texas fire marshals' conference october 17 to 21, 2011
DESCRIPTION
Texas Fire Marshals' Conference October 17 to 21, 2011. Codes & Standards for Kitchen Fire Suppression Systems A review of NFPA 96, 17A, and UL-300. Presenting Today’s Program. Jim Murphy. Industry Forecast. National Restaurant Association 2011 Executive Summary - PowerPoint PPT PresentationTRANSCRIPT
Texas Fire Marshals' ConferenceOctober 17 to 21, 2011
Codes & Standards forKitchen Fire Suppression Systems
A review of NFPA 96, 17A, and UL-300
Presenting Today’s Program
Jim Murphy
Industry Forecast
National Restaurant Association2011 Executive Summary
• Forecast $604 Billion in Sales – 4% of US GDP• $1.7 Billion per Day
• 960,000 Restaurant Locations• 12.8 Million employees – about 10% of US total
Fire Loss Data – Eating and Drinking Establishments
Eating and Drinking Establishment Fire Data (Summary from NFPA Fire Analysis – November 2010)
Ave. Annual Number of Reported Fires (2004-2008)
8.160 (Approximate) Annual Civilian Deaths 3
Property Damage $229 million
Annual Civilian Injuries 100
Deadliest single building fire in US history and most deadly for this occupancy type was the Coconut Grove Nightclub in Boston, where 492 people died.
The second most deadly occupancy type fire occurred in 1977 at the Beverly Hills Supper Club in Southgate, Kentucky which resulted in 165 deaths.
In 2010 NFPA reports that 18 Firefighters died responding to or returning from alarms. This represents 22% of on duty fire deaths.
157 Fires per week 22 Fires per day
Breakdown of Cooking EquipmentNFPA Data from the 2003 Report
CAUSE OF FIRESNUMBER OF FIRES
% OF FIRES
Stove 4,700 15.4%Deep Fat Fryer 1300 11.3%Oven 500 4.1%Open Fired Grill 400 3.2%Grease Hood or Duct 300 3.1%Portable Cooking or Warming Unit 100 1.0%Unclassified 400 3.2%
Codes & Standards that ApplyIn addition to NFPA 96 & 17A
2008 Current Edition Scope & Purpose Current Edition - Adoption by AHJ ? Need to be familiar with it’s contents even
where IFC is used for enforcement
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
To provide the minimum fire safety requirements (preventative and operative) related design, installation, operation, inspection, and maintenance of all public and private cooking operations.
Purpose – to reduce the potential fire hazard of cooking operations, irrespective of the type of cooking equipment used
In those cases where the AHJ determines that the existing situation presents an unacceptable degree of risk, the AHJ shall be permitted to apply retroactively any portion of this standard.
Scope Of NFPA Pamphlet a
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Approved.“Acceptable to the authority having jurisdiction.”– NFPA does not approve, inspect, or certify
Authority Having Jurisdiction. (referred to as AHJ) “ The organization, office, or individual responsible for approving equipment, an installation, or a procedure.”
Listed. Equipment or material included in a list published by an organization acceptable to the AHJ
Shall. “Indicated a mandatory requirement.”– Note: Should indicates a recommendation.
Chapter 3 -General Definitions
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Grease Filter. A removable component designed to capture grease and direct it to a safe collection point
Grease Filter Mesh Type. This filter is not tested, listed, or acceptable for commercial cooking operations due to the increased fire hazard.
Spark Arrester A device or method that minimizes the passage of air-borne sparks and embers into a plenum, duct, and flue.
Chapter 3 -General Definitions
Chapter 3 -General Definitions
“Liquid tight” Constructed and performing in such a manner as not to permit the passage of any liquid at any temperature.
“Grease tight” Constructed and performing in such a manner as not to permit the passage of any grease under normal cooking conditions.
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Hood, Fixed Baffle. A listed unitary exhaust hood design where the grease removal device is a non-removable assembly that contains an integral fire activated water-wash fire system listed for this purpose.
Chapter 3 -General Definitions
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
High Limit Control Device – An operating device installed and serving as an integral part of a fryer that provides secondary limitation of the grease temperature …
Single Hazard Area – Where two or more hazards can be simultaneously involved in fire by reason of their proximity as determined by the authority having jurisdiction.
Chapter 3 -General Definitions
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
4.1.1 Cooking equipment used in processes producing smoke or grease-laden vapors shall be equipped with an exhaust system complying with all the equipment and performance requirements of this standard.
4.1.2 All such equipment and performance shall be maintained per this standard during all periods of operation of the cooking equipment.
The following equipment shall be kept in good working condition: 1. Cooking equipment 2. Hoods 3. Ducts (if applicable) 4. Fans 5. Fire suppression systems 6. Special effluent or energy control equipment
All air flows shall be maintained. Maintenance and repairs shall be performed on all components at
intervals necessary to be able to maintain these conditions.
Chapter 4 -General Requirements
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
4.1.9* Cooking equipment used in fixed, mobile or temporary concessions, such as a truck, bus, trailer, pavilion, tent, or any form of roofed enclosure, shall comply with this standard unless all or part of the installation is exempted by the AHJ.
*The AHJ might exempt temporary facilities, such as a tent, upon evaluation for compliance to the applicable portions of this standard. Although it might not be practical to enforce all requirements of NFPA 96 in temporary facilities, the AHJ should determine that all necessary provisions are considered that impact on the personal safety of the occupants.
Chapter 4 -General Requirements
NFPA 96Temporary Concessions
Tent Fire in Polk Tent Fire in Polk County Florida - County Florida - 20012001
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Chapter 4 - GeneralClearance of 18” or to 3” – sheet metal, mineral wool bats & wire mesh or ceramic blanket, 1” spacer
4.2.4.3 …on the wall ..to the floor ..same as 4.2.1
4.2.4.2 In the event of a fire within exhaust system …shall be inspected by qualified personnel to determine … structurally sound
Chapter 5 Hoods 5.1 Construction
– 18 Gauge Steel – both Constructed and Supported (20 Gauge Stainless steel)
– All seams, joints, penetrations, “Shall” have a continuous external weld.
• Penetrations shall be permitted to be sealed by a Penetrations shall be permitted to be sealed by a listed device.listed device.
• Internal weld is permitted provided it is formed or Internal weld is permitted provided it is formed or ground smooth. ground smooth.
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
If you want steel exhaust hoods then we install steel exhaust hoods
Fire Dampers
– 5.3.4 Dampers• A fire actuated damper A fire actuated damper
“Shall” be installed in the “Shall” be installed in the supply air plenum at each supply air plenum at each point where the supply air point where the supply air duct penetrates the duct penetrates the continuously welded shell continuously welded shell of the assembly.of the assembly.
Shall be listedShall be listed Maximum Temperature of link 286Maximum Temperature of link 286°F°F
5.2 Hood Size Hoods shall be sized and configured to provide for capture and removal of grease laden vapors.
5.4 Listed Hood Assemblies. … installed in accordance with the terms of their listing…
Note that the IMC requires a 6” overlap of the hood to the appliances
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Chapter 6 Grease Removal Devices
6.1.1 Listed grease filters … shall be provided.
6.1.2 Filters (UL 1046) 6.1.3 Mesh filters “Shall” NOT
be used.
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
– 6.2.1.1 Distance from cooking equipment “Shall be as great as possible but not less than 18 inches.
– 6.2.1.2 Char-broilers “Shall” maintain a minimum vertical distance of 48 inches.
– 6.2.1.3 If no exposed flame and where flue gases bypass filters then not less than 6 inches clearance
– 6.2.2.2 A baffle plate can be used but still needs 18 inches and it must be at least 6” from filters
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Chapter 6 Grease Removal Devices
Chapter 6 Grease Removal Devices
6.2.4 Filters shall be equipped with a drip tray beneath their lower edges. The tray shall be kept to the minimum size needed to collect grease and shall be pitched to drain into an enclosed metal container having a capacity not exceeding one gallon. Grease filters that require a specific orientation to drain grease shall be clearly so designated …cannot be installed in the wrong direction
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
NFPA 96Grease Removal Devices
FiltersFilters– ……The filters The filters shallshall
be constructed so be constructed so that filters cannot that filters cannot be installed in thebe installed in theWrong Wrong OrientationOrientation
NFPA 96Grease Removal Devices
Grease FiltersGrease Filters– Extracted Extracted
grease drains grease drains down the filters down the filters to the holes in to the holes in the bottomthe bottom
Drain HolesDrain Holes
Chapter 7 Duct Systems
7.1 General – “Shall” not pass through fire walls
– “Shall” lead as directly as possible to the outside of the building.
– “Shall” not be interconnected with any other building ventilation or exhaust system.
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Chapter 7 Duct Systems
7.2 Clearance of 18” to 3” – sheet metal, mineral wool
bats, wire mesh, 1” spacer
Same as HoodsPer 4.2
Improper Clearances
Do it yourself duct
Not welded Wrong gauge steel Not liquid tight
7.3 Openings
Openings / Clean-outs – “Shall” be provided at the sides or at the top of
the duct, whichever is more accessible, and at changes of direction.
Access Panels per 7.4.3 Openings for installation, servicing, and
inspection of listed fire protection devices and for duct cleaning shall be provided in ducts and enclosures …
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
NFPA 96Openings/Clean-Outs
Clean-Outs Clean-Outs – A sign A sign shallshall be be
placed on all placed on all access panels access panels stating the followingstating the following
ACCESS PANELACCESS PANEL DO NOT DO NOT OBSTRUCTOBSTRUCT
Chapter 7 Duct Construction / Installation
7.5.1 Ducts “Shall be constructed of and supported by carbon steel not less than 16 gauge (18 ga. Stainless steel)
7.5.2.1 All seams, joints, penetrations,and hood to duct collar connections shall have a liquidtight continuous external weld.
See details for duct to hood connections
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Duct Construction / Installation Termination of Exhaust Ducts
7.8.2 Rooftop
• Minimum of 10 ft. clearance from the outlet to adjacent Minimum of 10 ft. clearance from the outlet to adjacent buildings, property lines, and air intakes.buildings, property lines, and air intakes.
• Minimum of 18 inches above roof with the exhaust Minimum of 18 inches above roof with the exhaust discharge a minimum of 40 inches above the roof discharge a minimum of 40 inches above the roof surface, with the flow directed up and away from the surface, with the flow directed up and away from the surface of the roof.surface of the roof.
• Hinged upblast fan supplied with flexible weather-proof Hinged upblast fan supplied with flexible weather-proof electrical cable “Shall” be provided. This allows for electrical cable “Shall” be provided. This allows for proper inspection and cleaning.proper inspection and cleaning.
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
NFPA 96Duct Construction/Installation
10’
Air IntakeAir Intake
10’
40”
Exhaust
18”
BuildingBuilding
To Property To Property Line,Building or Line,Building or Electric ServiceElectric Service
Duct Construction / Installation
7.8.3 Wall Terminations - “Shall” be provided with the following properties
• Through a non combustible wall with a minimum of 10 ft. of Through a non combustible wall with a minimum of 10 ft. of clearance from the outlet to adjacent buildings, property lines, clearance from the outlet to adjacent buildings, property lines, grade level, combustible construction, electrical equipment or grade level, combustible construction, electrical equipment or lines, and the closest point of any air intake or operable door lines, and the closest point of any air intake or operable door or window at or below the plane of the exhaust termination.or window at or below the plane of the exhaust termination.
• Exhaust flow directed perpendicularly outward from the wall Exhaust flow directed perpendicularly outward from the wall face or upward.face or upward.
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
TerminationDuct termination at
least 18” above roof
Upblast fan discharge is 40” above roof.
10’ from adjacent buildings, property lines, air intakes
Duct must maintain clearance from combustibles
Improper Installation
Fan not 10’ above grade
Exhaust and Makeup air fan not properly separated
Fan curb attached directly to vinyl siding
Improper Termination
Placement Curb sits on wooden
base No cleaning
provisions Clearance to
combustibles, wires, window
Improper Termination
Improper installation of down-blast fan
Fire Hazards Overdue for a
cleaning
Improper Termination
Clearance to combustible issue
Proper Installation
Hinged Upblast Fan Proper housing 40” Above Roofline UL listed for Kitchen
Exhaust Wired per NEC
Proper Installation
Correct installation on a limited combustible wall using a UL listed Hood Assembly
Chapter 8 Air Movement
8.1.1.1 Approved upblast fans with motors surrounded by the airstream shall be hinged, supplied with flexible weatherproof electrical cable and service hold-open retainers, and listed for this use.
8.1.2.1 In-Line Exhaust Fans – motors outside airstream – belts, pulleys protected with greasetight housing.
8.1.4 Exhaust fan housings shall be constructed of carbon steel not less than 16 gauge or stainless 18 gauge or per the terms of the listing
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Chapter 8 Air Movement
8.2.1.1 The air velocity through any duct shall not be less than 500 ft. per minute.
8.2.3.1 … exhaust fan shall continue to run after the extinguishing system has been activated …
8.3.1 “Shall” be adequate to prevent negative pressures in the commercial cooking area from exceeding 0.02 in. water column.
8.3.2 When its fire extinguishing system discharges, makeup air supplied internally to a hood shall be shutoff.
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Chapter 9 Auxiliary Equipment
9.1.1 Dampers shall not be installed in exhaust ducts or duct systems– 9.1.2 Where specifically listed for such use or where required as part of a listed
or approved device or system.
9.2.3.1 Lighting … shall be listed for use over commercial cooking appliances …
9.2.4 NFPA 70 (electrical requirements). No wiring in ducts.
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Chapter 9 Auxiliary Equipment 9.3.3 Any equipment, listed or otherwise, that provides
secondary filtration or air pollution control and that is installed in the path of travel of exhaust products shall be provided with an approved automatic fire-extinguishing system for the protection of the component sections of the equipment and shall include protection of the ductwork downstream of the equipment, whether or not the equipment is provided with a damper.
9.3.4 If the equipment provides a source of ignition, it shall be provided with detection to operate the fire-extinguishing system protecting the equipment.
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Fire-extinguishing equipment for the protection of grease removal devices, hood exhaust plenums, and exhaust duct systems shall be provided.
Cooking equipment that produces grease laden vapors and that might be a source of ignition of grease in the hood, grease removal device, or duct shall be protected by fire-extinguishing equipment.
Fire Extinguishing Equipment
IMC 509.1 IBC 904.11.1 904.11.2
Appliances
Appliances
Split Vat Fryer Single Vat Fryer
Other Codes / Standards for Cooking Appliances Electric Appliances
• UL 197 - constructionUL 197 - construction• NEC 422 – circuit, overcurrent, disconnectsNEC 422 – circuit, overcurrent, disconnects• IFC 904.11.2 - interlocks IFC 904.11.2 - interlocks • NEC 110.3(B) – clearances per markingsNEC 110.3(B) – clearances per markings
Gas Appliances• ANSI Z83 – construction; Z21.69 quick disconnectsANSI Z83 – construction; Z21.69 quick disconnects• IFC 904.11.2 disconnects/interlocksIFC 904.11.2 disconnects/interlocks
Solid Fuel Appliances• UL 2162 – constructionUL 2162 – construction• IMC 301.6 – floorsIMC 301.6 – floors• IMC 507.2.3 – exhaust hoodIMC 507.2.3 – exhaust hood
– 9.12.1 Listed floor mounted food service equipment, such as ranges for hotels and restaurants, deep fat fryers ….shall be installed at least 6” from combustible material.
– 9.12.2 Unlisted floor-mounted food service equipment shall be installed to provide a clearance to combustible material of not less than 18 in. (460 mm) at the sides and rear of the equipment and from the vent connector and not less than 48 in. above cooking tops and at the front of the equipment.
NFPA 54NFPA 54 – – National Fuel Gas CodeNational Fuel Gas Code
Chapter 9 Installation of Specific Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Fire extinguishing equipment shall include BOTH automatic fire extinguishing systems as primary protection and portable fire extinguishers as secondary backup.
Automatic fire-extinguishing systems shall comply with standard UL300 … or other equivalent standards and shall be installed in accordance the requirements of the listing.
In existing systems, when changes in the cooking media, positioning, or replacement of cooking equipment occur, the fire-extinguishing system shall be made to comply with 10.2.3
Fire Extinguishing Equipment
50.4.3.5 In existing systems, when changes in
the cooking media, positioning, or replacement of cooking equipment occur, the fire-extinguishing system shall be made to comply with UL 300.Exception' Automatic fire-extinguishing equipment provided as part
of listed recirculation systems complying with standard UL 197, Standard for Commercial Electric Cooking Appliances.
(Note: IFC contains same language)
NFPA 1 – Fire Prevention Code
Checking for the UL 300 Label
The Tank Label Indicates That This System Meets The Requirements Of UL 300, NFPA 17A, & NFPA 96
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
10.2.2 A placard identifying the use of the extinguisher as a secondary backup means to the automatic fire suppression system shall be conspicuously placed near each portable fire extinguisher in the cooking area
10.2.4 Grease removal devices, hood exhaust plenums, exhaust ducts, and cooking equipment not addressed in UL300 or other equivalent test standards, shall be protected with an automatic fire-extinguishing system in accordance with the applicable NFPA Standard and all local building and fire codes , and shall be approved by the authority having jurisdiction.
Chapter 10 – Fire Extinguishing Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Automatic fire extinguishing systems shall be installed in accordance with the terms of the listing, the manufacturer's instructions, and the following standards where applicable. NFPA 12, Standard on Carbon Dioxide Extinguishing SystemsNFPA 13, Standard for the Installation of Sprinkler systemsNFPA 17, Standard for Installation of Dry Chemical Extinguishing SystemsNFPA 17A, Standard for Wet Chemical Extinguishing Systems
Fire Extinguishing Equipment
IMC 509.1, IBC 904.11, IFC 904.11, ANSI/UL-300
All require systems per NFPA 96 (which calls to NFPA 17A)
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
10.2.7.1 Any abandoned pipe or conduit from a previous installation shall be removed…
10.2.7.3 The addition of obstructions to spray patterns from the cooking appliance nozzles such as baffle plates, shelves, or any modifications shall not be permitted.
Chapter 10 – Fire Extinguishing Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
10.2.8.1 Grease removal devices, hood exhaust plenums, and exhaust ducts requiring protection in accordance with 10.1.1, shall be permitted to be protected by a listed fixed baffle hood containing a constant or fire-actuated water system that is listed and is compliance with UL-300 or other equivalent standards and shall be installed in accordance of their listings.
Each such area not provided with a listed water-wash extinguishing system shall be provided with a fire-extinguishing system listed for the purpose.
Chapter 10 – Fire Extinguishing Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
The water for listed fixed baffle hood assemblies shall be permitted to be supplied from the domestic water supply when the minimum water pressure and flow are provided in accordance with the terms of the listing. The water supply shall be monitored by a supervised water supply control valve.
The water wash in the fixed baffle hood, specifically listed to extinguish a fire, shall be activated by the cooking equipment extinguishing system.
Fire Extinguishing Equipment
NFPA 96Fire Extinguishing Equipment
– ……Containing a constant Containing a constant or fire-actuated water or fire-actuated water spray system that is spray system that is listedlisted to extinguish a to extinguish a fire in the grease fire in the grease removal devices, hood removal devices, hood exhaust plenums, and exhaust plenums, and exhaust ductsexhaust ducts
NFPA 96Fire Extinguishing Equipment
The Water The Water Supply Supply – ShallShall be be
monitored by monitored by an annunciated an annunciated low water low water pressure switchpressure switch
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
10.3 Simultaneous Operation Fixed pipe extinguishing systems in a single hazard area (See Section 3.3 for the definition of Single Hazard Area) shall be arranged for simultaneous automatic operation upon actuation of any one of the systems.–Not required where the fixed pipe extinguishing system is an automatic sprinkler system.
–Not required where dry or wet chemical system shall be permitted to be used to protect common exhaust ductwork by one of the methods specified in NFPA 17, Standard for Dry Chemical Extinguishing Systems, or NFPA-17A, Standard for Wet Chemical Extinguishing Systems.
Chapter 10 – Fire Extinguishing Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
10.4 Fuel Shutoff Upon activation of any fire extinguishing system for a
cooking operation, all sources of fuel and electric power that produce heat to all equipment requiring protection by that system shall automatically shut off.–Not steam supplied from an external source.
Any gas appliance not requiring protection, but located under the same ventilating equipment, shall also automatically shut off upon activation of any extinguishing system.
Shutoff devices shall require manual reset.
Chapter 10 – Fire Extinguishing Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Manual Activation
A readily accessible means for manual activation shall be located between 42 in. and 48 in. above the floor, located in a path of exit or egress, and clearly identify the hazard protected.
The manual means of system activation, shall be permitted to be common with the automatic means if the manual activation device is located between the control head or releasing device and the first fusible link.
Fire Extinguishing Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
10.6 System Annunciation Upon activation of an automatic fire extinguishing
system,an audible alarm or visual indicator shall be provided to show that the system has activated.
Where a fire alarm signaling system is serving the occupancy where the extinguishing system is located, the activation of the automatic fire extinguishing system shall activate the fire alarm signaling system.
Chapter 10 – Fire Extinguishing Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
10.7 System Supervision 10.7.1 Where electrical power is required to operate the
automatic fire extinguishing system, it shall be monitored by a supervisory alarm, with a standby power supply provided.–Not where automatic fire extinguishing systems include automatic mechanical detection and actuation as a backup detection system.
–Not where automatic fire extinguishing systems are interconnected or interlocked with the cooking equipment power sources so that if the fire system becomes inoperable due to power failure, all sources of fuel or electric power that produce heat to all cooking equipment serviced by that hood shall automatically shut off.
Chapter 10 – Fire Extinguishing Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
10.8 Special Design and Application. Hoods containing automatic fire extinguishing systems
are protected areas; therefore, these hoods are not considered obstructions to overhead sprinkler systems and shall not require floor coverage underneath.
A single listed detection device shall be permitted for more than one appliance when installed in accordance with the terms of the listing.
Chapter 10 – Fire Extinguishing Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
10.9 Review and Certification 10.9.1 Where required, complete drawing of the
system installation, including the hood(s), exhaust duct(s), and appliances, along with the interface of the fire extinguishing system detectors, piping, nozzles, fuel shutoff devices, agent storage container(s), and manual actuation device(s), shall be submitted to the authority having jurisdiction.
Chapter 10 – Fire Extinguishing Equipment
When Drawings required they are prepared with the advise of the AHJ and include sufficient details to satisfy the AHJ.
They can range from a simple 8 ½ x 11 hand sketch to AutoCAD
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
10.9.2.1 Installation of systems shall be performed only by persons properly trained and qualified to install the specific system being provided.
10.9.2.2 The installer shall provide certification to the authority having jurisdiction that the installation is in complete agreement with the terms of the listing and the manufacturer's instructions and/or approved design.
Annex - Although training and qualification may be available elsewhere, the manufacturer of the equipment being installed should be considered an appropriate source of training and qualification.
Chapter 10 – Fire Extinguishing Equipment
Fire Extinguishers Fire Extinguishers Serviced HereServiced Here
Fresh SushiFresh Sushi
Certification of systems
Fuel shut off operable gas/electric
Fully functioning Accessories tested
– Pull Station
– Detection
– Building Alarm
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Portable Fire Extinguishers 10.10.1* Portable fire extinguishers shall be installed in kitchen
cooking areas in accordance with NFPA 10, Standard for Portable Fire Extinguishers and shall be specifically listed for such use.
Extinguishers shall use agents that saponify upon contact with hot grease such as sodium bicarbonate and potassium bicarbonate dry chemical and potassium carbonate solutions.
Class B gas-type portables shall not be permitted in kitchen cooking areas.
Annex - The system used to rate extinguishers for Class B fires (flammable liquids in depth) does not take into consideration the special nature of heated grease fires. Cooking grease fires are a special hazard requiring agents that saponify (make a soap foam layer to seal the top surface of the grease) for this application.
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
10.10.5 Other fire extinguishers in the kitchen area shall be installed in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
[ Note that NFPA 10 States - Portable Fire Extinguisher shall be installed in the kitchen cooking areas in accordance with NFPA 10, Table 3-3.1 for Extra (High) Hazard ]
Chapter 7 – Fire Extinguishing Equipment
NFPA 10 Portable Extinguishers 4.3.2* Class K Fire Extinguishers for Cooking Oil Fires. Fire
extinguishers provided for the protection of cooking appliances that use combustible cooking media (vegetable or animal oils and fats) shall be listed and labeled for Class K fires. Class K fire extinguishers manufactured after January 1, 2002, shall not be equipped with “extended wand–type” discharge devices.
4.3.2.1 Fire extinguishers installed specifically for the protection of cooking appliances that use combustible cooking media (animal, vegetable oils and fats) prior to June 30, 1998, shall not be required to comply with 4.3.2. (Also see 4.3.2.3.)
4.3.2.2* A placard shall be conspicuously placed near the extinguisher that states that the fire protection system shall be activated prior to using the fire extinguisher.
NFPA 10 Portable Extinguishers
4.3.2.3 Existing dry chemical extinguishers without a Class K listing that were installed for the protection of Class K hazards shall be replaced with an extinguisher having a Class K listing when the dry chemical extinguishers become due for either a 6 year maintenance or hydrostatic test
Fire Extinguishing Fire Extinguishing EquipmentEquipment– ShallShall include both include both
automatic fire automatic fire extinguishing systems extinguishing systems asas primary protectionprimary protection
– And portable fire And portable fire extinguishers as extinguishers as secondary protectionsecondary protection
PlacardPlacard– A placard identifying the A placard identifying the
use of the extinguisher as use of the extinguisher as A SECONDARYA SECONDARY backup backup means to the automatic means to the automatic fire suppression system fire suppression system shallshall be conspicuously be conspicuously placed near placed near EACH EACH portable fire extinguisher portable fire extinguisher in the cooking areain the cooking area
Class “K” Fire Test
Follows UL 300 Standard test protocol– Large “high efficiency” fryer (80 LB capacity)– Vegetable oil with anti-foaming agents– Auto-ignition temperature of 6850F or more– No re-flash permitted– Three consecutive successful extinguishment
Class “K” Extinguisher Use
Traditional dry chemical extinguishers can not cool the appliance
Reflash can occur in less than 60 seconds
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Exhaust systems shall be operated whenever cooking equipment is turned on.
Instructions for manually operating the system shall be posted conspicuously in the kitchen and shall be reviewed with employees by the management.
Cooking equipment shall not be operated while its fire-extinguishing system or exhaust system is nonoperational or otherwise impaired.
Chapter 11 – Use and Maintenance of Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
– An Inspection and servicing of the fire-extinguishing system and listed exhaust hoods containing a constant or fire-actuated water system shall be made at least every six months by properly trained and qualified persons.
– All actuation components shall be checked for proper operation during the inspection in accordance with the manufacturer’s listed procedures.
– Fusible links (including fusible links on fire damper assemblies) and automatic sprinkler heads shall be replaced at least semi-annually, or more frequently if necessary where required by the manufacturer.
– Year of mfg. And date of installation shall be marked on system inspection tag. The tag shall be signed or initialed by the installer.
Chapter 11 – Use and Maintenance of Equipment
Inspection
System out of hydro Manufacturer out of
business UL listing not valid Malfunctioning fryer No remote pull Combustible wall
Inspection
Duct Nozzle New Duct Nozzle found
during an inspection, had not been checked on a routine 6 month schedule
Inspection Fusible Links
Bottom - New UL “Listed” Fusible Link
Top Link in service for 6 months may fuse at 600 or 700 degrees
What to look for during inspections
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
11.3 The entire exhaust system shall be inspected by properly trained, qualified, and certified company or person(s) acceptable to the AHJ in accordance with Table 11.3
Chapter 11 – Use and Maintenance of Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Table 11.3Chapter 11 – Use and Maintenance of Equipment
Type or Volume of Cooking FrequencySystems serving solid fuel
cooking operations Monthly
Systems serving highvolume cooking operations
such as 24 hr. cooking,charbroiling or wok cooking
Quarterly
Systems serving moderatevolume cooking operations
Semi-annually
Systems serving low volumecooking operations such as
churches, day camps,seasonal, or senior centers
Annually
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Upon inspection, if found to be contaminated with deposits from grease-laden vapors, the entire exhaust system shall be cleaned by a properly trained, qualified, and certified company or person(s) acceptable to the authority having jurisdiction in accordance with Section 11-3.
Chapter 11 – Use and Maintenance of Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Hoods, grease removal devices, fans, ducts, and other appurtenances shall be cleaned to bare metal at frequent intervals prior to surfaces becoming heavily contaminated with grease or oily sludge.
After the exhaust system is cleaned to bare metal, it shall not be coated with powder or other substance.
After cleaning, … shall place or display in the kitchen area a label indicating the date cleaned and the name of the servicing company, and the areas not cleaned.
Where required, certificates of inspection and cleaning shall be submitted to the AHJ
Chapter 11 – Use and Maintenance of Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Components of the fire-extinguishing system shall not be rendered inoperable during the cleaning process
Cleaning chemicals shall not be applied on fusible links or other detection devices of the automatic extinguishing system
Chapter 11 – Use and Maintenance of Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
12.1.1 Cooking equipment shall be approved based on one of the following criteria:
1.1. Listing by a testing laboratoryListing by a testing laboratory2.2. Test data acceptable to the AHJTest data acceptable to the AHJ
12.1.2.1 All listed appliances shall be installed in accordance with the terms or their listings and the manufacturer’s instructions.
Chapter 12 – Minimum Safety Requirements for Cooking Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Cooking appliances requiring protection shall not be moved, modified, or rearranged without prior reevaluation of the fire extinguishing system by the system installer or servicing agent, unless otherwise allowed by the design of the fire extinguishing system.Cooking appliances moved to perform maintenance and cleaning provided the appliances are returned to their original positioning prior to cooking operations, and any disconnected fire extinguishing system nozzles attached to the appliances are reconnected in accordance with the manufacturer's listed design manual.
Chapter 12 – Minimum Safety Requirements for Cooking Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
Annex - The effectiveness of an automatic extinguishing system is affected by the placement of the nozzles. For this reason, it is essential that the cooking appliances are situated in the area in which they were when the extinguishing equipment was designed and installed. If an appliance is moved from under the equipment for cleaning or other reason, it should be replaced to its original position prior to initiating a cooking operation.
Chapter 11 – Minimum Safety Requirements for Cooking Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
All deep fat fryers shall be installed with at least a 16 in. space between the fryer and surface flames from adjacent cooking equipment. (previously NFPA 96, 1994 9-1.2.2)
Where a steel or tempered glass baffle plate is installed at a minimum 8 in. (203 mm) in height between the fryer and surface flames of the adjacent appliance the requirement does not apply
If the fryer and the surface flames are at different planes the minimum height shall be measured from the higher of the two.
Chapter 12 – Minimum Safety Requirements for Cooking Equipment
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
14.1.6 Solid fuel cooking operations shall have spark arresters to minimize the passage of airborne sparks and embers into plenums and ducts.
14.1.7 Where the solid fuel cooking operation is not located under a hood, a spark arrester shall be provided to minimize the passage of sparks and embers into flues and chimneys
Chapter 14 – Solid Fuel Cooking Operations
Flame Gard Inc.
Type 1 Filter with arrestor
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
14.7.1 Solid fuel cooking operations that produce grease laden vapors shall be protected by listed fire-extinguishing equipment.
Where acceptable to the authority having jurisdiction, solid fuel burning cooking appliances constructed of solid masonry or reinforced portland or refractory cement concrete and vented in accordance with NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances, Chapters 3 and 4, shall not require automatic fire extinguishing equipment.
Chapter 14 – Solid Fuel Cooking Operations
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
14.7.8 All solid fuel appliances (whether or not under a hood) with fire boxes of 5 cu ft (0.14 m 3 ) volume or less shall at least have a 2-A-rated type water-type or a 6 L wet chemical fire extinguisher listed for Class K fires in accordance with NFPA in the immediate vicinity of the appliance.
Chapter 14 – Solid Fuel Cooking Operations
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
14.7.10.1 Solid fuel appliances with fire boxes exceeding 5 cu ft (0.14 m 3 ) Shall be provided with a fixed water pipe system with a hose in kitchen capable of reaching the firebox.
The system shall have a minimum operating pressure of 40 psi and shall provide a minimum of 5 gpm.
The nozzle cannot produce a solid stream.
Chapter 14 – Solid Fuel Cooking Operations
NFPA 96 – Standard for Ventilation Control & Fire Protection of Commercial Cooking Operations
14.8 Solid fuel appliances shall be inspected, cleaned, and maintained in accordance with procedures outlined in Chapter 11, and with 18.8.1 through 14.8.5
14.9 Fuel Storage, Handling, and Ash Removal–Install appliances on noncombustible floors that extend 3 feet in all directions from the appliance
–Fuel storage shall not exceed a one-day supply where stored in the same room as the appliance – not stored closer than 3’ to appliance – not in the path of ash removal – shall be protected with sprinkler systems or a fixed pipe system 14.7.1 through 14.7.12
–Combustible or flammable liquids shall not be used to assist ignition.
Chapter 14 – Solid Fuel Cooking Operations
NFPA 17A – Wet Chemical Extinguishing Systems
2009 Current Edition 2002 Edition cited by many
Jurisdictions (time to catch up)
Distributors work with most conservative / most current or face legal issues
NFPA 17A – Wet Chemical Extinguishing Systems
Design considerations applicable to wet chemical systems.
System design principles applicable to the products of one manufacturer are not applicable to the products of another manufacturer.
Minimum requirements are specified for restaurant, commercial, and institutional hoods, plenums, ducts and associated cooking appliances.
The Authority having jurisdiction shall determine compliance with standard.
Scope Of NFPA Pamphlet a
* Pre-engineered System. – Predetermined flow rates, nozzle pressures, and quantities of
liquid agent.
– Specific pipe size, maximum and minimum pipe lengths, (maybe expressed in equivalent feet) flexible hose specifications, number of fittings, and number and types of nozzles
– The hazards protected are specifically limited as to type and size
– Prescribed by a testing laboratory, based on actual fire tests.
– Limitations contained in the manufacturer’s listed installation and maintenance manual, which is part of the listing.”
General Definitions
NFPA 17A – Wet Chemical Extinguishing Systems
Inspection. Inspection is a “quick check” by system owner to give reasonable assurance that the system is fully charged and operable.
Maintenance. “Maintenance is a thorough check by a trained person to give maximum assurance that the extinguishing system will operate as intended It includes a through examination and any necessary repair or replacement of system components.”
Manufacture’s listed manual. The pamphlet referenced as part of the listing… .
General Definitions
NFPA 17A – Wet Chemical Extinguishing Systems
Trained. “One who has undergone the instructions necessary to safely design and install and reliably perform the maintenance and recharge service.”
Qualifications. “ Only persons properly trained shall be considered competent to design, install, and service pre-engineered wet chemical systems.”
General Definitions
NFPA 17A – Wet Chemical Extinguishing Systems
OfficeOffice
WarehouseWarehouse
Fully LicensedFully Licensed
Earl’s ExtinguishersEarl’s Extinguishers
Only components referenced or permitted in the manufacturer’s listed manual ... shall be used.
Discharge nozzles, shall be listed for their intended use. – strainers – corrosion-resistant materials– permanently marked – be provided with suitable devices to prevent grease and other foreign
material into the piping. Operating devices, Shall be listed Manual Actuators
– Provided with operating instructions and identify the hazard it protects
Components
NFPA 17A – Wet Chemical Extinguishing Systems
Restaurant Systems
ComponentsComponents– Must beMust be ListedListed In In
The Manufacturer’s The Manufacturer’s ManualManual for use in for use in the particular the particular system being system being serviced or installedserviced or installed
Ansul Gas Valve Is Listed With Ansul Ansul Gas Valve Is Listed With Ansul andand Amerex Systems Amerex Systems
Restaurant Systems ComponentsComponents– If components are If components are
NotNot from the same from the same manufacturermanufacturer• System is System is NotNot UL UL
listedlisted• No fire testingNo fire testing• No 500 cycle No 500 cycle
mechanical testingmechanical testing• No warranties are No warranties are
in placein placePyro-Chem Corner Pulley Pyro-Chem Corner Pulley FSI NozzlesFSI Nozzles – – Ansul Fusible Link BracketAnsul Fusible Link Bracket
Pipe and Fittings – Galvanized pipe and fittings shall not be used. – In accordance with manufacturer’s manual.
Wet Chemical.– Shall be listed for that particular system and recommended by
manufacturer of the system.CAUTION: Wet chemical solutions of different manufacturer’s shall not
be mixed. Wet Chemical
Caution No. 2 Wet chemical, … can have corrosive effects on electrical components and cooking equipment. Prompt cleanup will minimize staining or corrosion.
Components
NFPA 17A – Wet Chemical Extinguishing Systems
Wet chemical fire extinguishing system shall comply with standard UL 300.
See the manufacturer’s listed manual for system limitations and applications
Each protected cooking appliance, individual hood, and branch exhaust duct directly connected to the hood shall be protected by a system or systems designed for simultaneous operation
Where two or more hazards may be simultaneously involved in fire by reason of proximity, shall be protected by individual systems installed to operate simultaneously
System Requirements, Applications
NFPA 17A – Wet Chemical Extinguishing Systems
Components 4.4.2
NFPA 17A – Wet Chemical Extinguishing Systems
Manual actuators shall not require a force of more than 40 lb (178 N).
Manual actuators shall not require a movement of more than 14 in. (356 mm) to secure operation.
All manual actuators shall be provided with operating instructions.
These instructions shall be permitted to include the use of pictographs and shall have lettering at least ¼ in. (6.35 mm) in height. (See 5.2.1.4.)
All remote manual operating devices shall be identified as to the hazard they protect.
Restaurant Systems Remote ReleaseRemote Release
– UL Allows for aUL Allows for a MaximumMaximum of 40 lbs. of 40 lbs. of pull of pull oror push to push to trip the systemtrip the system
– UL Allows for a UL Allows for a MinimumMinimum of ½” of of ½” of travel or a travel or a MaximumMaximum of 14” of of 14” of traveltravel
System locationCylinders to located within temperature listed range.Not located where subject to damage.Accessible for inspection, maintenance, and recharge.Located near the hazard not where they will be exposed to the fire.
Nozzles– Discharge nozzles shall be so connected and supported that
they will not be readily put out of alignment.
System Requirements
NFPA 17A – Wet Chemical Extinguishing Systems
Restaurant Systems Agent CylindersAgent Cylinders
– Agent cylinders must Agent cylinders must be located outside of be located outside of the hazardthe hazard
– Locating cylinders Locating cylinders within the hazard can within the hazard can cause damage to the cause damage to the agent cylindersagent cylinders
Special Requirements– Detection shall be provided above each appliance or
group of appliances protected by a single nozzle.
Exception: Appliances located directly below an exhaust duct opening and placed within the first 12 inches of the entrance to the duct.
– Hood or duct penetrations shall have a liquid tight seal.
– Automatic protection shall be provided for all common exhaust ducts. (see Appendix).
System Requirements
NFPA 17A – Wet Chemical Extinguishing Systems
Restaurant Systems
DetectionDetection– System detection System detection
may be by may be by thermostats, fusible thermostats, fusible links, or pressurized links, or pressurized temperature temperature sensitive tubingsensitive tubing
PRM – Pneumatic PRM – Pneumatic Releasing ModuleReleasing Module
KP Restaurant Fire Suppression SystemsKP Restaurant Fire Suppression Systems
PRM DETECTOR TUBINGPRM DETECTOR TUBING
KP Restaurant Fire Suppression SystemsKP Restaurant Fire Suppression Systems
Linear Fusible Link Detection NetworkLinear Fusible Link Detection Network
MRM
HOOD
24” MAX. DIST.FROM END OF HOOD
24” MAX. DIST.LINK TO LINK
24” MAX. DIST.FROM END OF HOOD
HANDY CONDUIT BOX2 1/8” X 4”
TERMINAL CONNECTOR& EMT FITTING
TERMINAL CABLE SEGMENT
LINK TO LINKCABLE SEGMENT
LINK TO MRMCABLE SEGMENT
PLENUM
DUCT
CABLE EYE BOLT SUPPORTREQUIRED ON EACH SIDE OF THE DUCT
CE
NTE
R O
F
LIN
K
CE
NTE
R O
F
LIN
K
CE
NTE
R O
F
LIN
K
ZONE OF PROTECTIONZONE OF PROTECTIONNozzle PN14178Nozzle PN14178
CENTERLINE TOTAL FLOOD NOZZLES17”
34” DEPTH ZONE of PROTECTION
HOOD DEPTH
6” MAX.
20” MAX 20” MAX
LENGTH OF HOOD
ZD Restaurant Fire Suppression SystemZD Restaurant Fire Suppression System
Manual Page: 3-7 Manual Page: 3-7 APPLIANCE PROTECTIONAPPLIANCE PROTECTION
Special Requirements– Movable cooking equipment shall be
provided with a means to ensure correct positioned in relation to the appliance discharge during cooking operations
System Requirements
NFPA 17A – Wet Chemical Extinguishing Systems
Approval of plans are required they shall be submitted to the authority having jurisdiction for approval before work starts. The completed system shall be tested by trained personal as required by the manufacturer’s listed manual. The tests shall determine that the system has been properly install and will function as intended (see Appendix).
Plans and Acceptance Tests
NFPA 17A – Wet Chemical Extinguishing Systems
Restaurant Systems Appliance CoverageAppliance Coverage
– Proof of proper Proof of proper coverage must be coverage must be provided from the provided from the installerinstaller
– When in doubt When in doubt request a copy of the request a copy of the pages from of the pages from of the manufacturer’s manufacturer’s listedlisted installation manualinstallation manual
Installer Designed Illegal SystemInstaller Designed Illegal System
Recharge. After any discharge, or if insufficient charge is noted during inspection or maintenance procedure shall be conducted per MLM– Piping shall be flushed in accordance to MLM
Inspection, Maintenance, and Recharging
NFPA 17A – Wet Chemical Extinguishing Systems
Owners Inspection– Conducted on monthly basis in accordance
with MLM• (h) (h) The hood, duct, and protected cooking The hood, duct, and protected cooking
appliances have not been replaced, appliances have not been replaced, modified, or replaced.modified, or replaced.
Inspection, Maintenance, and Recharging
NFPA 17A – Wet Chemical Extinguishing Systems
A trained person who has undergone the instructions necessary to perform the maintenance and recharge service reliably and has the applicable manufacturer’s manual and service bulletins shall service the wet chemical system at intervals not more than 6 months apart as outlined .
Inspection, Maintenance, and Recharging
NFPA 17A – Wet Chemical Extinguishing Systems
Wet chemical containers shall be subject to a hydrostatic pressure test at intervals not exceeding 12 years.
Wet chemical agent removed from the containers prior to hydrostatic testing shall be discarded.
Inspection, Maintenance, and Recharging
NFPA 17A – Wet Chemical Extinguishing Systems
To protect the hazard during hydrostatic testing, if there is no connected reserve, alternate protection acceptable to the AHJ shall be provided.
Inspection, Maintenance, and Recharging
NFPA 17A – Wet Chemical Extinguishing Systems
Wet chemical solutions are relatively harmless and normally have no lasting significant effects on skin, respiratory system, or clothing. They may produce mild, temporary irritation, but symptoms usually will disappear when contact is eliminated. Irritation of the eyes should be treated by flushing with tap water for 15 minutes or longer. Any condition or prolonged irritation should be referred to a physician for treatment.
Annex - Explanatory Material
NFPA 17A – Wet Chemical Extinguishing Systems
Disposal of wet chemical is best handled by flushing with water.
Investigated to determine not to produce splash.
Annex - Explanatory Material
NFPA 17A – Wet Chemical Extinguishing Systems
Power Ventilator for Restaurant Cooking Equipment UL 762, YZHW
Hood and Grease Duct Accessories UL 1978, YYXS
Grease Filters UL 1046, AKUS
Grease Duct Enclosures UL 2221, YYET Grease Ducts UL 1978, YYGQ
Through Penetration Fire Stop System UL 1479, XHEZ
Luminaries UL 1598, IETX
Fire Extinguishing System UL 300, GMXH, GOAS
Exhaust Hood UL 710, YXZR, YYCW
Cooking Equipment UL 197, KNGT, KNNS ANSI Z83, LGQX UL 795, LBOZ UL 2162, LCJX, LVTT
Commercial Cooking
UL Categories and Standards
UL 300 Standard “Fire Extinguishing Systems For The Protection of Restaurant Cooking Areas” – Effective November 21, 1994
Attempt to make fire testing more realistic.– Shut-off of fuel (heat) source at time of discharge instead of at time of
ignition.
– Two minute pre-burn. Two minutes of extra heat input.
– All claims must be tested.
– Extinguishment tests at both maximum And minimum nozzle heights.
– Splash tests required on certain appliances.
UL 300 – Update
UL 300 – Update
Standard Changes from November 1994– Grease Auto-ignition Temperature Increased
from 650°F to 685°F.
– Tilt Skillet / Braising Pan Protect as Fryer.
UL 300 – Update
Video from FEMA Shows comparison of UL-300 protocol to Subject
300 protocol for fryer testing Also shows sprinkler system using EA-1 sprinkler
head (no longer UL listed for fryer coverage)
Available from FEMA for $3 on CD – multiple languages
For more information:
Jim Murphy
Amerex Corporation
(804) 639-2271
http://www.Amerex-Fire.com
*******************************************************************Fire Equipment Manufacturers’ Association
CD’s include the UL-300 video, extinguisher education and rack hose training
www.femalifesafety.org/ (216) 241-7333
Follow up to this Presentation
The following slides are not part of today’s presentation but might be useful in identifying deficiencies in fire suppression system installations.
An electronic copy of today’s presentation was furnished and might be a better way to review the following slides.
Find the Deficiencies Find the Deficiencies in the Following Slidesin the Following Slides
Improper InstallationsImproper InstallationsImproper MaintenanceImproper Maintenance
www.fsfc.ufl.edu
8/09/02 FSFC 1620 143
8/09/02 FSFC 1620 144
Actuation lineActuation line
No distribution pipe No distribution pipe to nozzlesto nozzles
This system was left This system was left for six months until for six months until another company another company found it on the semi-found it on the semi-annual inspectionannual inspection
This System Was on This System Was on the Ground Floor of a the Ground Floor of a Large ResortLarge Resort
8/09/02 FSFC 1620 145
8/09/02 FSFC 1620 146
Pipe is bentPipe is bent
Nozzles not pointing Nozzles not pointing into broilerinto broiler
No nozzle capsNo nozzle caps
8/09/02 FSFC 1620 147
8/09/02 FSFC 1620 148
Nozzle over Nozzle over warmerwarmer
No nozzles over No nozzles over two grillstwo grills
Nozzle cap offNozzle cap off
Too many flow Too many flow points on one points on one branch linebranch line
8/09/02 FSFC 1620 149
8/09/02 FSFC 1620 150
Plastic bins on top of Plastic bins on top of hoodhood
Shelf blocking coverageShelf blocking coverage
No nozzle in the Under No nozzle in the Under Shelf broiler [the Shelf broiler [the griddle]griddle]
Obsolete Dry Chemical Obsolete Dry Chemical SystemSystem
8/09/02 FSFC 1620 151
8/09/02 FSFC 1620 152
Nozzle covering appliance Nozzle covering appliance outside of hoodoutside of hood
Remote pull next to hazardRemote pull next to hazard
8/09/02 FSFC 1620 153
8/09/02 FSFC 1620 154
Duct needs cleaningDuct needs cleaning
Fusible link cable is Fusible link cable is broken jamming the broken jamming the cablecable
This was the only link This was the only link in the systemin the system
Conduit is full of Conduit is full of greasegrease
This System Was in a This System Was in a HospitalHospital
8/09/02 FSFC 1620 155
8/09/02 FSFC 1620 156
Fryers are not Fryers are not under the hoodunder the hood
Fire system is Fire system is over the hazardover the hazard
Obsolete Dry Obsolete Dry Chemical Chemical SystemSystem
Remote release Remote release is on face of is on face of hoodhood
8/09/02 FSFC 1620 157
8/09/02 FSFC 1620 158
No deficienciesNo deficiencies
8/09/02 FSFC 1620 159
8/09/02 FSFC 1620 160
Duct needs cleaningDuct needs cleaning
No nozzle in ductNo nozzle in duct
Fusible link is not in Fusible link is not in the entrance to the the entrance to the ductduct
Duct is pop-riveted Duct is pop-riveted to the hoodto the hood
Mesh filtersMesh filters
Broiler is not Broiler is not protectedprotected
8/09/02 FSFC 1620 161
8/09/02 FSFC 1620 162
Nozzles are not aimed at Nozzles are not aimed at the midpoint of each fryerthe midpoint of each fryer
8/09/02 FSFC 1620 163
8/09/02 FSFC 1620 164
Nozzle aimed at wallNozzle aimed at wall
8/09/02 FSFC 1620 165
8/09/02 FSFC 1620 166
No No deficienciesdeficiencies
8/09/02 FSFC 1620 167
8/09/02 FSFC 1620 168
No coverage in No coverage in broilerbroiler
Coverage of stove Coverage of stove blocked by the blocked by the broiler and the shelfbroiler and the shelf
8/09/02 FSFC 1620 169
8/09/02 FSFC 1620 170
Apron hanging over Apron hanging over remote pull stationremote pull station
8/09/02 FSFC 1620 171
8/09/02 FSFC 1620 172
Filters need cleaningFilters need cleaning
The shelf blocks the The shelf blocks the chemical from reaching chemical from reaching the appliances the appliances
No coverage of the No coverage of the salamander broilersalamander broiler
8/09/02 FSFC 1620 173
8/09/02 FSFC 1620 174
Charcoal broiler cannot Charcoal broiler cannot be used under the same be used under the same hood as grease hood as grease producing appliancesproducing appliances
ABC fire extinguisher ABC fire extinguisher rated 2A-10BCrated 2A-10BC
Class A hazardClass A hazard
8/09/02 FSFC 1620 175
8/09/02 FSFC 1620 176
Cylinder is mounted Cylinder is mounted to the hood with to the hood with screwsscrews
No quick seal No quick seal
Remote pull is Remote pull is higher than 60”higher than 60”
Obsolete SystemObsolete System
8/09/02 FSFC 1620 177
8/09/02 FSFC 1620 178
Wrong nozzle over Wrong nozzle over the char broilerthe char broiler
Nozzle heights are Nozzle heights are wrongwrong
No nozzles over the No nozzles over the salamandersalamander
Grill coverage is Grill coverage is blocked by shelfblocked by shelf
8/09/02 FSFC 1620 179
8/09/02 FSFC 1620 180
Only 3 appliance Only 3 appliance nozzlesnozzles
Wrong nozzles over the Wrong nozzles over the char broiler char broiler
Nozzle is covered with Nozzle is covered with foilfoil
Salamander is not Salamander is not coveredcovered
Coverage is blocked to Coverage is blocked to the griddle and char the griddle and char broilerbroiler
8/09/02 FSFC 1620 181
8/09/02 FSFC 1620 182
This plug is This plug is where 4 nozzles where 4 nozzles used to beused to be
8/09/02 FSFC 1620 183
8/09/02 FSFC 1620 184
No links on this side of No links on this side of the hood the hood
No nozzles over these No nozzles over these appliancesappliances
(Range, tilt skillet, or in (Range, tilt skillet, or in the upright broiler)the upright broiler)
8/09/02 FSFC 1620 185
8/09/02 FSFC 1620 186
The control head The control head cartridge of a Pyro cartridge of a Pyro Chem system can Chem system can only fire three only fire three cylinderscylinders
This system has four This system has four cylinderscylinders
This System Would This System Would Never Have Never Have DischargedDischarged
8/09/02 FSFC 1620 187
8/09/02 FSFC 1620 188
System is a Pyro-System is a Pyro-Chem systemChem system
Both nozzles are Both nozzles are Kidde plenum Kidde plenum nozzlesnozzles
Char broiler is next Char broiler is next to the fryerto the fryer
8/09/02 FSFC 1620 189
8/09/02 FSFC 1620 190
No nozzles in No nozzles in the double the double upright broilerupright broiler
8/09/02 FSFC 1620 191
8/09/02 FSFC 1620 192
Nozzle aimed wrongNozzle aimed wrong
Nozzle heights are Nozzle heights are wrong wrong
No nozzles in No nozzles in salamandersalamander
8/09/02 FSFC 1620 193
Nozzle Nozzle positions are positions are wrongwrong
Filters are not Filters are not at minimum 45 at minimum 45 degree angledegree angle
8/09/02 FSFC 1620 195
8/09/02 FSFC 1620 196
Hose used to Hose used to connect second connect second cylindercylinder
Cardboard stored Cardboard stored under hoodunder hood
8/09/02 FSFC 1620 197
8/09/02 FSFC 1620 198
No nozzles in the No nozzles in the salamandersalamander
Coverage is blocked to Coverage is blocked to the griddle by the the griddle by the salamandersalamander
8/09/02 FSFC 1620 199
8/09/02 FSFC 1620 200
One nozzle over first One nozzle over first applianceappliance
Three nozzles over top Three nozzles over top of the broilersof the broilers
No nozzles in broilersNo nozzles in broilers
No nozzles over stoveNo nozzles over stove
Charcoal next to stove Charcoal next to stove and broilerand broiler
8/09/02 FSFC 1620 201
8/09/02 FSFC 1620 202
Ansul systemAnsul system
No scissors in fusible No scissors in fusible link housingslink housings
No duct nozzlesNo duct nozzles
Pyro-Chem nozzlesPyro-Chem nozzles
8/09/02 FSFC 1620 203
8/09/02 FSFC 1620 204
Ansul nozzle on Ansul nozzle on a Range Guard a Range Guard systemsystem
8/09/02 FSFC 1620 205
8/09/02 FSFC 1620 206
Duct is screwed to Duct is screwed to the wall and uses the wall and uses the wall as the the wall as the ductduct
8/09/02 FSFC 1620 207
8/09/02 FSFC 1620 208
Duct is riveted to Duct is riveted to the plenumthe plenum
Grease is leaking Grease is leaking out of the ductout of the duct
8/09/02 FSFC 1620 209
8/09/02 FSFC 1620 210
Grease is leaking Grease is leaking from the fanfrom the fan
8/09/02 FSFC 1620 211
8/09/02 FSFC 1620 212
Wood shingles Wood shingles attached to ductattached to duct
Grease is leaking Grease is leaking from the fan and from the fan and duct and flowing into duct and flowing into the rain gutter and the rain gutter and down the down down the down spoutspout
NFPA 96 requires NFPA 96 requires Safe access to clean Safe access to clean fans and ductsfans and ducts
8/09/02 FSFC 1620 213
8/09/02 FSFC 1620 214
The hood is made of The hood is made of plywoodplywood
The hood has no filtersThe hood has no filters
The fryer is outside the The fryer is outside the hoodhood
8/09/02 FSFC 1620 215
8/09/02 FSFC 1620 216
No fusible link detector in No fusible link detector in the duct openingthe duct opening
8/09/02 FSFC 1620 217
8/09/02 FSFC 1620 218
Improper clearance for ductImproper clearance for duct
Duct is not proper gaugeDuct is not proper gauge
Duct flange is rivetedDuct flange is riveted
Paper towels stored on top of hoodPaper towels stored on top of hood
Paper towels under fryers to Paper towels under fryers to contain the greasecontain the grease
Wire and plug to fryers not codeWire and plug to fryers not code
Cardboard on floor to catch the Cardboard on floor to catch the grease that splatters on the floorgrease that splatters on the floor
8/09/02 FSFC 1620 219
8/09/02 FSFC 1620 220
Fryer nozzles not Fryer nozzles not protecting the fryerprotecting the fryer
Fryer outside of the Fryer outside of the hoodhood
Open flame next to Open flame next to fryerfryer
Kitchen Is on the Kitchen Is on the Ground Floor of a Ground Floor of a Large Multi- Story Large Multi- Story HotelHotel
For more information: