Page 1: The Installation of Electric Fence - st.gov.my · Figure 4 : Lightning protection system and component used iv. Annex CC – Installation of electric security fences Annex CC.2 –
Page 2: The Installation of Electric Fence - st.gov.my · Figure 4 : Lightning protection system and component used iv. Annex CC – Installation of electric security fences Annex CC.2 –

1

Page 3: The Installation of Electric Fence - st.gov.my · Figure 4 : Lightning protection system and component used iv. Annex CC – Installation of electric security fences Annex CC.2 –

2 The Installation of Electric Fence 3

PARTIES WHO NEED TO KNOW ABOUT THE PROCEDURE OF INSTALLING THE ELECTRIC FENCE

THE INSTALLATION OF ELECTRIC FENCE

All Competent Persons: Engineer, Supervisor, Chargeman, Wireman

All Registered Electrical Contractors with Energy CommissionAll Utilities: Electric, Water & Telecommunication

All Government Departments: Federal & State

All Premise Owners: Commercials or Industrial

PURPOSEThis booklet is intended to enforce the method of installing the electric fence

in order to improve the safety level of the installation according to MS IEC

60335-2-76 standard. This booklet is also to inform of the procedures that

must be complied with by the applicant in order to obtain approval from the

Energy Commission on the installation of electric fence.

BACKGROUNDPreviously the Energy Commission had issued a directive and a circular

pertaining to the needs and method of installing the electric fence. In line

with the current technology, the existing directive and previous circular of

installing the electric fence need to be revised. Therefore, a conducive and

comprehensive method of installing the electric fence concurrent to the

international standards needs to be prepared.

Generally the installation of electric fence installed by some parties is to

prevent their properties from being trespassed by intruders either animal or

human. The types of premises involved in the installation of electric fence are

those that involve activities related to agriculture and security control such

as military, power utility, water and others. Therefore, these installations of

electric fence need to be installed in a control manner and safe in accordance

to the Electricity Supply Act 1990, Electricity Regulations 1994 and other

relevant standards so as to prevent the occurrence of on the part of the

intruder/trespasser.

COMPLIANCE WITH LEGISLATION The proper and safe method of installing the electric fence shall begin

from the stage of design until the stages of construction, supervision,

maintenance and monitoring. It needs to be implemented in accordance

with the requirements of the Electricity Regulations 1994. The respective

regulations that need to be complied with are as follows:-

• Regulation 15 : Requirement of any conductor for the purpose

of connection to an installation which shall be constructed, installed,

arranged, protected, worked and maintained shall be sufficient in size,

power and number as to prevent danger.

• Regulation 65 : Requirement of competent persons (Part VI of the

Second Schedule) who shall prepare and submit plans, drawings and

specifications for voltage/ampere limit of an installation.

• Regulation 68 : Requirement to appoint competent person either an

Electrical Services Engineer, Competent Electrical Engineer or Electrical

Supervisor to inspect the electric fence installation.

• Regulation 75 : Requirement to appoint a registered electrical

contractor with Energy Commission which hold a valid Certificate of

Registration to perform or carry out the installation of electric fence.

• Regulation 110 : Electric fence installation shall be maintained in

good, working order and safety precautions shall be observed at all times

to prevent danger.

Page 4: The Installation of Electric Fence - st.gov.my · Figure 4 : Lightning protection system and component used iv. Annex CC – Installation of electric security fences Annex CC.2 –

4 The Installation of Electric Fence 5

• Regulation 111 : Requirement to appoint a competent person or

a person acting under the control of a competent person who shall

undertake to carry out any repair, replacement, servicing or cleaning of

the installation.

METHODS OF ELECTRIC FENCE INSTALLATIONTo ensure the installation of electric fence is continuously carried out in a

proper and safe manner, the Energy Commission has provided the method of

installing the electric fence which complies with standard of MS IEC 60335-

2-76 – Particular requirements for electric fence energizers.

(Note: MS IEC 60335-2-76 standard can be purchased from SIRIM Berhad)

Some of the main priorities that need to be emphasized during the construction

stage of electric fence either of energizer type A, B, C, or D are as stated in

the clauses and Annexes of MS IEC 60335-2-76 standard as follows:-

i. Clause 22.108 - Energizer output characteristics shall be such that

- the impulse repetition rate shall not exceed 1 Hz

- the impulse duration of the impulse in the 500 Ω component of the

standard load shall not exceed 10 ms

- for energy limited energizers the energy/impulse in the 500 Ω

component of the standard load shall not exceed 5 Joule (J)

Figure 1 : Measurement of voltage value at electric fence (pulse conductor) being done using Voltmeter.

ii. Clause 22.109 - If the energizer is provided with more than one fence

circuit (sometimes it defines zone), the output characteristics shall

be within limits in 22.108 for any possible connection of the fence

circuits. The impulses for the individual sets of output terminals shall

be synchronized.

Figure 2 : The use of panel for synchronizing supply system if more than one energizer applies.

Figure 3 : Area which is supplied by more than one different sources of energizers has been synchronized for supply to the electric fence.

Page 5: The Installation of Electric Fence - st.gov.my · Figure 4 : Lightning protection system and component used iv. Annex CC – Installation of electric security fences Annex CC.2 –

6 The Installation of Electric Fence 7

iii. Annex BB – Instructions for installation and connection of electric

fences.

Annex BB1 & BB2 – Requirements for electric animal/security

fences:-

- Any electric animal/security fence shall not be supplied from two

separate energizers or from independent fence circuits of the same

energizer.

- For any two separate electric animal/security fences, each supplied

from a separate energizer independently timed, the distances between

the wires of the two electric animal/security fences shall be at least

2.0/2.5 m. If this gap is to be closed, this shall be effected by means

of electrically non-conductive material or an isolated metal barrier.

Figure 5 : Earthing system for the installation of electric fence

Figure 6 : Distance of physical barrier shall be at least 2.0 / 2.5 meters if receives two supplies from different energizers and both supplies not synchronised. (Note: 2.0 m for animal while 2.5 m for security)

Figure 4 : Lightning protection system and component used

iv. Annex CC – Installation of electric security fences

Annex CC.2 – Location of electric security fence

- The electric fence should be separated from the public access area

by means of a physical barrier.- Where an electric fence is installed in an elevated position, such as on

the inner side of a window or skylight, the physical barrier may be less

than 1.5 m high where it covers the whole of the electric fences. If the

bottom of the window or skylight is within a distance of 1.5 m from the

floor or access level then the physical barrier need only extend up to

a height of 1.5 m above the floor or access level.

(Note: Refer to figures 7, 8 & 9 for examples of physical barrier)

Figure 7 : A physical barrier type based on a combination of concrete wall and chain-link (wire) constructed at least 1.5 meter height. The pulse conductor is installed begins on the concrete wall.

Page 6: The Installation of Electric Fence - st.gov.my · Figure 4 : Lightning protection system and component used iv. Annex CC – Installation of electric security fences Annex CC.2 –

8 The Installation of Electric Fence 9

REMINDER!

A Competent Electrical Engineer must ensure the installation of electric

fence under his responsibility is installed in compliance with the standard of

MS IEC 60335-2-76.

(Note: The latest version of the standard MS IEC 60335-2-76 needs to be referred to from time to time).

Figure 8 : A physical barrier type of concrete wall constructed at least 1.5 meter height. The pulse conductor installed begins on the concrete wall.

Figure 9 : A physical barrier type made of chain-link (steel) been constructed at least 1.5 meter height. The pulse conductor installed begins on the steel.

OTHER INFORMATION RELATED TO THE INSTALLATION OF ELECTRIC FENCE (Figures 10 & 11)

(Note: The electric fence owned by a premise owner is ONLY allowed to

be commissioned when it has obtain in the written approval from Energy

Commission via its regional offices. The procedure of application is as

Attachment A).

Figure 10 : The distance comply to the requirement of clauses as Annex CC1 & CC4

Figure 11 : Other components used

Page 7: The Installation of Electric Fence - st.gov.my · Figure 4 : Lightning protection system and component used iv. Annex CC – Installation of electric security fences Annex CC.2 –

10 The Installation of Electric Fence 11

PROCEDURES OF ELECTRIC FENCE APPLICATION

1. Applicant is required to make application of installing the electric fence

at the nearest Energy Commission regional office where the installation

is located. Applicant need to complete the Application of Approval on

Installation of Electric Fence Form (as Attachment B). This form can

be downloaded from the ST website. The following are the documents

required to be enclosed together :-

i) Name premise / installation owner;

ii) Address where the electric fence will be installed and the total perimeter

of the installation

iii) The registered electrical contractor with ST who will install the electric

fence;

iv) Diagrams and specification of the electric fence which shows the

complete structure of the height, type of equipment, product, signage

and others. All components and equipment in the diagrams need to

be clearly labeled. These diagrams need to be signed at least by a

Competent Electrical Engineer who has been engaged by the owner.

v) Schematic drawing shows the sources of electric supply to the

conductivity of wire of the fence, size and type of cable being used.

This schematic drawing need to be signed at least by a Competent

Electrical Engineer who has been engaged by the owner.

vi) The submission of certification and test report for the energizer (type A,

B, C or D) must comply with the IEC 60335-2-76:2006 standard from

IEC CB Scheme laboratories or APLAC.

(Note : Energizer is not a regulated equipment therefore once it imported to Malaysia the importer needs to obtain a release letter from the Custom’s office issued by Energy Commission)

vii) Once the installation of electric fence ready, it needs to be supervised

and tested by the competent person who has been engaged by the

owner. Therefore, the engaged competent person shall submit to

the Energy Commission the Form G (Supervision and Completion

Certificate) and Form H (Test Certificate) as required by Regulation 14,

Electricity Regulations 1994.

viii) An inspection will be carried out by Energy Commission officers once

the installation of electric fence is completed. The visit will be carried

out together with the engaged electrical contractor, the responsible

Electrical Supervisor/Competent Electrical Engineer and the owner/

representative of the installation.

ix) Once the Energy Commission’s regional office satisfied on the

compliance of installing the electric fence, a written approval will be

issued to the owner. Once the owner has obtained the approval from

the Energy Commission, the electric fence can start operation or

commission.

x) The owner of the electric fence installation shall engage a competent

person with a minimum of an Electrical Supervisor level to inspect the

installation at least once every two(2) years. This is to ensure installation

is always safe. The inspection report needs to be submitted to Energy

Commission.

xi) There is no fee imposed for the approval.

xii) The Energy Commission will cancel the approval letter on the electric

fence installation if the installation is either :-

a. no longer being used; or/and

b. found to be unsafe

ATTACHMENT A

Page 8: The Installation of Electric Fence - st.gov.my · Figure 4 : Lightning protection system and component used iv. Annex CC – Installation of electric security fences Annex CC.2 –

12 The Installation of Electric Fence 13

2. The flow chart of the summarised procedure for the application on

installation of electric fence is shown below

FLOW CHART ON THE PROCEDURE OF ELECTRIC FENCE APPLICATION

APPLICATION OF APPROVAL ON INSTALLATION OF ELECTRIC FENCE

UNDER REGULATION 15, ELECTRICITY REGULATION 1994

ATTACHMENT B

Name of the owner

(Either an individual/representative of company or agency. If company/agency, name of the responsible officer)

Identification Card No.(please submit a photocopy of NRIC)

No. of Company Registration(only if applicable)

Address of the owner

Address of Electric Fence

Installation (if different from the address of the owner)

Purpose of installing the electric

fence

Duration of the installationI understand and acknowledge that the installation of electric fence at the above premise need to comply with the Electricity Supply Act 1990 & Electricity Regulations 1994 and the requirements set by the Energy Commission.

Signature of the owner & company’s / agency’s stamp:…………………………Date:…………………………………

Name of the Company

Certificate of Registration No. with

Energy Commission (please submit a copy of valid certificate)

Validity date of the certificate

Part A: INFORMATION ON INSTALLATION

Part B: INFORMATION ON ELECTRICAL CONTRACTOR

Page 9: The Installation of Electric Fence - st.gov.my · Figure 4 : Lightning protection system and component used iv. Annex CC – Installation of electric security fences Annex CC.2 –

14 The Installation of Electric Fence 15

Approval Application on Installation of Electric Fence under Regulation 15, Electricity Regulations 1994 Approval Application on Installation of Electric Fence under Regulation 15, Electricity Regulations 1994

Part C: INFORMATION ON ELECTRIC FENCE Part D: APPROVAL / CANCELLATION

APPROVAL by Energy Commission:

CANCELLATION of Approval Letter:

ST Regional Office

__________________

__________________

ST Regional Office

__________________

__________________

Reasons for cancellation: ________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

______________________________________________________________________

Date:_________

Date:_________

Diagram & specification of electric fence structure(please submit each diagram & brochure if available)• Structureoftheelectricfence• Typeofenergizer(Type A, B, C or D)•Wireoffence•Certification / test report & ST’s

Release Letter on energizer according to IEC 60335-2-76:2006 or MS IEC 60335-2-76 standard

•Configurationofwiring•Configurationofearthing

Reference:Reference:Reference:Reference:

Reference:Reference:

Drawing of site layout (please submit each diagram)

• Fencinglayout• Photosoffence&warning

signage• Single-lineschematicdrawingfor

supply source to energizer• Single-lineschematicdrawingfor

output of each energizer circuit

Reference:Reference:

Reference:

Reference:

Signature of Competent Electrical Engineer who endorsed the diagram & drawing.

Complete / Incomplete

Certificate of Competency No.

Form G (Supervision and Completion) need stamp & signature of competent person

Complete / Incomplete

Form H (Test) need stamp & signature of competent person

Complete / Incomplete

The site visit by ST together with electrical contractor and the responsible competent person has been conducted on the date as below:-

________________________

Satisfy / Not satisfy (If not satisfy, please improve the conditions as follows:

(………………………………….......................….

………………………………………………………

………………………………………………………

……………….......................................................)(use attachment if the space is insufficient)

Page 10: The Installation of Electric Fence - st.gov.my · Figure 4 : Lightning protection system and component used iv. Annex CC – Installation of electric security fences Annex CC.2 –

16 The Installation of Electric Fence 17

Regional Office (Pulau Pinang, Kedah & Perlis)Tingkat 10, Bangunan KWSP

13700 Seberang Jaya, Butterworth

PULAU PINANG

Tel: 04-398 8255

Fax: 04-390 0255

Regional Office (Perak)Tingkat 1, Bangunan KWSP

Jalan Greentown

30450 Ipoh

PERAK

Tel: 05-253 5413

Fax: 05-255 3525

Regional Office (Kelantan & Terengganu)Tingkat 6, Bangunan KWSP

Jalan Padang Garong

15000 Kota Bharu

KELANTAN

Tel: 09-748 7390

Fax: 09-744 5498

Regional Office (Pahang)Tingkat 7, Kompleks Teruntum

Jalan Mahkota

25000 Kuantan

PAHANG

Tel: 09-514 2803

Fax: 09-514 2804

List of Energy Commission Regional Offices and Address

Regional Office (Selangor, Kuala Lumpur & Putrajaya)Tingkat 10, Menara PKNS

No.17, Jalan Yong Shook Lin

46050 Petaling Jaya

SELANGOR

Tel: 03-7955 8930

Fax: 03-7955 8939

Regional Office (Johor)Suite 18A, Aras 18

Menara ANSAR 65

Jalan Trus

80000 Johor Bharu

JOHOR

Tel: 07-224 8861

Fax: 07-224 9410

Regional Office (West Coast of Sabah)Tingkat 7, Bangunan BSN

Jalan Kemajuan

88000 Kota Kinabalu

SABAH

Tel: 088-232 447

Fax: 088-232 444

Regional Office (East Coast of Sabah)Tingkat 3, Wisma Saban KM12

W.D.T. No.25

90500 Sandakan

SABAH

Tel: 089-666 695

Fax: 089-660 279

Page 11: The Installation of Electric Fence - st.gov.my · Figure 4 : Lightning protection system and component used iv. Annex CC – Installation of electric security fences Annex CC.2 –

18 The Installation of Electric Fence 19

Regional Office (Negeri Sembilan & Melaka)Tingkat 4, Wisma Perkeso

Jalan Persekutuan, MITC

75450 Ayer Keroh

MELAKA

Tel: 06-231 9594

Fax: 06-231 9620

Note

Page 12: The Installation of Electric Fence - st.gov.my · Figure 4 : Lightning protection system and component used iv. Annex CC – Installation of electric security fences Annex CC.2 –

20 The Installation of Electric Fence

Note