the effect of combining a relative-humidity-sensitive ventilation system with the moisture-buffering...

Upload: patricioperez-guerrero

Post on 30-May-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/14/2019 The Effect of Combining a Relative-humidity-sensitive Ventilation System With the Moisture-buffering Capacity of

    1/10

    The effect of combining a relative-humidity-sensitive ventilation system with

    the moisture-buffering capacity of materials on indoor climate and energy

    efficiency of buildings

    Monika Woloszyn a,b,c,, Targo Kalamees d, Marc Olivier Abadie e,f, Marijke Steeman g,Angela Sasic Kalagasidis h

    a Universite de Lyon, Lyon F-69003, Franceb Universite Lyon1, Villeurbanne F-69622, Francec INSA-Lyon, CETHIL UMR CNRS 5008, bat. Sadi Carnot, F-69621 Villeurbanne cedex, Franced

    Chair of Building Physics and Architecture, Tallinn University of Technology, Ehiteja tee 5 19086, Estoniae Pontifical Catholic University of Parana PUCPR/CCET-Thermal Systems Laboratory, Rua Imaculada Conceic- ao, 1155 Curitiba, PR 80215-901, BrazilfLEPTIAB-University of La Rochelle, Avenue M. Crepeau, 17000 La Rochelle, Franceg Department of Architecture and Urban Planning, UGENT-Ghent University, J. Plateaustraat 22, 9000 Ghent, Belgiumh Department of Building Technology, Chalmers University of Technology, Sven Hultins gata 8, 412 96 Gothenburg, Sweden

    a r t i c l e i n f o

    Article history:

    Received 23 November 2007

    Received in revised form

    20 April 2008

    Accepted 22 April 2008

    Keywords:

    Whole building HAM simulationRelative-humidity-sensitive (RHS)

    ventilation system

    Moisture-buffering

    Energy

    Indoor climate

    a b s t r a c t

    Indoor moisture management, which means keeping the indoor relative humidity (RH) at correct levels,

    is very important for whole building performance in terms of indoor air quality (IAQ), energy

    performance and durability of the building. In this study, the effect of combining a relative-humidity-

    sensitive (RHS) ventilation system with indoor moisture buffering materials was investigated. Four

    comprehensive heatairmoisture (HAM) simulation tools were used to analyse the performance of

    different moisture management strategies in terms of IAQ and of energy efficiency. Despite some

    differences in results, a good agreement was found and similar trends were detected from the results,

    using the four different simulation tools. The results from simulations demonstrate that RHS ventilation

    reduces the spread between the minimum and maximum values of the RH in the indoor air and

    generates energy savings. Energy savings are achieved while keeping the RH at target level, not allowing

    for possible risk of condensations. The disadvantage of this type of demand controlled-ventilation is

    that other pollutants (such as CO2) may exceed target values. This study also confirmed that the use of

    moisture-buffering materials is a very efficient way to reduce the amplitude of daily moisture

    variations. It was possible, by the combined effect of ventilation and wood as buffering material, to keep

    the indoor RH at a very stable level.

    & 2008 Elsevier Ltd. All rights reserved.

    1. Introduction

    Indoor moisture management, which means keeping theindoor relative humidity (RH) at correct levels, is very important

    for whole building performance in terms of indoor air quality

    (IAQ), energy performance and durability of the building envel-

    ope. Indeed, indoor air humidity strongly affects indoor climate.

    The main risk factors related to low RH may be associated with

    the dryness of the skin, mucous membranes, sensory irritation of

    the eyes and upper airways [13] as well as control of static

    electricity [4,5]. The risk factors of having high RH are connected

    with serious moisture problems for the building envelope and for

    the indoor climate [610], due to the growth of micro-organisms

    [11,12] and house dust mites [1315].Indoor air moisture is influenced by several factors, such as

    moisture sources (human presence and activity, equipment), air

    change rate and airflow in rooms, the release or uptake of

    moisture by hygroscopic surfaces of envelope and furniture,

    moisture flow through building envelope, possible condensation

    as well as moisture content of the outdoor air. Adequate

    ventilation is used in general in order to guarantee good IAQ

    and to keep the indoor RH at a target level. The effect of

    ventilation and resulting indoor humidity has a considerable

    impact on the energy performance of the building, especially in

    modern, very well insulated dwellings, where the part of the heat

    loss due to air renewal can account for as much as half of the total

    heat loss [16].

    ARTICLE IN PRESS

    Contents lists available at ScienceDirect

    journal homepage: www.elsevier.com/locate/buildenv

    Building and Environment

    0360-1323/$- see front matter & 2008 Elsevier Ltd. All rights reserved.doi:10.1016/j.buildenv.2008.04.017

    Corresponding author at: INSA-Lyon, CETHIL, bat. Sadi Carnot, F-69621

    Villeurbanne cedex, France. Tel.: +33472 436 269; fax: +33 472438 811.

    E-mail address: [email protected] (M. Woloszyn).

    Building and Environment 44 (20 09) 515 524

    http://www.sciencedirect.com/science/journal/baehttp://www.elsevier.com/locate/buildenvhttp://dx.doi.org/10.1016/j.buildenv.2008.04.017mailto:[email protected]:[email protected]://dx.doi.org/10.1016/j.buildenv.2008.04.017http://www.elsevier.com/locate/buildenvhttp://www.sciencedirect.com/science/journal/bae
  • 8/14/2019 The Effect of Combining a Relative-humidity-sensitive Ventilation System With the Moisture-buffering Capacity of

    2/10

    It is anticipated that the reduction of the amount of fresh cold

    air introduced into the building contributes to bringing down

    energy consumption. Evidently, the reduction of ventilation rates

    must be carefully designed to prevent deterioration of IAQ,

    including RH and pollutant levels. Previously conducted studies

    showed that humidity can be successfully used as a control

    parameter for ventilation, enabling energy savings without

    compromising IAQ throughout the whole year (both in cold andmild months). This is directly related to the reduction of mean

    ventilation rate, when the building is not used [17,18]. However,

    for dwellings with very high moisture load, the RHS ventilation

    may be used to improve IAQ, but lead to higher energy use [19].

    Moreover, relevant use of the moisture-buffering capacity of

    building materials contributes to stabilise the indoor climate in

    terms of variations of RH. For example, Ref. [20] showed that in

    the case of peak vapour production in the kitchen, about half of

    the produced vapour was absorbed by the materials. This

    moisture-buffering effect of materials was preventing surface

    condensation.

    All these interactions of indoor air humidity are complex, and

    realistic predictions of different factors require the use of

    advanced simulation tools. Simulation tools should be able totake the whole building into account and calculate room air

    humidity including exchange of moisture between indoor air and

    materials in contact with the indoor air. Several studies [2024]

    have shown that the moisture storage capacity of finishing

    materials has a significant effect on indoor RH and models that

    do not include the sorption process do not adequately model

    indoor RH. Mendes et al. [25] showed that whole-building energy

    simulation models that ignore moisture transfer in the building

    envelope may overestimate conduction peak loads up to 210% and

    underestimate the yearly integrated heat flux up to 59% that can

    lead to oversize heating, ventilation and air conditioning equip-

    ment (especially in dry climates) and underestimate energy

    consumption (primarily in humid climates).

    In this work, the possibilities of combining an RHS ventilation

    system with moisture-buffering capacity of materials were

    investigated with whole building HAM simulation tools. At the

    same time, four different simulation tools were tested to analyse

    the performance of different indoor moisture management

    strategies in terms of IAQ and of energy efficiency. Different

    simulation tools were used for two reasons: (1) to avoid any

    specific tool-related inaccuracy and (2) to compare capabilities

    and possible differences of different tools for assessing indoor

    moisture management issues.

    2. Methodology

    2.1. Studied configuration

    The simulation case is based on a real one-storey test building

    (see Fig. 1) with two rooms (volume 49.4 m3, area 19.3 m2), which

    are located at the outdoor testing site of the Fraunhofer-Institute

    of building physics in Holzkirchen, Germany (altitude: 680 m NN;

    latitude: 47.881, north; longitude: 11.731, east).

    The walls of the rooms were built with 24cm brick and

    externally insulated with 7 cm polystyrene. The internal surface in

    the reference room was standard gypsum plaster with a latex

    paint. The walls and the ceiling of the test room were first fully

    coated with aluminium foil and then (in some cases) covered with

    manufactured gypsum board (see Table 1). The roof was an 18 cm

    concrete slab, insulated with 20 cm polystyrene. A 25 cm concretefloor was insulated with 20 cm polystyrene and covered with PVC

    linoleum. Such material properties as density, porosity, specific

    heat capacity, thermal conductivity, moisture permeability, and

    moisture retention curve were measured in laboratory conditions

    and are described more in detail in Refs. [26,27].

    The indoor air temperature was held at 201C, using a

    temperature controlling electric heater in the centre of the room.

    A ventilation system provided constant air change, determined by

    tracer gas measurements (n 0.63h1 for the reference room and

    n 0.66h1 for the test room). To achieve a realistic assessment

    of the course of RH with regard to the moisture-buffering effect,

    2.4 kg of water was introduced by an ultrasonic evaporator into

    each room per day, which corresponds to the equivalent amount

    for a household of three persons [28].

    To differentiate short- and long-term moisture-buffering of

    surrounding surfaces, two moisture production cycles were

    chosen for each day: short but high moisture production in the

    morning from 6 to 8 a.m. (0.4 kg/h) and larger but moderate

    moisture production in the afternoon from 4 to 10p.m. (0.2 kg/h).

    ARTICLE IN PRESS

    Fig. 1. View and ground plan of test rooms: left-reference room with gypsum plaster and paint, and right-test room where different finishing materials were tested.

    Table 1

    Original finishing materials from experimental rooms

    Room Step 1 (17/0102/02) Step 2 (14/0219/03) Step 3 (28/0321/04)

    Reference (ach 0.63 h1) Gypsum plaster+paint Gypsum plaster+paint Gypsum plaster+paint

    Test (ach 0.66 h1) Aluminium foil Gypsum board on walls Gypsum board on walls+ceiling

    M. Woloszyn et al. / Building and Environment 44 (2009) 515524516

  • 8/14/2019 The Effect of Combining a Relative-humidity-sensitive Ventilation System With the Moisture-buffering Capacity of

    3/10

    These peaks simulate taking showers, washing, cooking and the

    presence of human beings. The temperature of the wall surfaces,

    temperature layering in the middle of the rooms, and RH in the

    rooms, as well as energy consumption of the heating system, were

    measured. The temperature and humidity in the centre of the

    room were considered for comparison. For outdoor boundary

    conditions, recorded weather data from Holzkirchen (January to

    April 2005) were used. In constant indoor temperature, indoor RHdepends on moisture production, air change rate, outdoor

    humidity by volume and on moisture flow exchanged between

    indoor air and building envelope. Two first parameters are the

    same in all steps. Outdoor humidity by volume was approximately

    the same in steps 1 and 2. In step 3, the outdoor humidity by

    volume was higher (see Fig. 2). Steps 1 and 2 presented cold and

    dry external conditions, and step 3 mild and humid ones.

    The influence of different ventilation system strategies and

    moisture-buffering capacity of the internal surface of finishing

    materials of building envelope on indoor RH were investigated. In

    some configurations, a constant airflow ventilation system was

    replaced by a RHS exhaust, where the ventilation airflow was

    controlled by the room RH level. Such a system adapts the airflow

    to changes in the indoor relative RH, as shown in Fig. 3 withRH1 25%, Q1 10m3/h, RH2 60%, Q2 40 m3/h. In some

    configurations, the moisture-buffering properties of the internal

    surface of finishing materials of the building envelope were

    changed.

    To study the influence of the ventilation system and properties

    of finishing materials, simulations were performed with five

    simulation runs (see Table 3):

    Run A: Experimental data, with constant ventilation (validationof the simulation models),

    Run B: Using original finishing materials (Table 1) and the

    original RHS ventilation system (Fig. 3), Run C: Using original finishing materials (Table 1) a n d a

    modified RHS ventilation system with modified maximum

    (Q2) and minimum (Q1) airflow values (ventilation was

    modified independently by the participants of the study),

    Run D: Using the original RHS ventilation system (Fig. 3), butchanging the moisture-buffering properties of materials

    (materials were chosen independently by the participants of

    the study), and

    Run E: Combining boththe ventilation and the materialsin order to reduce the energy consumption and to improve

    indoor RH.

    2.2. Simulation tools

    Four different commercially available simulation tools were

    used by five different institutions (see Table 2). All are whole-

    building simulation tools: multi-zone tools for building simula-

    tion of energy consumption, IAQ and thermal comfort in dynamic

    conditions, under the influence of the outdoor climate and

    variable loads. The different envelope parts (roof, walls and floor)

    may separate the zones from each other and from the outdoors.

    The geometry, material layers and their properties define the

    envelope parts. The envelope may include a number of openings,

    leaks, doors, and windows. Different heating, cooling, ventilation,

    and lighting systems can be attached to rooms. Heat balances may

    involve the heating/cooling devices, air handling units, elements

    of the envelope, direct sun gains through windows, leaks and

    thermal bridges, the internal thermal mass, occupants, lights,equipment.

    All four simulation tools include the main elements of

    moisture balance, discussed for example in Refs. [20,26,29]:

    vapour sources (occupants, equipment, etc.), airborne transport

    (air handling units, leaks, inter-zone flow) and sorption by

    materials in contact with the indoor air. The models of moisture

    flow between the indoor air and materials depend on the

    modelling of heat and moisture transfers in the elements of

    building envelope. Two tools can represent coupled heat and mass

    transfers in the envelope (IDA-ICE and HAM-Tools) and two use

    simplified models to represent the buffering effect of hygroscopic

    materials (TRNSYS and Clim2000). In the following, the main

    elements of moisture-buffering modelling are described, and

    reference is made to the literature for further details of the

    physical models used in the simulation tools.

    2.2.1. Moisture transfer through the envelope parts

    2.2.1.1. Coupled heat and mass flow models. Detailed, one-dimen-

    sional coupled heat and water vapour transfer models are im-

    plemented in IDA-ICE and HAM-Tools. Both are based on similar

    equations, and suppose that moisture transfer is governed by one

    moisture transfer potential, the humidity by volume, v (kg/m3).

    The governing equations for the moisture (1) and energy (2)

    transfer are then:

    qv

    qt

    q

    qxdv

    qv

    qx

    , (1)

    rcqTqt

    qqx

    l qTqx

    hvap qv

    qt, (2)

    ARTICLE IN PRESS

    Fig. 2. Outdoor conditions for all three steps.

    Relative

    Humidity (%)

    Q2

    Q1

    RH1

    Air flow(m3/h)

    RH2

    Fig. 3. Original RHS ventilation system test room (no moisture-bufferingmaterials) and reference room (painted plaster).

    M. Woloszyn et al. / Building and Environment 44 (2009) 515524 517

  • 8/14/2019 The Effect of Combining a Relative-humidity-sensitive Ventilation System With the Moisture-buffering Capacity of

    4/10

    where r is the density of the material (kg/m3), dv is the vapour

    permeability (m2/s), l is the thermal conductivity [W/(m K)], c is

    the specific heat capacity of the material [J/(kg K)] and hvap is the

    latent heat of vaporisation (J/kg). In the current study, the liquidflow and airflow through the envelope are neglected. This sim-

    plification does not influence the result, because infiltration air-

    flow is included to the overall ventilation rate and condensation

    did not occur. The walls are discretised, using finite volume

    method with several nodes per wall.

    2.2.1.2. Simplified moisture-buffering models. Both TRNSYS versions

    and Clim2000 simulation tools only compute heat transfers in

    building envelope elements and use simplified models to assess

    moisture-buffering capacity of materials in contact with the in-

    door air. Both tools use similar types of penetration depth models

    with two nodes (one for deep layer and one for surface layer) to

    represent the average behaviour of room materials.

    Humidity levels in materials (in deep and surface layers) arethen described using Eqs. (3) and (4):

    Asurfdosurf

    dt bsurfoint osurf bdeepodeep osurf, (3)

    Adeepdodeep

    dt bdeep;osurf odeep. (4)

    In TRNSYS, moisture transfers are governed by differences in the

    humidity ratio o (), and both transfer coefficients b and storage

    coefficients A are computed, using materials properties for vapour

    transfers and the quantity of materials in the room.

    In Clim2000, only Eq. (3) is used, the differences in the

    humidity ratio o () are simply replaced by differences in water

    vapour density r (kg/m3) and rdeep is fixed to represent the mean

    value of indoor air RH. Transfer coefficients b and storagecoefficients A were experimentally evaluated by Duforestel and

    Dalicieux [38] to represent low absorption and high absorption

    finishing materials and furniture.

    2.2.2. Validation of simulation models: RH and energy demand with

    constant ventilation rate

    Even though in this study previously validated simulation tools

    were used, it was necessary to validate the simulation models. The

    validation was performed on a configuration very similar to the

    case study analysed in this paper. Validation against experimental

    data is essential, because all simulation tools are different: they

    have different simulation possibilities and limitations, material

    properties are defined differently, etc. In this study, simulation

    tools were tested against experimental data for both test and

    reference rooms (referred as run A in this study). Validation was

    done as the blind test (only input parameters were given [26]).

    More detailed description of the experimental data and compar-

    ison between simulated and measured data can be found in Refs.

    [26,27]. Fig. 4 shows an example of indoor air RH for two typicaldays. Simulation tools are able to represent correctly experimental

    data; the spread between the simulated and the measured values

    is in general below 10% of RH. The spread between experimental

    and simulated data is always lower than 5% for CTH and lower

    than 10% for UG. For the three remaining results (TTU, CETHIL and

    PUCPR) the spread is lower than 10% during 95% of the time,

    meaning that the difference is higher than 10% only once a day

    (during the highest moisture production). This difference is the

    largest for the reference room simulated by CETHIL, for minimum

    and maximum values. This fact can be easily explained by the

    simplified model used to represent moisture sorption by painted

    plaster (envelope material directly in contact with the indoor air).

    Simplified model used in Clim2000 has only two sets of default

    parameters (see Section 2.2.2); which do not correspond to thematerials used in the experiment. Certainly, they can be adjusted,

    ARTICLE IN PRESS

    Table 2

    Simulation tools and users in this study

    Si mulation tool Detail ed presentation of the tool Vali dati on of the tool Institution, country

    TRNSYS (version 16) [30,31] [32] UG (University of Ghent), Belgium

    IDA-ICE [3335] [36,37] TTU (Tallinn University of Technology), Estonia

    Clim2000 [38,39] [20,40] CETHIL (Centre de Thermique de Lyon), France

    HAM-Tools [41,42] [43,44] CTH (Chalmers University), Sweden

    TRNSYS (version 15) [30,31] [32] PUCPR (Pontifical Catholic University of Parana), Brazil

    0

    10

    20

    30

    40

    50

    60

    70

    27/1 0:00 27/1 12:00 28/1 0:00 28/1 12:00 29/1 0:00

    Relativehumidity(%)

    UG PUCPR

    TTU CTH

    CETHIL experimental measurements

    0

    10

    20

    30

    40

    50

    60

    70

    27/01 00:00 27/01 12:00 28/01 00:00 28/01 12:00 29/01 00:00

    Relativehumidity(%)

    UG PUCPR

    TTU CTH

    CETHIL experimental measurements

    Fig. 4. Comparison of measured indoor RH with simulation results (left-test room, right-reference room).

    M. Woloszyn et al. / Building and Environment 44 (2009) 515524518

  • 8/14/2019 The Effect of Combining a Relative-humidity-sensitive Ventilation System With the Moisture-buffering Capacity of

    5/10

    using experimental data of indoor RH. However, the results

    presented here are the direct results of the blind test, without any

    tuning of parameters according to monitored data.

    Also, overall energy demand is simulated for both steps 1

    and 2; the difference between the experimental and simulated

    results is under 10% for CETHIL, TTU, PUCPR and UG, as

    represented in Fig. 5.

    The comparison between simulated and measured data showssatisfactory performance of simulation models. In the following,

    the tools are used to perform parametric studies.

    3. Results and discussion

    The sets of results used in this study are presented in Table 3.

    Results included calculated hourly averaged temperatures, heating

    energy, RH, ventilation flow, as well as vapour flow between air

    and construction for both test and reference rooms. Run A was

    used for validation against the experimental data and as reference

    for assessment of indoor moisture management performance. As

    the computed indoor temperature was exactly equal to 20 1C for all

    simulation tools, the RH was used for comparative purposes.

    3.1. Impact of indoor moisture management strategies on the indoorclimate

    Daily evolution of indoor RH for both ventilation systems in a

    room with no hygroscopic surfaces (test room of step 1, Table 1) is

    presented in Fig. 6. Clearly, the amplitude of RH variations is

    smaller for RHS ventilation. Fig. 7 provides more details about the

    statistical distribution of RH. It is noticeable that maximum values

    are very similar for both systems, (even slightly lower for RHS

    system). However, the mean and average values, as well as the

    minimum values are higher for RHS system. Minimum values are

    approximately 20% RH for the RHS system and go as low as 10% in

    the case of constant ventilation. The target values of the indoor air

    RH were between 40% and 50%, as proposed by EN 15251 [45] for

    class A buildings.As shown in Fig. 8, the impact of ventilation systems is much

    smaller in the mild period. The spread of RH values is still smaller

    and the minimum values are higher for RHS ventilation. However,

    the differences are very small, approximately 23% of RH. Both

    Figs. 8 and 9 illustrate the influence of moisture-buffering on the

    indoor RH. When some hygroscopic surfaces are in contact with

    the indoor air, the amplitude of RH variations is much lower; it

    drops approximately from 50% to 20%. This was confirmed by run

    D, presented in Fig. 10 where the participants proposed some

    hygroscopic materials associated with RHS ventilation. In this

    case, the amplitude was less than 20%; and 50% of values were

    within an interval of 8%, considered very stable. TTU and CTH used

    wood to reduce very efficiently RH variations. Indeed, the

    maximum spread was then 15% for TTU and 24% for CTH. PUCPR

    ARTICLE IN PRESS

    0

    100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    energydemand(kWh)

    STEP 1 STEP 2

    experiment UG TTU CETHIL CTH PUCPR

    Fig. 5. Comparison of measured heating energy use with simulation results for the

    reference room and two simulation steps (step 117 days, step 234 days).

    Table 3

    Studied configurations and sets of results

    Run A (exp./sim.) Run B (sim.) Run C (sim.) Run D (sim.) Run E (sim.)

    Ventilation Constant RHS Proposed by participant RHS Proposed by participant

    Indoor materials Original Original Original Proposed by participant Proposed by participant

    Ste p 1 (17 /01 02/02 ) U G, TT U, CETHIL, C TH, P UCPR UG, T TU, C ETHIL , CT H, PUCPR UG, TT U, PUC PR UG, T TU UG, TT U

    Step 2 (14/0219/03) UG, TTU, CETHIL, CTH, PUCPR UG, TTU, CETHIL, CTH, PUCPR UG, TTU, PUCPR UG, TTU, CTH UG, TTU

    Step 3 (28/0321/04) UG, TTU, CETHIL, CTH, PUCPR UG, TTU, CETHIL, CTH, PUCPR UG, TTU, PUCPR UG, TTU, CTH, PUCPR UG, TTU, PUCPR

    0

    10

    20

    30

    40

    50

    60

    70

    29/1 0:00

    Relativehumidity(%)

    UG PUCPR TTU CTH CETHIL

    0

    10

    20

    30

    40

    50

    60

    70

    Relativehumidity(%)

    UG PUCPR TTU CTH CETHIL

    27/1 0:00 27/1 12:00 28/1 0:00 28/1 12:00 29/1 0:0027/1 0:00 27/1 12:00 28/1 0:00 28/1 12:00

    Fig. 6. Indoor RH in the test room computed by all participants: run A-constant ventilation rate (left) and run B-RHS ventilation (right).

    M. Woloszyn et al. / Building and Environment 44 (2009) 515524 519

  • 8/14/2019 The Effect of Combining a Relative-humidity-sensitive Ventilation System With the Moisture-buffering Capacity of

    6/10

    used an enlarged surface of gypsum board (which resulted in a

    maximum spread of 25%), and UG used concrete to buffer

    humidity variations (and obtained a maximum spread of 22%).

    Additional simulations have been performed to improve the

    RHS ventilation by adapting it to the outdoor climate (run C).

    Indeed, run B confirmed that the indoor RH in the test room

    was often below 40% because of the dry outside air in winter. For

    steps 2 and 3 the indoor RH never dropped under 25%,and thus the lowest airflow rate (10 m3/h) was almost never

    applied. The suggestion was to increase this lower limit to

    decrease the ventilation rate in low RH regions. Finally, a

    more stable indoor RH was achieved for the following schemes

    (see Fig. 11):

    Step 1 (cold): If the indoor RH o40%, the airflow rate is set to10m3/h, if RH 450%, it is set to 40 m3/h; in between the flow is

    linearly interpolated. In this case, the humidity outside wasquite low and no buffering occurred. Not much difference in

    ARTICLE IN PRESS

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    UG TTU CETHIL CTH PUCPR

    RelativeHu

    midity[%]

    min - max 25-75 percentile mean median

    target RH

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    UG TTU CETHIL CTH PUCPR

    RelativeHu

    midity[%]

    min - max 25-75 percentile mean median

    target RH

    Fig. 7. Indoor RH in the test room during step 1 for both ventilation systems: run A-constant ventilation rate (left) and run B-RHS ventilation (right).

    20

    30

    40

    50

    60

    70

    80

    90

    UG TTU CETHIL CTH PUCPR

    RelativeHumidity[%]

    min - max 25-75 percentile mean median

    target RH

    20

    30

    40

    50

    60

    70

    80

    90

    UG TTU CETHIL CTH PUCPR

    RelativeHumidity[%]

    min - max 25-75 percentile mean median

    target RH

    Fig. 8. Indoor RH during step 3 for both ventilation systems (UG, TTU and CTH include hygroscopic materials and CETHIL and PUCPR do not): run A-constant ventilation

    rate (left) and run B-RHS ventilation (right).

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    16/04

    00:00

    16/04

    12:00

    17/04

    00:00

    17/04

    12:00

    18/04

    00:00

    Relativehumidity(%)

    UG PUCPR TTU CTH CETHIL

    Fig. 9. Indoor RH in step 3 with (UG, CTH) and without (TTU, CETHIL, PUCPR)

    additional moisture-buffering materials for constant ventilation.

    20

    30

    40

    50

    60

    70

    80

    90

    UG TTU CTH PUCPR

    RelativeHumidity[%]

    min - max 25-75 percentile mean median

    target RH

    Fig.10. Indoor RH in step 3, run D: with RHS ventilation and hygroscopic materials

    proposed by the participant.

    M. Woloszyn et al. / Building and Environment 44 (2009) 515524520

  • 8/14/2019 The Effect of Combining a Relative-humidity-sensitive Ventilation System With the Moisture-buffering Capacity of

    7/10

    indoor RH was noticed when applying another ventilation

    scheme.

    Step 2 (cold): If the indoor RH o40%, the airflow rate is set to10m3/h, if RH450%, it is set to 20 m3/h; in between the flow is

    linearly interpolated. In this case the maximum ventilation

    rate could be decreased because there is moisture-buffering

    and the outdoor air is still quite dry.

    Step 3 (mild): If the indoor RH o40%, the airflow rate is set to10m3/h, if RH450%, it is set to 50 m3/h; in between the flow is

    linearly interpolated. Here again the maximum airflow rate

    was increased, because of the higher indoor humidity caused

    by the higher humidity of the outdoor air.

    3.2. Impact of indoor moisture management strategies on energy

    demand

    Ventilation airflow rates for runs A and B for the test room are

    compared in Fig. 12. During step 1 (cold period), the average value

    of the airflow was approximately 63% of the constant ventilation

    airflow rate. The differences are much less significant for the mild

    period, where both mean ventilation rates are very similar. Verygood agreement between all tools on both average and amplitude

    values can be seen in Fig. 12, left for step 1 with no hygroscopic

    materials. Only CTH obtained larger maximum spread; however,

    the maximum value represents only very few singular points

    corresponding precisely to the instant when the ventilation starts,

    due to a sudden peak in vapour production. The spread between

    values computed by different tools is higher for step 3 ( Fig. 12,

    right). This is partly explained by the fact that hygroscopic

    materials were differently represented in all tools.

    Energy demand is presented in Fig. 13. Ventilation systems are

    compared for both average values (representing energy demand)

    and maximum values (representing heating power to be in-

    stalled). During the cold season (low outdoor absolute humidity,

    see Fig. 13 left), reduction in energy demand is clearly identified inthe case of RHS ventilation. The energy savings computed by all

    tools are between 14% and 17% of energy demand. This is directly

    correlated with the reduction of the average value of fresh air

    flowing into the room. However, most of the simulations predict

    higher peak power (rise of as much as 8%) in the case of RHS

    ventilation. This is easily explained by the sudden rise of air

    change when vapour release starts, which combined with the very

    cold outdoor leads to a higher heating power demand, in order to

    ARTICLE IN PRESS

    Fig. 11. Different RHS ventilation schemes adapted to the outdoor climate.

    0

    5

    10

    15

    20

    25

    30

    35

    40

    45

    PUCPR

    Ventilationflow[m3/h]

    min - max 25-75 percentile mean median

    constant vent.

    0

    5

    10

    15

    20

    25

    3035

    40

    45

    Ventilationflow[m3/h]

    min - max 25-75 percentile mean median

    constant vent.

    UG TTU CETHIL CTH PUCPRUG TTU CETHIL CTH

    Fig. 12. Computed ventilation airflow during step 1 (left) and during step 3 (right).

    0

    200

    400

    600

    800

    1000

    1200

    1400

    PUCPR

    Powerdemand[W]

    Av. Const Max Const Av. RHS Max RHS

    0

    200

    400

    600

    800

    1000

    1200

    1400

    Powerdemand[W]

    Av. Const Max Const Av. RHS Max RHS

    UG TTU CETHIL CTH PUCPRUG TTU CETHIL CTH

    Fig. 13. Power demand for runs A and B (no hygroscopic materials) during step 1 (left) and during step 3 (right).

    M. Woloszyn et al. / Building and Environment 44 (2009) 515524 521

  • 8/14/2019 The Effect of Combining a Relative-humidity-sensitive Ventilation System With the Moisture-buffering Capacity of

    8/10

    maintain constant temperature. In reality, the situation might be

    somewhat different, because most vapour sources are associated

    with heat release (physical activity, cooking, shower, etc.).

    For mild periods, the difference in energy use by both

    ventilation systems is much lower (between 1% and 7%). It

    confirms values from Fig. 12, right, where the average airflow

    values for RHS ventilation are very similar to the constant

    ventilation rate.

    3.3. RH versus CO2 sensitive ventilations

    IDA-ICE was used to include the effect of indoor CO2 on both

    IAQ estimations and on controlling the ventilation rate. Indeed,

    reducing energy used for ventilation of buildings should be made

    without compromising the IAQ. Indoor CO2 levels can be used as

    an indicator of the presence of human body odour and also are

    often employed as an indicator to control the performance of a

    ventilation system. In runs C and E, the ventilation systems with

    the airflow controlled by carbon dioxide (CO2) adapt the airflow to

    changes in the indoor CO2

    when CO2o600 ppm, the flow is set to the minimum value ofQmin 10m

    3/h,

    when CO241500 ppm, the flow is set to the maximum value ofQmax 40 m

    3/h, and

    when CO2 is between the minimum and the maximum, theairflow rate is linearly interpolated.

    According to new standard EN 15251 [45], 1200 ppm was used

    as the maximum permissible indoor air CO2 content (outdoor CO2concentration was 400 ppm) for third indoor climate category.

    A slightly higher limit for maximum ventilation was set to

    increase the capacity of the ventilation system.The diurnal CO2 and humidity production patterns used in the

    simulation tool are shown in Fig. 14. CO2 production was

    calculated based on metabolic activity rate of 0.8 met during

    the night and 1.2 met during peaks in the morning and the

    afternoon.

    The main results, presented in Table 4, were:

    In the case of constant ventilation, the lowest CO2 level butalso the highest energy consumption and RH deviation were

    observed.

    There was similar energy consumption in the case of CO2- andRH-controlled ventilation systems, especially during cold

    period (steps 1 and 2).

    Hygroscopic indoor surface materials (wood fibreboard com-pared to gypsum board) damped the fluctuations of indoor RH

    in all cases, irrespective of ventilation system.

    During cold period, in the case of RH controlled ventilation, thelongest period when the CO2 was higher than 1200 ppm

    occurred.

    During warm period (step 3), both RH and CO2 controlledventilations, were keeping the CO2 levels under the limit.

    During warm period (step 3), with RHS ventilation and woodfibreboard, the best stability of HR values was achieved (65% of

    the time RH values were within the target interval).

    4. Conclusions

    This study confirmed that RHS ventilation is a good way of

    reducing building energy demand in residential buildings. This

    fact is directly related to the reduction of the mean ventilation

    rate when the building is not used. Presented results demon-

    strate that RHS ventilation reduces the spread between the

    minimum and the maximum values of RH. In the tested case, it

    was found that the use of a RHS system could reduce the mean

    ventilation rate of 3040% in the cold period and generate 1217%

    ARTICLE IN PRESS

    Fig. 14. Diurnal CO2 and humidity production pattern.

    Table 4

    Percentage of time when the indoor climate parameters were out of the target RH (4050%) and over acceptable CO2 limit value (1200 ppm) and associated average power

    demand

    Run A Run B Run C Run D Run EVentilation flow Constant RH controlled CO2 controlled RH controlled CO2 controlled

    Indoor surfaces Aluminium foil Gypsum board Gypsum board Wood fibreboard Wood fibreboard

    Step 1 (17.012.02)

    CO2 41200 ppm 0 33 0 33 0

    RH out of [4050%] 84 79 80 79 80

    Average power demand (W) 674 571 589 571 589

    Step 2 (14.0219.03)

    CO2 41200 ppm 0 35 0 45 0

    RH out of [4050%] 83 65 67 57 72

    Average power demand (W) 650 562 570 550 558

    Step 3 (28.0321.04)

    CO2 41200 ppm 0 1 0 0 0

    RH out of [4050%] 62 49 79 35 69

    Average power demand (W) 392 388 351 390 348

    M. Woloszyn et al. / Building and Environment 44 (2009) 515524522

  • 8/14/2019 The Effect of Combining a Relative-humidity-sensitive Ventilation System With the Moisture-buffering Capacity of

    9/10

    of energy savings. However, during the mild period, the savings

    are much lower (only about 2%), mainly because of much higher

    external moisture content. It should be stressed that the energy

    savings are realised while keeping the peak RH values at the

    same level, therefore, without raising the risk of condensation.

    This is a significant advantage of this type of demand controlled

    ventilation.

    However, reducing energy used for ventilation of buildingsshould be made without compromising the IAQ. For example, in

    cold climates outdoor air is very dry; therefore, the indoor air is

    also dry, but even then the ventilation rate cannot be too low.

    Moisture production depends directly on the human activity.

    Moreover, indoor CO2 levels can be used as an indicator of the

    presence of human body odour. Then, the compromise could be a

    combination of CO2 controlled and RH controlled ventilation

    systems. Of course all other pollutants (e.g. VOCs or CO) should be

    kept within correct limits. Therefore, the lower and upper limits of

    ventilation rate must be carefully chosen.

    This study also confirmed that the use of moisture-buffering

    materials is a very efficient way to reduce the amplitude of daily

    moisture variations. It was even possible, by the combined effect

    of ventilation and wood as buffering material (see Fig. 10) to keepthe indoor RH at a very stable level, between 43% and 59%.

    The deviation of results between different simulation tools,

    remaining within a reasonable range, gives some more confidence

    in the tools. Also all codes, with rather different HAM models,

    proved their performance in HAM modelling of whole buildings.

    Acknowledgements

    This study was done within the cooperative project Annex 41

    Whole Building Heat, Air and Moisture Response of the

    International Energy Agencys (IEA) Energy Conservation in

    Buildings and Community Systems (ECBCS) program [46]. More

    details about whole building hygrothermal modelling in the IEAAnnex 41 can be found in Ref. [26]. All participants of the IEA

    Annex 41 are acknowledged for their useful discussions and

    remarks.

    The authors gratefully acknowledge the support from Ing.

    Kristin Lengsfeld from the Fraunhofer Institute for Building

    Physics (IBP) in Holzkirchen, Germany, who provided the experi-

    mental data needed for validation.

    The authors want to thank for financial support of this study:

    Brazilian Research Council (CNPq) of the Secretary for Science and

    Technology of Brazil, Tallinn University of Technology (B605,

    V352) and ADEME, France (Grant no. 03 04 C 0147).

    References

    [1] Wolkoff P, Kjrgaard SK. The dichotomy of relative humidity on indoor airquality. Environmental International 2007;33:8507.

    [2] Fanger PO. Air humidity, comfort and health. Lyndby, Denmark: TechnicalUniversity of Denmark; 1971.

    [3] Wyon DP, Fang L, Mayer HW, Sundell J, Weirsoe CG, Sederberg-Olsen N, et al.Limiting criteria for human exposure to low humidity indoors. In: Proceed-ings of the 9th international congress on indoor air quality, vol. IV, July 26,2002. Monterey, USA. p. 4005.

    [4] Brundrett GW. A review of the factors influencing electrostatic shocks in theoffices. Journal of Electrostatics 1977;2(4):295315.

    [5] Paasi J, Nurmi S, Vuorinen R, Strengell S, Maijala P. Perfomance of ESDprotective materials at low relative humidity. Journal of Electrostatics2001;5152(14):42934.

    [6] Fang L, Clausen G, Fanger PO. The impact of temperature and humidity onperception of indoor air quality. Indoor Air 1998;8:8090.

    [7] Fang L, Clausen G, Fanger PO. Impact of temperature and humidity on theperception of indoor air quality during immediate and longer whole-bodyexposures. Indoor Air 1998;8:27684.

    [8] Fang L, Wargocki P, Witterseh T, Clausen G, Fanger PO. Field study on theimpact of temperature, humidity and ventilation on perceived air quality.

    In: Proceedings of the 8th international congress on indoor air quality, vol. 2.Edinburgh, UK, 1999. p. 10712.

    [9] Bornehag CG, Blomquist G, Gyntelberg F, Jarvholm B, Malmberg P, Nordvall L,et al. Dampness in buildings and health. Nordic interdisciplinary review of thescientific evidence on associations between exposure to dampness inbuildings and health effects (NORDDAMP). Indoor Air 2001;11(2):7286.

    [10] Bornehag CG, Sundell J, Bonini S, Custovic A, Malmberg P, Skerfving S,et al. Dampness in buildings as a risk factor for health effects, EUROEXPO:a multidisciplinary review of the literature (19982000) on dampness

    and mite exposure in buildings and health effects. Indoor Air 2004;14(4):24357.[11] Adan OCG. On the fungal defacement of interior finishes. Doctoral thesis,

    Eindhoven University of Technology; 1994. p. 224.[12] Rowan NJ, Johnstone CM, McLean RC, Anderson JG, Clarke JA. Prediction of

    toxigenic fungal growth in buildings by using a novel modelling system.Applied and Environmental Microbiology 1999(65):481421.

    [13] Hart BJ. Life cycle and reproduction of house-dust mites: environmentalfactors influencing mite populations. Allergy 1998;5(48):137.

    [14] Korsgaard J. House-dust mites and absolute indoor humidity. Allergy1983;38(2):8592.

    [15] Arlian LG, Neal JS, Vyszenski-Moher DL. Reducing relative humidity to controlthe house dust mite Dermatophagoides farinae. Journal of Allergy and ClinicalImmunology 1999;104(4 Pt. 1):8526.

    [16] Jokisalu J, Kurnitski J. Simulation of energy consumption in typical Finnishdetached house. Helsinki University of Technology, HVAC Laboratory, reportB74, 2002.

    [17] Afshari A, Bergse NC. Humidity as a control parameter for ventilation. Indoorand Built Environment 2003;12:2156.

    [18] Savin, JL, Berthin S, Jardinier M. Assessment of improvement brought byhumidity sensitive and hybrid ventilation/HR-Vent project. In: Proceedings of26th AIVC conference on ventilation in relation to the energy performance ofbuildings. Brussels, Belgium, 2005. p. 15767.

    [19] Woloszyn M, Shen J, Mordelet A, Brau J. Numerical simulations of energyperformance of a ventilation system controlled by relative humidity. In:Proceedings of 26th AIVC conference on ventilation in relation to the energyperformance of buildings. Brussels, Belgium, 2005. p. 295300.

    [20] Plathner P, Woloszyn M. Interzonal air and moisture transport in a testhouse. Experiment and modelling. Buildings and Environment 2002;37(2):18999.

    [21] Isetti C, Laurenti L, Ponticello A. Predicting vapour content of the indoor airand latent loads for air-conditioned environments: effect of the moisturestorage capacity of the walls. Energy and Buildings 1988;12:1417.

    [22] Plathner P, Ross D. The effect of sorption on airborne moisture movement indwellings. International Journal of Ventilation 2003;1(3):2018.

    [23] El Diasty R, Fazio P, Budaiwi I. Modelling of indoor air humidity: thedynamic behaviour within an enclosure. Energy and Buildings 1992;19(1):6173.

    [24] Koronthalyova O. The coupled effect of hygroscopic materials and ventilationregime on indoor humidity. IEA Annex 41 report A41-T1-Sl-06-1; 2006.

    [25] Mendes N, Winkelmann FC, Lamberts R, Philippi PC. Moisture effects onconduction loads. Energy and Buildings 2003;35(7):63144.

    [26] Woloszyn M, Rode C. Annex 41, Subtask 1: Modelling principles and commonexercises. Draft final report for the energy conservation in buildings andcommunity systems executive committee of the International Energy Agency,2008.

    [27] Holm A, Lengsfeld K. Moisture-buffering effectexperimental investigationsand validation. In: Proceedings buildings X conference, thermal performanceof the exterior envelopes of whole buildings. Clearwater Bach, FL; 2007.

    [28] Hartmann, et al. Feuchteschaden und Schimmelpilzbefall in Wohnungen.Bundesbaublatt Jg 2001;53(3):3842.

    [29] Hens H. Modelling: hygric aspects. Chapter. In: Condensation and energy:source book. IEA-Annex 14. Leuven, Belgium: Acco; 1991.

    [30] Klein SA, Beckman WA, Mitchell JW, Duffie JA, Duffie NA, Freeman TL, et al.TRNSYS 16 A TRaNsient system simulation program, user manual. Madison:Solar Energy Laboratory, University of Wisconsin-Madison; 2004.

    [31] Crawley DB, Hand JW, Kummert M, Griffith BT. Contrasting the capabilities ofbuilding energy performance simulation programs. Version 1.0, 2005.

    [32] Voit P, Lechner Th, Schuler M. Common EC validation procedure fordynamic simulation programs application with TRNSYS, TRANSSOLARGmbH. In: Conference of international simulation societies 94. Zurich,1994.

    [33] Sahlin P, Eriksson L, Grozman P, Johnsson H, Shapovalov A, Vuolle M. Wholebuilding simulation with symbolic DAE equations and general purposesolvers. Building and Environment 2004;39(8):94958.

    [34] Sahlin P. Modelling and simulation methods for modular continuous systemsin buildings. Doctoral dissertation. Stockholm, Sweden: KTH; 1996.

    [35] Kurnitski J, Vuolle M. Simultaneous calculation of heat, moisture, andair transport in a modular simulation environment. In: Proceedingsof the Estonian academy of sciences engineering, vol. 6/1, March 2000.p. 2547.

    [36] Achermann M. Validation of IDA ICE. Version 2.11.06 with IEA task 12 envelope BESTEST. Hochschule Technik+Architektur Luzern. HLK Engineering,2000.

    [37] Kropf S, Zweifel G. Validation of the building simulation program IDAICE according to CEN 13791 thermal performance of buildings calcula-tion of internal temperatures of a room in summer without mechanical

    ARTICLE IN PRESS

    M. Woloszyn et al. / Building and Environment 44 (2009) 515524 523

  • 8/14/2019 The Effect of Combining a Relative-humidity-sensitive Ventilation System With the Moisture-buffering Capacity of

    10/10

    cooling general criteria and validation procedures. Hochschule Techni-k+Architektur Luzern. HLK Engineering, 2001.

    [38] Duforestel T, Dalicieux P. A model of hygroscopic buffer to simulate the indoorair humidity behaviour in transient conditions. In: Proceedings of Europeanconference on energy performance and indoor climate in buildings, vol. 3.Lyon, France, 1994. p. 7917.

    [39] Woloszyn M, Rusaouen G, Covalet D. Whole building simulation tools:Clim2000. IEA Annex 41 report A41-T1-F-04-3. Zurich, Switzerland, 1315May 2004. 15pp.

    [40] Lomas KJ, et al. Empirical validation of building energy simulation programs.Energy and Buildings 1997;26:25375.[41] Sasic Kalagasidis A. HAM-Tools. An integrated simulation tool for heat, air and

    moisture transfer analyses in building physics. Doctoral thesis. ChalmersUniversity of Technology, Gothenburg, Sweden, 2004.

    [42] Sasic Kalagasidis A, Weitzmann P, Nielsen TR, Peuhkuri R, Hagentoft C-E, RodeC. The international building physics toolbox in Simulink. Energy andBuildings 2007;39(6):66574.

    [43] Sasic Kalagasidis A. The whole model validation for HAM-Tools. Casestudy: hygrothermal conditions in the cold attic under different ventila-tion regimes. In: Proceedings of the 9th International Conference onPerformance of the Exterior Envelopes of Whole Buildings. Clearwater Beach,FL, 2004.

    [44] Hagentoft C-E, Sasic Kalagasidis A, Adl-Zarrabi B, Roels S, Carmeliet J, Hens H,et al. Assessment method of numerical prediction models for combined heat,air and moisture transfer in building components. Benchmarks for one-dimensional cases. Journal of Thermal Envelope and Building Science 2004;

    27:32752. (4, April).[45] EN 15251:2007. Indoor environmental input parameters for design andassessment of energy performance of buildings addressing indoor air quality,thermal environment, lighting and acoustics. CEN, European Committee forStandardization.

    [46] Hens H. Annex 41whole building heat, air and moisture response. In:Proceedings of 26th AIVC conference on ventilation in relation to the energyperformance of buildings. Brussels, Belgium, 2005.

    ARTICLE IN PRESS

    M. Woloszyn et al. / Building and Environment 44 (2009) 515524524