temperature limit alarm - omega engineering

16
INSTRUCTION SHEET Shop online at: omega.com e-mail: [email protected] For latest product manuals: omegamanual.info CN63500 Temperature Limit Alarm M4497-0513 FM APPROVED, UL RECOGNIZED 2-LINE BY 4-DIGIT DISPLAY EXCEED, OUTPUT, AND ALARM ANNUNCIATORS FOUR BUTTON SILICONE RUBBER KEYPAD THERMOCOUPLE OR RTD SENSOR INPUT REMOTE RESET INPUT MAIN LIMIT OUTPUT: 5A RELAY. SELECTABLE FOR HIGH OR LOW TRIP ACTIVATION OPTIONAL ALARMS: 5A RELAY(S) OPTIONAL NEMA 4X/IP65 SEALED FRONT BEZEL PARAMETER SECURITY VIA PROGRAMMABLE LOCKOUTS FM APPROVED PROCESS CONTROL EQUIPMENT UL Recognized Component, File # E123489 GENERAL DESCRIPTION The CN63500 is a Factory Mutual approved temperature limit alarm, intended to provide an independent shutdown for thermal processes. The CN63500 accepts signals from a variety of temperature sensors (thermocouple or RTD elements), and its comprehensive programming allows it to meet a wide variety of application requirements. Dual 4-digit displays allow viewing of the process temperature and limit setpoint simultaneously. Front panel indicators inform the operator of the process and output status. The main limit output and alarm outputs are field replaceable. The limit output is selectable for high or low trip activation. If the process temperature goes above the limit setpoint for a high trip, or below the limit setpoint for a low trip, the limit relay will de-energize to initiate a process shutdown. The limit output cannot be reset until the process temperature returns to the proper operating range; manual reset is required (local or remote). Sensor failure will initiate a process shutdown. Relay alarm(s) can be configured to activate according to a variety of actions (Absolute HI or LO, Deviation HI or LO, and Band IN or OUT) with adjustable hysteresis. A standby feature suppresses the alarm during power-up until the process stabilizes outside the alarm region. The unit is constructed of a lightweight, high impact plastic case with a tinted front panel. The front panel meets NEMA 4X/IP65 specifications when properly installed. Multiple units can be stacked horizontally or vertically. Modern surface-mount technology, extensive testing, plus high immunity to noise interference makes the CN63500 extremely reliable in industrial environments. SAFETY SUMMARY All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Do not use the CN63500 to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the unit. CAUTION: Risk of Danger. Read complete instructions prior to installation and operation of the unit. CAUTION: Risk of electric shock. -0.0 +0.6 -0.000 +0.024 -0.0 +0.6 -0.000 +0.024 (45 ) 1.772 (45 ) 1.772 (9.4) 0.37 4.17 (105.9) 1.95 1.95 (49.5) (49.5) EX OUT A1 A2 P R DIMENSIONS In inches (mm) PANEL CUT-OUT LP0682A

Upload: others

Post on 26-Dec-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

INSTRUCTIONSHEET

Shop online at: omega.com e-mail: [email protected] latest product manuals: omegamanual.info

CN63500Temperature Limit Alarm

M4497-0513

FM APPROVED, UL RECOGNIZED

2-LINE BY 4-DIGIT DISPLAY

EXCEED, OUTPUT, AND ALARM ANNUNCIATORS

FOUR BUTTON SILICONE RUBBER KEYPAD

THERMOCOUPLE OR RTD SENSOR INPUT

REMOTE RESET INPUT

MAIN LIMIT OUTPUT: 5A RELAY. SELECTABLE FOR HIGH OR LOW TRIP ACTIVATION

OPTIONAL ALARMS: 5A RELAY(S)

OPTIONAL NEMA 4X/IP65 SEALED FRONT BEZEL

PARAMETER SECURITY VIA PROGRAMMABLE LOCKOUTS

FMAPPROVED

PROCESS CONTROL EQUIPMENT

UL Recognized Component, File # E123489

GENERAL DESCRIPTIONThe CN63500 is a Factory Mutual approved temperature limit alarm,

intended to provide an independent shutdown for thermal processes. The CN63500 accepts signals from a variety of temperature sensors (thermocouple or RTD elements), and its comprehensive programming allows it to meet a wide variety of application requirements.

Dual 4-digit displays allow viewing of the process temperature and limit setpoint simultaneously. Front panel indicators inform the operator of the process and output status. The main limit output and alarm outputs are field replaceable.

The limit output is selectable for high or low trip activation. If the process temperature goes above the limit setpoint for a high trip, or below the limit setpoint for a low trip, the limit relay will de-energize to initiate a process shutdown. The limit output cannot be reset until the process temperature returns to the proper operating range; manual reset is required (local or remote). Sensor failure will initiate a process shutdown.

Relay alarm(s) can be configured to activate according to a variety of actions (Absolute HI or LO, Deviation HI or LO, and Band IN or OUT) with adjustable hysteresis. A standby feature suppresses the alarm during power-up until the process stabilizes outside the alarm region.

The unit is constructed of a lightweight, high impact plastic case with a tinted front panel. The front panel meets NEMA 4X/IP65 specifications when properly

installed. Multiple units can be stacked horizontally or vertically. Modern surface-mount technology, extensive testing, plus high immunity to noise interference makes the CN63500 extremely reliable in industrial environments.

SAFETY SUMMARYAll safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

Do not use the CN63500 to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the unit.

CAUTION: Risk of Danger. Read complete instructions prior to

installation and operation of the unit.

CAUTION: Risk of electric shock.

-0.0+0.6-0.000+0.024

-0.0+0.6

-0.000+0.024

(45 )

1.772

(45 )

1.772(9.4)0.37 4.17 (105.9)

1.95

1.95(49.5)

(49.5)EX OUT A1 A2

PR

DIMENSIONS In inches (mm) PANEL CUT-OUT

LP0682A

2

GENERAL SPECIFICATIONS1. DISPLAY: 2 line by 4-digit LED

Upper (Main) Display: 0.4" (10.2 mm) high red LEDLower (Secondary) Display: 0.3" (7.6 mm) high green LEDDisplay Messages:

“OLOL” - Appears when measurement exceeds + sensor range.“ULUL” - Appears when measurement exceeds - sensor range.“OPEN” - Appears when open sensor is detected.“SHrt” - Appears when shorted sensor is detected (RTD only)“...” - Appears when display values exceed + display range.“-..” - Appears when display values exceed - display range.

LED Status Annunciators:EX - Temperature exceeds limit setpointOUT - Limit output is de-energizedA1 - Alarm #1 is activeA2 - Alarm #2 is active

2. POWER:Line Voltage Models: 85 to 250 VAC, 50/60 Hz, 8 VA.Low Voltage Models:

DC Power: 18 to 36 VDC, 7 W.AC Power: 24 VAC +/-10%, 50/60 Hz, 9 VA

3. CONTROLS: Four rubber push buttons: R, P, Up, Down4. MEMORY: Nonvolatile E2PROM retains all programmable parameters and

values.5. ENVIRONMENTAL CONDITIONS:

Operating Range: FM rated @ 0 to 65°C, UL rated @ 0 to 55°CStorage Range: -40 to 80°COperating and Storage Humidity: 85% max. relative humidity (non-

condensing) from 0°C to 65°C.Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2g.Shock to IEC 68-2-27: Operational 20 g (10g relay)Altitude: Up to 2000 meters

6. ISOLATION BREAKDOWN RATINGS:AC line with respect to all inputs and outputs: 2300 V for 1 minute (250

V working)Relay contacts to all other inputs and outputs: 2300 VACDC Power with respect to sensor input: 50 V working (500 V for 1 minute)

7. CERTIFICATIONS AND COMPLIANCES: CE Approved

EN 61326-1 Immunity to Industrial LocationsEmission CISPR 11 Class AIEC/EN 61010-1RoHS Compliant

Factory Mutual (FM) Listed: File #3030454UL Recognized Component, File #E123489Type 4X Enclosure rating (Face only) IP65 Enclosure rating (Face only)IP20 Enclosure rating (Rear of unit)Refer to EMC Installation Guidelines section of the bulletin for additional

information.8. CONNECTION: Wire clamping screw terminals

Wire Gage Capacity: Two 14 AWG (2.55 mm), four 18 AWG (1.02 mm), or four 20 AWG (0.61 mm).

Terminal Torque: 1.0Nm (8.9 in-lbs.). 1.4Nm (12.4 in-lbs.) max.

9. CONSTRUCTION: Black plastic alloy case and collar style panel latch. Panel latch can be installed for vertical or horizontal instrument stacking. One piece tinted plastic bezel. Bezel assembly with circuit boards can be removed from the case to change the output board without removing the case from the panel or disconnecting wiring. Unit meets NEMA 4X/IP65 requirements for indoor use, when properly installed. Flame resistant. Installation Category II, Pollution Degree 2.

10. WEIGHT: 0.38 lbs (0.17 kgs)

INPUT SPECIFICATIONS1. SENSOR INPUT:

Sample Period: 100 msecStep Response Time: Less than 300 msec typ., 400 msec max. (to within

99% of final value)Normal Mode Rejection: Greater than 40 dB @ 50/60 HzCommon Mode Rejection: Greater than 120 dB, DC to 60 HzOvervoltage Protection: Input overload 120 VAC for 15 seconds max.

2. Failed Sensor Response:Main Output: Sensor failure will initiate a process shutdownDisplay: “OPEN”Alarms: Upscale

3. INDICATION ACCURACY: ±(0.3% of Span +1°C) at 23°C ambient after 20 minute warm-up. (Includes NIST conformity, cold junction effect, A/D conversion errors and linearization conformity. Span Drift (maximum): 130 PPM/°C

4. RTD INPUT: 2 or 3 wire, 100 Ω platinum, alpha = 0.00385 (DIN 43760), alpha = 0.0039162Excitation: 150 µA typicalResolution: 1 or 0.1 degreeLead Resistance: 15 Ω max. per input lead

5. THERMOCOUPLE INPUT:Types: T, E, J, K, R, S, B, N, Linear mV, software selectableInput Impedance: 20 MΩ all typesLead resistance effect: 0.25 µV/ΩCold junction compensation: Less than ±1°C typ., (±1.5°C max), error over

0 to 65°C max. ambient temperature range. Defeated for Linear mV indication mode.

Resolution: 1° for all types, or 0.1° for T, E, J, K, and N only.

6. REMOTE RESET INPUT: Internally pulled up to +5 VDC (1MΩ).VIL: 0.85 V max., VIH: 3.65 V min., VIN MAX: 5.25 VDC, IOFF: 1µA max.

no standardno standard-5.00 to +56.00

orange (+) blue (-)

orange (+) red (-)

-200 to +1300°C -328 to +2372°FN

no standardgrey (+) red (-)

+149 to +1820°C +300 to +3308°FB

white (+) blue (-)

black (+) red (-)

0 to 1768°C +32 to 3214°FS

white (+) blue (-)

black (+) red (-)

0 to 1768°C +32 to +3214°FR

brown (+) blue (-)

yellow (+) red (-)

-200 to +1250°C -328 to +2282°FK

yellow (+) blue (-)

white (+) red (-)

-200 to +760°C -328 to 1400°FJ

brown (+) blue (-)

violet (+) red (-)

-200 to +750°C -328 to +1382°FE

white (+) blue (-)

blue (+) red (-)

-200 to +400°C -328 to +752°FT

BS 1843ANSIWIRE COLOR

mV

RANGETC TYPE

RTD TYPE RANGE

385 -200 to +600°C -328 to +1100°F

392 -200 to +600°C -328 to +1100°F

OHMS 2.0 to 320.0

3

OUTPUT SPECIFICATIONS1. LIMIT AND ALARM OUTPUT RELAYS:

Contact Rating: 5 A @ 250 VAC or 30 VDC (resistive load).Life Expectancy: 100,000 cycles at max. load rating. (Decreasing load

increases life expectancy.)2. LIMIT OUTPUT: CN63500-R1-AL1: Form-C relay; CN63500R1-AL2:

Form-A relay. Selectable for high or low trip activation. If the process temperature goes above the limit setpoint for a high trip, or below the limit setpoint for a low trip, the limit relay will de-energize to initiate a process shutdown. The limit output cannot be reset until the process temperature returns to the proper operating range; manual reset is required (local or remote).

Annunciators:“EX” - Lit when the process temperature exceeds the limit setpoint.“OUT” - Lit when the limit output is de-energized.

3. ALARM OUTPUTS (Optional): One or two Form-A relays.Modes:

Absolute High Acting Absolute Low ActingDeviation High Acting Deviation Low ActingInside Band Acting Outside Band Acting

Reset Action: Programmable; automatic or latched. Latched alarms can be reset regardless of limit exceed condition.

Standby Mode: Programmable; enable or disable.Hysteresis: Programmable.Annunciator: “A1” and “A2” programmable for normal or reverse acting.

Although this unit is designed with a high degree of immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into a unit may be different for various installations. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed are some EMI guidelines for a successful installation in an industrial environment.1. A unit should be mounted in a metal enclosure, which is properly connected

to protective earth.2. Use shielded cables for all Signal and Control inputs. The shield connection

should be made as short as possible. The connection point for the shield depends somewhat upon the application. Listed below are the recommended methods of connecting the shield, in order of their effectiveness.a. Connect the shield to earth ground (protective earth) at one end where the

unit is mounted.b. Connect the shield to earth ground at both ends of the cable, usually when

the noise source frequency is over 1 MHz.3. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors, feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be run through metal conduit that is properly grounded. This is especially useful in applications where cable runs are long and portable two-way radios are used in close proximity or if the installation is near a commercial radio transmitter. Also, Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components.

4. Long cable runs are more susceptible to EMI pickup than short cable runs.5. In extremely high EMI environments, the use of external EMI suppression

devices such as Ferrite Suppression Cores for signal and control cables is effective.6. To protect relay contacts that control inductive loads and to minimize radiated and conducted noise (EMI), some type of contact protection network is normally installed across the load, the contacts or both. The most effective location is across the load.a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide

varistor (MOV) across an AC inductive load is very effective at reducing EMI and increasing relay contact life.

b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor switch, care must be taken not to exceed the breakdown voltage of the transistor when the load is switched. One of the most effective ways is to place a diode across the inductive load. External diode protection at the load is always a good design practice to limit EMI. Although the use of a snubber or varistor could be used.

7. Care should be taken when connecting input and output devices to the instrument. When a separate input and output common is provided, they should not be mixed. Therefore a sensor common should NOT be connected to an output common. This would cause EMI on the sensitive input common, which could affect the instrument’s operation.

EMC INSTALLATION GUIDELINES

18 to 36 VDC / 24 VAC

85 to 250 VAC

PART NUMBERS

LIMIT OUTPUT ALARM 1 OUTPUT ALARM 2 OUTPUT PART NUMBERS

Form-C Relay Form-A Relay CN63500-R1-AL1-LVForm-A Relay Form-A Relay Form-A Relay CN63500-R1-AL2-LV

REPLACEMENT OUTPUT BOARD

CN6-RBDLA210CN6-RBD48111

CN6-RBD48111CN6-RBDLA210

REPLACEMENT OUTPUT BOARD

CN63500-R1-AL2Form-A RelayForm-A RelayForm-A RelayCN63500-R1-AL1Form-A RelayForm-C Relay

PART NUMBERSALARM 2 OUTPUTALARM 1 OUTPUTLIMIT OUTPUT

4

The CN63500 meets NEMA 4X/IP65 requirements for indoor use to provide a watertight seal in steel panels with a minimum thickness of 0.09 inch, or aluminum panels with a minimum thickness of 0.12 inch. The units are intended to be mounted into an enclosed panel. It is designed so that the units can be stacked horizontally or vertically. The bezel assembly MUST be in place during installation of the unit.

Instructions:1. Prepare the panel cutout to the dimensions.2. Remove the panel latch from the unit. Discard the cardboard sleeve.3. Carefully remove the center section of the panel gasket and discard. Slide

the panel gasket over the unit from the rear, seating it against the lip at the front of the case.

4. Insert the unit into the panel cutout. While holding the unit in place, push the panel latch over the rear of the unit, engaging the tabs of the panel latch in the farthest forward slot possible.

5. To achieve a proper seal, tighten the panel latch screws evenly until the unit is snug in the panel, torquing the screws to approximately 7 in-lbs (79 N-cm). Over tightening can result in distortion of the panel, and reduce the effectiveness of the seal.

Note: The installation location of the CN63500 is important. Be sure to keep it away from heat sources (ovens, furnaces, etc.), and away from direct contact with caustic vapors, oils, steam, or any other process byproducts in which exposure may affect proper operation.

Multiple Unit StackingThe CN63500 is designed for close spacing of multiple units. Units can be

stacked either horizontally or vertically. For vertical stacking, install the panel latch with the screws to the sides of the unit. For horizontal stacking, the panel latch screws should be at the top and bottom of the unit. The minimum spacing from center line to center line of units is 1.96" (49.8 mm). This spacing is the same for vertical or horizontal stacking.

Note: When stacking units, provide adequate panel ventilation to ensure that the maximum operating temperature range is not exceeded.

Caution: Disconnect power to the unit and to the output control circuits to eliminate the potential shock hazard when removing the bezel assembly.

Unit Removal ProcedureTo remove a unit from the panel, first loosen the panel latch screws. Insert

flat blade screwdrivers between the latch and the case on either side of the unit, so that the latches disengage from the grooves in the case. Push the unit through the panel from the rear.

Removing Bezel AssemblyThe bezel assembly must be removed from the case to replace the output

board. To remove the bezel assembly, insert a flat blade screwdriver into the pry slot on either side of the unit. Twist the screwdriver handle until the unit is ejected enough to allow removal.

Caution: The bezel assembly contains electronic circuits that can be damaged by static electricity. Before removing the assembly, discharge static charge on your body by touching an earth ground point. It is also important that the bezel assembly be handled only by the bezel itself. Additionally, if it is necessary to handle a circuit board, be certain that hands are free from dirt, oil, etc., to avoid circuit contamination that may lead to malfunction. If it becomes necessary to ship the unit for repairs, place the unit in its case before shipping.

Installing Bezel AssemblyTo install the bezel assembly, insert the assembly into the case until the bezel

is fully seated against the lip of the case. Properly installing the bezel assembly is necessary for watertight sealing.

1.96 (49.8)MIN.

IF NEMA 4 IS NOT REQUIRED,THIS PANEL MATERIAL MAY BE REMOVED.

PANELCUT-OUT

STANDARDPRY

PANEL

SLOT

CASELIP

BEZEL

EB0783

RP

1

2

3

4

5

6

7

8

9

10

13 14

1211

2.39 (60.7)MAX.

1.96 (49.8)MAX.

PANEL LATCH INSTALLED FORVERTICAL UNIT STACKING HORIZONTAL UNIT STACKING

PANEL LATCH INSTALLED FOR

MAX.2.39 (60.7)

MAX.1.96 (49.8)

1

2

3

4

5

6

7

8

9

10

13 14

1211

-0.0+0.6

-0.000+0.024

-0.0+0.6

-0.000+0.024

(45 )

1.772

(45 )

1.772 LATCHING

BEZEL

LATCHINGPANEL LATCH

PANELMOUNTING

SCREW

TABS

SLOTS

PANEL

PANEL GASKET

1.0 INSTALLING THE CN63500

5

2.0 WIRING THE CN63500After the unit has been mechanically mounted, it is ready to be wired. All

wiring connections are made to the rear screw terminals. When wiring the unit, use the numbers on the label and those embossed on the back of the case, to identify the position number with the proper function.

All conductors should meet voltage and current ratings for each terminal. Also cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that power supplied to the unit (AC or DC) be protected by a fuse or circuit breaker. Strip the wire, leaving approximately 1/4" (6 mm) bare wire exposed (stranded wires should be tinned with solder). Insert the wire under the clamping washer and tighten the screw until the wire is clamped tightly.Caution: Unused terminals are NOT to be used as tie points. Damage to the

CN63500 may result if these terminals are used.

POWER WIRINGAC Power

Primary AC power is connected to terminals #11 and #12, labeled AC. To reduce the chance of noise spikes entering the AC line and affecting the CN63500, an AC feed separate from that of the load should be used to power the CN63500. Be certain that the AC power to the CN63500 is relatively “clean” and within the variation limit. Connecting power from heavily loaded circuits or circuits that also power loads that cycle on and off (contacts, relays, motors, etc.), should be avoided.

DC PowerDC Power (18 to 36 VDC) is connected to terminals #11 and #12 labeled

DC+ and DC- respectively.

CAUTION: Observe proper polarity when connecting DC voltages. Damage to the unit may occur if polarity is reversed.

SIGNAL WIRINGThermocouple

When connecting the thermocouple, be certain that the connections are clean and tight. If the thermocouple probe cannot be connected directly to the CN63500, thermocouple wire or thermocouple extension-grade wire must be used to extend the connection points (copper wire does not work). Always refer to the thermocouple manufacturer’s recommendations for mounting, temperature range, shielding, etc. For multi-probe temperature averaging applications, two or more thermocouple probes may be connected to the CN63500 (always use the same type). Paralleling a single thermocouple to more than one CN63500 is not recommended. Generally, the red wire from the thermocouple is negative and connected to the CN63500’s common.

RTDWhen connecting the RTD, be certain that the connections are clean and

tight. RTD sensors have a higher degree of accuracy and stability than thermocouple sensors. Most RTD sensors available are the three wire type. The third wire is a sense lead for canceling the effects of lead resistance of the probe. Four wire RTD elements may be used by leaving one of the sense leads disconnected. Two wire RTD sensors may be used in either of two ways:A) Attach the RTD to terminals #8 and #10. Install a copper sense wire of the

same wire gauge as the RTD leads. Attach one end of the wire at the probe and the other end to terminal #9. Complete lead wire compensation is obtained. This is the preferred method.

B) Attach the RTD to terminals #8 and #10. Install a shorting wire between terminals #9 and #10. A temperature offset error of 2.5°C/ohm of lead resistance exists. The error may be compensated by programming a temperature offset.

Note: With extended cable runs, be sure the lead resistance is less than 15 ohms/lead.

RELAY CONNECTIONSTo prolong contact life and suppress electrical noise interference due to the

switching of inductive loads, it is good installation practice to install a snubber across the contactor. Follow the manufacturer's instructions for installation.

Note: Snubber leakage current can cause some electromechanical devices to be held ON.

*Terminal numbers are model dependent. See Terminal Configurations for description.

REMOTE RESET WIRINGThe use of shielded cable is recommended. Follow the EMC installation

guidelines for shield connection.Terminal #6 is the Remote Reset. Any form of mechanical switch may be

connected to terminal #6 (REMOTE RESET) and terminal #8 (COMM.). Sinking open collector logic with less than 0.7 V saturation and off-state leakage current of less than 1 µA may also be used.

POWER

-

+

CONNECTIONNOTC

COMM.

USER INPUT

AT5 AMPS

250 VAC

CONTROLLER

N.O.LOAD FUSE

N.C.

AC/DC POWER

*

*

*

Thermocouple Connection

RTD Connection

POWER

COMM.

RTD

USER INPUT

RTDPROBE

6

3.0 FRONT PANEL DESCRIPTION

EX OUT A1 A2

PR

ILLUMINATES WHEN THE LIMIT OUTPUT IS DE-ENERGIZED.

ILLUMINATES WHEN ALARM 2 IS ON.

ILLUMINATES WHEN THEPROCESS TEMPERATURE

EXCEEDS THE LIMIT

SECONDARY DISPLAY-DISPLAYS THE LIMIT SETPOINT.ALSO DISPLAYS MNEMONIC OR

NUMERIC VALUE WHEN

MAIN DISPLAY-DISPLAYS THE PROCESS TEMPERATURE.ALSO DISPLAYS MNEMONIC OF SELECTEDPARAMETER IN A CONFIGURATION MODULE.

MODIFYING A PARAMETER.

SETPOINT.

ILLUMINATES WHEN ALARM 1 IS ON.

The front panel bezel material is flame and scratch resistant, tinted plastic that meets NEMA 4X/IP65 requirements, when properly installed. Continuous exposure to direct sunlight may accelerate the aging process of the bezel. The bezel should be cleaned only with a soft cloth and neutral soap product. Do NOT use solvents. There are two 4-digit LED displays, a red upper Main Display and a lower green Secondary Display.

There are up to four panel annunciators, with red backlighting, that illuminate to inform the operator of the CN63500 and output status. See the front panel diagram for a description of the annunciators. Four front panel buttons are used to access different modes and parameters. The following is a description of each button.

Do NOT use tools of any kind (screwdrivers, pens, pencils, etc) to operate the keypad of this unit.

Button FunctionsR - The Reset (R) button is used to reset the limit and alarm relays. The limit output

cannot be reset until the process temperature returns to the proper operating range. Latched alarms can be reset regardless of limit exceed condition.

P - The Parameter (P) button is used to access programming, enter the change, and scroll through the available parameters in any mode.

UP, DN - The Up/Down buttons are used to modify parameters.

CN63500 POWER-UPUpon applying power, the CN63500 delays input indication and control

action for five seconds to perform several self-diagnostic tests and to display basic CN63500 information. Initially, the CN63500 illuminates both displays and all annunciators to verify that all display elements are functioning. The CN63500 then displays the programmed input sensor type in the main (top)

display and the revision number of the CN63500’s operating system in the secondary (bottom) display. The CN63500 checks for correct internal operation and displays an error message (E-xx) if an internal fault is detected. (See the Troubleshooting section for further information.)

Upon completion of this sequence, the CN63500 begins displaying the input value and setpoint, and updates the outputs based upon this condition.

CN63500 CONFIGURATION OVERVIEWThe CN63500 is programmed with certain parameter settings from the

factory. Factory settings are listed in parentheses in the various Configuration of Parameters tables. In many cases, these settings must be changed to the particulars of the application before proper operation can be started.

The CN63500 is typically in the Normal Display Mode. In this mode, the process temperature is displayed in the main (top) display, and the limit setpoint is displayed in the secondary (bottom) display. When changes to the parameter configurations are needed, the P button is pressed, and the CN63500 will enter into the Parameter Mode.

PARAMETER CONFIGURATION BASIC STARTUPFor basic start-up, it is important to verify or change Input Parameter Module

(1-IN) parameters tYPE and SCAL, and Output Parameter Module (2-OP) parameter LiAC (Limit Trip Action). For alarm set-up, it is important to verify or change Alarms Parameter Module (4-AL) parameters ACt1, AL-1, ACt2, and AL-2.

If the above Input parameters or the input wiring connections are not correct, then the main (top) display may display an error message or incorrect value. Verify the input programming and wiring. (If incorrect display continues, refer to the Troubleshooting section.) All other parameter configurations are important but will not prevent the CN63500 from showing a correct display.

4.0 PARAMETER MODEThe Parameter Mode is accessed by pressing the P Button from the

Normal Display Mode. While in the Parameter Mode, the temperature is displayed in the main (top) display, and the parameter is displayed in the secondary (bottom) display. The correct password must be entered before any parameters can be accessed. To modify values, use the UP or DOWN button while the parameter is displayed. Use the P button to accept the new value, and to scroll through the parameters. The CN63500 will automatically return to the normal display mode if no action is taken. The CN63500 responds to the new

values immediately, but the change is not committed to non-volatile memory until the CN63500 is returned to the Normal Display Mode. If power loss occurs before returning to the normal display mode, the new values must be re-entered.

To gain access to the Configuration Parameter Modules continue to CNFP and press the UP button. These modules allow access to the fundamental set-up parameters of the CN63500. If the setpoint or alarm values are modified, the CNFP step will be skipped.

DISPLAY PARAMETER RANGE DESCRIPTION

PASS Password to access parameters 0 to 250 If an incorrect value is entered, the CN63500 will display “End” momentarily, and then return to the normal display mode. The default password is 10. The wildcard password is 222 (in case the password is forgotten).

SP Limit setpoint -999 to 9999 Range limited by SPLO & SPHI.AL-1 * Alarm #1 -999 to 9999 The Alarm parameters can be independently locked out from

appearing. See Configuration Module 3, Parameter Lock-outs.AL-2 * Alarm #2 -999 to 9999CNFP Configuration parameter modules “Up” button: enter

configuration modules.

End End of Parameter Mode When the parameter list has been scrolled through, the CN63500 will display “End” momentarily, and then return to the normal display mode.

Parameter Mode Reference Table

These modules allow access to the fundamental set-up parameters of the CN63500. The modules are grouped into related programming steps, such as inputs, outputs, alarms, etc. Upon completion of each module, the program returns to “CNFP”.

* Model Number Dependent.

7

CONFIGURATION PARAMETER MODULESThe Configuration Parameter modules are accessed by pressing the UP button

from CNFP in the Parameter Mode. The UP or DOWN buttons can be pressed to move to the desired Parameter Module. The P button is then pressed to enter into that module. The main (top) display will be the parameter, and the secondary (bottom) display will be the parameter value. The UP or DOWN buttons are used to modify the desired parameter value, and the P button enters the new value, and moves to the next parameter. The CN63500 responds to the new values after the

P button is pressed, however, the change is not committed to permanent memory until the CN63500 is returned to the Normal Display Mode. If power loss occurs before returning to the Normal Display Mode, the new values must be entered again. At the end of each module, the CN63500 will go back to CNFP. Other Parameter Modules can be accessed by pressing the UP or DOWN buttons, or pressing P will return to the Normal Display Mode.

Parameters that are model number, or program dependent will only be displayed when the appropriate options are installed or programmed.

CONFIGURE MODULE 1 - INPUT PARAMETERS (1-IN)DISPLAY PARAMETER RANGE

(FACTORY SETTING) DESCRIPTION/ COMMENTS

tYPE Input Type tc-t - Type T TC tc-E - Type E TC tc-J - Type J TC tc-K - Type K TC tc-r - Type R TC tc-S - Type S TC tc-b - Type B TC tc-N - Type N TC LIN - Linear mV

r385 - 385 curve RTD r392 - 392 curve RTD

rLIN - Linear ohms (tc-J)

Select from the list of various thermocouple and RTD sensors.

SCAL Temperature Scale °F or °C (°F)

Select either degrees Fahrenheit (F) or degrees Celsius (C). If changed, be sure to check all parameters.

dCPt Temperature Resolution 0 or 0.0 (0)

Select either 1 or 0.1 degree resolution. If changed, be sure to check all parameters.

FLtr Digital Input Filtering and Display Update

SHFt Input Signal Shift (correction offset)

-999 to 9999 1 or 0.1 degree

(0)

If the CN63500 temperature disagrees with a reference temperature instrument or if the temperature sensor has a known calibration, the CN63500 temperature can be compensated by a correction offset. The following equation expresses the relationship: Desired Display Temp = (CN63500 Temp) + SHFt. Normally set to 0.

SPLO Limit Setpoint Lower Limit -999 to 9999 1 or 0.1 degree

(0)

The CN63500 has programmable high and low setpoint limit values to restrict the setting range of the limit setpoint. Set the limit values so that the temperature setpoint value cannot be set outside the safe operating area of the process. SPHI must be above SPLO.SPHI Limit Setpoint Upper Limit -999 to 9999

1 or 0.1 degree (9999)

CONFIGURE MODULE 2 - OUTPUT PARAMETERS (2-OP)DISPLAY PARAMETER RANGE

(FACTORY SETTING) DESCRIPTION/ COMMENTS

LiAc Limit Output Trip Action LO - Low Acting HI - High Acting

(HI)

The limit output is selectable for high or low trip activation. If the process temperature goes above the limit setpoint for a high trip, or below the limit setpoint for a low trip, the limit relay will de-energize to initiate a process shutdown. See the Limit Output Action section for details.

0 to 40 - least input filtering 3 - most input filtering

4 - most input filtering and slower 500 msec display update rate (outputs still

update at 100 msec rate) (1)

Select the relative degree of input signal filtering and display update rate. The filter is an adaptive digital filter that discriminates between measurement noise and actual process changes. Therefore, the influence on step response time is minimal. If the signal is varying too greatly due to measurement noise, increase the filter value. Conversely, if the fastest CN63500 response is desired, decrease the filter value.

8

CONFIGURE MODULE 3 - LOCkOUT PARAMETERS (3-LC)DISPLAY PARAMETER DESCRIPTION/ COMMENTS

PASS Password 0 to 250 (10)

AL * Alarms #1 and #2 access level

The alarm(s) parameter in the Parameter Mode can be configured to be completely locked out, read only, or fully accessible.

FPrS Front panel reset NO - disabled YES - active

(YES)

The front panel R button can be enabled or disabled. The Remote Reset input is not affected by this setting.

The password is required to access all parameters. The password can be set to any value between 0 and 250. A wildcard password, 222, can be used as an alternative to the programmed password.

* Model Number Dependent.

CONFIGURE MODULE 4 - ALARMS PARAMETERS (4-AL)

RANGE (FACTORY SETTING)

DISPLAY PARAMETER RANGE (FACTORY SETTING) DESCRIPTION/ COMMENTS

Act1 Alarm 1 action mode A-HI - absolute high A-LO - absolute low d-HI - deviation high d-LO - deviation low b-IN - band inside

b-Ot - band outside (A-HI)

rSt1 Alarm 1 reset mode Auto - automatic LATC - manual reset

(Auto)

Stb1 Alarm 1 standby function (delay)

NO or YES (NO)

AL-1 Alarm 1 value -999 to 9999 (0)

Act2 * Alarm 2 action mode The Alarm 2 parameters are programmed independently of alarm 1. See the corresponding Alarm 1 parameter for description.

rSt2 * Alarm 2 reset mode Auto - automatic LATC - manual reset

(Auto)

Stb2 * Alarm 2 standby function (delay)

NO or YES (NO)

AL-2 * Alarm 2 value -999 to 9999 (0)

AHYS Alarm hysteresis value 1 to 250 (1)

Automatic reset alarms are reset by the CN63500 when the alarm condition clears. Latched alarms require operator action to reset the alarm condition. The front panel R button, if enabled, can be used to reset a latched alarm (see FPrS in Configure Module 3). A latched alarm condition may also be reset via the Remote Reset input. See the Reset Action diagram in the Alarms section.

When deviation low-acting with positive alarm value (d-LO), deviation high-acting with negative value (d-HI), or band inside-acting (b-IN) is selected for the alarm action, the indicator is OFF when the alarm output is ON. See the Alarms section for complete details of each action. If changed, check alarm values.

The alarm values are either absolute values, or relative to the limit setpoint value (deviation and band alarms). An absolute alarm value is the value that is entered for the alarm. A relative alarm value is the mathematical sum of the temperature limit setpoint value and the alarm value (positive or negative), thus a relative alarm tracks the limit setpoint value as it is changed. If the alarm action is set as a Band Alarm, then only a positive alarm value can be entered.

The alarm value(s) have a programmable hysteresis band to prevent alarm output chatter near the alarm trigger point. The hysteresis value should be set to eliminate this effect. A value of 2 to 5 is usually sufficient for most applications. A single alarm hysteresis value applies to both alarms. See the Alarm Action Figures, in the Alarms section, for the effect of hysteresis on the various alarm types.

A-HI - absolute high A-LO - absolute low d-HI - deviation high d-LO - deviation low b-IN - band inside

b-Ot - band outside (A-HI)

The alarm(s) may be independently configured to exhibit a power-on, standby delay which suppresses the alarm output from turning ON until the temperature first stabilizes outside the alarm region. After this condition is satisfied, the alarm standby delay is canceled and the alarm triggers normally, until the next CN63500 power-on. This feature also works for deviation and band alarms when the setpoint is changed via keypad. This action suppresses “nuisance” alarms. See the Alarm Standby diagram in the Alarms section.

* Model Number Dependent.

LOC - lockout, prevents the alarms from appearing

rEd - read only, alarms appear, but cannot be modified

Ent - enter, alarms appear, and can be modified

(Ent)

9

CONFIGURE MODULE 9 - FACTORy SERvICE OPERATIONS (9-FS)DISPLAY PARAMETER RANGE DESCRIPTION/ COMMENTS

CodE Factory service function code

48 - Calibrate instrument CN63500 calibration. Refer to the Calibration section for details.

66 - Reset parameters to factory settings

Entering code 66 restores all parameters to factory settings. The unit indicates the operation after the P button is pressed, by displaying “rSEt” in the lower display momentarily.

77 (twice in succession) - Reset CN63500 calibration to nominal values

Caution: this operation erases the CN63500 calibration values and defaults the values to nominal settings. Reading errors of ±10% may result. Do not perform this operation unless the CN63500 has lost calibration. Loss of calibration is signaled by an “E-CL” error flag at power-up. To clear this flag, perform calibration procedure as noted in the Calibration section. Alternatively, “stepping” through one of the calibration procedures clears the error flag, but does NOT validate the calibration accuracy in any manner.

USER PARAMETER VALUE CHART CN63500 Number _____________

MNEMONIC PARAMETER USER SETTING

Limit Setpoint

Alarm 2 Value

Password

Alarm 1 Value

Input ParametersMNEMONIC PARAMETER USER SETTING

Temperature Scale Units

Limit Setpoint Lower Limit

Digital Filtering

Input Sensor Type

Input Offset

Limit Setpoint Upper Limit

Temperature Resolution

Output ParametersMNEMONIC PARAMETER USER SETTING

Limit Output Trip Action

Lockout ParametersMNEMONIC PARAMETER USER SETTING

Alarm(s) Access Level

Front Panel Reset

Password

Configure Alarm ParametersMNEMONIC PARAMETER USER SETTING

Alarm 1 Reset Mode

Alarm 2 Reset Mode

Alarm 2 Value

Alarm 1 Value

Alarm Hysteresis Value

Alarm 1 Action Mode

Alarm 2 Action Mode

Alarm 2 Standby Enabled

Alarm 1 Standby Enabled

10

LIMIT OUTPUT ACTIONThe limit output is selectable for high or low trip activation. If the process

temperature goes above the limit setpoint for a high trip, or below the limit setpoint for a low trip, the limit relay will de-energize to initiate a process shutdown. The limit output cannot be reset until the process temperature returns to the proper operating range; manual reset is required. The following action figures describe the status of the limit output and the front panel indicators for various over/under setpoint, and reset conditions. Reset is either by the front panel R button, if enabled, or by the Remote Reset input, terminal #6. Refer to Configure Module 2 - Output Parameters for details of configuring the limit output. Refer to Configure Module 3 - Lockout Parameters for details of configuring the front panel Reset button.

Process Temp

Annunciator

Annunciator

LimitOutput

OUT

Setpoint

Reset

EXceed

OFF

OFF

OFF

EnergizedDe-energized

ON

ON

ONOFF

OFF

ON

OFF

Energized

High Trip Action

Low Trip Action

5.0 ALARMS (OPTIONAL)The alarm action figures describe the status of the alarm output and the front

panel indicator for various over/under temperature conditions. The alarm output wave form is shown with the output in the automatic reset mode. Select the alarm action with care -- in some configurations, the front panel indicator (LED)

might be OFF while the output is ON. Refer to Configure Module 4 - Alarm Parameters for details of configuring the alarms.

OUTPUT OFFLED OFF

OUTPUT ONLED ON

OUTPUT OFFLED OFF

OUTPUT ONLED ON

TEMPABSOLUTE HIGH-ACTING ALARM (A-HI)

ALHYS

Setpoint

Reset

Annunciator

LimitOutput

OUT

EXceedAnnunciator

Process Temp

Energized

OFF

OFF

OFF

De-energized

ON

ON

ON ON

OFF

OFF

Energized

OFF

AL

ABSOLUTE LOW-ACTING ALARM (A-LO)

TEMP

LED ONOUTPUT ON

LED OFFOUTPUT OFF

LED ONOUTPUT ON

LED OFFOUTPUT OFF

HYS

OUTPUT OFFLED OFF

OUTPUT ONLED ON

OUTPUT OFFLED OFF

OUTPUT ONLED ON

INPUT

DEVIATION HIGH-ACTING WITH POSITIVE ALARM VALUE (d-HI)

SP + AL

SP

HYS

SP + (-AL)

DEVIATION HIGH-ACTING WITH NEGATIVE ALARM VALUE (d-HI)

INPUT

LED OFFOUTPUT ON

LED ONOUTPUT OFF

SP

HYS

OUTPUT ONLED OFF

OUTPUT OFFLED ON

11

Alarm Reset Sequence Alarm Standby Delay Sequence

ON OFF

ALARM VALUE

OFF ON OFF

OFF

TIME

AUTOMATICRESET

MANUALRESET

MANUAL RESETPERFORMED BY OPERATOR

INPUTALARM MODE

(ABSOLUTE LOW ACTING SHOWN)

ON OFF ON

OFF ON OFF ON

ON OFF ON OFF ON

UNITPOWER-ON

STANDBYENABLED

STANDBYDISABLED

TIME

INPUT

ALARM VALUE

ALARM MODE(ABSOLUTE LOW ACTINGW/AUTO-RESET SHOWN)

CALIBRATION CHECKS The instrument has been fully calibrated at the factory for all input types. If

the unit appears to be indicating or controlling incorrectly, see the Troubleshooting section before attempting this procedure.

If the CN63500 is suspected of reading incorrectly, the instrument may be checked for indication accuracy without disturbing the factory calibration. The following procedures may be used for this purpose.

Note: Allow ½ hour warm-up before checking these parameters.

mV Reading Check1. Connect a DC mV source with an accuracy of 0.03% or better to terminal #8

(-) & #9 (+).2. Configure Input Parameters Module 1 for linear mV (Lin) input, under tYPE.3. Compare the CN63500 read-out to the standard at various points over the range

(-5.00 mV to 56.00 mV). The tolerance is ±(0.15% of reading + 1 LSD).4. Calibrate the CN63500 if the readings are out of tolerance.

Thermocouple Cold Junction Temperature Check1. Connect a thermocouple probe of known accuracy (Types T, E, J, K, N only)

to CN63500. Select the probe used in Configure Module 1.2. Connect a reference temperature probe to measuring end of thermocouple to

monitor temperature. Allow sufficient time for temperatures to equalize.3. Compare CN63500 display with reference temperature probe. The CN63500

display should equal the calibrated probe temperature. (Tolerance is ±1ºC.)4. Calibrate the cold junction temperature if out of tolerance.

RTD Ohms Reading Check1. Connect RTD simulator (with an accuracy of 0.1 ohm or better) capable of

operating with less than 150 µA to terminals #8, #9, & #10.2. Configure Input Parameters Module 1 for linear ohms (rLin) input, under tYPE.3. Compare the CN63500 read-out with the RTD simulator at various points over

the range 2.0 to 300.0 ohms. The tolerance is ±(0.3% of span + 1 LSD).4. Calibrate the CN63500 RTD ohms if out of tolerance.

Error Flag E-CLIf error flag “E-CL” appears at power-up, a loss of calibration parameters due

to noise spikes has occurred. Entering code 77 twice in Factory Service Operations Module (9-FS) erases the CN63500 calibration values and defaults the values to nominal settings. Reading errors of ±10% may result. It is recommended that the CN63500 be fully recalibrated. If using thermocouple only, the RTD calibration need not be performed.

Note: the “E-CL” flag may be cleared by “stepping” through cold junction calibration procedure without the need to change any calibration values. A ±10% reading error will still exist.

INPUT

DEVIATION LOW-ACTING WITH POSITIVE ALARM VALUE (d-LO)

SP + AL

OUTPUT OFFLED ON

OUTPUT ONLED OFF

SP

HYS

OUTPUT ONLED OFF

OUTPUT OFFLED ON

SP + (-AL)

DEVIATION LOW-ACTING WITH NEGATIVE ALARM VALUE (d-LO)

INPUT

LED ONOUTPUT ON

LED OFFOUTPUT OFF

LED ONOUTPUT ON

LED OFFOUTPUT OFF

SP

HYS

OUTPUT ONLED OFF

OUTPUT OFFLED ON

OUTPUT ONLED OFF

INPUT

BAND INSIDE ACTING (b-IN)

SP + AL

OUTPUT OFFLED ON

OUTPUT ONLED OFF

OUTPUT OFFLED ON

SP - AL

SP

HYS

HYS SP - AL

LED ONOUTPUT ON

LED OFFOUTPUT OFF

LED ONOUTPUT ON

SP + AL

BAND OUTSIDE ACTING (b-Ot)INPUT

LED OFFOUTPUT OFF

LED ONOUTPUT ON

LED OFFOUTPUT OFF

HYS

HYS

SP

12

Millivolt Calibration (CAL)Connect precision millivolt source with an accuracy of 0.03% to terminals #8

(-) & #9 (+). Cold Junction or RTD ohms calibration MUST be performed after millivolt calibration.

Thermocouple Cold Junction Calibration (CJC)This procedure must be performed AFTER an accurate mV calibration.1. Exit Factory Service Operations (continually press P until “End”), and return

to Normal Display Mode.2. Connect a thermocouple probe of known accuracy to the CN63500 (Types T,

E, J, K, and N only). Select the probe type used in Configure Module 1.3. Connect a reference temperature probe to the measuring end of the CN63500

thermocouple probe. The two probes should be shielded from air movement and allowed sufficient time to equalize in temperature. (As an alternative, the CN63500 thermocouple probe may be placed in a calibration bath of known temperature.)

4. Compare CN63500 display with reference temperature probe (or calibration bath). If the displayed CN63500 temperature does not equal the reference probe temperature, calculate the CJ error as follows:

CJ Error = reference probe temperature - displayed CN63500 temperature5. Enter Factory Service Operations Module (9-FS).

RTD Ohms Calibration (RTD)This procedure must be performed AFTER an accurate mV calibration.

Connect one leg of precision resistance (accuracy of 0.1 ohm) to terminals #9 and #10 together, and the other leg to #8.

6.0 CALIbRATIONWhen re-calibration is required (generally every two years), this procedure

should be performed by qualified technicians using appropriate equipment. Equipment source accuracy of 0.03% or better is required.

The procedure consists of: applying accurate mV signals, setting the thermocouple cold junction temperature, and applying precision resistance, among others. Allow a 30 minute warm-up period before starting this procedure. Do not use thermocouple wire for the millivolt or RTD ohms calibration.

This procedure may be aborted by disconnecting power to the CN63500 before exiting the configuration mode. The existing calibration settings remain in affect.Note: After completing any of the calibration sequences, the CN63500 defaults

the input sensor type to thermocouple type “J” (tc-J). Be sure to set input sensor for proper type.

Note: The CN63500 must be restored to normal display mode before any data is stored.

Not required if only using TC input. This procedure can only be performed AFTER an accurate mV calibration.yes/noRTD resistance calibrationrtd

Not required if only using RTD input. This procedure can only be performed AFTER an accurate mV calibration.

yes/noThermocouple cold junction temperature calibration

CJC

Calibration required for both RTD and TC input. If this procedure is performed, the cold junction temp or RTD ohms calibration procedures in turn must be completed.

Calibrate instrument.

yes/no

48

Millivolt calibration

Enter function code

CAL

CodE

DESCRIPTION/ COMMENTSRANGEPARAMETERDISPLAY

Factory Service Operations - Calibration (9-FS)

Wait 10 seconds, press P.Apply 14.0 mV

Wait 10 seconds, press P.

Wait 10 seconds, press P.

Apply 56.0 mV

Apply 42.0 mV

StP5

StP4

StP2

Wait 10 seconds, press P.Apply 28.0 mVStP3

Apply 0.0 mVStP1

DESCRIPTION/ COMMENTSACTIONDISPLAY

Wait 10 seconds, press P.

Cold Junction TemperatureCJC

DESCRIPTION/ COMMENTSPARAMETERDISPLAY

Note: If the initial value for CJC is not within the range of 15°C to 40°C, enter 25.0° for CJC and repeat the Cold Junction Calibration procedure.

Observe the indicated cold junction temperature. Add the calculated CJ Error to the displayed value. Enter the sum as the new value for CJC. Exit 9-FS and repeat step 4.

Wait 10 seconds, press P.Rtd2

Wait 10 seconds, press P.Rtd1

DESCRIPTION/ COMMENTSACTIONDISPLAY

Connect 0.0 ohm (jumper wire)

Connect 277.0 ohm

13

PROBLEMS POSSIBLE CAUSE REMEDIES

1. Check power.2. Verify power reading.3. Check connections.4. Check installation.

CN63500 NOT WORKING 1. Incorrect parameter set-up. 1. Check set-up parameters.

“E-FP” IN DISPLAY 1. Defective front panel button. 1. Press R to escape, then check all buttons for proper operation.2. Replace unit.

“E-UP” IN DISPLAY 1. Internal problem with CN63500. 1. Replace unit.

“E-E2” IN DISPLAY 1. Loss of setup parameters due to noise spike or other EMI event.

“E-CL” IN DISPLAY 1. Loss of calibration parameters due to noise spike or other EMI event.

1. Press R to escape, then check CN63500 accuracy.a. Recalibrate CN63500. (See Factory Service Module code 77.)b. Reset parameters to factory default settings.

1. Display value exceeds display range.2. Defective or mis-calibrated cold junction circuit.3. Loss of set-up parameters.4. Internal malfunction.

1. Change resolution to display whole number and verify reading.2. Perform cold junction calibration.3. Check set-up parameters.4. Perform Input calibration.

“OPEN” IN DISPLAY 1. Probe disconnected.2. Broken or burned-out probe.3. Corroded or broken terminations.4. Excessive process temperature.

1. Connect probe.2. Replace probe.3. Check connections.4. Check process parameters.

“OLOL” IN UPPER DISPLAY

“ULUL” IN UPPER DISPLAY 1. Input is below range of CN63500.2. Temperature below range of input probe.3. Defective or incorrect transmitter or probe.4. Excessive low temperature for probe.5. Loss of setup parameters.

“OLOL” OR “ULUL” IN LOWER DISPLAY

1. Signal input exceeds allowable range by 5%. 1. Check remote signal source.

1. Check input parameters.2. Change to input sensor with a lower temperature range.3. Replace transmitter or probe.4. Raise temperature.5. Perform input calibration.

The majority of problems can be traced to improper connections or incorrect set-up parameters. Be sure all connections are clean and tight, that the correct output board is fitted, and that the set-up parameters are correct.

For further technical assistance, contact technical support at the appropriate company numbers listed.

“...” or “-..” IN DISPLAY

1. Check input parameters.2. Change to input sensor with a higher temperature range.3. Replace transmitter or probe.4. Reduce temperature.5. Perform input calibration.

7.0 TROUbLESHOOTING

1. Press R to escape, then check all set-up parameters. a. Check sensor input and AC line for excessive noise.

b. If fault persists, replace CN63500.

1. Input exceeds range of CN63500.2. Temperature exceeds range of input probe.

3. Defective or incorrect transmitter or probe.4. Excessive high temperature for probe.5. Loss of setup parameters.

NO DISPLAY 1. Power off.2. Brown-out condition.3. Loose connection or improperly wired.4. Bezel assembly not fully seated into rear of CN63500.

14

8.0 INSTALLING AN OUTPUT bOARDThe CN63500 is supplied with an output board installed.

Replacing Output Board1. Remove the bezel assembly.2. Lift up on the top bezel board latch while gently pulling out on the bezel/

display board assembly. Do NOT remove the display board from the bezel.3. Remove the output board by pulling it away from the other boards. Replace

the output board by aligning the board to board connector. Be certain the connector is fully mated.

4. Connect the bezel/ display board assembly by guiding the board ends into the bezel latches. Slide the assembly on evenly until the display board connector is completely engaged and bezel latches are fully seated onto the boards.

AL1

LIMIT

AL2

#CN6-RBD48111Output BoardForm-A Relay

Form-C RelayOutput Board#CN6-RBDLA210

AL1

LIMIT

EB0784

MD1797

A2A1

OUTEX

POUTPUT BOARD

POWER

CPU BOARD

SUPPLYBOARD

OUTPUT BOARDCONNECTORBEZEL/DISPLAY

BOARD ASSEMBLY

BEZEL BOARDLATCH

DISPLAYBOARD

CONNECTOR

9.0 TERMINAL CONFIGURATIONS

50/60 HZ 8VA

14

~12

85-250 VACAC

1A2 N.O. 13COMM.

COMM.

A1 N.O.LIMITRELAY

ALARMRELAYS

4N.O.5

~AC

11

23

6 REMOTERESET

9 TC10 RTD

87

COMM.

+-

50/60 HZ 9VAAC 24V ±10%

(-)DC 18-36V 7W

14

12

ALARM COMM.

COMM.

A1 N.O.

RELAY

RELAYS

LIMIT5

POWER (+)11

4

23

N.O.

A2 N.O. 1 13RESET

10 RTD

89

7

TC

COMM.

+-

REMOTE6

ALARM 1

LIMIT

RELAY

RELAY

COMM.

TC

RESETREMOTE

11

AC~85-250 VAC

50/60 HZ 8VA

COMM. 5 10

AC

12~ RTD

13

N.O.N.C.

COMM.34

2N.O. 1

789

614

-+

50/60 HZ 9VA

(-)

14

12

DC 18-36V 7WAC 24V ±10%

COMM.

COMM.

RELAY

RELAYLIMIT

5POWER(+)

11

2

43N.O.

N.C.

ALARM 1 N.O. 1 13RESET

10 RTD

89

7

TC

COMM.

+-

REMOTE6

Form-A Limit Relay with 2 Alarms Form-A Limit Relay with 2 Alarms

Form-C Limit Relay with 1 Alarm Form-C Limit Relay with 1 Alarm

AC Models DC Models

WARRANTY/DISCLAIMEROMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 25 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal two (2) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.

If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.

OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.

CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.

RETURN REQUESTS/INQUIRIESDirect all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.

OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering. OMEGA is a registered trademark of OMEGA ENGINEERING, INC.© Copyright 2006 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.

FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:1. Purchase Order number to cover the COST of the repair,2. Model and serial number of the product, and3. Repair instructions and/or specific problems relative to the product.

FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA:1. Purchase Order number under which the product was PURCHASED,2. Model and serial number of the product under warranty, and3. Repair instructions and/or specific problems relative to the product.

OMEGAnet® Online Serviceomega.com

Internet [email protected]

Servicing North America:U.S.A.: One Omega Drive, P.O. Box 4047ISO 9001 Certified Stamford, CT 06907-0047 TEL: (203) 359-1660 FAX: (203) 359-7700 e-mail: [email protected]

Canada: 976 Bergar Laval (Quebec) H7L 5A1, Canada TEL: (514) 856-6928 FAX: (514) 856-6886 e-mail: [email protected]

For immediate technical or application assistance:U.S.A. and Canada: Sales Service: 1-800-826-6342/1-800-TC-OMEGA®

Customer Service: 1-800-622-2378/1-800-622-BEST®

Engineering Service: 1-800-872-9436/1-800-USA-WHEN®

Mexico: En Español: (001) 203-359-7803 e-mail: [email protected] FAX: (001) 203-359-7807 [email protected]

Servicing Europe:Czech Republic: Frystatska 184, 733 01 Karviná, Czech Republic TEL: +420 (0)59 6311899 FAX: +420 (0)59 6311114 Toll Free: 0800-1-66342 e-mail: [email protected]

Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany TEL: +49 (0)7056 9398-0 FAX: +49 (0)7056 9398-29 Toll Free in Germany: 0800 639 7678 e-mail: [email protected]

United Kingdom: One Omega Drive, River Bend Technology CentreISO 9002 Certified Northbank, Irlam, Manchester M44 5BD United Kingdom TEL: +44 (0)161 777 6611 FAX: +44 (0)161 777 6622 Toll Free in United Kingdom: 0800-488-488 e-mail: [email protected]

It is the policy of OMEGA Engineering, Inc. to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.WARNING : These products are not designed for use in, and should not be used for, human applications.

Where Do I Find Everything I Need for Process Measurement and Control?

OMEGA…Of Course!Shop online at omega.com

TEMPERATURE] Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies] Wire: Thermocouple, RTD & Thermistor] Calibrators & Ice Point References] Recorders, Controllers & Process Monitors] Infrared Pyrometers

PRESSURE, STRAIN AND FORCE] Transducers & Strain Gages] Load Cells & Pressure Gages] Displacement Transducers] Instrumentation & Accessories

FLOW/LEVEL] Rotameters, Gas Mass Flowmeters & Flow Computers] Air Velocity Indicators] Turbine/Paddlewheel Systems] Totalizers & Batch Controllers

pH/CONDUCTIVITY] pH Electrodes, Testers & Accessories] Benchtop/Laboratory Meters] Controllers, Calibrators, Simulators & Pumps] Industrial pH & Conductivity Equipment

DATA ACQUISITION] Data Acquisition & Engineering Software] Communications-Based Acquisition Systems] Plug-in Cards for Apple, IBM & Compatibles] Datalogging Systems] Recorders, Printers & Plotters

HEATERS] Heating Cable] Cartridge & Strip Heaters] Immersion & Band Heaters] Flexible Heaters] Laboratory Heaters

ENVIRONMENTAL MONITORING AND CONTROL] Metering & Control Instrumentation] Refractometers] Pumps & Tubing] Air, Soil & Water Monitors] Industrial Water & Wastewater Treatment] pH, Conductivity & Dissolved Oxygen Instruments