Theoretical Discussion: Impacts of Air flow on AC Performance ASHRAE Summer Meeting June 30, 2004 Hugh I Henderson, Jr., P.E. CDH Energy Corp. Cazenovia, NY www.cdhenergy.com

Upload: others

Post on 30-Jan-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

  • Theoretical Discussion:

    Impacts of Air flow on AC

    Performance

    ASHRAE Summer Meeting

    June 30, 2004

    Hugh I Henderson, Jr., P.E.

    CDH Energy Corp.

    Cazenovia, NY

    www.cdhenergy.com

  • Overview

    • Use Manufacturer’s “Catalog” Data to

    Show Impact of Airflow on Performance

    – efficiency & capacity

    • Use Public Domain Steady-State

    Refrigeration Model to Evaluate Flow

    Impacts

  • Catalog Data for

    3-ton RTU

    • Combined “Gross” Coil Performance Data with Fan Curves

    – 300 to 500 cfm/ton

    • Shows Combined Impact of Flow:

    – comp efficiency increases with flow

    – fan power increases with flow

    9.0

    9.2

    9.4

    9.6

    9.8

    10.0

    10.2

    10.4

    10.6

    10.8

    800 900 1000 1100 1200 1300 1400 1500 1600

    Airflow (cfm)

    Net

    EE

    R (

    Btu

    /Wh

    ) 80/72

    80/67

    80/62

    -

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0.90

    1.00

    800 900 1000 1100 1200 1300 1400 1500 1600

    Airflow (cfm)

    SH

    R (

    -)

    80/72

    80/67

    80/62

  • Fan Performance

    Impacts EER

    Trends

    3-ton, Standard-Fan, Direct Drive

    0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    800 900 1000 1100 1200 1300 1400 1500 1600

    Airflow (cfm)

    Un

    it S

    tati

    c P

    ressu

    re (

    in)

    Fan

    Po

    wer

    (kW

    )

    3-ton, Standard-Fan, Direct Drive

    0.230

    0.235

    0.240

    0.245

    0.250

    0.255

    0.260

    0.265

    0.270

    0.275

    0.280

    0.285

    800 900 1000 1100 1200 1300 1400 1500 1600

    Airflow (cfm)

    No

    rmali

    zed

    Fan

    Po

    wer

    (Watt

    /cfm

    )

    • Unit Static Ranges from 0.16 to 0.49 in

    • RTU similar to Residential

    – direct drive, FC fan

    – DX coil & furnace section

    • 0.24-0.28 W/cfm

    Static

    Power

  • Impact of Flow at

    Nominal Conditions 80/67F, 95F

    3-ton RTU

    97%

    98%

    99%

    100%

    101%

    102%

    800 900 1000 1100 1200 1300 1400 1500 1600

    Airflow (cfm)

    Rela

    tive V

    alu

    e

    GROSS Efficiency

    NET Efficiency

    3-ton RTU

    95%

    96%

    97%

    98%

    99%

    100%

    101%

    102%

    103%

    104%

    800 900 1000 1100 1200 1300 1400 1500 1600

    Airflow (cfm)

    Rela

    tive V

    alu

    e

    Power

    NET Capacity

    • NET Capacity and Power change by ±2-3%

    • NET EER changes by less than 1%

  • Use AC Model to Evaluate Trends

    • Public-Domain Refrigeration System Model

    – 20+ years of history

    – validated by ASHRAE 859-RP, others

    – web-interface, parametric run mode

    • Default Model Inputs

    – 2.5 ton, reciprocating compressor,

    – R22, 400 cfm/ton

    – supply fan: 0.365 W/cfm (constant value)

  • Refrigeration

    Model

    Output

  • Almost No DB Impact AC Model Performance

    55 60 65

    Entering WB (F)

    8.0

    8.5

    9.0

    9.5

    10.0

    Ne

    t E

    ER

    (B

    tu/W

    h)

    70DB 72DB

    74DB

    76DB

    78DB

    80DB

    82DB

    EER is a

    function of

    WB – except

    for dry coil

  • Impact of Entering WB

    AC Model Performance

    250 300 350 400 450 500 550

    Normalized Airflow (cfm/ton)

    8.0

    8.5

    9.0

    9.5

    10.0

    Ne

    t E

    ER

    (B

    tu/W

    h)

    56WB

    58WB

    60WB

    62WB

    64WB

    66WB

    68WB

  • What Are Typical Entering Conditions?

    Nominal: 80F & 51% RH 67F WB

    Typical: 75F & 55% RH 64F WB

    Mild: 80F & 35% RH 62F WB

    …BUT so is…

    75F & 48% RH

    Dry Climate: 75F & 35% RH 58F WB

  • Impact of Fan Power (at 64F WB)

    AC Model Performance

    250 300 350 400 450 500 550

    Normalized Airflow (cfm/ton)

    8.5

    9.0

    9.5

    10.0

    10.5

    11.0N

    et

    EE

    R (

    Btu

    /Wh

    ) 0.1 W/cfm

    0.2 W/cfm

    0.3 W/cfm

    0.4 W/cfm

    0.5 W/cfm

    0.365 W/cfm

  • AC Model Performance

    250 300 350 400 450 500 550

    Normalized Airflow (cfm/ton)

    7

    8

    9

    10

    11

    Ne

    t E

    ER

    (B

    tu/W

    h) 0.1 W/cfm

    0.2 W/cfm

    0.3 W/cfm

    0.4 W/cfm

    0.5 W/cfm

    Impact of Fan Power (at 60F WB)

    0.365 W/cfm

  • AC Model Performance

    250 300 350 400 450 500 550

    Normalized Airflow (cfm/ton)

    7

    8

    9

    10

    11

    Ne

    t E

    ER

    (B

    tu/W

    h)

    0.1 W/cfm

    0.2 W/cfm

    0.3 W/cfm

    0.4 W/cfm

    0.5 W/cfm

    Impact of Fan Power (at 58F WB)

    0.365 W/cfm

  • What Fan Power is Typical?

    • Same 3-ton RTU offers High Static Option with

    Belt Driven Fan

    – Fan speed set to provide flow & static

    • Fan Power Can Change by Factor of 5 Across the

    Range: 0.2 to 1.0 Watt/cfm

    cfm/ton 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2

    300 0.20 0.28 0.38 0.48 0.54 0.63 0.69 0.75 0.80 0.86

    333 0.22 0.30 0.38 0.49 0.55 0.63 0.69 0.75 0.80 0.85

    367 0.24 0.32 0.36 0.50 0.55 0.61 0.66 0.72 0.77 0.82

    400 0.27 0.34 0.41 0.53 0.56 0.61 0.67 0.73 0.78 0.83

    433 0.29 0.37 0.46 0.54 0.58 0.64 0.71 0.76 0.82 0.87

    467 0.32 0.41 0.48 0.55 0.60 0.66 0.73 0.79 0.84 0.90

    500 0.35 0.44 0.51 0.57 0.63 0.70 0.76 0.83 0.89 0.95

    Unit Static (in)

    Normalized Fan Power (Watts/cfm)

    Riding Fan

    Curve

  • What if I Don’t Need the Latent

    Capacity in My Dry Climate?

    • Don’t Worry Your Not Getting Much…. COIL1_TEST_4B_10B_16B_22B 08/30/02 07:42:04 Cycle #1 (Comp ON time: 45.0 minutes)

    0 20 40 60 80 100

    time (minutes)

    -20

    -10

    0

    10

    20

    30

    Capacity (

    MB

    tu/h

    )

    Compressor

    Sensible

    Latent Addition

    Latent Removal

    Off-Cycle

    Evaporation

    Sensible Latent

    EER ~

    Sensible EER

  • Summary

    • Airflow has Very Little Impact on EER near

    Nominal Conditions

    – but more impact at dry coil conditions

    • The Variation of EER with Airflow

    Depends on Fan Power

    • Best Airflow Rate Depends on Climate and

    Equipment Characteristics