the energy modeling improv game: can your team achieve the lowest eui?
TRANSCRIPT
THE GAME QUARTER #1 QUARTER #2
QUARTER #3 QUARTER #4
MASSING &
ORIENTATION
BUILDING
ENVELOPE
INTERNAL LOADS FRESH
START
THE BUILDING
• Building Type: Outpatient Clinic –
Business Occupancy
• Location: Houston, TX
• Size: 50,000 gsf
STARTING LINE
ASHRAE 90.1-2007
• 40% WWR
• U(net)-0.75, SHGC-0.25, VT-0.275
• Steel framed walls with R-13 batt
• Roof insulation entirely above deck
R-20
Heating
7%
Receptacles
25%
DHW
2%
Cooling
27%
Lights
26%
Fans
11%
Heat rejection
2%
MASSING &
ORIENTATIONQUARTER #1
SELECT AN ORIENTATION
NRow 1
Row 3
Row 2
L-Shape Courtyard U-Shape Rectangle(100’x250’)
H-Shape
MASSING &
ORIENTATION QUARTER #1
TEAM B RESULTS
0
100
200
300
400
500
600
Heating Receptacles DHW Cooling Lights Fans Heat rejection
An
nu
al E
ne
rgy C
on
su
mp
tio
n (
MB
tu)
Starting Line Q1 Q2 Q3 Q4
Q 0 1 2 3 4
EUI (kBtu/ft2) 42 41 39 37 37
Peak Cooling (tons) 118 113 113 109 114
BUILDING
ENVELOPEQUARTER #2
SELECT 3 OF THE FOLLOWING ENVELOPE MODIFICATIONS:
A. ROOF INSULATION
B. EXTERIOR WALL INSULATION
C. WINDOW GLASS TYPE
E. WINDOW EXTERIOR SHADING
3
D. WINDOW AREA
QUARTER #2: Envelope Modification ( select only 3 of the following 5 options ):
A. Roof Insulation
0 3” Polyurethane R-20
1 4” Polyurethane R-25
2 5” Polyurethane R-30
3 6.5” Polyisocyanurate R-40
B. Exterior Wall Insulation
0 Steel-framed R-13 batt R-6
1 + 1.5” Polystyrene ci R-5
2 + 2” Polyurethane ci R-12
3 + 3” Polyisocyanurate ci R-20
Window Area
0 40% Window-to-Wall Area
1 20% Window-to-Wall Area
2 60% Window-to-Wall Area
3 70% Window-to-Wall Area
C. Window Glass Type
U-Value SHGC VT
0 0.75 0.25 0.275
1 0.36 0.23 0.47
2 0.50 0.25 0.275
3 0.50 0.66 0.73
4 0.45 0.40 0.50
D. Exterior Shading
Horizontal overhang 0.5 projection factor
A B PF=A/B
BUILDING
ENVELOPEQUARTER #2
TEAM B RESULTS
3
0
100
200
300
400
500
600
Heating Receptacles DHW Cooling Lights Fans Heat rejection
An
nu
al E
ne
rgy C
on
su
mp
tio
n (
MB
tu)
Starting Line Q1 Q2 Q3 Q4
Q 0 1 2 3 4
EUI (kBtu/ft2) 42 41 39 37 37
Peak Cooling (tons) 118 113 113 109 114
INTERNAL LOADSQUARTER #3
SELECT 2 OF THE FOLLOWING INTERNAL LOAD MODIFICATIONS:
A. 10% Lighting Power Density Reduction
B. 50% Plug Load On Occupancy Sensors
C. Skylights to Achieve 50% Daylight Zone
D. Side Daylight Harvesting
INTERNAL LOADSQUARTER #3
TEAM B RESULTS
0
100
200
300
400
500
600
Heating Receptacles DHW Cooling Lights Fans Heat rejection
An
nu
al E
ne
rgy C
on
su
mp
tio
n (
MB
tu)
Starting Line Q1 Q2 Q3 Q4
Q 0 1 2 3 4
EUI (kBtu/ft2) 42 41 39 37 37
Peak Cooling (tons) 118 113 113 109 114
FRESH
STARTQUARTER #4
MASSING & ORIENTATION
INTERNAL LOADS – 2 of 4
FRESH START
BUILDING SHAPE & ORIENTATION
ROOF INSULATION
EXTERIOR WALL INSULATION
WINDOW GLASS TYPE
DAYLIGHT HARVESTING LIGHTING POWER REDUCTION
SELECT OPTIONS LISTED BELOW:
SKYLIGHTS
BUILDING ENVELOPE – 3 of 5
PLUG LOAD CONTROLS
WINDOW AREA
EXTERIOR SHADING
DOES YOUR DESIGN
MEET CODE?
0
100
200
300
400
500
600
Heating Receptacles DHW Cooling Lights Fans Heat rejection
An
nu
al E
ne
rgy C
on
su
mp
tio
n (
MB
tu)
Starting Line 2015 IECC
FRESH
STARTQUARTER #4
TEAM B RESULTS
INTERNAL LOADS – 2 of 4
FRESH START
0
100
200
300
400
500
600
Heating Receptacles DHW Cooling Lights Fans Heat rejection
An
nu
al E
ne
rgy C
on
su
mp
tio
n (
MB
tu)
Starting Line Q1 Q2 Q3 Q4 2015 IECC
Q 0 1 2 3 4 2015 IECC
EUI (kBtu/ft2) 42 41 39 37 37 39
Peak Cooling (tons) 118 113 113 109 114 115