FLORIDA SOLAR ENERGY CENTER A Research Institute of the University of Central Florida Danny Parker Danny Parker Consortium for Energy Efficiency Consortium for Energy Efficiency Workshop on Cool Roofing Workshop on Cool Roofing San Francisco, December 2005 San Francisco, December 2005 Ten Years of Cool Roofing Ten Years of Cool Roofing Research at the Research at the Florida Solar Energy Center Florida Solar Energy Center

Upload: letuyen

Post on 11-Apr-2018

216 views

Category:

Documents


2 download

TRANSCRIPT

FLORIDA SOLAR ENERGY CENTERA Research Institute of the University of Central Florida

Danny ParkerDanny Parker

Consortium for Energy Efficiency Consortium for Energy Efficiency Workshop on Cool Roofing Workshop on Cool Roofing

San Francisco, December 2005San Francisco, December 2005

Ten Years of Cool Roofing Ten Years of Cool Roofing Research at the Research at the

Florida Solar Energy CenterFlorida Solar Energy Center

Attic Thermal Processes

Altered attic heat transfer mechanisms; Radiant Barrier

Radiant Barrier Pilot Project

Site #199 attic temp before and after retrofit – June 22, 2000

Julian Date160 165 170 175 180 185 190

Atti

c A

ir Te

mpe

ratu

re (o F)

70

80

90

100

110

120

130RBS Retrofit

Site #199 RBS retrofit impact on attic air temp and AC cooling demand

Hour of Day (Standard Time)0 2 4 6 8 10 12 14 16 18 20 22 24

Tem

pera

ture

(o F)

70

80

90

100

110

120

130

Coo

ling

kW

0

1

2

3

4

5Attic Temp (pre):avg=91.0; max=113.7Attic Temp (post): avg=88.3; max=101.5AC (pre): avg=2.23 kW;max=3.79 kWAC (post): avg=1.79 kW; max=2.69 kW

SummerPeak

Overall Results: 9 Sites

o Average cooling energy savings: 3.6 kWh/day (9.3%)

o Peak demand reduction; 420 W (16%)o 8.4o drop in avg. max daily attic temp.o Improved load shape: most reduction

during day; nighttime demand elevatedo Improvements to customer comfort

RBS impact on summer attic air temp and AC cooling demand in eight homes

Hour of Day (Standard Time)0 2 4 6 8 10 12 14 16 18 20 22 24

Tem

pera

ture

(o F)

70

80

90

100

110

120

Coo

ling

kW

0.0

0.5

1.0

1.5

2.0

2.5

3.0Attic Temp: (pre):avg= 89.4; max= 114.8Attic Temp:(post):avg= 87.0; max= 106.4AC(pre):avg=1.61 kW;max= 2.64 kWAC(post):avg= 1.46 kW;max= 2.22 kW

SummerPeak

Reflective Roof Retrofits

Experiments: 1993 - 1998Dark roofed attics can reach 130 - 140EF on summer afternoons. A white color will reflect much of this heat back to the sky. Reducing the temperature in the attic is doubly importantbecause of the presence of the cooling ducts.

Pre-post experiments in 19 homes:- 19 % average reduction in cooling energy use- 23 % average reduction in peak demand

Reference:Parker, D.S., Chandra, S., Barkaszi, S.F. and Beal, D.J., 1995B. "Measured Cooling Energy Savings from Reflective Roofing Systems in Florida: Field and Laboratory Results," Thermal Performance of the Exterior Envelopes of Buildings VI, p. 489, December 4 _ 8, 1995, Clearwater, FL.

Dark Gray vs. White?

Big Differences Seen…

Roof Whitened

Atti

c A

ir Te

mpe

ratu

re F

.

Day

AC

Pow

er D

eman

d: W

atts

Attic Temp AC Energy

0 2 4 6 8 10 12 14

80

90

100

110

120

0

500

1000

1500

2000

2500

3000

3500

4000

4500

FPL Demonstration Project: Ft. Myers, FL

Study Homes: RGS, RWM, RWB, RWF

Study Homes: RTB, RWS, RSL

Detailed Instrumentation

Attic Air Temps

Time of Day (EST)

0 2 4 6 8 10 12 14 16 18 20 22 24

Ave

rage

Tem

pera

ture

s (o F)

70

80

90

100

110

120

RWB: Max = 89.0 FRWF: Max= 87.8 FRWM: Max= 91.7 FRWS: Max= 103.6 FRSL: Max= 83.2 FRGS: Max= 110.2 FRTB: Max= 98.8 F

SummerPeak

Period

Influence on Peak Attic Temperatures

Max Daily Air Temperature (oF)84 85 86 87 88 89 90 91 92 93 94 95

Max

Atti

c Te

mpe

ratu

re (o F)

80

85

90

95

100

105

110

115

120

125

130

135

140

80

85

90

95

100

105

110

115

120

125

130

135

140RGS

RWS

RTB

RWB

RWF

RWM

Avg. Cooling over Unoccupied Period

Time of Day (EST)

0 2 4 6 8 10 12 14 16 18 20 22 24

Ave

rage

Ele

ctric

al D

eman

d (W

atts

)

0

200

400

600

800

1000

1200

1400RWB Avg = 13.3 kWh/dayRWF Avg = 13.3 kWh/dayRWM Avg = 12.2 kWh/dayRWS Avg = 15.6 kWh/dayRSL Avg = 14.9 kWh/dayRGS Avg = 17.0 kWh/dayRTB Avg = 16.2 kWh/day

SummerPeak

Period

Impact of East facing glass(RWB, RWF, RWS)

West facing glass(RGS,RTB,RSL, RWM)

Final Results Summary: Best Estimates

Table 21 Summary of Normalized Savings and Demand

Reductions from Regression Estimates

Case DescriptionCooling Savings Peak Demand ReductionkWh Percent kW Percent

RGS (Control) 0 0% 0 0%RWS (White Shingle) 300 4% 0.48 17% RSL (Sealed Attic) 620 9% 0.13 5%RTB (Terra Cotta Tile) 180 3% 0.36 13%RWB (White S-Tile) 1,380 20% 0.92 32%RWF (White Flat Tile) 1,200 17% 0.98 34%RWM (White Metal) 1,610 23% 0.79 28%

* Percentages relative to typical values for average sized detached South Florida homes detailed in Appendix H.

Table 21 Summary of Normalized Savings and Demand

Reductions from Regression Estimates

Case DescriptionCooling Savings Peak Demand ReductionkWh Percent kW Percent

RGS (Control) 0 0% 0 0%RWS (White Shingle) 300 4% 0.48 17% RSL (Sealed Attic) 620 9% 0.13 5%RTB (Terra Cotta Tile) 180 3% 0.36 13%RWB (White S-Tile) 1,380 20% 0.92 32%RWF (White Flat Tile) 1,200 17% 0.98 34%RWM (White Metal) 1,610 23% 0.79 28%

* Percentages relative to typical values for average sized detached South Florida homes detailed in Appendix H.* Percentages relative to typical values for average sized detached South Florida homes detailed in Appendix H.

Flexible Roof Facility

Time of Day: June 16, 19970 2 4 6 8 10 12 14 16 18 20 22 24

Mea

sure

d At

tic A

ir T

empe

ratu

re (F

.)

60

70

80

90

100

110

120

130

140White tileBlack shngl, RBS, 1:150 ventBlack shngl, RBS, 1:300 ventRed tileBlack shngl, 1:300 ventWhite metal: 1:300 ventAmb. air temperature

FRF Roof /Attic Testing

o Roofs/Ventilationo Cool roofing systemso Measured heat fluxo Attic air temperatureo Weather conditionso Summer 2002-2003:

Unfinished vs. Finished metal roofing systems

o Long-term testing of unfinished metals

Emittance/reflectance

FRF Testing 2003

o Metal Roofing long term exposure

Unfinished Galvanized Unfinished GalvalumeIR Reflective Metal shinglesWhite metal roofControl= Dark shingles

Attic Temps over Summer

Average Temps Over Summer

Time of Day: June 1 - September 30, 2003

0 2 4 6 8 10 12 14 16 18 20 22 24

Mea

sure

d At

tic A

ir Te

mpe

ratu

re (o F)

70

75

80

85

90

95

100

105

110

115

120

125Galvalum metal: Max= 99.2o

Sealed attic(dbl roof): Max= 83.5o

Brown IR Selective Metal Tile: Max= 101.5o

Galvanized Metal: Max= 103.6o

Dark Shingle: Max=116.7o

White Metal: Max= 94.6o

Ambient Air: Max= 85.2o

Max Attic TemperaturesMax Attic Temperatures

o Galvalume Metal111 oF

o Dbl Roof, sealed85 oF

o IR Reflective Shingle106 oF

o Galvanized Metal114 oF

o Black Shingle (Control)140 oF

o White Metal Panel104 oF

o Outdoor Air Temp= 95 oF

Ceiling Flux…Different StoryCeiling Flux…Different Story

Time of Day: June 5- September 30, 2002

0 2 4 6 8 10 12 14 16 18 20 22 24

Mea

sure

d C

eilin

g H

eat F

lux

(Btu

/hr/f

t2 )

-0.5

0.0

0.5

1.0

1.5

2.0

2.5Galvalum 5-vee metal (Avg= 0.43)Dbl Roof w/Sealed Attic/Insulated deck (Avg= 0.98)Ivory IR Reflective Metal Shingle (Avg= 0.39)Galvanized 5-vee metal (Avg= 0.53)Black Shingle (Avg= 0.70)White standing seam metal (Avg= 0.30)Zero Heat Flux Line

Change in PerformanceFRF Test Results for Summer 2003

Increase in Avg Max Mid Attic Air Temperaturefrom 2002

Test Cell Description

Galvalum Galvanized Std Shingle White Mtl Air Temp

Max

Atti

c Te

mpe

ratu

re C

hang

e (o F)

-1

0

1

2

3

4

5

NoChange

Journal of Light Journal of Light ConstructionConstruction, June 2003

Information to the public…Information to the public…

Roof Research: What Next?

o Continue test of spectrally selective roofing materials

o Innovative roofing systems (e.g. sealed roofs, ventilation systems)

o Integrated Power Roofs (PV, solar, thermal control etc).

Night Sky Cooling Potential

oo Cool Night SkyCool Night Sky30 oF below ambient40-50/W/m2 in FloridaRoof: 1 ton coolingClear, calm nightsClouds, wind, reduce impact

Measured Night Cooling Potential: FRF

o FRF Test Cell with White metal Roof

o Roof surface temperature

o Average over Summer of 2001

o Shows sizeable cooling potential most nights

Flexible Roof Facility:Average Metal Roof Temperature Depression

Summer 2001

Time of Day: June - September 2001

0 2 4 6 8 10 12 14 16 18 20 22 24

Mea

sure

d Te

mpe

ratu

re (o F)

70

80

90

100

110Ambient air temp: Min= 72.2oFWhite metal roof: Min= 69.0oF

Interior Setpoint (77 oF)

NightCooling

NightCooling

NightCool Schematic

NightCool Simulation

o Modified Givoni-IngersollModel

o Simulate major influences with model

o Evaluate for sealed attic model with exposed metal roof

o Florida, Tampa= ~2 kW cooling potential under typical night conditions

Use two small buildings for test of concept

o Control and experimento Full exposed metal roof

on battens (no decking) with sealed attic

o Channel air to space when cooling conditions are met

o Use dehumidfier with heat rejection to attic

o Fully instrumented

Evaluation Sensitivity for Tampa, FL

o Major factorsCFM air flow and fan powerAmbient dewpoint(limiting factor on roof temperature)Wind if low dewpointInlet air temperature

o Minor factorsRoof tiltSurface emissivity

Excellent Predicted Performance…

o Tampa, FloridaHot humid climate challenge for conceptDaily summer cooling reduction of 15 kWhSEER of 37 Btu/Wh

o Atlanta, Georgia50 kWh/day coolingSEER = 71 Btu/Wh

o Phoenix, ArizonaVery hot arid climate23 kWh of daily summer coolingSEER of 61 Btu/Wh

Two small buildings for test of concept

o Control and experimento Full exposed metal roof

on battens (no decking) with sealed attic

o Channel air to space when conditions met

o Use dehumidfier with heat rejection to attic

o To be fully instrumented

Two Test Buildings Completed…

Experimental has open metal roof…

Other issues in Florida…Other issues in Florida…

Exposed White Metal Roof Runs Cooler…

o Runs 2 oF cooler without space conditioning

o Runs up to o4 F cooler on clear summer days

o Instrumentation with conditioning/dehumidifica-tion system to begin later in autumn 2005

Getting advantages on Getting advantages on the street…the street…

o More reflective roofing is no cost option within any roofing type, but…

o Need to influence decision at time of construction or re-roof

o Metal will have greatest reflectance longevity

o Chinese menu approachReflective roofRadiant BarrierMore insulation, interior ductsSealed attic with cool roofing

o Savings will be ~20-25% for cooling with very reflective roof

o 10 – 15% with moderately reflective tile roof with good venting

o ~10% for radiant barrier with good ventilation

o Peak savings are larger

Thank you!