tecumseh refrigerant piping

Upload: aries26march

Post on 05-Apr-2018

262 views

Category:

Documents


2 download

TRANSCRIPT

  • 7/31/2019 Tecumseh Refrigerant Piping

    1/24

    A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 85

    5

    INSTALLATION ANDREPLACEMENT

    INFORMATIONI. Compressor Tube Connections . . . . . . . .86

    II. Refrigerant Line Sizes . . . . . . . . . . . . . . .88

    III. Refrigerant Line Pressure Drops . . . . . . .93

    IV. Refrigerant Line Velocities . . . . . . . . . . . .98

    V. Service Valves . . . . . . . . . . . . . . . . . . . .103

    VI. Processing the System . . . . . . . . . . . . .103

    VII. System Cleanup and Compressor

    Replacement After Compressor

    Failure. . . . . . . . . . . . . . . . . . . . . . . . . . .104

    VIII. Replacing Compressors in Water-Utilizing Systems: Preventing

    Explosions. . . . . . . . . . . . . . . . . . . . . . . .108

    For more free Tecumseh literature please visit

    www.HVACRinfo.com

    http://www.hvacrinfo.com/http://www.hvacrinfo.com/
  • 7/31/2019 Tecumseh Refrigerant Piping

    2/24

    86 Chapter 5

    I. Compressor Tube

    Connections

    Tecumseh Products Company supplies compressorsto hundreds of manufacturers requiring different

    tubing sizes and arrangements. Because of this thesame compressor model may be foun d in th e field inmany suction and discharge tube variations, eachdepending upon the specific application in which itis installed.

    Suction connections can usually be identified as thelargest diameter stub tube in the housing. If 2 stubshave the same outer diameter (OD), then the onewith th e heavier wall will be the suction conn ection.If both of the largest stub t ubes are the same O Dand wall thickness, then either can be used as thesuction connection. Whenever possible, suction

    connections should be kept away from the hermeticterminal area so that condensation will not drip onherm etic terminals, causing corrosion.

    The stub tube, not chosen for the suction connec-tion, may be u sed for p rocessing t he system.

    Ident ification of compressor connections can usuallybe accomplished without difficulty; however, occa-sionally some question arises concerning oil coolertub es and process tub es.

    Oil cooler tubes are found only in low temperaturerefrigeration models. These tubes connect to a coilor hairpin bend within the compressor oil sump.This coil or hairpin bend is not open inside thecomp ressor and its only fun ction is to cool the com-pressor sump oil. The oil cooler tubes are most gen-erally connected to a separated tubing circuit in theair cooled condenser.

    Process tubes are installed in compressor housingsduring manufacture as an aid in factory dehydrationand charging.

    Standard discharge tubing arrangements for Tecum-seh hermetic compressors are outlined below. Dis-charge tubes are generally in the same positionwithin any model family. Suction and process tubepositions may vary substantially.

    Figure 5-1. Standard discharge tubing arrangements.

    DischargeTube

    DischargeTube

    DischargeTube

    DischargeTube

    On some AE refrigerationmodels the terminal coverfaces the other way.

    OptionalOil Cooler Tubes

    AERefrigeration

    AW-E AW-F

    AEAir Conditioning

  • 7/31/2019 Tecumseh Refrigerant Piping

    3/24

    A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 87

    Figure 5-1. Standard discharge tubing arrangements - continued.

    AKAir Conditioning

    DischargeTube

    DischargeTube

    DischargeTube

    DischargeTube

    Discharge

    Tube

    DischargeTube

    AJ

    AH

    AVAZ

    AN

    AG

    AB

    RK

  • 7/31/2019 Tecumseh Refrigerant Piping

    4/24

    88 Chapter 5

    II. Refrigerant Line Sizes

    A. R-12 and R-22 Refrigerant Line Sizes forRemote Systems Commercial

    RefrigerationThe recommended suction line sizes are based pri-marily on the velocities necessary for good oilreturn. In most instances, the resulting pressuredrop will be acceptable for suction lines up to 100in length.

    Refer to these installation considerations for goodoil return on comm ercial systems:

    Slope horizontal suction line downwards in thedirection of th e comp ressor at least 1 /2 fall per

    10 feet of line.

    The setting of the refrigerant control device(expansion valve) should maintain a minimum

    of superheat. This is typical of the usual direct

    expansion evaporator s where the oil is return ed

    by refrigerant vapor.

    In the case of a flooded type evaporator (bot-tom feed, top suction h eader, large internal vol-

    ume, low refrigerant/oil velocities), it is

    necessary to maintain a liquid spillover into th e

    suction line so as to return the oil with the liq-

    uid refrigerant and to minimize oil trapping in

    the evaporator. If because of the spillover, the

    return gas is wet at the compressor, a suction

    line accum ulator shou ld be installed adjacent to

    the comp ressor.

    O n systems with evaporato rs below -10F, theoil/refrigerant mixture reaches a maximum vis-

    cosity when the refrigerant superheat is about

    30F on R-22 and R-502 and when about 4 5F

    to 60 F superheat on R -12 systems. O il may

    return sluggishly in such cases because of the

    high viscosity. Two solutions should be consid-

    ered:

    a. Reduce superheat.

    b. Add a liquid to suction gas heat

    exchanger close to the evaporator but

    outside the refrigerated space.

    O n m ultiple evaporator systems, prevent th e oil(and refrigerant) from collecting in an idle coil.If the evaporator coils are to operate indepen-

    dently of each other, each should have its own

    suction riser sized to t he coils capacity.

    Insulate suction lines.

    Tables 5-1 and 5-2 show recommended suction linesizes for installations where that line is horizontal ordown flow. In the event the suction line is up flow,use one stan dard size smaller. EXAM PLE: W here a7/8 diameter tube is recommended on that tablefor horizontal or down flow, the recommended size

    for up flow would be 3/4 diameter.

  • 7/31/2019 Tecumseh Refrigerant Piping

    5/24

    A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 89

    Table 5-1: R-12 Refrigerant Line Sizes for Remote Systems Commercial Refrigeration

    Cond. Unit

    CAPACITY

    (BTU/Hr.)

    SUCTION LINE SIZESAT SYSTEM EVAPORATOR DESIGN TEMPERATURE Liquid Line

    Size-40F -20F 0F +20F +40F

    1200 5/8 1/2 3/8 3/8 3/8 1/4

    2400 3/4 5/8 1/2 1/2 3/8 1/4

    3600 7/8 3/4 5/8 1/2 1/2 1/4

    4800 1 1/8 7/8 5/8 5/8 1/2 1/4

    6000 1 1/8 7/8 3/4 5/8 1/2 1/4

    7200 1 1/8 1 1/8 7/8 3/4 5/8 1/4

    8400 1 3/8 1 1/8 7/8 3/4 5/8 3/8

    9600 1 5/8 1 1/8 7/8 3/4 5/8 3/8

    10800 1 5/8 1 1/8 1 1/8 7/8 5/8 3/8

    12000 1 5/8 1 3/8 1 1/8 7/8 3/4 3/8

    18000 2 1/8 1 5/8 1 1/8 1 1/8 7/8 3/8

    24000 2 5/8 2 1/8 1 3/8 1 1/8 1 1/8 1/2

    36000 3 1/8 2 1/8 1 5/8 1 3/8 1 1/8 1/2

    48000 3 5/8 2 5/8 2 1/8 1 5/8 1 3/8 1/2

    60000 3 5/8 2 5/8 2 5/8 1 5/8 1 3/8 1/2

    72000 4 1/8 3 1/8 2 5/8 2 1/8 1 5/8 1/2

    Table 5-2: R-22 Refrigerant Line Sizes for Remote Systems Commercial Refrigeration

    Cond. UnitCAPACITY(BTU/Hr.)

    SUCTION LINE SIZES

    AT SYSTEM EVAPORATOR DESIGN TEMPERATURE Liquid LineSize-40F -20F 0F +20F +40F

    1200 3/8 3/8 3/8 3/8 1/4

    2400 1/2 1/2 3/8 3/8 1/4

    3600 5/8 1/2 1/2 3/8 1/4

    4800 3/4 5/8 1/2 3/8 1/4

    6000 3/4 5/8 1/2 1/2 1/4

    7200 7/8 3/4 5/8 1/2 1/4

    8400 7/8 3/4 5/8 1/2 1/4

    9600 1 1/8 3/4 5/8 5/8 1/4

    10800 1 1/8 7/8 3/4 5/8 3/8

    12000 1 1/8 7/8 3/4 5/8 3/8

    18000 1 3/8 1 1/8 7/8 3/4 3/8

    24000 1 3/8 1 1/8 1 1/8 7/8 3/8

    36000 1 5/8 1 3/8 1 3/8 1 1/8 1/2

    48000 2 1/8 1 5/8 1 3/8 1 1/8 1/2

    60000 2 1/8 2 1/8 1 5/8 1 3/8 1/2

    72000 2 5/8 2 1/8 1 5/8 1 3/8 1/2

  • 7/31/2019 Tecumseh Refrigerant Piping

    6/24

    90 Chapter 5

    B. R-22 Refrigerant Line Sizes for RemoteSystems Air Conditioning and HeatPumps

    Condensers and evaporators should be designed andcircuited to maintain adequate velocity to prevent

    oil trapping.

    The tube sizes suggested below are for connectinglines of remote systems. The basis for selection is tomaintain adequate velocity which assures oil returnto the compressor, an acceptable pressure drop toassure compressor capacity and minimum tubingcost.

    To assure ad equate oil retu rn, suction line velocitiesshould be minimum of 750 fpm for horizontal ordown flow and 1500 fpm for up flow. Gas velocitiesof 3000 fpm or more will create noise problems andshould be avoided.

    W here a choice of line sizes is possible because of th eoverlap in the compressor capacity table, the largersized lines are suggested to minimize the systempressure d rop.

    Consider th ese installation notes:

    Suction line sizes (up flow) provide adequategas velocities to assure oil return to the com-

    pressor and, therefore, remain constant in size

    regardless of the vertical lift. Suction line trapsare not required. H orizontal suction lines are

    sized larger to reduce pressure drop.

    Suction line lengths in excess of 100 are notrecommended.

    O n h eat pum p systems, the lines serving asboth a discharge line and suction line, should

    be sized as a suction line.

    Liquid line sizes are based on pressure dropsthat will not permit gas formation for horizon-

    tal lengths up to 100.The recommendations shown in Table 5-3 are basedon the use of standard refrigeration grade tubingand do not include considerations for additionalpressure d rop due to elbows, valves, or reduced jointsizes.

    Table 5-3: R-22 Refrigerant Line Sizes for Remote Systems Air Conditioning and Heat Pumps

    SUCTION LINE OUTER DIAMETER

    Nominal Compressor

    Cooling Capacity(BTU/Hr.) Vertical Up

    Flow

    Vertical

    Down Flowor

    Horizontal

    Liquid LineOuter

    Diameter

    Discharge Line Length &

    Outer Diameter

    25 50 1001500 FPM 2500 FPM

    5700 9400 3/8 1/2 1/4 5/16 5/16 3/8

    8000 13000 1/2 1/2 1/4 5/16 3/8 3/8

    11200 18500 1/2 5/8 5/16 3/8 3/8 1/2

    17000 30000 5/8 3/4 5/16 3/8 1/2 1/2

    27000 44000 3/4 7/8 3/8 3/8 1/2 5/8

    38000 51000 7/8 1 1/8 3/8 1/2 5/8 5/8

    38000 67000 7/8 1 1/8 1/2 1/2 5/8 5/8

    60000 102000 1 1/8 1 3/8 1/2 5/8 3/4 3/4

    96000 156000 1 3/8 1 5/8 5/8 3/4 3/4 7/8

    144000 228000 1 5/8 2 1/8 5/8 3/4 7/8 1 1/8

  • 7/31/2019 Tecumseh Refrigerant Piping

    7/24

    A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 91

    C. R-502 and R-134a Refrigerant Line Sizesfor Remote Systems CommercialRefrigeration

    The selection of suction gas line sizes should beguided by th e following criteria:

    Assurance of adequate velocity th us in suringoil return capability. (The tube size must be

    limited to maintain velocities no less than 750

    fpm for horizontal and down flow and no less

    than 1 500 fpm for up flow.)

    Assurance of acceptable pressure drop. (Thetube size should be limited to maintain veloci-

    ties no greater than 1500 fpm for horizontal

    and down flow and no greater than 2500 fpm

    for up flow.

    Assurance of satisfactory sound level. (Thetube size should be limited to maintain veloci-

    ties no greater than 30 00 fpm .)

    Assurance of minimum tubing cost. (Thetube size should be as small as possible while

    satisfying the th ree points men tioned above.)

    Tables 5-4 and 5-5 show recommended suction linesizes for installations where that line is horizontal ordown flow. In the event the suction line is up flow,use one stan dard size smaller. EXAM PLE: W here a7/8 diameter tube is recommended on that tablefor horizontal or down flow, the recommended sizefor up flow would be 3/4 diameter.

    Table 5-4: R-502 Refrigerant Line Sizes for Remote Systems Commercial Refrigeration

    Cond. UnitCAPACITY

    BTU/HR.

    SUCTION LINE SIZES

    AT SYSTEMS EVAPORATOR DESIGN TEMPERATURE Liquid Line

    Size-40F -20F 0F +20F +40F

    1200 1/2 3/8 3/8 3/8 3/8 1/4

    2400 5/8 1/2 1/2 3/8 3/8 1/4

    3600 3/4 5/8 1/2 1/2 3/8 1/4

    4800 7/8 3/4 5/8 1/2 1/2 1/4

    6000 1 1/8 7/8 5/8 5/8 1/2 1/4

    7200 1 1/8 7/8 3/4 5/8 1/2 1/4

    8400 1 1/8 7/8 3/4 5/8 1/2 1/4

    9600 1 1/8 1 1/8 7/8 3/4 5/8 1/4

    10800 1 3/8 1 1/8 7/8 3/4 5/8 3/8

    12000 1 3/8 1 1/8 7/8 3/4 5/8 3/8

    18000 1 5/8 1 3/8 1 1/8 7/8 3/4 3/8

    24000 2 1/8 1 5/8 1 3/8 1 1/8 7/8 3/8

    36000 2 5/8 2 1/8 1 5/8 1 3/8 1 1/8 1/2

    48000 2 5/8 2 1/8 1 5/8 1 3/8 1 1/8 1/2

    60000 3 1/8 2 5/8 2 1/8 1 5/8 1 3/8 1/2

    72000 3 5/8 2 5/8 2 1/8 1 5/8 1 3/8 1/2

  • 7/31/2019 Tecumseh Refrigerant Piping

    8/24

    92 Chapter 5

    Table 5-5: R-134a Refrigerant Line Sizes for Remote Systems Commercial Refrigeration

    Cond. UnitCAPACITY

    (BTU/Hr.)

    SUCTION LINE SIZES

    AT SYSTEMS EVAPORATOR DESIGN TEMPERATURE Liquid Line

    Size-40F -20F 0F +20F +40F

    1200 5/8 1/2 3/8 3/8 3/8 1/4

    2400 3/4 5/8 1/2 1/2 3/8 1/4

    3600 7/8 3/4 5/8 1/2 1/2 1/4

    4800 1 1/8 7/8 3/4 5/8 1/2 1/4

    6000 1 1/8 7/8 3/4 5/8 1/2 1/4

    7200 1 3/8 1 1/8 7/8 3/4 5/8 1/4

    8400 1 3/8 1 1/8 7/8 3/4 5/8 3/8

    9600 1 5/8 1 1/8 7/8 3/4 5/8 3/8

    10800 1 5/8 1 3/8 1 1/8 7/8 3/4 3/8

    12000 1 5/8 1 3/8 1 1/8 7/8 3/4 3/8

    18000 2 1/8 1 5/8 1 3/8 1 1/8 7/8 3/8

    24000 2 5/8 2 1/8 1 3/8 1 3/8 1 1/8 1/2

    36000 3 1/8 2 1/8 2 1/8 1 3/8 1 1/8 1/2

    48000 3 5/8 2 5/8 2 1/8 1 5/8 1 3/8 1/2

    60000 3 5/8 3 1/8 2 5/8 2 1/8 1 5/8 1/2

    72000 4 1/8 3 1/8 2 5/8 2 1/8 1 5/8 1/2

  • 7/31/2019 Tecumseh Refrigerant Piping

    9/24

    A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 93

    III. Refrigerant Line Pressure Drops

    Figure 5-2. Refrigerant line pressure drops for Freon 12 refrigerant (reprinted by permission of DuPontFluorochemicals).

    .

    2

    .

    3

    .

    4

    .

    6

    .

    8

    2 3 4 6 8 1

    0

    2

    0

    3

    0

    4

    0

    6

    0

    8

    0

    1

    00

    2000

    3000

    4000

    6000

    8000

    10

    ,000

    BTU's Per HR

    0.

    2

    0.

    2

    0.

    3

    0.

    4

    0.

    6

    0.

    8 1 2 3 4 5 6 810

    20

    30

    40

    50

    0.

    3

    0.

    4

    0.

    6

    0.

    8 1 2 3 4 5 6 810

    20

    30

    40

    50

    EXAMPLE:

    5.5 Tons at -4 0C Evap. 85F Cond.

    3 1/8" Suction Line Pressure Drop = 0.155 p.s.i./100 ft.3/4" Liquid Line Pressure Drop = 1.0 p.s.i./100 ft.

    At 120F Condenser

    At 100F Condenser

    At 80F Condenser

    61/8

    "

    51/8

    "

    41/8

    "

    35/8

    "

    31/8

    "

    21/8

    "

    15/8

    "

    11/8

    "

    7/8"

    3/4"

    5/8"

    1/2"

    3/8"

    -60

    F

    Eva

    pora

    torT

    empe

    ratu

    re

    -40F

    40F

    Dis

    char

    geL

    ines

    80

    F

    Con

    dens

    er

    100F

    Con

    dens

    er

    120

    FC

    onde

    nser

    Liqu

    idL

    ine

    -20

    F

    20F

    0F

    13/8

    "O.D.TypeLCo

    pper

    Tubing

    25/8

    "

    Tons of Refrigeration

    Pressure Drop In Lbs. Per Sq. In. Per 100 Ft.

    NOTE: Pressure drops do notallow for pulsating flow. Ifflow is pulsating, use nextlarger pipe size. Liquidline determined at 0Fevap. & 80F cond.Discharge lines at 0Fevap. Other conditions donot appreciably changeresult. Vapor evap. outlet

    assumed to be at 65F.

  • 7/31/2019 Tecumseh Refrigerant Piping

    10/24

    94 Chapter 5

    Figure 5-3. Refrigerant line pressure drops for Freon 22 refrigerant (reprinted by permission of DuPont

    Fluorochemicals).

    0.

    2

    0.

    3

    0.

    4

    0.

    6

    0.

    8

    1 2 3 4 6 8 10

    20

    30

    40

    60

    80

    100

    2000

    3000

    4000

    6000

    8000

    10

    ,000

    BTU's Per HR

    0.

    2

    0.2 0.3 0.4 0.6 0.8 1 2 3 4 5 8 10 20 30 40 506

    0.

    3

    0.

    4

    0.

    6

    0.

    8 1 2 3 4 5 6 810

    20

    30

    40

    50

    At 80F Condenser

    At 100F Condenser

    At 120F Condenser

    61/8

    "

    51/8

    "

    41/8

    "

    35/8

    "

    25/8"

    15/8

    "

    11/8

    "

    7/8"

    3/4"

    5/8"

    1/2"

    3/8"

    -60FE

    vaporator

    Temperature

    -40F

    13/8

    "O.D.TypeL

    Copper

    Tubing

    31/8

    "

    21/8

    "

    Tons of Refrigeration

    Pressure Drop In Lbs. Per Sq. In. Per 100 Ft.

    EXAMPLE:

    5.5 Tons at -40F Evap. 85F Cond.

    2 5/8" Suction Line Pressure Drop = 0.18 p.s.i./100 ft.

    5/8" Liquid Line Pressure Drop = 1.7 p.s.i./100ft.

    -20F

    20F

    40F

    Dischargelin

    es80F

    Condenser

    100F

    Condenser

    120FC

    ondenser

    Liquid

    Line

    0F

    NOTE: Pressure drops do not allowfor pulsating flow. If flow ispulsating, use next largerpipe size. Liquid linedetermined at 0F evap. &80F cond. Discharge linesat 0F evap. Otherconditions do not

    appreciably change result.Vapor evap. outlet assumedto be at 65F.

  • 7/31/2019 Tecumseh Refrigerant Piping

    11/24

    A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 95

    Figure 5-4. Refrigerant line pressure drops for Freon 502 refrigerant (reprinted by permission of DuPont

    0.2

    0.3

    0.4

    0.6

    0.8

    1 2 3 4 6 8 10

    20

    30

    40

    60

    80

    100

    200

    0

    300

    0

    400

    0

    600

    0

    800

    0

    10,00

    0

    BTU's Per HR

    0.2

    0.2

    0.3

    0.4

    0.6

    0.8 1 2 3 4 6 81

    020

    30

    40

    50

    2 3 4 5 6 810 20 30 40500.3 0.4 0.6 0.8 1

    At 80F CondenserAt 100F Condenser

    At 120F Condenser

    71/8

    "

    61/8

    "

    51/8

    "

    41/8

    "

    35/8

    "

    31/8

    "

    25/8

    "

    21/8

    "

    15/8

    "

    13/8

    "

    11/8

    "

    7/8"

    3/4"

    1/2"

    3/8"

    5/8"O

    .D.TypeL

    Copp

    erTubin

    g

    -60

    FEva

    pora

    torT

    empe

    ratu

    re

    -40

    F

    Tons of Refrigeration

    Pressure Drop In Lbs. Per Sq. In. Per 100 Ft.

    EXAMPLE:

    5.5 Tons at -40F Evap. 85F Cond.

    Choose 2 5/8" Suction Line Pressure Drop = 0.3

    Choose 3/4" Liquid Line Pressure Drop = 1.7

    -20

    F

    20F

    40F

    Disch

    arge

    Lin

    e

    Liqu

    idL

    ine0

    F

    NOTE: Pressure drops do not allow forpulsating flow. If flow is pulsating,

    use next larger pipe size.

  • 7/31/2019 Tecumseh Refrigerant Piping

    12/24

    96 Chapter 5

    Figure 5-5. Refrigerant line pressure drops for HP62 (404A) refrigerant (reprinted by permission of DuPont

    Fluorochemeicals).

    0.1

    0.2

    0.3

    0.4

    0.6

    0.8

    1 2 3 4 6 8 10

    20

    30

    40

    60

    80

    100

    200

    300

    400

    600

    800

    1000

    0.0

    10.4

    0.6

    0.8 1 2 3 4 6 81

    0

    0.0

    80.1

    0.2

    0.3

    0.0

    2

    0.0

    2

    0.0

    3

    0.0

    4

    0.0

    6

    0.0

    80.1

    0.2

    0.3

    0.4

    0.6

    0.8 1 2 3 4 6 81

    0

    0.0

    3

    0.0

    4

    0.0

    6

    At 30C Condenser

    At 40C Condenser

    At 50C Condenser

    61/8

    "O.D.TypeLCo

    pper

    Tub

    ing

    51/8

    "

    41/8

    "

    35/8

    "

    31/8

    "

    25/8

    "

    21/8"

    15/8

    "

    13/8

    "

    11/8

    "

    7/8"

    3/4"

    5/8"

    1/2"

    3/8"

    -50C

    Evaporato

    rTe

    mpe

    ratu

    res

    -40C

    -20C

    0C

    -30C

    -10C

    10C

    Dis

    charge

    Lin

    es

    Lines

    Lin

    es

    Pressure Drop In Kpai Per Meter

    Tons of Refrigeration

    EXAMPLE:

    15 kW at -40C Evap., 40C Cond.

    2 1/8" Suction Line Pressure Drop = 0.11kPa/m5/8" Liquid Line Pressure Drop = 0.47 kPa/m

    NOTE: Pressure drops do notallow for pulsating flow.If flow is pulsating, usenext larger pipe size.Liquid line and discharge

    lines determined at -20Cevap. and 30C cond.Other conditions do notappreciably changeresult. Vapor at evap.

    outlet assumed to be at 20C.

  • 7/31/2019 Tecumseh Refrigerant Piping

    13/24

    A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 97

    Figure 5-6. Refrigerant line pressure drops for HFC-134a refrigerant (reprinted by permission of DuPontFluorochemicals).

    0.2

    0.3

    0.4

    0.5

    0.60.8 1 2 3 4 6 81

    020

    30

    40

    0.1

    0.2

    0.4

    0.6

    1 2 4 6 10

    20

    30

    40

    60

    100

    0.1

    0.2

    0.3

    0.4

    0.6

    0.8 1 2 3 6 81

    020

    30

    40

    60

    80

    100

    At 80F CondenserAt 100F Condenser

    At 120F Condenser

    61/8

    "O.D.TypeL

    Copp

    erTu

    bing

    -60F

    EvaporatorTe

    mperatu

    re

    -40F

    -20F

    20F

    40F

    Dis

    charg

    eL

    ines

    Liquid

    Lin

    es

    0F

    51/8

    "

    41/8

    "

    35/8

    "

    31/8

    "

    25/8

    "

    21/8

    "

    15/8

    "

    13/8

    "

    11/8

    "

    7/8"

    3/4"

    5/8"

    1/2"

    3/8"

    Pressure Drop In Psi Per 100 Ft.

    Tons of Refrigeration

    EXAMPLE:

    25 Tons at -40F Evap. and 100F Cond.

    2 5/8" Suction Line

    Pressure Drop = 5.5 p.s.i./100 ft.

    1 1/8" Liquid Line

    Pressure Drop = 1.6 p.s.i./100 ft.

    NOTE: Pressure drops do notallow for pulsating flow.If flow is pulsating, usenext larger pipe size.Liquid line and discharge

    lines determined at 0Fevap. and 80F cond.Other conditions do notappreciably changeresult. Vapor at evap.

    outlet assumed to be at 65F.

  • 7/31/2019 Tecumseh Refrigerant Piping

    14/24

    98 Chapter 5

    IV. Refrigerant Line Velocities

    Figure 5-7. Refrigerant line velocities for Freon 12 refrigerant (reprinted by permission of DuPont

    Fluorochemicals).

    0.

    1

    0.

    2

    2000

    3000

    4000

    6000

    8000

    10

    ,000

    BTU's Per HR

    0.

    4

    0.

    6

    1 2 4 6 10

    20

    40

    60

    100

    15

    20

    30

    40

    50

    60

    70

    80

    100

    150

    200

    300

    400

    500

    600

    1000

    1500

    2000

    3000

    4000

    5000

    6000

    7000

    8000

    10

    ,000

    800

    700

    15

    20

    30

    40

    50

    60

    70

    80

    100

    150

    200

    300

    400

    500

    600

    1000

    1500

    2000

    3000

    4000

    5000

    6000

    7000

    8000

    10

    ,000

    800

    700

    At 80F Condenser

    EXAMPLE:

    5.5 Tons at -4 0F Evap. 85F Cond.

    3 1/8" Suction Line Velocity = 1916 ft./min.3/4" Liquid Line Velocity = 94 ft./min.

    At 100F Condenser

    At 120F Condenser

    61/8

    "

    -60FEvap

    orator

    Temperature

    -40F

    -20F

    0F

    20F

    40F

    80F

    Condenser

    51/8

    "

    41/8

    "

    35/8

    "

    13/8

    "

    3/4"

    5/8"

    31/8

    "

    25/8

    "

    21/8

    "

    15/8

    "

    11/8

    "

    7/8"

    O.D.TypeLCo

    pper

    Tubing

    1/2"

    3/8"

    Tons of Refrigeration

    Velocity In Feet/Minute

    100F

    Condenser

    LiquidLine

    Discha

    rgeLines12

    0F

    Conden

    ser

    NOTE: Liquid line determined at0F evap. and 80F cond.Discharge lines at 0Fevap. Net refrigeration for"Freon" 12 includessuction gas at 65F.

  • 7/31/2019 Tecumseh Refrigerant Piping

    15/24

    A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 99

    Figure 5-8. Refrigerant line velocities for Freon 22 refrigerant (reprinted by permission of DuPont Fluorochemicals).

    0.

    1

    0.

    2

    0.

    4

    0.

    6

    1 2 4 6 10

    20

    40

    60

    100

    200

    0

    300

    0

    400

    0

    600

    0

    800

    0

    10

    ,00

    0

    BTU's Per HR

    15

    15

    20

    30

    40

    60

    80

    100

    150

    200

    300

    400

    600

    800

    1000

    1500

    2000

    3000

    4000

    6000

    8000

    10

    ,000

    20

    30

    40

    60

    80

    100

    150

    200

    300

    400

    600

    800

    1000

    1500

    2000

    3000

    4000

    6000

    8000

    10

    ,000

    At 80F CondenserAt 100F Condenser

    At 120F Condenser

    51/8

    "

    41/8

    "

    -60FEv

    aporatorTe

    mperatu

    re

    Discha

    rgelin

    es80F

    Cond

    enser

    -40F

    -20F

    20F

    40F

    Liquid

    Line

    100F

    Cond

    enser

    120F

    Conden

    ser

    0F

    35/8

    "

    31/8

    "

    25/8

    "

    21/8

    "

    15/8

    "

    13/8

    "

    11/8

    "

    7/8"O

    .D.TypeLCo

    pper

    Tubing

    5/8"

    1/2"

    3/8"

    3/4"

    Tons of Refrigeration

    Velocity, Feet/M inute

    EXAMPLE:

    5.5 Tons at -40F Evap. 85F Cond.

    2 5/8" Suction Line Velocity = 1718 ft./min.5/8" Liquid Line Velocity = 114 ft./min.

    NOTE: Liquid line determinedat 0F evap. and 80Fcond. Discharge linesat 0F evap. Netrefrigeration for "Freon"22 includes suction gasat 65F.

  • 7/31/2019 Tecumseh Refrigerant Piping

    16/24

    100 Chapter 5

    Figure 5-9. Refrigerant line velocities for Freon 502 refrigerant (reprinted by permission of DuPont

    Fluorochemicals).

    0.1

    0.2

    0.4

    0.6

    1 2 4 6 10

    20

    40

    60

    100

    2000

    3000

    4000

    6000

    8000

    10,0

    00

    BTU's Per HR

    15

    20

    30

    40

    50

    60

    80

    100

    150

    200

    300

    400

    500

    600

    800

    1000

    1500

    2000

    3000

    4000

    5000

    6000

    8000

    10,0

    00

    15

    20

    30

    40

    50

    60

    80

    100

    150

    200

    300

    400

    500

    600

    800

    1000

    1500

    2000

    3000

    4000

    5000

    6000

    8000

    10,0

    00

    At 80F CondenserAt 100F Condenser

    At 120F Condenser

    61/8

    "

    15/8

    "

    13/8

    "

    11/8

    "

    7/8"

    3/4"

    5/8"

    1/2"

    3/8"

    51/8

    "

    41/8

    "

    35/8

    "

    31/8

    "

    25/8

    "

    21/8

    "

    -60FEv

    aporator

    Temperature

    -40F

    -20F

    0F

    20F

    40F

    Discha

    rgeLines80

    FConde

    nser

    100F

    Conden

    ser

    120F

    Cond

    enser

    Liquid

    Line

    Tons of Refrigeration

    Velocity, Feet/Minute

    EXAMPLE:

    5.5 Tons at -40F Evap. 85F Cond.

    2 5/8" Suction Line Velocity = 1555 ft./min.3/4" Liquid Line Velocity = 105 ft./min.

    NOTE: Liquid line determined

    at 0F evap. and 80Fcond. Discharge linesat 0F evap. Netrefrigeration for "Freon"502 includes suction gas

    at 65F.

  • 7/31/2019 Tecumseh Refrigerant Piping

    17/24

    A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 101

    Figure 5-10. Refrigerant line velocities for HP62 (404A) refrigerant (reprinted by permission of DuPont

    Fluorochemicals).

    0.

    1

    0.

    2

    0.

    3

    0.

    4

    0.

    6

    0.

    8

    1 2 3 4 6 8 10

    20

    30

    40

    60

    80

    100

    200

    300

    400

    600

    800

    100

    0.

    1

    0.

    2

    0.

    3

    0.

    4

    0.

    6

    0.

    8 1 2 3 4 6 810

    20

    30

    40

    60

    80

    100

    0.

    2

    0.

    3

    0.

    4

    0.

    6

    0.

    8 1 2 3 4 6 810

    20

    30

    40

    60

    80

    100

    At 30C Condenser

    At 40C Condenser

    At 50C Condenser

    61

    /8"O

    .D.Typ

    eLC

    opperTu

    bing

    51

    /8"

    41

    /8"

    35

    /8"

    31

    /8"

    25

    /8"

    7/8"

    3/4"

    5/8"

    3/8"1/

    2"

    21

    /8"

    15

    /8"

    11

    /8"

    13

    /8"

    -50C

    EvaporatorTe

    mperatu

    res

    -40C

    -30

    C

    -20C

    0C-1

    0C

    10C

    Dis

    charg

    eL

    ines

    Liquid

    Lin

    es

    Velocity In M/S

    Kilowatts of Refrigeration

    EXAMPLE:

    55 kW at -40C Evap., 40C Cond.

    2 1/8" Suction Line Velocity = 38 m/s1 3/8" Liquid Line Velocity = 0.55 m/s

    NOTE: Liquid line and discharge lines determined at -20C evap.and 30C cond. Other conditions do not appreciably changeresult. Net refrigeration for HP-62 includes suction gas at 20 C.

  • 7/31/2019 Tecumseh Refrigerant Piping

    18/24

    102 Chapter 5

    Figure 5-11. Refrigerant line velocities for HFC-134a refrigerant (reprinted by permission of DuPont Fluorochemicals).

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    1 2 3 4 6 8 10

    20

    30

    40

    60

    80

    100

    200

    300

    400

    600

    800

    1000

    0.2

    0.1

    0.2

    0.3

    0.4

    0.6

    0.8 1 2 3 4 6 81

    020

    30

    40

    60

    80

    100

    0.3

    0.4

    0.6

    0.8 1 2 3 4 6 81

    020

    30

    40

    60

    80

    100

    At 30C Condenser

    EXAMPLE:

    45 kW at -30C Evap., 40C Cond.

    3 1/8" Suction Line Velocity = 18 m/s1 3/8" Liquid Line Velocity = 0.37 m/s

    NOTE: Liquid line determined at -20C evap. and 30C cond.

    Discharge lines at -20C evap. Other conditions do not

    appreciably change result. Net refrigeration forHFC-134a includes suction gas at 20C.

    At 40C Condenser

    At 50C Condenser

    61/

    8"O

    .D.Typ

    eLCoppe

    rTu

    bin

    g

    51/

    8"

    41/

    8"

    31/

    8"

    21/

    8"3

    5/8"

    25/

    8"

    15/

    8"

    13/

    8"

    11/

    8"

    7/8"

    3/4"

    5/8"

    1/2"

    3/8"

    -50C

    EvaporatorTe

    mperatu

    res

    -40C

    -30C

    -20

    C

    -10C

    0C

    10C

    -40

    C

    Condenser

    -50

    C

    Condenser

    Liq

    uid

    Line

    s

    Dis

    charg

    eLin

    es-

    30C

    Cond

    ens

    er

    Kilowatts of Refrigeration

    Velocity In M/S

  • 7/31/2019 Tecumseh Refrigerant Piping

    19/24

    A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 103

    V. Service Valves

    As shipped with the compressors, the rotolock ser-vice valves have a small plastic dust plug inside thethreaded end. Be sure to remove this plug before

    installing.Service valves on Tecumseh systems are frontseated by turning the valve stem clockwise. Thiscloses the valve and opens the gauge por t.

    Turning the stem counter-clockwise back seats thevalve and t hu s opens th e system and closes the gaugeport.

    If present, t he valve port t o th e system cont rol (highpressure cutout, low pressure control, fan controletc.) is always open regardless of the position of thevalve stem.

    If it is desired to operate th e system with the servicegauge operating, it is necessary to crack the valvefrom its back seated position for the gauges to per-form. Before removing the gauges, close the gaugeport by return ing th e valves to t heir fully open posi-tion (back seated).

    Remember to check the packing gland nut (ifpresent ) on the stem for snugness before leaving t he

    job . Install t he cover n ut over th e valve stem as a sec-ond ary safeguard against leaks at th e stem.

    VI. Processing the System

    The performance and longevity of a refrigerationsystem is stron gly influen ced by h ow th e system wasprocessed, that is, how the system was prepared foroperation at the time of installation. The procedureis:

    1. O n split systems, install the liquid and suction

    line. See Refrigerant Line Sizes on pages 88-

    92 for recommended line sizes. A properly

    sized suction line accumulator is recom-

    mended . See Accum ulator Selection D ata onpage 118 for accumulator sizing. Insulate the

    suction line to reduce heat exchange and

    excessive return gas temperatures to the com-

    pressor.

    2. To prevent oxidation and scale forming inside

    the tubes, it is good practice to flow dry nitro-

    gen through the tubing during the soldering

    operations. A light flow of abou t 1/ 4 cub ic feet

    per minu te is sufficient.

    3. Install a filter in th e liquid line imm ediately

    ahead of th e capillary tube or expansion valve.

    A liquid line drier should also be installed.

    4. A suction line filter/drier is recomm ended to

    prot ect the comp ressor. A suction accumu lator

    must be installed on those systems having

    defrost cycles (heat pumps, low temperature

    refrigeration) or the likelihood of periodic

    floodbacks (bulk milk coolers, ice machines).

    See Accum ulator Selection D ata on page 118

    for accumu lator sizing.

    5. Pressure test the system for leaks using the

    safety precautions outlined in System Flush-

    ing, Purging, and Pressure Testing for Leaks

    on pages 4-5. D o not p ressurize the system

    beyond 150 PSIG fi eld leak test pr essure.

    6. Use a vacuum pum p (not a compressor) to

    draw a vacuum of 1000 microns or less from

    both sides of the system. It is a waste of time to

    attempt to draw a vacuum on a system with

    the pump connected only to the low side.

    Entry must be made directly into the high

    pressure side to properly evacuate that p ort ion

    of the system. Use a good electronic gauge to

    measure the vacuum. An accurate reading can-

    not be made with a refrigeration gauge.

    Remember 29 of mercury as read on a com-

    pound gauge equals 23,368 microns of vac-

    uum.

    WARNING! Never use a compressor to

    evacuate a system. Instead, use a high vac-

    uum pump specifically designed for that pur-

    pose.

    Never start the compressor while it is under

    deep vacuum. Always break a vacuum with

    refrigerant charge before energizing the

    compressor.

    Failure to follow these instructions can dam-

    age the hermetic terminal and may result in

    terminal venting. As always, to reduce the

    risk of serious injury or death from fire due

    to terminal venting, never energize the com-

    pressor unless the protective terminal cover

    is securely fastened.

  • 7/31/2019 Tecumseh Refrigerant Piping

    20/24

    104 Chapter 5

    7. If a suction line accum ulator is present, charge

    into the accumulator to prevent liquid refrig-

    erant from reaching the compressor. If this is

    not possible, then break the vacuum by allow-

    ing refrigerant vapor to enter the low side at

    the suction service valve. When the system

    pressure reaches 60 psig for R-22 (70 psig for

    R-502, 35 psig for R-12), start the compressor

    and cont inue charging at rate not m ore than 5

    pounds per minutes for the larger systems and

    somewhat less for smaller systems. Follow the

    safety precautions outlined in System Charg-

    ing on p ages 5-6.

    8. Ch eck fans and blowers for correct direction

    of rotation, belt tension, and proper air flow

    (CFM).

    9. With th e protective terminal cover securely

    fastened, run the compressor and allow the

    system pressures and temperatures to stabilize.

    Systems vary in their operating characteristics

    bu t generally these approximations will apply:

    10. Before leaving the job ru n the system for

    awhile. Listen for abnormal noises. Feel the

    bottom crankcase housing and d etermine th at

    it is warm. Is the compressor upper housing

    sweating indicating that liquid refrigerant is

    reaching the compressor? Is the return gas

    temperature at the compressor 65F or less

    and not more than 80F? Recheck pressures,

    amps, fan motors, belts, CFM, etc.

    VII. System Cleanup and

    Compressor Replacement

    After Compressor Failure

    Once you determine that a compressor needs to be

    replaced you must then determine whether the sys-tem has been contaminated. C omp ressor m otor fail-ure can lead to such contamination. (Whilecomp ressor motor failure is sometimes referred to asmotor burnout, it does not mean that a fire actu-ally occurs inside a hermetic compressor.) Evensmall amounts of contamination must be removedfrom the system to avoid damaging the replacementcompressor. Therefore, it is important to thoroughlyclean a refrigeration/air conditioning system if sys-tem con tamination is present.

    If a compressor motor failure has occurred,refrigerant or mixtures of refrigerant and oil inthe system can be acidic and cause chemicalburns. As always, to avoid injury, wear appro-priate protective eyewear, gloves and clothingwhen servicing an air conditioning or refrigera-tion system. If refrigerant or mixtures of refrig-erant and oil come in contact with skin or eyes,flush the exposed area with water and get medi-cal attention immediately.

    The following outlines a process for compressorreplacement and system clean-up for a systemequipp ed with a Tecum seh comp ressor. You shouldrefer to the original equipment manufacturers(O EM ) service information.

    A. Determine Extent of SystemContamination

    Following the precautions in Refrigerants andOther Chemicals and Compressor Removal onpage 4, remove the compressor.

    Use the following guidelines to determine whethercontamination, if any, is limited to the compressoror extends to t he system.

    If the discharge line shows no evidence of contami-nation and t he suction stub is clean or has only lightcarbon deposits, then the contaminants are limitedto th e compressor hou sing (Com pressor H ousing

    Table 5-6: Pressure and TemperatureStabilization

    Pressure Temperature

    Saturated Head

    Pressure

    Ambient temperature F + 25F for

    air cooled condenser.

    Water cooled Discharge water F + 10F

    Saturated evaporator pressure

    Air Conditioning Discharge air F - 20F

    Medium

    TemperatureProduct temperature -10F to -12F

    Low Temperature Product temperature -6to -8F

    ! WARNING

  • 7/31/2019 Tecumseh Refrigerant Piping

    21/24

    A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 105

    Contamination). A single installation of liquid and

    suction line filter-driers shou ld cleanup t he system.

    If, however, the discharge line or the suction line

    shows evidence of contamination, the compressor

    was running at the time of the motor failure and

    contaminants were pumped throughout the system

    (System Con tamination). If System Con tamination

    has occurred, several changes of the liquid and suc-

    tion line filter-driers will be needed to cleanup the

    system. In addition, the expansion device will need

    to be replaced. If the system is a heat pump, t he four

    way valve should be replaced.

    B. Install Replacement Compressor and

    Components1. Install the replacement compressor with new

    external electrical components (capacitors,

    relay, overload, etc., where applicable). Check

    the contacts of the starting control or contac-

    tor.

    2. Install an oversized liquid line filter-drier.

    3. Install a generously sized suction line filter-

    drier imm ediately upstream of th e compr essor.

    The drier when permanently installed in aclean system, or as initially installed in a dirty

    system, must have a pressure drop not more

    than that of Table 5-3. Pressure taps must be

    supplied imm ediately before and after the suc-

    tion filter-drier to permit the pressure drop to

    be measured.

    If a suction line accumulator is present and

    System Contamination has occurred, it must

    be thoroughly flushed to remove any trapped

    sludge and thus prevent it from plugging the

    oil return hole. The filter-drier should be

    installed upstream of the accumulator and the

    compressor.

    In the case of Compressor Housing Contami-

    nation, the filter-drier should be installed

    between the compressor and the suction line

    accumulator.

    Rubber refrigeration hoses are not satisfactory

    for temporarily hooking up th e suction line fil-

    ter-drier to the system since the acid quickly

    breaks down the rubber and plastic.

    4. Follow the precautions in System Flushing,

    Purging, and Pressure Testing for Leaks on

    pages 4-5, to purge the system and pressure

    test for leaks.

    C. Evacuate the System

    Evacuate the system to less than 1000 microns,

    using a good vacuum pum p (not a compressor) and

    an accurate high vacuum gauge. O perate the pu mp

    at 10 00 microns, or less, for several hou rs to be sure

    the vacuum is maintained.

    An alternate method of removing moisture and non -

    cond ensables from the system is:

    1. Evacuate the system to 29 inches vacuum.

    Break vacuum with refrigerant to be used for

    final charging of system and vapor charge to

    35-50 pounds gauge pressure. Leave vapor

    charge in system for a minimum of five min-

    utes. Reduce pressure to 0 gauge p ressure.

    2 . Repeat step 1.

    3. Evacuate system to 29 inches vacuum. Ch arge

    system with the specified kind and quantity of

    refrigerant.

    WARNING! Never use a compressor to evacuate

    a system. Instead, use a high vacuum pump specif-

    ically designed for that purpose.

    Never start the compressor while it is under deep

    vacuum. Always break a vacuum with refrigerantcharge before energizing the compressor.

    Failure to follow these instructions can damage

    the hermetic terminal and may result in terminal

    venting. As always, to reduce the risk of serious

    injury or death from fire due to terminal venting,

    never energize the compressor unless the protec-

    tive terminal cover is securely fastened.

  • 7/31/2019 Tecumseh Refrigerant Piping

    22/24

    106 Chapter 5

    D. Charge the System and Check thePressure Drop

    Charge the system and place in operation. Followthe safety precautions outlined in System Charg-ing on pages 5-6. Immediately after startup, checkthe pressure drop across the suction line filter-drier.This will serve two purposes:

    Verify that the drier selection was correct; thatis, large enough.

    Serve as a base point to wh ich subsequent pr es-sure checks can be compared.

    Because the permissible pressure drop across thedrier is relatively small, it is suggested that a differ-ential pressure gauge be used for the measuremen t.

    E. Measure the Pressure Drop

    After the system has been operating for an hour orso, measure th e pressure d rop across the suction linefilter-drier.

    In th e case of Com pressor Hou sing Con tamination,little change should be noted. The pressure dropwill, in m ost instances, be below t hat t olerable for apermanent installation (see Table 5-3).

    On the other hand, where System Contaminationoccurred, an increased pressure drop will be mea-sured. Change the suction filter-drier an d the liquidline filter-drier whenever the pressure dropapproaches or exceeds that allowed for temporaryoperation during cleanup (see Table 5-4).

    Keep changing both the suction and liquid line fil-ter-driers until th e pressure d rop stabilizes at a figureequal to or below that permitted for permanentoperation in a system (see Table 5-3). At t his point ,it is the service persons option as to whether to leavethe suction drier in the system or remove it from

    operation.

    If the system is to be opened to permit the perma-nent removal of the suction filter-drier then the liq-uid line filter-drier should be changed once more.

    Table 5-3: Suggested Maximum Pressure Drop (PSI) for Permanent Suction Filter-Drier Installation

    Application Air Cond. High Medium Low Low

    Evaporator Range, F +55 to +32 +55 to +20 +30 to -10 +10 to -20 -20 to -40

    R-12 2 2 1 1/2 1/2 1/2

    R-22 3 3 2 1 1/2

    R-502 3 3 2 1 1/2

    Table 5-4: Suggested Maximum Pressure Drop (PSI) for Temporary Suction Filter-Drier InstallationDuring Cleanup

    Application Air Cond. High Medium Low Low

    Evaporator Range, F +55 to +32 +55 to +20 +30 to -10 +10 to -20 -20 to -40

    R-12 9 9 6 2 3/4

    R-22 15 15 9 3 1 1/2

    R-502 15 15 9 3 1 1/2

  • 7/31/2019 Tecumseh Refrigerant Piping

    23/24

    A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 107

    F. Test for Acidity If Multiple Motor FailuresHave Occurred

    If the system has suffered m ultiple motor failures, itis advisable that the oil of the replacement be testedafter Section E and judged acid free before the sys-tem is considered satisfactorily cleaned. An oil sam-ple may be taken from a hermetic system if at thetime the replacement com pressor was installed an oiltrap is installed in th e suction line (see Figure 5-12).W hen the trapped oil level appears in the sight glass(less than an ounce is needed) the oil may be slowlytransferred to the b eaker of th e acid t est kit as avail-able from several manufacturers. A reading of lessthan 0.05 acid nu mb er is an ind ication that the sys-

    tem is free of acid. A reading of higher than 0.05means continued cleaning is required. Return to B2on page 105.

    G. Monitor the System

    The above procedure for the cleanup of hermeticsystems after motor failure through the use of suc-tion line filter-drier will prove satisfactory in mostinstancesprov id ed the system is monitored and keptclean by repeated drier changes, if such are needed.T he failure to follow th ese minimum cleanup recom-mendations will result in an excessive risk of repeatmotor failure.

    Figure 5-12. Method of obtaining oil sample on hermetic system. After satisfactory oil test,Schrader valve may be capped and the oil sampler taken to next job.

    Schrader Valve Vertically Downward

    Female Schrader Valve Connection

    1/2" Liquid Sight Glass

    1/2" Shut Off Valve

    2"

    Minimum

    At Least 6 Diameters

    Suction Line

  • 7/31/2019 Tecumseh Refrigerant Piping

    24/24

    VIII. Replacing Compressors in

    Water-Utilizing Systems:

    Preventing Explosions

    In certain water-utilizing refrigeration systems,water can leak into the refrigerant side of th e system.This can lead to an explosion of system compo-nents, including b ut not limited to, the comp ressor.If such an explosion occurs, the resulting blast cankill or seriously injure anyone in the vicinity.

    Water-utilizing systems that have single-wall heatexchangers may present a risk of explosion. Suchsystems may include:

    water source heat pump/air conditioning sys-tems, and

    water cooling systems, such as icemakers, watercoolers, and juice dispensers.

    Water-utilizing systems that have single-wall heatexchangers present a risk of explosion unless theyhave either:

    a high pressure cut-out which interrupts powerto ALL leads to the com pressor or

    an external p ressure relief valve.

    Before replacing a compressor in a water-utilizingsystem, read and follow Prevention of Water-Utiliz-ing System Explosions on pages 6-7.