AcoustAlert Software Manual AcoustAlert is manufactured by: Modular Communications SA 30 Burt Drive, Newton Park, Port Elizabeth, South Africa Telephone: +27 (0)41 364 2653 Contact: [email protected]

Upload: others

Post on 18-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual

AcoustAlert is manufactured by:

Modular Communications SA 30 Burt Drive, Newton Park, Port Elizabeth, South Africa Telephone: +27 (0)41 364 2653 Contact: [email protected]

Page 2: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 2

• We reserve the right to make any technical modifications be it physical hardware, processor firmware or software.

• We reserve the right to issue software and firmware updates which must be implemented in order to engage support.

• The trademark, AcoustAlert is a registered trade mark of Modular Communications SA (Pty) Ltd.

• We retain all copyright and other intellectual property rights in everything developed, designed or created by us either before or during the course of an engagement including systems, methodologies, software, know-how and working papers. We also retain all copyright and other intellectual property rights in all reports, written advice or other materials provided by us to you, although the fees you pay us allow you to use those materials for the purposes for which they were created under any engagement with Modular Communications SA (Pty) Ltd.

• This document may not be copied, photocopied, reproduced, translated, transferred to an electronic medium or converted to a machine-readable form either whole or in part without first receiving written permission from Modular Communications SA (Pty) Ltd.

• The manufacturer accepts no liability for damage or loss to property or pecuniary damages arising due to minor defect of the product or documentation, e.g. print or spelling errors, and for those not caused by intention or gross negligence of the manufacturer

All rights reserved:

Page 3: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 3

1 About this document 4 2 Introduction 5 3 Installation 6 4 Opening the software 9 5 AcoustAlert configuration 10 6 Moxa Configuration 20 7 Layout Editor 36 8 Moxa Output User Control 40 9 Zone Conditions 41 10 Alarm Handling 42 11 Live log viewer 43 12 Reports generator 44

Table of contents

Page 4: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 4

1.1 Validity This document applies to the Advanced Acoustic Processor with trade name AcoustAlert

• Hardware version 1.1

• AcoustAlert x64 version 2.3.6

1 About this document

Page 5: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 5

This document is used to install, configure and operate AcoustAlert x64.

The installer needs administrative rights to be installed.

2 Introduction

Page 6: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 6

Run the installer found on the installation media supplied

The install process will install all

required redistributables.

Click “Install” to continue with the

installation.

Click “Next” to continue with the

installation.

3 Installation

Page 7: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 7

Click “Next” to continue with the

installation.

Enter the user name and organization

desired as shown alongside.

Click “Next” to continue with the

installation.

3 Installation

4

Page 8: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 8

Click “Install” to continue with the

installation.

Click “Finish” to complete the

software installation.

3 Installation

5

Page 9: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 9

Run AcoustAlert x64 found on the desktop or in the start menu.

The following will be

displayed.

4 Opening the software

6

Page 10: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 10

Click on “Menu” on the top left corner and click on “AcoustAlert

Configuration”.

Enter the default password “3” and click on Enter.

The following screen is then

shown.

Click on “AcoustAlert

Configuration” followed by

clicking on “Network Settings”.

The network adapter where the

AcoustAlert devices can be

discovered must be set here.

5 AcoustAlert Configuration

7

Page 11: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 11

Select the network adapter from

the drop-down list as shown

alongside.

Click on “Set network adapter” to

save the selected adapter.

5 AcoustAlert Configuration

8

Page 12: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 12

The current selected network

adapter is then shown as

illustrated alongside.

We now need to setup the

AcoustAlert devices.

Click on “Device Configuration” to

configure the AcoustAlert

device(s).

Now click on “Discover

AcoustAlert devices” to discover

the devices found.

5 AcoustAlert Configuration

9

Page 13: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 13

Click on the MAC address drop-

down to select the devices

discovered.

Enter a name for the AcoustAlert

unit and an IP address for the

AcoustAlert device.

Please ensure that the name and

IP are unique; and that the IP

address is in the same range as

the computer.

Click on save once the

information required is entered.

5 AcoustAlert Configuration

10

Page 14: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 14

Select Input Configuration.

This where the inputs that are

connected are enabled and

names assigned to each input.

Click on the AcoustAlert Device

drop-down to select the

AcoustAlert device to configure.

5 AcoustAlert Configuration

11

Page 15: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 15

Check “Input 1 Active” check box

when in use then enter a unique

name for the input.

Check “Input 2 Active” check box

when in use then enter a unique

name for the input.

Click on “Save” to store this unit’s

details.

Click on “Zone Configuration” to

setup the zone configuration.

This is where the AcoustAlert

input can be configured as

required.

5 AcoustAlert Configuration

12

Page 16: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 16

Click on the drop-down list by

Zone name and select the Zone to

configure as shown alongside.

For the Zone to be configured

the following needs to done:

Detection % (i.e. the level of

disturbance to generate an

alarm)

Display Position (1 to 40 needs

to be selected)

Pre-Alarm Level (A Pre-Alarm

can be set-up or set to 0 to be

disabled)

Acknowledge Timeout (can be

setup to automatically

acknowledge alarms or set to 0

to be disabled)

5 AcoustAlert Configuration

13

Page 17: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 17

The Detection % starts at 2%

being the least sensitive to 100%

being the most sensitive.

Detection % is based on the level

of disturbance.

Display position is used for the

default layout

40 Zones can be setup and

monitored in total.

5 AcoustAlert Configuration

14

Page 18: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 18

The Pre-Alarm level is based on

the same principle as the

detection % and 0 will disable

Pre-Alarm monitoring.

The Acknowledge Timeout is used

for when the operator is

expected to respond and

acknowledge an alarm; before

automatically acknowledging the

alarm within the time specified.

5 AcoustAlert Configuration

15

Page 19: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 19

Click on “Save” to save the zone

configuration.

Click on “AcoustAlert Status” to

return to the front-end

monitoring.

The AcoustAlert zone(s) that have

been setup will now be shown and

monitoring will begin on the

Zone(s).

5 AcoustAlert Configuration

Page 20: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 20

Click on “Menu” on the top left corner and click on “AcoustAlert

Configuration”.

Enter the default password “3” and click on Enter.

Click on Moxa Configuration

followed by clicking on Device

Config.

Moxa IO Devices are added to

the AcoustAlert system here.

Moxa E1212 & E1214 are

currently supported.

6 Moxa Configuration

Page 21: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 21

Click on the Select Device drop-

down list.

Click on New Device to add a

Moxa IO to the system

Please note that the Moxa device

IP address is to be configured

using Moxa ioSearch.

Enter a name for the Moxa unit

and an IP address for the Moxa

device.

Please ensure that the name and

IP are unique; and that the IP

address is in the same range as

the computer.

Click on save once the

information required is entered.

6 Moxa Configuration

Page 22: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 22

Click on the Input tab

The inputs that are used will now

be configured.

Click on the Select Device drop

down list and select a MoxaIO

device.

6 Moxa Configuration

Page 23: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 23

Click on the Input 1 to Input 6

active for inputs that will be used

as a zone.

Enter a unique name for each

input, this will be the zone name.

Click on save once the required

information is entered.

Click on the Output tab.

The Outputs that are used will

now be configured.

6 Moxa Configuration

Page 24: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 24

Click on the Select Device drop

down list and select a MoxaIO

device.

Click on the Output 1 to Output 6

active for Outputs that will be

used.

Enter a unique name for each

Output, this will be the output

name.

Click on save once the required

information is entered.

6 Moxa Configuration

Page 25: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 25

Click on the Zone tab.

This is where you can assign the

Moxa input as a Zone to be

monitored.

Click on select input drop down

list and select a moxa input.

6 Moxa Configuration

Page 26: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 26

For the Zone to be configured the

following needs to done:

Alarm state (i.e. Is the alarm

condition open or closed)

Display Position (1 to 40 needs to

be selected)

Acknowledge Timeout (can be

setup to automatically

acknowledge alarms or set to 0 to

be disabled)

Click on Alarm state drop down

list and select either Normally

Closed or Normally Open.

6 Moxa Configuration

Page 27: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 27

Display position is used for the

default layout

40 Zones can be setup and

monitored in total.

Click on “Save” to save the zone

configuration.

6 Moxa Configuration

Page 28: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 28

Click on Alarm tab.

The MoxaIO outputs are

configured here.

There is 2 types of outputs one

being user controlled and the

other is an automatically

controlled output based on Zone

input conditions.

Click on the Select Output drop

down list and select a Moxa

output to configure.

6 Moxa Configuration

Page 29: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 29

We will now configure a Zone

event output.

Click on Output Type drop down

list and select Zone event.

To configure the Zone event we

require the following:

Active State (Must the output

switch to which state based on

the input zone status)

Zone Input (The input to be

monitored for the output

condition)

Zone Status (The state of the

zone input to switch to alarm

state)

6 Moxa Configuration

Page 30: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 30

Click on Active State drop down

list.

If the Active State selected is

Closed then based on the zone

status an Output will change to

Active state when the zone status

changes to the required

condition.

Click on Zone input drop down list

and select a Zone.

The Zone is the input that is

monitored such as AcoustAlert

Zones and MoxaIO Zones.

6 Moxa Configuration

Page 31: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 31

Click on Zone Status drop down

list.

The Zone Status is the state that

is needed to change the Output

Active state.

Once the Zone event parameters

have been entered click on Save

to save the Zone event.

6 Moxa Configuration

Page 32: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 32

We will now configure a User

Controlled output.

Select an output from the down

list.

Click on Output Type drop down

list and then click on User control.

6 Moxa Configuration

Page 33: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 33

In order to configure a User

control a display position and

Active State are required.

Click on Display Position drop

down list and select a display

position. This is used for the

default layout on the front-end

monitoring software.

6 Moxa Configuration

Page 34: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 34

Click on Active State and select

the state of the Moxa output

when the user changes the

output state to Active.

Once the parameters have been

entered click on Save.

Click on “AcoustAlert Status” to

return to the front-end

monitoring.

6 Moxa Configuration

Page 35: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 35

The Zones from AcoustAlert

and Moxa are shown on the

left.

The User controlled output(s)

are shown on the right-hand

side.

This is the default layout.

6 Moxa Configuration

Page 36: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 36

We are now going to configure the front-end monitoring layout.

The main graphic can be changed here and allowing the plotting of

zones to the desired location on the main graphic.

To do this click on “Menu” followed by clicking on “Layout Editor”.

Enter the password, default is “3”.

To change the graphic click “Menu” followed by clicking on “New

Map”.

An open dialog is shown, go to the

location of the image and click on “Open”.

The preferred size will be as follows:

i. Height = Screen Height – 60 pixels

ii. Width = Screen Width – 16 pixels

e.g.

1024 x 768 requires 1008 x 708

1920 x 1080 requires 1904 x 1020

7 Layout Editor

16

Page 37: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 37

The selected graphic

will be shown as

selected.

Move the mouse over any zone name and the mouse icon

will change to a hand icon. This allows you to hold the left

click of the mouse in and move the zone location to any

desired location.

7 Layout Editor

17

Page 38: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 38

Move the zones to

the desired

locations.

After moving the zones to the areas required click on “Menu” followed

by clicking on “Save Layout”.

Click on “Menu” followed by “Return to Alarm Display” to show changes

on the alarm display.

7 Layout Editor

18

Page 39: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 39

The new graphic and

zone layout is now

shown on the alarm

handling screen.

7 Layout Editor

19

Page 40: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 40

Open circuit fault condition.

Short circuit fault condition.

Offline fault condition.

Pre-Alarm condition.

Alarm Condition.

Disabled Condition.

Normal operating condition.

8 Zone Conditions

20

Page 41: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 41

In order to switch a Moxa output

to an active state go to output

and double click on its name

The output will now change to

active.

Double click on the output to

return to a normal state.

9 User Control Moxa Output

21

Page 42: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 42

To handle and acknowledge a condition double click on a

zone.

The following box is shown with details

on the event.

Enter response in the text dialog box.

Click on “Ignore conditions” to ignore

nuisance events for the specified time

only if necessary. Click on “Accept” to

acknowledge the alarm.

The Zone is then reset to a normal state.

10 Alarm Handling

22

Page 43: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 43

Hover the mouse

over “Live log” in

order to view the

last events that

occurred on the

system.

11 Live log viewer

23

Page 44: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 44

We are now going to look at

generating reports.

Click on “Menu” followed by

“Reports Generator” to generate

reports.

Enter the password, default is “3”.

Change the start date and time as desired.

Change the end date and time as desired.

Alarms report type generates a report

based on alarm activations only.

Conditions report type generates a report

based on conditions only.

AcoustAlert Zone report type generates a

report based on a particular AcoustAlert

zone.

Everything report type generates a report

based on all events.

Click on “Generate report”.

12 Reports Generator

24

Page 45: The acoustalert manual€¦ · followed by clicking on Device Config. Moxa IO Devices are added to the AcoustAlert system here. Moxa E1212 & E1214 are currently supported. 6 Moxa

AcoustAlert Software Manual Revision 7 2018

www.acoustalert.com 45

The report can

now be viewed.

The facility exists to export reports and print reports as

required.

Click on “Menu” and then “New Report” to generate a

different report else click on “Alarm Display” to return to

alarm display monitoring.

12 Reports Generator

10