The consequences of electrical insulation failures in ageing umbilicals: copper loss and hydrogen generation.
![Page 2: The consequences of electrical insulation failures in ... · The consequences of electrical insulation failures in ageing umbilicals: copper loss and hydrogen generation](https://reader033.vdocuments.us/reader033/viewer/2022051511/6009e2466d2917642b7ac8c3/html5/thumbnails/2.jpg)
Copyright © 2019 Viper Innovations Ltd, All Rights ReservedConfidential & Proprietary Information Page 2
Earthing Arrangements
IEC has standardised on three families of earthing – TN, TT, IT
1st Letter is connection between earth and supply
2nd Letter is connection between earth and device being supplied
TN TT IT
![Page 3: The consequences of electrical insulation failures in ... · The consequences of electrical insulation failures in ageing umbilicals: copper loss and hydrogen generation](https://reader033.vdocuments.us/reader033/viewer/2022051511/6009e2466d2917642b7ac8c3/html5/thumbnails/3.jpg)
Copyright © 2019 Viper Innovations Ltd, All Rights ReservedConfidential & Proprietary Information Page 3
Monitoring of IT Systems
IEC 60364 is the international harmonised standard that details requirements for low voltage electrical installations.
•Part 4-41 (Protection for safety – Protection against electric shock) specifies that an IT (floating earth) system shall always be equipped with a suitable protective or monitoring device.
•For high system availability, an IMD should be used, to indicate the first fault, with suitable automatic disconnection of the supply
![Page 4: The consequences of electrical insulation failures in ... · The consequences of electrical insulation failures in ageing umbilicals: copper loss and hydrogen generation](https://reader033.vdocuments.us/reader033/viewer/2022051511/6009e2466d2917642b7ac8c3/html5/thumbnails/4.jpg)
Copyright © 2019 Viper Innovations Ltd, All Rights ReservedConfidential & Proprietary Information Page 4
Cable Insulation Integrity Measurement
Leakage current 𝑓() of 3 sub-currents
![Page 5: The consequences of electrical insulation failures in ... · The consequences of electrical insulation failures in ageing umbilicals: copper loss and hydrogen generation](https://reader033.vdocuments.us/reader033/viewer/2022051511/6009e2466d2917642b7ac8c3/html5/thumbnails/5.jpg)
Copyright © 2019 Viper Innovations Ltd, All Rights ReservedConfidential & Proprietary Information Page 5
Experimental Set-Up
Viper
![Page 6: The consequences of electrical insulation failures in ... · The consequences of electrical insulation failures in ageing umbilicals: copper loss and hydrogen generation](https://reader033.vdocuments.us/reader033/viewer/2022051511/6009e2466d2917642b7ac8c3/html5/thumbnails/6.jpg)
Copyright © 2019 Viper Innovations Ltd, All Rights ReservedConfidential & Proprietary Information Page 6
The IMD two-week effect
Single point damage to insulation equivalent to an insulation resistance of 30kΩ
Day 1 Day 14
Copper Corrosion
![Page 7: The consequences of electrical insulation failures in ... · The consequences of electrical insulation failures in ageing umbilicals: copper loss and hydrogen generation](https://reader033.vdocuments.us/reader033/viewer/2022051511/6009e2466d2917642b7ac8c3/html5/thumbnails/7.jpg)
Copyright © 2019 Viper Innovations Ltd, All Rights ReservedConfidential & Proprietary Information Page 7
The IMD Electrochemical Cell
![Page 8: The consequences of electrical insulation failures in ... · The consequences of electrical insulation failures in ageing umbilicals: copper loss and hydrogen generation](https://reader033.vdocuments.us/reader033/viewer/2022051511/6009e2466d2917642b7ac8c3/html5/thumbnails/8.jpg)
Copyright © 2019 Viper Innovations Ltd, All Rights ReservedConfidential & Proprietary Information Page 8
IMD Experimentation
At the positive surface:
![Page 9: The consequences of electrical insulation failures in ... · The consequences of electrical insulation failures in ageing umbilicals: copper loss and hydrogen generation](https://reader033.vdocuments.us/reader033/viewer/2022051511/6009e2466d2917642b7ac8c3/html5/thumbnails/9.jpg)
Copyright © 2019 Viper Innovations Ltd, All Rights ReservedConfidential & Proprietary Information Page 9
AC Power Experimentation
At the negative surface:
![Page 10: The consequences of electrical insulation failures in ... · The consequences of electrical insulation failures in ageing umbilicals: copper loss and hydrogen generation](https://reader033.vdocuments.us/reader033/viewer/2022051511/6009e2466d2917642b7ac8c3/html5/thumbnails/10.jpg)
Copyright © 2019 Viper Innovations Ltd, All Rights ReservedConfidential & Proprietary Information Page 10
The two conductors after AC power applied
Tarnishing of copper: 2 Cu(s) + O2(g) → 2 CuO(s)
![Page 11: The consequences of electrical insulation failures in ... · The consequences of electrical insulation failures in ageing umbilicals: copper loss and hydrogen generation](https://reader033.vdocuments.us/reader033/viewer/2022051511/6009e2466d2917642b7ac8c3/html5/thumbnails/11.jpg)
Copyright © 2019 Viper Innovations Ltd, All Rights ReservedConfidential & Proprietary Information Page 11
Copper Corrosion after AC power applied
![Page 12: The consequences of electrical insulation failures in ... · The consequences of electrical insulation failures in ageing umbilicals: copper loss and hydrogen generation](https://reader033.vdocuments.us/reader033/viewer/2022051511/6009e2466d2917642b7ac8c3/html5/thumbnails/12.jpg)
Copyright © 2019 Viper Innovations Ltd, All Rights ReservedConfidential & Proprietary Information Page 12
V-LIM Changes to Reduce Copper Loss
IMD current is a minimum at High IR and a maximum at low IR
The output voltage from the IMD can be reduced as the IR reduces without loss of accuracy.