the bitterness of poor quality is remembered long after
TRANSCRIPT
The bitterness of poor quality is remembered long after The bitterness of poor quality is remembered long after the sweetness of low price is forgotten!the sweetness of low price is forgotten!
Heat Pump Sizing Using ACCA Heat Pump Sizing Using ACCA ManualManual J8 J8 ItIt’’s a Building Code Requirements a Building Code Requirement
Size the Equipment BEFORE You BuildSize the Equipment BEFORE You Build
HVAC
• Heating, Ventilation and Air Conditioning
• Provides comfort for people• Allows humans to exist under adverse
conditions.
WHY CARE ABOUT THE HVAC EQUIPMENT?
Human Comfort Zone
(After All, it(After All, it’’s Humans s Humans WeWe’’re Experimenting With)re Experimenting With)
HEAT PUMP SIZING
FSEC Study (1996 – 489 HVAC contractors)
•Rules of thumb prevail•Intentionally oversize•Tons per square foot (350-700)•Whatever’s on sale•CFM per square foot•Manual J (33%)
COMFORT
• Comfort is primary intent of HVAC systems.
• Productivity• Building Durability• Health• Mold
HVAC BUZZWORDS
• BTU = British Thermal Unit – energy to heat 1 pound of water from 39°F to 40°F
• 1 Ton = 12,000 BTUh• Dry Bulb Temperature = air temperature• Wet Bulb Temperature = “temperature of adiabatic saturation”
psychrometer or a piece of cloth on a thermometer, temp it evaporates –less than dry bulb
• Dew Point = Temperature were air is saturated and condensation starts• Relative Humidity = Amount of water vapor in the air• CFM = Cubic Feet per Minute, air volume• FPM = Feet Per Minute, air velocity• Pascal Pa = Pressure (1 Pa = .000145 Psi) ~ 250 Pa = 1” wc• Sensible Load = reduces the temperature• Latent Load = reduces the moisture• Sensible Heat Ratio (SHR) = ratio between the sensible and total load• Grains for moisture = indicate amount of water vapor per pound of air• Manual J = method for estimating the loads• Manual D = method for designing & sizing the duct work from the Manual
J• Psychrometrics = the measurement of the heat and water vapor
properties of air • Enthalpy = a measure of the total energy of a thermodynamic system
HEAT PUMPS
• Heat pumps “remove” heat from the house in the summer and dump it outside– cooling season
• Heat pumps “remove” heat from the outside air in the winter and dump inside – heating season
• Cooling Degree Days (CDD) & Heating Degree Days (HDD) – typical outside base 65°F (example Avg temp for the day is 80°F – 65°F= 15 CDD for one month 450 CDD
• North Florida – Climate Zone 2 – design for the cooling season
HEAT FLOW
• Conduction• Convection• Radiation
SOLAR HEAT GAIN COEFFICIENT (SHGC)
• The amount of solar heat energy allowed to pass through a window
• Example: SHGC = 0.40• Allows 40% through and
turns 60% away
ENERGY EFFICIENCY
LOW-E WINDOWS AND COMFORT
Mean Radiant Temperature (MRT) has 40% Mean Radiant Temperature (MRT) has 40% more impact than ambient temperaturemore impact than ambient temperature
70700 0 F Ambient/65% RHF Ambient/65% RH
77770 0 FF77770 0 FF 9090
0 0 FF90900 0 FF
76760 0 F Ambient/45% RHF Ambient/45% RH
Less ComfortLess ComfortMore ComfortMore Comfort
CONTROLLING AIR FLOW:RULE #1
Where there is a Where there is a driving forcedriving force, , air will take the path of least air will take the path of least resistance through largest hole.resistance through largest hole.
airair
CONTROLLING AIR FLOW: RULE #2
More PressureMore PressureMore MoistureMore Moisture
More HotMore Hot(air and moisture)(air and moisture)
Less PressureLess PressureLess MoistureLess MoistureLess HotLess Hot
Driving Forces always move inDriving Forces always move inpredictable directions:predictable directions:
CONTROLLING AIR FLOW:RULE #3
One OutOne Out = One In= One In
HVAC SYSTEM DESIGN
Importance of Design• Undersized systems = discomfort• Oversized systems = wear & tear on equipment, discomfort (cooling), unnecessary expense, higher initial cost• Duct design can affect efficiency and system’s ability to heat/cool evenly
The “RIGHT SIZED” equipment is critical for performance. 95% of problems related to over sizing, duct leakage, poor duct design
OBTAIN A GOOD SYSTEM DESIGN AND INSTALLATION
• Find a contractor that will take the time to design and install it right• Create specifications for contractors• Ensure specifications are followed
The HVAC equipment, duct layout, and ductwork The HVAC equipment, duct layout, and ductwork are the are the ““heart, veins & arteriesheart, veins & arteries”” of the house.of the house.
Seek out “Best Value” – this is a “cost” avoidance issue -cheap doesn’t work unless you want lots of call backs.
STEPS to a COMFORTABLE HOMEOWNER
• Manual J8 – Load Analysis• Manual D – Duct system design & sizing• Manual S – Equipment selection• Installation – duct sealing/insulation,
thermostat location• Commissioning – Compressor and AHU checks• Ducts – verify CFM/FPM and balance system
MANUAL J8
• Procedure used to estimate the heat loss and gain of conventional residential structures for the purpose of HVAC sizing
• Determine room-by-room loads• Manual J examines:
– Enclosure elements– Air leakage– System losses / gains– Sun position– Latent and internal gains
HEAT LOSS
HEAT GAIN
HEAT TRANSFER
U-Value is the rate of heat flow in Btu/h through a one ft2 area when one side is 1oF warmer
Resistance (R-Value)U = 1 / RExample R30 = U.033 ~ R11 = U.09
Measuring Heat LossQ = U x A x ∆T
• Q = heat flow (BTUH)• U = thermal conductivity (U=1/R)• A = surface area (square feet)• ∆T = temperature difference across component (°F)
HOW MANUAL J WORKS
• BTUH heat loss or gain through an assemblyQ BTUH = U x A x ∆T
• Example– 500 sq. ft. of wall insulated to R-19– Interior temp at 75° and exterior at 89°– U-value = 1/R – value: 1/19 = .053– Delta T is the difference in temperature across a building
component that governs heat loss or gain: 89° - 75° = 14°
.053 x 500 x 14 = 371 BTUH
OBJECTIVES OF MANUAL J8 LOAD CALCULATION
•To determine the proper sizing of HVAC equipment for a structure(Block Load) •To determine the heating & cooling requirements for individual rooms ( Room by Room load) •Determine Proper Duct Design
Why Bother Sizing?Obviously don’t want one to small
Avoid CallbacksSo just make it real big
HIGH PERFORMANCE HOUSES
• So what is the cause for concern?– Improved thermal envelope leads to reduced
heating and cooling loads which results in smaller HVAC equipment
– Used to use 400 sqft / ton as an estimation of size
– Now 600 and up to 1000 sqft / ton – Reduced amount of airflow in the system– Standard to oversize ducts result in lower
velocities– Lower velocities at diffusers reduce throw and
mixing– Impact of duct leakage is amplified
WHY USE MJ8
The heating and cooling load estimates affect every aspect of the system design procedure
•Type of system (variable volume/capacity)•Equipment selection•Placement and selection of air distribution hardware•Duct routing and airway sizing or pipe layout and sizing
Because of this the load calculation must be as accurate as possible
DESIGN CONDITIONS ONLY OCCUR FOR A FEW DOZEN HOURS PER SEASON
RADIANT LOADS CAN HAVE THE LARGEST IMPACT
EAST ElevationEAST Elevation WEST ElevationWEST Elevation
WATCH the INPUTS
LOAD VS TOTAL CAPACITY
The total system capacity ~ example: 3 TONS (36,000 The total system capacity ~ example: 3 TONS (36,000 Btuh) is required only about 3Btuh) is required only about 3--4% of the time.4% of the time.
MJ8 ROOM by ROOM
AIR INFILTRATION
Measures how much air leaks in/out of a home’s envelope by studying how much air must be removed from the home to reach a certain pressure level (50 Pascal reference), thus testing the efficiency of the building envelope.Directly influences the size of the equipment because it affects the latent and sensible loads.
Blower Door Test
DUCT LEAKAGE
Influences how the building reacts in terms of health, safety, durability, comfort, and energy efficiency.
•Can be estimated with a high degree of accuracy.•Can be tested with a high degree of accuracy.•Can be eliminated.
HEAT PUMP EFFICIENCY
Heating Mode• Measured by HSPF • ENERGY STAR at HSPF 8.2Cooling Mode• Cooling efficiency measured by SEER• Federal minimum SEER 13• ENERGY STAR criterion SEER 14
ENERGY EFFICIENCY
EQUIPMENT RIGHT-SIZING
BenefitsBenefits::•• Lower CostLower Cost•• Increased Efficiency Increased Efficiency •• Longer Lifetime Longer Lifetime •• Better Moisture Better Moisture
ControlControl•• Improved ComfortImproved Comfort•• Reduced CallbacksReduced Callbacks
14
13
12
11
10
9
8
7
SEER
NEW CONSTRUCTION MISTAKES
•The Infiltration always is a guess!!!•Using the wrong Infiltration rate•Actually just assume leaky construction•Assuming Duct & Envelope Leakage Equivalent•Same plan is used for multiple subdivisions•Looking at worst case scenarios•Not Evaluating Overhangs & Benefits•Add some for parties•What’s on sale
All of this can lead to improper sizing of HVAC Equipment
THE SCIENCE BEHIND THE VALUE CONTROLLING AIR FLOW: INSULATION
Resists Heat FlowResists Heat Flow
Air FlowAir Flow
……need need Air BarrierAir Barrier
THE SCIENCE BEHIND THE VALUE
WHY CONTROL AIR FLOW?
Warm AirWarm AirGets Cold Gets Cold
Loses MoistureLoses Moisture
Impact:Impact:All action happens at All action happens at surfaces where warm surfaces where warm air can condensate on air can condensate on cold surfaces. cold surfaces. Air flow must be Air flow must be controlled to avoid controlled to avoid moisture problems.moisture problems.
THE SCIENCE BEHIND THE VALUE
WHY CONTROL AIR FLOW
Without Insulation:Without Insulation:
Inside:Inside:7070ooF, 45F, 4500F Dew Pt.F Dew Pt.Outside:Outside:
3030ooFF
5555ooFF3434ooFF
With Insulation:With Insulation:
Impact:Impact:Insulated walls create Insulated walls create cold surfaces.cold surfaces.Insulated homes must Insulated homes must be sealed tight to avoid be sealed tight to avoid moisture problems.moisture problems.
THE SCIENCE BEHIND THE VALUE
CONTROLLING MOISTURE FLOW
HotHot--Humid ClimateHumid Climate::
Inside:Inside:7070ooFF
Outside:Outside:8585ooF, F,
DrivingDrivingForceForce
7272ooFFVapor BarrierVapor Barrierfaced insulation, faced insulation, faced sheathing, faced sheathing, unfaced insulation.unfaced insulation.
ENERGY EFFICIENCYINSULATION: VALUE KILLERS
••Incomplete Air BarrierIncomplete Air Barrier••Misalignment with Air BarrierMisalignment with Air Barrier•• GapsGaps•• VoidsVoids•• CompressionCompression•• Wind IntrusionWind Intrusion
ENERGY EFFICIENCY
ALIGN AIR AND THERMAL BARRIERS
•• ContinuousContinuous•• Full contact withFull contact with
interior air barrier interior air barrier (e.g., sheet rock)(e.g., sheet rock)
•• Fully enclose Fully enclose conditionedconditionedspacespace
ENERGY EFFICIENCYAIR BARRIER ALIGNMENT: BONUS ROOM
125125ooFF
110110ooFF 110110ooFF
100100ooFF
BonusBonusRoomRoom
GarageGarageThermal Thermal
BypassBypassThermal Thermal BypassBypass
SolutionSolution::••align insulationalign insulation••add air barriersadd air barriers
ENERGY EFFICIENCYAIR BARRIER ALIGNMENT: CANTILEVER
SolutionSolution::••align insulationalign insulation••add air barriersadd air barriers
Thermal Thermal BypassBypass
Thermal Thermal BypassBypass
Cantilever Cantilever
ENERGY EFFICIENCY
TIGHT CONSTRUCTION: WHY?
•• Eliminate unwanted heat loss/gain Eliminate unwanted heat loss/gain •• Eliminate potential moisture problemsEliminate potential moisture problems
by avoiding humid air flow through construction by avoiding humid air flow through construction assembliesassemblies
•• Eliminate outdoor pollutantsEliminate outdoor pollutants(e.g., humidity, dust, pollen)(e.g., humidity, dust, pollen)
ENERGY EFFICIENCY
TIGHT CONSTRUCTION: HOW?
• Seal Un-designed Holes– Cracks– Holes– Shafts
• Control Air Flow with Designed Holes– Mechanical Ventilation– Exhaust Fans– Pressure Balancing
ENERGY EFFICIENCYTIGHT CONSTRUCTION: HOLES/CRACKS
ENERGY EFFICIENCY
ENERGY EFFICIENT DUCTS
•• Ducts Sized with ACCA Manual DDucts Sized with ACCA Manual D
•• Seal With MasticSeal With Mastic
•• InsulateInsulate
•• Avoid Using Building Cavities as DuctsAvoid Using Building Cavities as Ducts
•• Get it Inside if PossibleGet it Inside if Possible
ENERGY EFFICIENCY
SEALING DUCTS: PROBLEMS
ENERGY EFFICIENCY
SEALING DUCTS WITH MASTIC
ENERGY EFFICIENCY
ENERGY EFFICIENT EQUIPMENT
Heating:Heating:••Super Efficiency: Super Efficiency: 90+ AFUE90+ AFUE•• HSPF 8.2 HSPF 8.2 Cooling:Cooling:••14 SEER14 SEER••MultiMulti--SpeedSpeedAir Handler:Air Handler:••Variable Speed Blower Motor Variable Speed Blower Motor ••AirAir--Tight CabinetTight Cabinet
SUMMARYENERGY EFFICIENCYPERFORMANCE ADVANTAGE
Unless youUnless you’’re prepared to break the laws re prepared to break the laws of physics, energy efficiency delivers:of physics, energy efficiency delivers:
•• Lower Utility CostsLower Utility Costs•• More More ComfortComfort•• More Durability More Durability •• Improved Indoor Air QualityImproved Indoor Air Quality•• Environmental ProtectionEnvironmental Protection•• Less call backsLess call backs•• Happy Homeowner Happy Homeowner –– more salesmore sales
FOR MORE INFORMATION
Visit us on the Web:http://www.usahers.com
Or call Tim @ 904-571-9955Henry @ 904-233-7299