPERATURE, °C

RE

LAT

IVE

HU

MID

ITY,

%

EXPOSEDROOF

UNEXPOSED ROOF

ECZ

9 13

17

9 13

17

Fig. 1. Hourly values of room air dry bulb temperature and relative humidity for BPF = 10% and ACH = 3:5 ac=h in the month of April.

Figs. 7–9 show the results for the various combinationsof ACH and BPF in May. Here, an air change rate of 2–5 ac=h is not su=cient to provide the comfort conditions foreither type of roofs. An air change rate of 10 ac=h providescomfort for both exposed and unexposed roofs, providedthat the bypass factor is 20%. It may also be noted that theroom conditions change much more when the ACH changesfrom 2 to 5 or 5 to 10 ac=h as compared to the di3erencebetween the conditions for exposed and unexposed roofsfor a given ACH. So, a small increase in ACH can takecare of the roof exposure.In the month of June, both dry bulb temperature and hu-

midity of ambient air are quite high. The conditions of airin a room with direct evaporative cooling are not within theECZ but are close to it, implying that the discomfort will beconsiderably mitigated by going in for higher values of ACHeven though the BPF may be somewhat high (of the orderof 40%). The conditions have been quantiLed using Sharmaand Ali’s [6] thermal sensation index (S) which indicatesthat by using adequate air4ow rate, the room air conditionsare acceptable in the tropical summer.Figs. 10–12 show the room air conditions for di?erent

values of ACH (10 and 40 ac=h) and BPF (20% and 40%).The BPF=100% which represents simple ventilation (with-out any evaporative cooling), has also been included hereto allow comparison with the cases where the supply air iscooled by evaporation.Figs. 13–15 represent thermal sensation on the numerical

scale (S) suggested by Sharma and Ali, for di?erent valuesof ACH and BPF for the months of April–June in Delhi. Itis seen that S indicates lesser warmth than what would beinferred from the ECZ. So, the room air conditions that arewithin the ECZ are obviously comfortable according to thethermal sensation scale (and the tropical summer index).For air change rates of 5–10 ac=h and a bypass factor of 10–40%, some of the numerical values of thermal sensation are¡ 4 (implying slightly cool condition) in April and May.For the month of June, a higher value of ACH=40 ac=h (withBPF=40%) is required for obtaining S6 4. Thus, a cooler

Page 3: Thermal comfort in a room with exposed roof using evaporative cooling in Delhi

K. Kant, S.C. Mullick / Building and Environment 38 (2003) 185–193 187

APRIL, ACH=4 ac/h, BPF=10%

20

30

40

50

60

70

80

90

20 22 24 26 28 30 32 34 36 38 40

TEMPERATURE, °C

RE

LA

TIV

E H

UM

IDIT

Y, %

ECZ

9 13

17

UNEXPOSED

ROOFEXPOSED

ROOF

9 13

17

Fig. 2. Hourly values of room air dry bulb temperature and relative humidity for BPF = 10% and ACH = 4 ac=h in the month of April.

APRIL, BPF=10%

20

30

40

50

60

70

80

90

20 22 24 26 28 30 32 34 36 38 40

ROOM AIR DBT, °C

RO

OM

AIR

RH

, %

UNEXPOSED ROOF EXPOSED ROOF

9

913

1713

17

913

17

913

17

913

17

913

17

10ac/h

5ac/h

2ac/h

Fig. 3. Hourly values of room air dry bulb temperature and relative humidity for BPF = 10% and ACH = 2; 5 and 10 ac=h in the month of April.

with a bypass factor of about 40% and air 4ow rate to provideup to 40 ac=h will satisfy the comfort condition.

3. Conclusion

An evaporative cooler can provide indoor thermal com-fort in April and May in Delhi. In June, the room air con-ditions can be brought close to an extended comfort zonesuggested by Watt [5], implying that the discomfort will beconsiderably mitigated. Moreover, on a thermal sensationscale developed by Sharma and Ali [6], pertinent to the trop-ical summer, the conditions will be within the comfortable

range. A cooler of 20–40% BPF and adequate air4ow rateto supply up to 40 ac=h may be used here. For a room withan exposed roof and the heat loads considered in this study,an air change rate of 5 ac=h in April, 10 ac=h in May and40 ac=h in June should su=ce.

Appendix A.

A.1. The room studied and weather data

For the purpose of the case study, a thermally e=cienttypical room, 4 m × 4 m × 3:6 m high consisting of insu-

Page 4: Thermal comfort in a room with exposed roof using evaporative cooling in Delhi

188 K. Kant, S.C. Mullick / Building and Environment 38 (2003) 185–193

APRIL, BPF 20%

20

30

40

50

60

70

80

90

20 22 24 26 28 30 32 34 36 38 40

ROOM AIR DBT, °C

RO

OM

AIR

RH

, %

EXPOSED ROOF UNEXPOSED ROOF

13

13

17

9

9 13

17

9

179 13

17

9 13

ECZ

10ac/h

5ac/h

2ac/h

13

917

Fig. 4. Hourly values of room air dry bulb temperature and relative humidity for BPF = 20% and ACH = 2; 5 and 10 ac=h in the month of April.

APRIL, BPF=40%

20

30

40

50

60

70

80

90

20 22 24 26 28 30 32 34 36 38 40

ROOM AIR DBT, °C

RO

OM

AIR

RH

, %

UNEXPOSED ROOF EXPOSED ROOF

9

13

17

9

13

17 913

17

9

9

9

10 ac/h

5 ac/h

2 ac/hECZ

17

1

Fig. 5. Hourly values of room air dry bulb temperature and relative humidity for BPF = 40% and ACH = 2; 5 and 10 ac=h in the month of April.

HOURLY WATER CONSUMPTION IN APRIL

0

1

2

3

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

TIME, Hrs

WAT

ER

C

ON

SU

MP

TIO

N,

kg/h

ACH=4 ac/h, BPF=10% ACH=5 ac/h, BPF=20% ACH=10 ac/h, BPF=40%

Fig. 6. Hourly values of water consumption for the three combination of ACH and BPF viz. (4,10), (5,20), (10,40).

Page 5: Thermal comfort in a room with exposed roof using evaporative cooling in Delhi

K. Kant, S.C. Mullick / Building and Environment 38 (2003) 185–193 189

Table 1Uncomfortable hours and extent of discomfort for di?erent combinations of ACH and BPF in April

Exposed roof Unexposed roof

Discomfort due to excessive Discomfort due to excessive Discomfort due to excessive Discomfort due to excessivetemperature humidity temperature humidity

BPF ACH(%) (ac=h) (Degree-Hours) (Duration, h) (Gram-Hours) (Duration, h) (Degree-Hours) (Duration, h) (Gram-Hours) (Duration, h)

10 2 85 1–24 0 — 69 1–24 0 —10 5 0 — 0 — 0 — 0 —10 10 0 — 0 — 0 — 2 9–13

20 2 96 1–24 0 — 83 1–24 0 —20 5 0 — 0 — 0 — 0 —20 10 0 — 0 — 0 — 0 —

40 2 120 1–24 0 — 113 1–24 0 —40 5 6 12–21 0 — 2 15–20 0 —40 10 0 — 0 — 0 — 0 —

MAY, BPF=10%

20

30

40

50

60

70

80

90

20 22 24 26 28 30 32 34 36 38 40

ROOM AIR DBT, °C

RO

OM

AIR

RH

, %

UNEXPOSED ROOF EXPOSED ROOF

10 ac/h

2 ac/hECZ

1313

9 13

9

13

17

9 13

17

9

9

17

9

5 ac\h

13

Fig. 7. Hourly values of room air dry bulb temperature and relative humidity for BPF = 10% and ACH = 2; 5 and 10 ac=h in the month of May.

lated walls, ceilings and 4oor as speciLed by wall number32, Table 29, Chapter 26 of the ASHRAE Handbook ofFundamentals 1981 [3], was chosen as a repetitive unit ina multistory o=ce building in Delhi. The walls consist of101:6 mm concrete with 50:8 mm insulation and 12:7 mmLnish. The U value of the structure is 0:693 W=m2 K andits weight is 260 kg=m2. It is assumed that the room has one1:2 m× 1:2 m window in the south-facing exterior wall; allother walls and 4oor are interior partitions. Absorptance ofexterior surface to solar radiation is 0.8 and re4ectance of in-ner surface is 0.7. It is assumed that the room is occupied bythree persons doing light work (activity level=5). It is alsoassumed that the radiative energy due to lights, equipment,

etc. is 139 W and the capacitance of room air and furnishingsis 1000 kJ=K. The walls are modeled using the ASHRAEtransfer function approach. Transfer function coe=cients aretaken directly from the data Lle, ASHRAE.COF, providedwith TRNSYS [4]. It is assumed that the direct evaporativeair cooler draws 100% fresh air and supplies it to the roomafter adiabatic evaporation (without recirculation) and pro-vides a regulated mass 4ow of supply air for the room. Itis also assumed that there is an arrangement to regulate thebypass factor (BPF) of the supply air. We can have anyvalue of BPF starting from BPF = 0% representing supplyair that is saturated, up to BPF = 100% representing venti-lation with 100% ambient air (i.e., without any evaporative

Page 6: Thermal comfort in a room with exposed roof using evaporative cooling in Delhi

190 K. Kant, S.C. Mullick / Building and Environment 38 (2003) 185–193

MAY, BPF=20%

20

30

40

50

60

70

80

90

20 22 24 26 28 30 32 34 36 38 40

ROOM AIR DBT, °C

RO

OM

AIR

RH

, %

UNEXPOSED ROOF EXPOSED ROOF

9 13

179

13

17

913

17

9 13

179 13

17

9

13

17

ECZ 2 ac/h

5 ac/h

10 ac/h

Fig. 8. Hourly values of room air dry bulb temperature and relative humidity for BPF = 20% and ACH = 2; 5 and 10 ac=h in the month of May.

MAY, BPF=40%

20

30

40

50

60

70

80

90

20 22 24 26 28 30 32 34 36 38 40

ROOM AIR DBT, °C

RO

OM

AIR

RH

, %

UNEXPOSED ROOF EXPOSED ROOF

5 ac/h

10 ac/h9

13913

13

17

913

179 13

913

91717

17 17ECZ

Fig. 9. Hourly values of room air dry bulb temperature and relative humidity for BPF = 40% and ACH = 2; 5 and 10 ac=h in the month of May.

cooling). Thus, BPF= x% represents x% ambient air mixedwith (100− x)% saturated air.

A.2. Weather data

The weather data has been obtained from the handbookby Mani [7]. The handbook provides mean hourly values ofsolar radiation, ambient air temperature, relative humidityand wind speed based on 10 yr of data.

Appendix B.

B.1. Thermal comfort

The rate of heat dissipation from the human body dependson several factors such as its level of activity and clothing,the temperature, humidity and speed of the surrounding air,and the temperature and distances of the surrounding sur-faces. When the temperature of the surroundings is high, a

Page 7: Thermal comfort in a room with exposed roof using evaporative cooling in Delhi

K. Kant, S.C. Mullick / Building and Environment 38 (2003) 185–193 191

JUNE, BPF=20%

20

30

40

50

60

70

80

90

20 22 24 26 28 30 32 34 36 38 40

ROOM AIR DBT, °C

RO

OM

AIR

RH

, %

UNEXPOSED ROOF EXPOSED ROOF

9

13

17

9

13

17

ECZ

20 ac/h

40 ac/h

Fig. 10. Hourly values of room air dry bulb temperature and relative humidity for BPF = 20% and ACH = 10 and 40 ac=h in the month of June.

JUNE, BPF=40%

20

30

40

50

60

70

80

90

20 22 24 26 28 30 32 34 36 38 40

ROOM AIR DBT, °C

RO

OM

AIR

RH

, %

UNEXPOSED ROOF EXPOSED ROOF

9

13

17

9

13

17

ECZ

40 ac/h

20 ac/h

Fig. 11. Hourly values of room air dry bulb temperature and relative humidity for BPF = 40% and ACH = 10 and 40 ac=h in the month of June.

major portion of heat generated by human body (throughmetabolism) has to be dissipated by evaporation of sweatfrom the skin. Several authors have developed thermal in-dices, which take into account the combined e?ect of thesefactors. For instance, Sharma and Ali [6] have evolved aTSI pertinent to the tropical summer conditions prevailingin India.Watt [5] has suggested Extended comfort zones (ECZ)

which take into account the dry bulb temperature (tdb), rel-ative humidity (rh) and velocity (V ) of air. The extendedcomfort zone “C” of Fig. 4, page 36 of the handbook is ap-plicable for an air velocity of 3:1 m=s. (In the present study itis assumed that the room has a ceiling fan of appropriate rat-

ing which provides air movement of over 3:1 m=s, wheneverrequired, so that this zone is applicable). According to theECZ, relative humidity up to 80% and dry bulb temperaturedepending on rh and V are acceptable. Its right-boundaryline passes through the points (26:7◦C, 80% rh) and (31:1◦C,20% rh). When the condition of room air is within the ECZ,there is thermal comfort for most of the occupants.Sharma and Ali [6] have developed a tropical summer in-

dex (TSI) and a thermal sensation (S) scale which expressthe in4uence of the wet bulb temperature (tw), the globetemperature (tg), and the air speed (V ) for the hot-dry andwarm-humid conditions prevailing in India. The TSI is de-Lned as the air=globe temperature of the still air at 50%

Page 8: Thermal comfort in a room with exposed roof using evaporative cooling in Delhi

192 K. Kant, S.C. Mullick / Building and Environment 38 (2003) 185–193

JUNE, BPF=100%

20

30

40

50

60

70

80

90

20 22 24 26 28 30 32 34 36 38 40

ROOM AIR DBT, °C

RO

OM

AIR

RH

, %

UNEXPOSED ROOF EXPOSED ROOF

20 ac/h

ECZ

9

17

40ac/h

1313

9

17

Fig. 12. Hourly values of room air dry bulb temperature and relative humidity for BPF = 100% and ACH = 10 and 40 ac=h in the month of June.

APRIL, EXPOSED ROOF

11.5

22.5

33.5

44.5

55.5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24TIME,Hrs.

TH

ER

MA

L S

EN

SAT

ION

NU

MB

ER

ACH=2 ac/h, BPF=10% ACH=2 ac/h, BPF=20% ACH=2 ac/h, BPF=40%

ACH=5 ac/h, BPF=10% ACH=5 ac/h, BPF=20% ACH=5 ac/h, BPF=40%

ACH=10ac/h, BPF=10% ACH=10 ac/h, BPF=20% ACH=10 ac/h, BPF=40%

Fig. 13. Hourly numerical values of thermal sensation in a room with an exposed roof, in the month of April.

1

2

3

4

5

6

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

TIME,Hrs.

TH

ER

MA

L S

EN

SAT

ION

NU

MB

ER

ACH=2 ac/h, BPF=10% ACH=2 ac/h, BPF=20% ACH=2 ac/h, BPF=40%

ACH=5 ac/h, BPF=10% ACH=5 ac/h, BPF=20% ACH=5 ac/h, BPF=40%

ACH=10 ac/h, BPF=10% ACH=10ac/h, BPF=20% ACH=10ac/h, BPF=40%

Fig. 14. Hourly numerical values of thermal sensation in a room with an exposed roof, in the month of May.

relative humidity, which produces the same overall sensa-tion as the environment under investigation. It is a measureof thermal comfort and can be used to verify whether thegiven indoor conditions would be acceptable to most of the

occupants. The related equations are:

TSI = 0:308tw + 0:754tg − 2:06V 1=2 − 0:841;

S = 0:067tw + 0:162tg − 0:449V 1=2 − 1:917:

Page 9: Thermal comfort in a room with exposed roof using evaporative cooling in Delhi

K. Kant, S.C. Mullick / Building and Environment 38 (2003) 185–193 193

JUNE, EXPOSED ROOF

1

2

3

4

5

6

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

TIME,Hrs.

TH

ER

MA

L S

EN

SAT

ION

NU

MB

ER

ACH=10 ac/h,BPF=20% ACH=10 ac/h,BPF=40% ACH=10 ac/h,BPF=100%

ACH=20 ac/h,BPF=20% ACH=20 ac/h,BPF=40% ACH=20 ac/h,BPF=100%

ACH=40 ac/h,BPF=20% ACH=40 ac/h,BPF=40% ACH=40 ac/h,BPF=100%

Fig. 15. Hourly numerical values of thermal sensation in a room with an exposed roof, in the month of June.

The thermal sensation scale ranges numerically from S = 1to 7 (much too cool, too cool, slightly cool, comfortable,slightly warm, too warm, much too warm). Thus, S=4 rep-resents comfortable condition and the values of S in excessof 4 represent the extent of discomfort due to heat. Sharmaand Ali have also suggested a tropical summer comfort zonebounded by 30–70% rh and 25–30◦C TSI lines on a psy-chrometric chart. It is centered around a point (27:5◦C, 50%rh) and extends to about 31◦C dry bulb temperature.

References

[1] Mathews EH, Kleingeld M, Grober LJ. Integrated simulation ofbuildings and evaporative cooling systems. Building and Environment1994;29(2):197–206.

[2] Kant K, Kumar A, Mullick SC. Space conditioning usingevaporative cooling for summers in Delhi. Building and Environment2001;36(V4):1–11.

[3] American Society of Heating, Refrigerating and Air-ConditioningEngineers, Inc., ASHRAE handbook of fundamentals, Table 29, NewYork: ASHRAE, 1981. p. 26.36.

[4] Klein SA, et al. TRNSYS: a transient system simulation program,version 14.1. Madison: Solar Energy Laboratory, University ofWisconsin, 1990.

[5] Watt John R. In: Evaporative air conditioning handbook, 2nd ed. NewYork: Chapman and Hall, 1986. p. 34–6 [Chapter IV].

[6] Sharma MR, Ali S. Tropical summer index—a study of thermalcomfort in Indian subjects. Building and Environment 1986;21(1):11–24.

[7] Mani A. Handbook of solar radiation data for India 1980. New Delhi:Allied Publishers, 1981, p. 265, 274–6.