![Page 1: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/1.jpg)
The Lightning Discharge
The Lightning Discharge
””
![Page 2: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/2.jpg)
ElectrostaticField5 to 30 kV/M
![Page 3: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/3.jpg)
108 V + 10%Ionized Path
![Page 4: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/4.jpg)
Step 10 - 260 Meters= Striking Distance (r)
+ + + + +
++++++
+ + + + +
r =Striking Distance
High Density Charge
r
Point of Discrimination+
+ +
+ +
+ +
+ +
+
+ + + + ++ + + + + + + + + +
10 < 40 Coulombs10 < 40 Coulombs
Striking Distance
Upward Streamers
+ +
+ +
+
![Page 5: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/5.jpg)
Storm GeneratedUpward Streamers
![Page 6: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/6.jpg)
•• SizeSize–– RangeRange 10 to 103 kM10 to 103 kM22
–– AverageAverage 15 kM15 kM2 2
•• ChargeCharge–– RangeRange 10 to 120 C10 to 120 C–– 99%99% 40 C40 C
•• Voltage at peak Voltage at peak 101099 to 10to 101010 VoltsVolts
•• Height Above Earth Height Above Earth 0.1 to 6 0.1 to 6 kMkM
Pre-Discharge(Cell Data)
PrePre--DischargeDischarge(Cell Data)(Cell Data)
![Page 7: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/7.jpg)
Leader Data (99%)Leader Data (99%)
•• Total ChargeTotal Charge 1 to 20 C1 to 20 C•• Average ChargeAverage Charge 5 C5 C•• Per Unit LengthPer Unit Length 1010--3 C/M3 C/M•• Propagation Speed Propagation Speed 0.4 0.4 -- 1.2 M/us1.2 M/us•• Pulse Rise TimePulse Rise Time 100 ns100 ns•• Leader PotentialLeader Potential 107 107 –– 1010 Volts1010 Volts•• Step Time Step Time 13 to 50 us13 to 50 us•• Step LengthStep Length 10 to 200 Meters10 to 200 Meters
![Page 8: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/8.jpg)
Return Stroke DataReturn Stroke DataPeak CurrentPeak Current 2 to 510 kA2 to 510 kA
99%99% << 200 kA200 kA
50%50% ≅≅ 30 kA30 kA
Polarity NegativePolarity Negative > 90%> 90%
Time Between flashesTime Between flashes > 10 Seconds> 10 Seconds
No. Strokes per Flash No. Strokes per Flash 11--2727
Time Between StokesTime Between Stokes 10 10 –– 30 ms 30 ms
Duration (99%)Duration (99%) 30 to 200 30 to 200 µµss
RFI Range (95%)RFI Range (95%) 200 kHz 200 kHz -- 20 20 mHzmHz
![Page 9: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/9.jpg)
+ + ++ ++ +
+ +++
+ ++
+ + + +
+ ++
+
+ + +++
Buried Data & Phone Lines
Earth Current TransientsEarth Current Transients
Nearby Strike
![Page 10: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/10.jpg)
Atmospheric TransientsAtmospheric Transients
Varying ElectrostaticField
Varying ElectrostaticField
Nearby StrikeNearby Strike
*Suspended Power Lines
*Inter-PlantData Lines
*Will Experience Induced Transients
![Page 11: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/11.jpg)
Computer System
PBXSatellite System
EMP Field
EMP Field
IT
ITIT
IT: Induced Transients
didt
= 100 kAus
Stroke Channel EMPStroke Channel EMP
![Page 12: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/12.jpg)
Note: A ground of 5 ohm develops 100kVduring a 50%tile strike
Grounding Resistance
Grounding ProblemGrounding Problem
![Page 13: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/13.jpg)
Secondary Effects SummarySecondary Effects Summary
• Earth Current Transients• Atmospheric Transients• Electromagnetic Pulse• The Bound Charge• Electrostatic Pulse
• Earth Current Transients• Atmospheric Transients• Electromagnetic Pulse• The Bound Charge• Electrostatic Pulse
![Page 14: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/14.jpg)
Strike Risk AssessmentStrike Risk Assessment•• Not An Exact ScienceNot An Exact Science•• One Strike Indicates Risk Of OthersOne Strike Indicates Risk Of Others•• Inconsistent HistoryInconsistent History•• Requires At Least 20 Years of StatisticsRequires At Least 20 Years of Statistics•• Depends On:Depends On:
•• Isokeraunic NumberIsokeraunic Number•• Structure, Height and SizeStructure, Height and Size•• Surroundings Surroundings •• Storm PatternsStorm Patterns
![Page 15: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/15.jpg)
![Page 16: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/16.jpg)
World Isokeraunic Map
![Page 17: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/17.jpg)
The OptionsThe Options
CollectorsCollectors
DivertersDiverters
PreventorsPreventors
![Page 18: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/18.jpg)
Air Terminal Concepts (not technology)
H
R
Assumed Protected Area
H1R2 Assumed
Protected Area
R1
No supporting foundation in physics*
*According to NFPA-780 9/99 study
![Page 19: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/19.jpg)
![Page 20: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/20.jpg)
Power Surges & Induced Transients(Power Lines)Power Surges & Induced Transients(Power Lines)
Induced Transients(Data & Control Lines)Induced Transients(Data & Control Lines)
Points Of VulnerabilityPoints Of VulnerabilityDirect Strikes(Towers, Elevated Structures)Direct Strikes(Towers, Elevated Structures)
![Page 21: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/21.jpg)
BRINGING LIGHTNING BRINGING LIGHTNING STRIKE PREVENTION STRIKE PREVENTION
INTO INTO THE 21st CENTURYTHE 21st CENTURY
![Page 22: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/22.jpg)
The Industry Standards…The Industry Standards…The Industry Standards…
• Over 250 Years with no Significant Changes
• No Foundation in Physics• Based on “historical precedent”
•• Over 250 Years with no Over 250 Years with no Significant ChangesSignificant Changes
•• No Foundation in PhysicsNo Foundation in Physics•• Based on “historical precedent” Based on “historical precedent”
![Page 23: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/23.jpg)
The Advent of CTSThe Advent of CTS
•• December 2001 December 2001 Over 33,000 System Years of Over 33,000 System Years of Accumulated Performance Accumulated Performance History.History.
![Page 24: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/24.jpg)
Foundational DefinitionsFoundational Definitions
•• Lightning is a DischargeLightning is a Discharge•• Discharge Transfers Charge Discharge Transfers Charge
(Ampere(Ampere--Seconds)Seconds)•• The CTS is a Charge Transfer The CTS is a Charge Transfer
System (CTS = generic name)System (CTS = generic name)
![Page 25: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/25.jpg)
The CTS ObjectiveThe CTS Objective•• Use Points to Transfer Charge Use Points to Transfer Charge
From Site Slowly and ContinuouslyFrom Site Slowly and Continuously•• Use the Storm Electric Field for Use the Storm Electric Field for
Motivating ForceMotivating Force
![Page 26: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/26.jpg)
The Technological Basis Demonstrated
The Technological Basis The Technological Basis DemonstratedDemonstrated
•• Field ExperimentsField Experiments
4 sets, 3 points4 sets, 3 points170 µa170 µa
![Page 27: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/27.jpg)
LEC SimulatorLEC Simulator
Defines Ionization Capability
![Page 28: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/28.jpg)
Lab TestsLab TestsMeasuring Point Discharge Current As A Measuring Point Discharge Current As A Function Of VoltageFunction Of Voltage
Visible CoronaVisible Corona
![Page 29: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/29.jpg)
A Visible Space ChargeA Visible Space ChargeSecurity Camera Video PhotoSecurity Camera Video Photo
ExxonMobile Bay, Alabama
ExxonExxonMobile Mobile Bay, Bay, AlabamaAlabama
####
![Page 30: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/30.jpg)
Strike Prevention Strike Prevention RequirementsRequirements
•• Prevent formation of upward leader Prevent formation of upward leader
from protected site.from protected site.
•• Prevent termination of downward Prevent termination of downward
leader from storm cell.leader from storm cell.
![Page 31: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/31.jpg)
< 30kV/m< 30kV/mCell inducedCell inducedCharge Charge (electrostatic shadow)(electrostatic shadow)
The The PrestrikePrestrike SituationSituation
![Page 32: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/32.jpg)
Isolating the SiteIsolating the SiteSpace ChargeSpace ChargePrevents Rising Prevents Rising LeadersLeaders
ProtectedProtectedArea (a)Area (a)
Cell Induced Cell Induced Charge (A)Charge (A)
IonizerIonizer
(GCC)Ground CurrentCollector
(GCC)Ground CurrentCollector
![Page 33: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/33.jpg)
Space ChargeSpace ChargeShieldShield
Up to 7000% reduction*Up to 7000% reduction*(to less than 500V/mtr.)(to less than 500V/mtr.)
< 30kV/m< 30kV/m
Protected AreaProtected Area
Electrostatic Field MeasurementsElectrostatic Field Measurements
* Major test site in Singapore
SensorSensor
![Page 34: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/34.jpg)
CTS ConclusionsCTSCTS ConclusionsConclusions
1. Sound Theoretical Bases (in physics)2. Verifiable Statistics (before/after data) 3. Theory Validated in Worldwide Lab & Field
Testing Programs
1.1. Sound Theoretical Bases (in physics)Sound Theoretical Bases (in physics)2.2. Verifiable Statistics (before/after data) Verifiable Statistics (before/after data) 3.3. Theory Validated in Worldwide Lab & Field Theory Validated in Worldwide Lab & Field
Testing ProgramsTesting Programs
![Page 35: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/35.jpg)
LEC’s CTS
Applications
WORLDWIDEINSTALLATIONS
LEC’s CTS
Applications
WORLDWIDEWORLDWIDEINSTALLATIONSINSTALLATIONS
![Page 36: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/36.jpg)
Off Shore PlatformOff Shore Platform
Papua, New Guinea
![Page 37: The Lightning Discharge - Dynamic positioningdynamic-positioning.com/proceedings/dp2004/environment_carpenter... · Exxon Mobile Bay, Alabama Exxon Mobile Bay, Alabama ## Strike Prevention](https://reader031.vdocuments.us/reader031/viewer/2022022521/5b27eb517f8b9a97338b4662/html5/thumbnails/37.jpg)
What a Recent IEEE Paper Said
“The end may be near for the two hundredyear old method of using Franklin rods to collect, control and convey to earth the awesome and destructive power of lightning.”
“The charge transfer system of preventinglightning strikes to the protected area is a valid concept and will replace the Franklinrod method.”
Donald W. Zipse, P.E., Life Fellow IEEE