TRUBA INSTITUTE OF ENGG. & INFO. TECHNOLOGY

BHOPAL

A

TECHNICAL SEMINAR

ON

“TESTING OF DC MACHINE” SUBMITTED BY:-

MRITYUNJAI KUMAR ANAND

ROLL NO. 0114EX101035

SUBMITTED TO:-

MR. PRIYANK NEMA

DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGG.

SESSION-2012-13

Page 2: testing of dc machine

CONTENTS1. Testing method of dc m/c.2. simple/direct test . (a) Explanation,(b) Numerical (C)

Disadvantage .3 .Swinburne’s test.4.Hopkinsion’s test

Page 3: testing of dc machine

TESTING OF DC MACHINE

Q:- Why testing are required ?

Ans-Machines are tested for finding out losses,

efficiency and temperature rise. For

small m/c we used DIRECT LOADING

test and for large shunt m/c, INDIRECT MET-

HOD are used.

Page 4: testing of dc machine

TESTING METHOD ARE

Simple / Direct test.

Swinburne’s / Indirect Method test.

Hopkinson’s / Regenerative / Back - to - Back / Heat –run test.

Page 5: testing of dc machine

Simple / Direct test This method is

suitable only for SMALL DC m/c. In direct, method the DC m/c is subjected to rated load and the entire o/p power is wasted. The ratio of o/p power to i/p power gives the efficiency of DC m/c.

Page 6: testing of dc machine

EFFICIENCY MOTOR Motor o/p={ω(s1-s2)r× 9. 81} Motor i/p= VtI. ή(motor)={o/p}/{i/p}. = [{ω(s1-s2)r× 9. 81}×100]/VtI where; s1&s2 are the tension on the belt. ω=2πn(motor speed in rad/sec r=radius of pulley in meters(=1/2 out

side pulley dia+1/2 belt thickness) Vt=terminal voltage & I=line current.

Page 7: testing of dc machine

NUMERICAL

A full load break test on a small d.c m/c shunt motor ,give the following data

Spring balance readings 25 kg & 9 kg Out side pulley diameter 19.5 cm Belt thickness 0.50 cm Motor speed 1500 rpm Applied voltage 230 v Line current 12.5 A Calculate the shaft torque, shaft power &

motor efficiency at rated load.

Page 8: testing of dc machine

SOLUTION Shaft torque=(S1-S2)×Effective radius

=(25.9)[(19.5/2)+(0.5/2)]×(1/100)kg-m =16×0.1×9.81 Nm=15.7 Nm Shaft power=ω×Shaft torque

=[(2π×1500)/60]×15.7=2470w Motor i/p=Vti=230×12.5=2875w ή(motor efficiency at rated

load)=[2470/2875]×100=85.6%

Page 9: testing of dc machine

DISADVANTAGES The spring balance readings are not

steady.

Friction torque does not const. At a particular setting of handwheels H1&H2

Page 10: testing of dc machine

INDIRECT METHOD

In this method ,no load m/c losses are first measured by a suitable test and then additional losses on load are determined from the m/c data ,in order to calculate the m/c efficiency .

The simplest method of measuring the no load m/c losses is by SWINBURNE’S METHOD.

Page 11: testing of dc machine

SWINBURNE’S METHOD As this is no load

test ,it can’t be performed on a dc series motor

In this method, the m/c whether it is a MOTOR or GENERATOR, is run as a no load shunt motor at rated speed

Page 12: testing of dc machine

If Ia0 and If are the no load armature and field current respectively .Then power absorbed by the armature (=Vt×Iao) is equal to the no load rotational loss W0 plus a small amount armature circuit loss Ia0^2 ×ra.

No load rotational loss W0=Vt×Iao- Ia0^2 ×ra.

Here armature circuit resistance ra includes the brush contact resistance also.

Shunt field loss=Vt×If.

Page 13: testing of dc machine

Let IL be the load current at which m/c efficiency is required.

Generator efficiency Generator o/p=Vt×IL Armature current Ia=IL+If Armature circuit loss= Ia^2×ra ra=armature circuit resistance

when hot. Total loss=W0+ Ia^2×ra+Vt×If ή(Generator)=[1-{(W0+

Ia^2×ra+Vt×If)}/{(Vt×IL+ W0+ Ia^2×ra+Vt×If)}]

Page 14: testing of dc machine

Motor efficiency When m/c is working as a motor

then Ia=IL-If Motor i/p=Vt×IL ή(motor efficiency)=[1-

{(W0+Ia^2×ra+If×Vt)}/{(Vt×IL)}]

Page 15: testing of dc machine

NUMERICAL A 400 v,20kw dc shunt motor takes

2.5 A when running light. For an armature resistance of 800Ω and brush drop 2V,find full load efficiency.

Page 16: testing of dc machine

SOLUTION Field current If=400/800=.5A No load armature current Ia0=2.5-0.5=2.0A Constant no load rotational loss W0=Vt×Ia0-Ia0^2×ra-Vb×Ia. =400×2.0-2^2×0.5-2×2=794w. Total constant

loss=W0+Vt×If=794+400×0.5

=994w At full load, let IL=Line current=Ia+If

Page 17: testing of dc machine

Power i/p=Power o/p +total loosses Vt×IL =20,000+994+Ia^2×ra+Vb×Ia 400(Ia+0.5)=20,000+994+Ia^2+2×Ia Ia=56.22A Armature ohmic

losses=56.22^2×0.5=1580.34w Brush drop losses=56.22×2=112.44w. Total

losses=994+1580.34+112.44=2686.78w. Power i/p=20,000+2686.78=22686..78w.ή(motor at full load)

=(20.000/22686.78)×100=88.157%

Page 18: testing of dc machine

ADVANTAGES Low power is required for testing

even large m/c, since only no load losses are to be supplied from the main.

It is convenient and economical.

The efficiency can be calculated at any load because constant losses are known.

Page 19: testing of dc machine

DISADVANTAGES As the test is on no load, it doesn’t indicate

whether the commutation on full load is satisfactory and whether the temperature rise would be within specified limit.

THIS TEST CAN’T BE APPLIED FOR A SERIES MOTOR because speed of series motor is very high at no load ,it is not possible to run series motor on no load.

Note:-In comparison to other the armature cu losses is so small that it may be neglected & constant loss may be take equal to no load i/p

Page 20: testing of dc machine

Regenerative/Hopkinson’s method.

In this method ,two identical d.c m/c are coupled ,both mechanically & electrically and are tested simultaneously. One of the m/c made to run as a MOTOR and it derives the other m/c as GENERATOR .

Page 21: testing of dc machine

For this test m/c 1 is as a dc shunt motor by a starter & brought upto rated speed with switch S open .Bothe the m/c run at same speed ,because these are MECHANICALLY coupled .

Page 22: testing of dc machine

TO PERFORM THE TEST FOLLOWING PROCEDURE IS ADOPTED M/c 1(motor) is started through starter

& its field rheostat is adjusted so that it runs at normal speed. The m/c 1(Motor) will drive m/c 2(Generator).The switch S is initially kept open.

The excitation of m/c 2 is gradually increased ( by decreasing the field circuit resistance).till the volt metre 1 reads ZERO.Then switch S is closed.

Page 23: testing of dc machine

M/c 2 is now floating neither taking any current from the supply nor delivering any current .Any desired load can be put on the set by adjusting the shunt field regulators.The m/c with lower excitation will act as a MOTOR and other m/c will act as a GENERATOR.

Let V=supply voltage I2=Armature current of m/c

2(Generator) I1= Armature current of m/c 1(motor) . If2=Field current of m/c 2(Generator). If1=Field current of m/c 1(Motor). Ra=Armature resistance of each m/c

Page 24: testing of dc machine

Motor i/p power =V(I+I2)=V×I1 Generator o/p power=V×I2. ............(1) If both the m/c have same efficiency

ή,then o/p of motor =ή×i/p =ήV(I+I2)= V×I1

=Generator i/p . o/p of Generator =ή×i/p .

=ή×ήV×I1=ή^2V(I1)............(2)From equ (1) & (2). ή^2V(I1)=V×I2. sqrt{(I2/(I1)}

Page 25: testing of dc machine

EFFICIENCY Armature circuit loss in Generator =I2^2×ra

. Armature circuit loss in Motor=I1^2×ra . Power drawn from supply= V×I.No load rotational loss in two m/c=W0= V×I-ra(I1^2+I2^2) .No load rotational loss for each m/c=W0/2 .Generator o/p= I2^2×ra.Generator loss=Wg=(W0/2)+V×If2+

I2^2×ra.ή(g)=[1-(Wg)/(V×I2+Wg)]

Page 26: testing of dc machine

Motor i/p=V(I1+If1) Total motor losses Wm=(W0/2)+

V×If1 +I1^2×ra . ή( Motor)=[1-(Wm)/V(I1+If2)]

Page 27: testing of dc machine

ADVANTAGE Total power taken from the supply is very

low. Therefore this method is very economical.

The temperature rise and the commutation condition can be checked under rated load condition.

Large m/c can be tested at rated load without consuming much power from the supply.

Efficiency at different load can be determine.

Page 28: testing of dc machine

DISADVANTAGES The main disadvantage of this

method is the necessity two practically identical m/c to be available

Page 29: testing of dc machine

THANK YOU....