JLG Associates, LLC
“The Aging of America’s Transformers”
by
Jon L. Giesecke, Director, JLG Associates, LLC
(610) [email protected]
The Weidmann Conference2006
JLG Associates, LLC
How Old is Old?
■The aging of the electrical infrastructure in the United States is a serious problem!!
■Until recently this problem has slipped thru the cracks. A new level of awareness is needed as these aging transformers are failing.
JLG Associates, LLC
Average Age
■As of today, our transformer population has an average age of 40 years
■The published life expectancy of many of our transformers is 40-50 years
■TIME’S UP…..NOW WHAT?
JLG Associates, LLC
WE MUST BE PRO-ACTIVE
WHAT’S NEEDED?
■The best asset management program using condition monitoring.
HOW?
JLG Associates, LLC
WE MUST BE PRO-ACTIVE
■ I have dedicated the past decade in search of the optimal tests for condition assessment of Oil Filled Power Transformers and their Sub-Systems.
JLG Associates, LLC
WE MUST BE PRO-ACTIVE
■ During that time, I helped develop a program using the newest technologies and the very best equipment, methods and techniques for condition assessments.
JLG Associates, LLC
WE MUST BE PRO-ACTIVE
■ Infrared, Vibration Analysis, DGA, Oil Quality and Functional Testing of the cooling systems and load tap changers was the backbone of the process.
■What was needed was an easy and reliable test method for Partial Discharge.
JLG Associates, LLC
WE MUST BE PRO-ACTIVEUSING THE NEWEST TECHNOLOGY
■A Partial Discharge (PD) testing method using acoustic sensors and a high frequency current transducer is now available
■This increases the protection factor for these utility industry assets:
Transformers, LTC’s, Lightning Arrestors, Pumps, OCB’s, GIS, etc.
JLG Associates, LLC
WE MUST BE PRO-ACTIVE
■This presentation will describe the process for PD detection / location and answer many key questions that may arise.
JLG Associates, LLC
■One Question…..What do Oil Circuit Breakers, Load Tap Changers and Voltage Regulators have in common?
■Anybody??????
However, before we start…..
JLG Associates, LLC
■Answer…..They all have contacts which arc under insulating oil!
Ahaa!
JLG Associates, LLC
■Something that shouldn't arc under oil……
■ANYBODY????
Abnormal Arcing(bad ju-ju)
JLG Associates, LLC
OIL FILLED POWER TRANSFORMERS
Abnormal Arcing(bad ju-ju)
JLG Associates, LLC
LET’S TAKE A WALK DOWN MEMORY LANE
■The Date…..1969■The Viet Nam War■Peace & Love■DGA■My Discharge from the Navy■Hippies & Flower Power■Bell Bottoms
JLG Associates, LLC
Let’s take a walk down memory lane.
Did he just say DGA???
JLG Associates, LLC
■ I was a maintenance electrician – high volt group.
■The high volt group was responsible for OCB, LTC and Regulator maintenance.
■Everything was based on time and operations / fault trippings
Back in the “OLD DAYS”
JLG Associates, LLC
■The most high tech device we all used was the Cincinnati Analyzer for breaker timing.
■Like many of you, I licked many charts until they came out with self stick. (new technologies)
Back in the “OLD DAYS”
JLG Associates, LLC
■ Then a brand new technology came into existence….DGA on Transformer Oil. By the way it was slow to catch on.
■ And yes, we were still using the old Cincinnati Analyzer
■ And doing overhauls based on time and operations
Back in the “OLD DAYS”
JLG Associates, LLC
I was threatened with bodily harm when I suggested doing DGA on an LTC
I imagine I would have been institutionalized if I had suggested doing DGA on OCB’s
Back in the “OLD DAYS”
JLG Associates, LLC
■BUT, as most of you know and are probably doing; both LTC and OCB problems are easily detected by DGA
■What about voltage regulators? Aren’t they in the same family?
■Arcing Contacts under oil, exhibit much of the same characteristics.
BACK TO THE FUTURE
JLG Associates, LLC
■And of course there came into major use in our industry, “Infrared Thermography”
■Everyone is doing IR■OCB and LTC infrared is very telling and
useful for diagnosing problems■A full set of functional tests on LTC’S
saved many costly failures
Back to the Future
JLG Associates, LLC
■Then along came “Ultrasonic Analysis”■Computerized motion analysis and capture
of 1st trip.■Wave Shape analysis,■Etc., Etc.
Back to the Future
JLG Associates, LLC
■A combination of ultrasonics and electrical capture of an arc is being done.
■And with it, the ability to analyze…■Source Locate■Trend■And make the big dollar decision on when
to say when.
JLG Associates, LLC
Today, we are able to capture and analyze a burst of acoustic
energy……BUT, HOW MANY DO???
JLG Associates, LLC
And Expand a selected Portion for a closer look
JLG Associates, LLC
And Expand even more to measure the Frequency Content.
JLG Associates, LLC
Technology today is able to capture the acoustic signal from the
operation of an LTC.
BUT, HOW MANY DO???
JLG Associates, LLC
Then expand and analyze the acoustic signal!
JLG Associates, LLC
Technology today is able to capture the Arcing from the operation of an
LTC.
JLG Associates, LLC
Then Expand and Analyze the Arc
B C
JLG Associates, LLC
Expand again to show the arcing contact and the follow-thru.
(B Phase)
B
JLG Associates, LLC
Then Expand C Phase for analysis.
(C Phase)
C
JLG Associates, LLC
AND BY THE WAY….
Did you realize???
This was a VACUUM TYPE LTC!
JLG Associates, LLC
■ I NOW HAVE THE ABILITY TO INSPECT VACUUM CONTACTS IN AN LTC DURING AN OPERATION….ALSO
■MECHANICAL LTC’S■ OCB’s ■ VOLTAGE REGULATORS
JLG Associates, LLC
■ ALSO THE ABILITY TO INSPECT OIL FILLED TRANSFORMERS AND SUPPORT EQUIPMENT DURING NORMAL OPERATION
■ CORE, WINDING, BUSHING LEADS■ PUMPS■ LA’S■ LTC’S
DETECTING PD AND ARCING IS FAST AND EASY
JLG Associates, LLC
“The Rest of the Story”
■When you look at the next few slides……
■Remember the top screen is acoustic energy…..
■The bottom screen is electrical energy…..
JLG Associates, LLC
THE COMPLETE LTC PICTURE FROM PREVIOUS SLIDES
JLG Associates, LLC
PARTIAL DISCHARGE IN MPT/GSU
JLG Associates, LLC
Cursors measure difference, PD is confirmed in this GSU
JLG Associates, LLC
Expand 1 Burst for a closer look.
JLG Associates, LLC
Expanding more shows #3 is closest (notice the spike shape)
JLG Associates, LLC
The fault Location Screen (front view) Pink Ball shows location of
PD.
JLG Associates, LLC
The fault Location (top down view)
JLG Associates, LLC
BAD LIGHTNING ARRESTOR (bottom screen only)
JLG Associates, LLC
ONE SPIKE FROM THE LA
JLG Associates, LLC
ONE SPIKE FROM PD (flip back and forth)
JLG Associates, LLC
Combining Data,a Holistic Approach
■ Partial Discharge Detection■ Infrared Thermography■ Vibration Analysis (main tank and pumps)■ Functional Testing of Cooling System & LTC■ DGA & Oil Quality Review■ Furan Analysis■ Review of Transformer Loading History
■ All done on energized, loaded transformers
JLG Associates, LLC
Combining Data,a Holistic Approach
■We only talked about one of the technologies from the list.
■Many times two or more methods point to the problem.
■Don’t short change yourself.■This knowledge is available, learn to do
a complete condition assessment.