MEC 551THERMAL ENGINEERING
CHAPTER 6REFRIGERATION
![Page 2: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/2.jpg)
2Global Aspiration …… A World Class University
KJM 381Overview - Energy Consumption
Malaysia (overall)
Educational building
![Page 3: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/3.jpg)
3Global Aspiration …… A World Class University
KJM 381
Carnot (or reversed Carnot) - operates between two constant temperature reservoirs i.e. heat transfer processes take place at constant temperature.
Review – Reversed Carnot Cycle
4 1 14
2
2
3
3
![Page 4: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/4.jpg)
4Global Aspiration …… A World Class University
KJM 381
![Page 5: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/5.jpg)
5Global Aspiration …… A World Class University
KJM 381
![Page 6: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/6.jpg)
6Global Aspiration …… A World Class University
KJM 381
Review – Thermodynamics 1st Law
)(1000
)(2000
122
12
212
...kWzzgVVhhmWQ netnet
)(1000
)(2000
122
12
212 kJzzgVVhhmWQ netnet
)/(1000
)(2000
122
12
212 kgkJzzgVVhhwq netnet
![Page 7: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/7.jpg)
7Global Aspiration …… A World Class University
KJM 381
Review – Control Volume
Compressors are devices used to increase pressure of a fluid. Work is supplied to these devices from an external source through a rotating shaft. Therefore, compressors involve work inputs.
![Page 8: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/8.jpg)
8Global Aspiration …… A World Class University
KJM 381
Energy balance: for compressor
outout
outoutoutoutout
inin
ininininin gzVhmWQgzVhmWQ
22
2...2...
outoutininin hmhmW...
12
..hhmW in
![Page 9: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/9.jpg)
9Global Aspiration …… A World Class University
KJM 381
Review – Isentropic Efficiencies
![Page 10: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/10.jpg)
10Global Aspiration …… A World Class University
KJM 381
Introduction
Refrigeration is defined as a process of making something cold, and ‘cold’ can be defined as an absence of heat.
The earliest and most common of the cold substances used for taking away heat was ice or snow. The Chinese, Greeks, Romans etc all use ice for food preservation.
![Page 11: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/11.jpg)
11Global Aspiration …… A World Class University
KJM 381
Refrigeration Machine in 1834
(B) Evaporator (C) Compressor
(D) Condenser(H) Valve
![Page 12: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/12.jpg)
12Global Aspiration …… A World Class University
KJM 381
Refrigeration Machine in 1950’s
![Page 13: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/13.jpg)
13Global Aspiration …… A World Class University
KJM 381
Refrigeration Machine at Home
![Page 14: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/14.jpg)
14Global Aspiration …… A World Class University
KJM 381
![Page 15: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/15.jpg)
15Global Aspiration …… A World Class University
KJM 381
Process Process Description1-2 Isentropic compression2-3 Constant pressure heat rejection3-4 Throttling process4-1 Constant pressure heat absorption
Vapor Compression Refrigeration Cycle
The processes in the vapor compression refrigeration cycle are as per following:
![Page 16: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/16.jpg)
16Global Aspiration …… A World Class University
KJM 381
Refrigeration cycle is based on the modification of reversed Carnot cycle
![Page 17: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/17.jpg)
17Global Aspiration …… A World Class University
KJM 381
The P-h diagram is another convenient diagram often used to illustrate the vapor-compression refrigeration cycle.
![Page 18: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/18.jpg)
18Global Aspiration …… A World Class University
KJM 381
![Page 19: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/19.jpg)
19Global Aspiration …… A World Class University
KJM 381
![Page 20: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/20.jpg)
20Global Aspiration …… A World Class University
KJM 381
COMPRESSOR: Provide the driving force for the entire system by drawing low pressure refrigerant in and adding pressure such that it exits at a higher temperature.
CONDENSER: Exhaust heat from the system by virtue of heat transfer across a temperature gradient. The refrigerant in the condenser is at a higher temperature than the ambient temperature.
Components Description
![Page 21: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/21.jpg)
21Global Aspiration …… A World Class University
KJM 381
EXPANSION VALVE: Allow the refrigerant to expand dramatically in a controlled process such that it exits the valve at a low quality liquid-vapor mixture.
EVAPORATOR: Absorb heat from the cold space by virtue of a temperature gradient, similar to the condenser.
![Page 22: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/22.jpg)
22Global Aspiration …… A World Class University
KJM 381
)( 12
..hhmW in
)( 32
..hhmQH
43 hh
)( 41
..hhmQ L
Component First Law ResultCompressor
Condenser
Expansion valve
Evaporator
Results of First Law
![Page 23: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/23.jpg)
23Global Aspiration …… A World Class University
KJM 381
Results of Second Law
12
41.
.
hhhh
W
QCOP
in
LR
12
32.
.
hhhh
W
QCOP
in
HHP
Cycle Second Law Result
Refrigerator
Heat pump
![Page 24: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/24.jpg)
24Global Aspiration …… A World Class University
KJM 381
![Page 25: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/25.jpg)
25Global Aspiration …… A World Class University
KJM 381
Refrigeration Effect, Load and Capacity
Refrigeration effect qL (kJ/ kg) is the heat extracted by a unit
mass of refrigerant during the evaporating process in the evaporator.
Refrigeration load QL (kW) is the required rate of heat
extraction by the refrigerant in the evaporator.
Refrigeration capacity, or cooling capacity, QRC (kW) is the
actual rate of heat extracted by the refrigerant in the evaporator.
![Page 26: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/26.jpg)
26Global Aspiration …… A World Class University
KJM 381
Example #1
A refrigerator uses refrigerant-134a as the working fluid and operates on an ideal vapor compression refrigeration cycle between 0.14 and 0.8 MPa. If the mass flow rate of the refrigerant is 0.05 kg/s, determine (a) the rate of heat removal from the refrigerated space and the power input to the compressor (b) the rate of heat rejection to the environment (c) the COP of the refrigerator.
![Page 27: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/27.jpg)
27Global Aspiration …… A World Class University
KJM 381
Example #2
A refrigerator uses refrigerant-134a as the working fluid. It enters the compressor as superheated vapor at 0.14 MPa, -10°C and is compressed to 0.8 Mpa and 50 °C. The refrigerant is cooled in the condenser to 0.72 MPa, 26°C and then is throttled to 0.15 MPa. The mass flow rate of the refrigerant is 0.05 kg/s. Determine (a) the rate of heat removal from the refrigerated space and the power input to the compressor (b) isentropic efficiency of the compressor (c) the COP of the refrigerator.
![Page 28: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/28.jpg)
Type of refrigerants:
28Global Aspiration …… A World Class University
KJM 381
Refrigerants
![Page 29: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/29.jpg)
29Global Aspiration …… A World Class University
KJM 381
Refrigerant Selection
R-134a (replaced R-12, which damages ozone layer) is used in domestic refrigerators and freezers, as well as automotive air conditioners.
R-502 (a blend of R-115 and R-22) is the dominant refrigerant used in commercial refrigeration systems such as those in supermarkets.
Two important parameters: the temperatures of the refrigerated space and the environment with which the refrigerant exchanges heat.
![Page 30: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/30.jpg)
30Global Aspiration …… A World Class University
KJM 381
COP comparison between different refrigerants under the same operating conditions.
![Page 31: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/31.jpg)
31Global Aspiration …… A World Class University
KJM 381
Cascade Refrigeration Systems
Very low temperatures can be achieved by operating two or more vapor-compression systems in series, called cascading.
![Page 32: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/32.jpg)
32Global Aspiration …… A World Class University
KJM 381
Applying the first law to the heat exchanger,
Then the COP becomes,
)()(
)(
1256
41
,
,
hhmhhm
hhm
W
QCOP
BA
B
innet
LcascadeR
)()(
85
32
hhhh
m
m
B
A
)()( 3285
.hhmhhm BA
![Page 33: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/33.jpg)
33Global Aspiration …… A World Class University
KJM 381
When the fluid used throughout the cascade refrigeration system is the same, the heat exchanger between the stages can be replaced by a mixing chamber (called a flash chamber).
Multistage Compression Refrigeration System
Flash chamber has a better heat transfer characteristics.
Such system is called multistage compression refrigeration system.
![Page 34: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/34.jpg)
34Global Aspiration …… A World Class University
KJM 381
![Page 35: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/35.jpg)
35Global Aspiration …… A World Class University
KJM 381
Example 3:Consider a two stage cascade refrigeration system operating between the pressure limits of 0.8 and 0.14 Mpa. Each stage operates on an ideal vapor compression refrigeration cycle with R-134a as the working fluid. Heat rejection from the lower cycle to the upper cycle takes place in an adiabatic counterflow heat exchanger where both streams enter at about 0.32 MPa. If the mass flow rate of the refrigerant through the upper cycle is 0.05 kg/s, determine (a) the mass flow rate of the refrigerant through the lower cycle. (b) the rate of heat removal from the refrigerated space and the power input to the compressor (c) the COP of the cascade refrigerator.
![Page 36: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/36.jpg)
36Global Aspiration …… A World Class University
KJM 381
Example #4
A vapor compression plant uses R-134a and has a suction pressure of 0.14 MPa and a condenser pressure of 0.8 MPa. The vapor is dry saturated on entering the compressor and there is no undercooling of the condensate. Part of the refrigerant evaporates during flashing process and this vapor is mixed with the refrigerant leaving the low pressure compressor. The mixture is then compressed to the condenser pressure by the high pressure compressor. The liquid in the flash chamber is throttled to the evaporator pressure and cools the refrigerated space as it vaporizes in the evaporator. Assuming the refrigerant leaves the evaporator as a saturated vapor and both compressors are isentropic. The compression is carried out isentropically in two stages and a flash chamber is employed at a pressure of 0.32 MPa. Calculate (a) the amount of vapor bled off at the flash chamber, (b) the amount of heat removed from the refrigerated space, (c) the compressor work, and (d) the coefficient of performance.
![Page 37: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/37.jpg)
37Global Aspiration …… A World Class University
The most widely used absorption refrigeration system is the ammonia-water system, where ammonia serves as the refrigerant and water as the transport medium.
Absorption Refrigeration Systems
COP QQ W
QQR
L
gen pump in
L
gen
Desired outputRequired input
Cooling effectWork input ,
The work input to the pump is usually very small, and the COP of absorption refrigeration systems is defined as:
![Page 38: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/38.jpg)
38Global Aspiration …… A World Class University
![Page 39: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/39.jpg)
39Global Aspiration …… A World Class University
KJM 381
Application of Refrigeration
Food processing, preservation and distribution.
![Page 40: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/40.jpg)
40Global Aspiration …… A World Class University
KJM 381
Application of Refrigeration
Chemical and process industries.
– Separation of gases– Condensation of gases– Solidification of solute– Storage of liquid at low pressure– Removal of heat of reaction (exothermic)– Recovery of solvents
![Page 41: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/41.jpg)
41Global Aspiration …… A World Class University
KJM 381
Domestic Refrigerator & Air-Conditioner
![Page 42: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/42.jpg)
42Global Aspiration …… A World Class University
KJM 381
Chiller & Cold Room
![Page 43: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/43.jpg)
43Global Aspiration …… A World Class University
KJM 381
![Page 44: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/44.jpg)
44Global Aspiration …… A World Class University
KJM 381
3 compressors (in standby mode)
![Page 45: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/45.jpg)
45Global Aspiration …… A World Class University
KJM 381
Evaporator
Condenser
CompressorExpansion valve
1
23
4
Refrigerant R-22 flows
Ethylene glycol flows
From heat exchanger
Cooling water flows
To heat exchanger
Make-up water tank
Make-up water flows
Cooling tower
![Page 46: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/46.jpg)
46Global Aspiration …… A World Class University
KJM 381
Case Study
Required process temperature in the reactor: -80°C
![Page 47: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/47.jpg)
47Global Aspiration …… A World Class University
KJM 381
Evaporator, LPC
Evaporator, HPC
Condenser, LPC
Condenser, LPC
Compressor, LPC
Compressor, HPC
Expansion valve
Expansion valve
1
23
4
5
67
8
From application
To application
Circulation pump
Refrigerant R23 flows
Refrigerant R507 flows
Main heater Fine heater
Cap tube
Cooling water supply (≈ 15°C)
Cooling water return (≈ 35°C)
Evaporator, LPC
Evaporator, HPC
Condenser, LPC
Condenser, LPC
Compressor, LPC
Compressor, HPC
Expansion valve
Expansion valve
1
23
4
5
67
8
From application
To application
Circulation pump
Refrigerant R23 flows
Refrigerant R507 flows
Main heater Fine heater
Cap tube
Cooling water supply (≈ 15°C)
Cooling water return (≈ 35°C)
![Page 48: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/48.jpg)
48Global Aspiration …… A World Class University
KJM 381
Example 5
Consider a two stage cascade refrigeration system operating between the pressure limits of 1.2 Mpa and 200 kPa with refrigerant R-134a as the working fluid. Heat rejection from the lower cycle to the upper cycle takes place in an adiabatic counterflow heat exchanger where the pressure at the upper and lower cycles are 0.4 and 0.5 Mpa, respectively. In both cycles, the refrigerant is saturated liquid at the condenser exit and saturated vapor at the compressor inlet, and the isentropic efficiency of the compressor is 80%. If the mass flow rate of refrigerant through the lower cycle is 0.15 kg/s, determine (a) the mass flow rate of the refrigerant through the upper cycle, (b) the rate of heat removal from the refrigerated space, and (c) the COP.
![Page 49: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/49.jpg)
49Global Aspiration …… A World Class University
KJM 381
Example 6
Consider a two stage cascade refrigeration system operating between the pressure limits of 1.2 MPa and 200 kPa with refrigerant R-134a as the working fluid. The refrigerant leaves the condenser as a saturated liquid and is throttled to a flash chamber operating at 0.45 MPa. Part of the refrigerant evaporates during the flashing process and this vapor is mixed with the refrigerant leaving the low pressure compressor. The mixture is then compressed to the condenser pressure by the high pressure compressor. The liquid in the flash chamber is throttled to the evaporator pressure and cools the refrigerated space as it vaporizes in the evaporator. The mass flowrate of the refrigerant through the low pressure compressor is 0.15 kg/s. Assuming the refrigerant leaves the evaporator as a saturated vapor and the isentropic efficiency is 80% for both compressor, determine(a) The mass flowrate of the refrigerant through the high pressure compressor, (b) the rate of heat removal from the refrigerated space, (c) COP, (d) The rate of heat removal and the COP if this refrigerator operated on a single stage cycle between the same pressure limits with the same compressor efficiency and the same flow rate as in part (a).
![Page 50: TEng - Ch06 MEC 551 Refrigeration](https://reader036.vdocuments.us/reader036/viewer/2022082210/5695cfcb1a28ab9b028f9157/html5/thumbnails/50.jpg)
50Global Aspiration …… A World Class University
KJM 381