tecumseh refrigerant piping
TRANSCRIPT
-
7/31/2019 Tecumseh Refrigerant Piping
1/24
A LOOK AT SERVICE SAFETY
Installation and Replacement Information 85
5
INSTALLATION ANDREPLACEMENT
INFORMATIONI. Compressor Tube Connections . . . . . . . .86
II. Refrigerant Line Sizes . . . . . . . . . . . . . . .88
III. Refrigerant Line Pressure Drops . . . . . . .93
IV. Refrigerant Line Velocities . . . . . . . . . . . .98
V. Service Valves . . . . . . . . . . . . . . . . . . . .103
VI. Processing the System . . . . . . . . . . . . .103
VII. System Cleanup and Compressor
Replacement After Compressor
Failure. . . . . . . . . . . . . . . . . . . . . . . . . . .104
VIII. Replacing Compressors in Water-Utilizing Systems: Preventing
Explosions. . . . . . . . . . . . . . . . . . . . . . . .108
For more free Tecumseh literature please visit
www.HVACRinfo.com
http://www.hvacrinfo.com/http://www.hvacrinfo.com/ -
7/31/2019 Tecumseh Refrigerant Piping
2/24
86 Chapter 5
I. Compressor Tube
Connections
Tecumseh Products Company supplies compressorsto hundreds of manufacturers requiring different
tubing sizes and arrangements. Because of this thesame compressor model may be foun d in th e field inmany suction and discharge tube variations, eachdepending upon the specific application in which itis installed.
Suction connections can usually be identified as thelargest diameter stub tube in the housing. If 2 stubshave the same outer diameter (OD), then the onewith th e heavier wall will be the suction conn ection.If both of the largest stub t ubes are the same O Dand wall thickness, then either can be used as thesuction connection. Whenever possible, suction
connections should be kept away from the hermeticterminal area so that condensation will not drip onherm etic terminals, causing corrosion.
The stub tube, not chosen for the suction connec-tion, may be u sed for p rocessing t he system.
Ident ification of compressor connections can usuallybe accomplished without difficulty; however, occa-sionally some question arises concerning oil coolertub es and process tub es.
Oil cooler tubes are found only in low temperaturerefrigeration models. These tubes connect to a coilor hairpin bend within the compressor oil sump.This coil or hairpin bend is not open inside thecomp ressor and its only fun ction is to cool the com-pressor sump oil. The oil cooler tubes are most gen-erally connected to a separated tubing circuit in theair cooled condenser.
Process tubes are installed in compressor housingsduring manufacture as an aid in factory dehydrationand charging.
Standard discharge tubing arrangements for Tecum-seh hermetic compressors are outlined below. Dis-charge tubes are generally in the same positionwithin any model family. Suction and process tubepositions may vary substantially.
Figure 5-1. Standard discharge tubing arrangements.
DischargeTube
DischargeTube
DischargeTube
DischargeTube
On some AE refrigerationmodels the terminal coverfaces the other way.
OptionalOil Cooler Tubes
AERefrigeration
AW-E AW-F
AEAir Conditioning
-
7/31/2019 Tecumseh Refrigerant Piping
3/24
A LOOK AT SERVICE SAFETY
Installation and Replacement Information 87
Figure 5-1. Standard discharge tubing arrangements - continued.
AKAir Conditioning
DischargeTube
DischargeTube
DischargeTube
DischargeTube
Discharge
Tube
DischargeTube
AJ
AH
AVAZ
AN
AG
AB
RK
-
7/31/2019 Tecumseh Refrigerant Piping
4/24
88 Chapter 5
II. Refrigerant Line Sizes
A. R-12 and R-22 Refrigerant Line Sizes forRemote Systems Commercial
RefrigerationThe recommended suction line sizes are based pri-marily on the velocities necessary for good oilreturn. In most instances, the resulting pressuredrop will be acceptable for suction lines up to 100in length.
Refer to these installation considerations for goodoil return on comm ercial systems:
Slope horizontal suction line downwards in thedirection of th e comp ressor at least 1 /2 fall per
10 feet of line.
The setting of the refrigerant control device(expansion valve) should maintain a minimum
of superheat. This is typical of the usual direct
expansion evaporator s where the oil is return ed
by refrigerant vapor.
In the case of a flooded type evaporator (bot-tom feed, top suction h eader, large internal vol-
ume, low refrigerant/oil velocities), it is
necessary to maintain a liquid spillover into th e
suction line so as to return the oil with the liq-
uid refrigerant and to minimize oil trapping in
the evaporator. If because of the spillover, the
return gas is wet at the compressor, a suction
line accum ulator shou ld be installed adjacent to
the comp ressor.
O n systems with evaporato rs below -10F, theoil/refrigerant mixture reaches a maximum vis-
cosity when the refrigerant superheat is about
30F on R-22 and R-502 and when about 4 5F
to 60 F superheat on R -12 systems. O il may
return sluggishly in such cases because of the
high viscosity. Two solutions should be consid-
ered:
a. Reduce superheat.
b. Add a liquid to suction gas heat
exchanger close to the evaporator but
outside the refrigerated space.
O n m ultiple evaporator systems, prevent th e oil(and refrigerant) from collecting in an idle coil.If the evaporator coils are to operate indepen-
dently of each other, each should have its own
suction riser sized to t he coils capacity.
Insulate suction lines.
Tables 5-1 and 5-2 show recommended suction linesizes for installations where that line is horizontal ordown flow. In the event the suction line is up flow,use one stan dard size smaller. EXAM PLE: W here a7/8 diameter tube is recommended on that tablefor horizontal or down flow, the recommended size
for up flow would be 3/4 diameter.
-
7/31/2019 Tecumseh Refrigerant Piping
5/24
A LOOK AT SERVICE SAFETY
Installation and Replacement Information 89
Table 5-1: R-12 Refrigerant Line Sizes for Remote Systems Commercial Refrigeration
Cond. Unit
CAPACITY
(BTU/Hr.)
SUCTION LINE SIZESAT SYSTEM EVAPORATOR DESIGN TEMPERATURE Liquid Line
Size-40F -20F 0F +20F +40F
1200 5/8 1/2 3/8 3/8 3/8 1/4
2400 3/4 5/8 1/2 1/2 3/8 1/4
3600 7/8 3/4 5/8 1/2 1/2 1/4
4800 1 1/8 7/8 5/8 5/8 1/2 1/4
6000 1 1/8 7/8 3/4 5/8 1/2 1/4
7200 1 1/8 1 1/8 7/8 3/4 5/8 1/4
8400 1 3/8 1 1/8 7/8 3/4 5/8 3/8
9600 1 5/8 1 1/8 7/8 3/4 5/8 3/8
10800 1 5/8 1 1/8 1 1/8 7/8 5/8 3/8
12000 1 5/8 1 3/8 1 1/8 7/8 3/4 3/8
18000 2 1/8 1 5/8 1 1/8 1 1/8 7/8 3/8
24000 2 5/8 2 1/8 1 3/8 1 1/8 1 1/8 1/2
36000 3 1/8 2 1/8 1 5/8 1 3/8 1 1/8 1/2
48000 3 5/8 2 5/8 2 1/8 1 5/8 1 3/8 1/2
60000 3 5/8 2 5/8 2 5/8 1 5/8 1 3/8 1/2
72000 4 1/8 3 1/8 2 5/8 2 1/8 1 5/8 1/2
Table 5-2: R-22 Refrigerant Line Sizes for Remote Systems Commercial Refrigeration
Cond. UnitCAPACITY(BTU/Hr.)
SUCTION LINE SIZES
AT SYSTEM EVAPORATOR DESIGN TEMPERATURE Liquid LineSize-40F -20F 0F +20F +40F
1200 3/8 3/8 3/8 3/8 1/4
2400 1/2 1/2 3/8 3/8 1/4
3600 5/8 1/2 1/2 3/8 1/4
4800 3/4 5/8 1/2 3/8 1/4
6000 3/4 5/8 1/2 1/2 1/4
7200 7/8 3/4 5/8 1/2 1/4
8400 7/8 3/4 5/8 1/2 1/4
9600 1 1/8 3/4 5/8 5/8 1/4
10800 1 1/8 7/8 3/4 5/8 3/8
12000 1 1/8 7/8 3/4 5/8 3/8
18000 1 3/8 1 1/8 7/8 3/4 3/8
24000 1 3/8 1 1/8 1 1/8 7/8 3/8
36000 1 5/8 1 3/8 1 3/8 1 1/8 1/2
48000 2 1/8 1 5/8 1 3/8 1 1/8 1/2
60000 2 1/8 2 1/8 1 5/8 1 3/8 1/2
72000 2 5/8 2 1/8 1 5/8 1 3/8 1/2
-
7/31/2019 Tecumseh Refrigerant Piping
6/24
90 Chapter 5
B. R-22 Refrigerant Line Sizes for RemoteSystems Air Conditioning and HeatPumps
Condensers and evaporators should be designed andcircuited to maintain adequate velocity to prevent
oil trapping.
The tube sizes suggested below are for connectinglines of remote systems. The basis for selection is tomaintain adequate velocity which assures oil returnto the compressor, an acceptable pressure drop toassure compressor capacity and minimum tubingcost.
To assure ad equate oil retu rn, suction line velocitiesshould be minimum of 750 fpm for horizontal ordown flow and 1500 fpm for up flow. Gas velocitiesof 3000 fpm or more will create noise problems andshould be avoided.
W here a choice of line sizes is possible because of th eoverlap in the compressor capacity table, the largersized lines are suggested to minimize the systempressure d rop.
Consider th ese installation notes:
Suction line sizes (up flow) provide adequategas velocities to assure oil return to the com-
pressor and, therefore, remain constant in size
regardless of the vertical lift. Suction line trapsare not required. H orizontal suction lines are
sized larger to reduce pressure drop.
Suction line lengths in excess of 100 are notrecommended.
O n h eat pum p systems, the lines serving asboth a discharge line and suction line, should
be sized as a suction line.
Liquid line sizes are based on pressure dropsthat will not permit gas formation for horizon-
tal lengths up to 100.The recommendations shown in Table 5-3 are basedon the use of standard refrigeration grade tubingand do not include considerations for additionalpressure d rop due to elbows, valves, or reduced jointsizes.
Table 5-3: R-22 Refrigerant Line Sizes for Remote Systems Air Conditioning and Heat Pumps
SUCTION LINE OUTER DIAMETER
Nominal Compressor
Cooling Capacity(BTU/Hr.) Vertical Up
Flow
Vertical
Down Flowor
Horizontal
Liquid LineOuter
Diameter
Discharge Line Length &
Outer Diameter
25 50 1001500 FPM 2500 FPM
5700 9400 3/8 1/2 1/4 5/16 5/16 3/8
8000 13000 1/2 1/2 1/4 5/16 3/8 3/8
11200 18500 1/2 5/8 5/16 3/8 3/8 1/2
17000 30000 5/8 3/4 5/16 3/8 1/2 1/2
27000 44000 3/4 7/8 3/8 3/8 1/2 5/8
38000 51000 7/8 1 1/8 3/8 1/2 5/8 5/8
38000 67000 7/8 1 1/8 1/2 1/2 5/8 5/8
60000 102000 1 1/8 1 3/8 1/2 5/8 3/4 3/4
96000 156000 1 3/8 1 5/8 5/8 3/4 3/4 7/8
144000 228000 1 5/8 2 1/8 5/8 3/4 7/8 1 1/8
-
7/31/2019 Tecumseh Refrigerant Piping
7/24
A LOOK AT SERVICE SAFETY
Installation and Replacement Information 91
C. R-502 and R-134a Refrigerant Line Sizesfor Remote Systems CommercialRefrigeration
The selection of suction gas line sizes should beguided by th e following criteria:
Assurance of adequate velocity th us in suringoil return capability. (The tube size must be
limited to maintain velocities no less than 750
fpm for horizontal and down flow and no less
than 1 500 fpm for up flow.)
Assurance of acceptable pressure drop. (Thetube size should be limited to maintain veloci-
ties no greater than 1500 fpm for horizontal
and down flow and no greater than 2500 fpm
for up flow.
Assurance of satisfactory sound level. (Thetube size should be limited to maintain veloci-
ties no greater than 30 00 fpm .)
Assurance of minimum tubing cost. (Thetube size should be as small as possible while
satisfying the th ree points men tioned above.)
Tables 5-4 and 5-5 show recommended suction linesizes for installations where that line is horizontal ordown flow. In the event the suction line is up flow,use one stan dard size smaller. EXAM PLE: W here a7/8 diameter tube is recommended on that tablefor horizontal or down flow, the recommended sizefor up flow would be 3/4 diameter.
Table 5-4: R-502 Refrigerant Line Sizes for Remote Systems Commercial Refrigeration
Cond. UnitCAPACITY
BTU/HR.
SUCTION LINE SIZES
AT SYSTEMS EVAPORATOR DESIGN TEMPERATURE Liquid Line
Size-40F -20F 0F +20F +40F
1200 1/2 3/8 3/8 3/8 3/8 1/4
2400 5/8 1/2 1/2 3/8 3/8 1/4
3600 3/4 5/8 1/2 1/2 3/8 1/4
4800 7/8 3/4 5/8 1/2 1/2 1/4
6000 1 1/8 7/8 5/8 5/8 1/2 1/4
7200 1 1/8 7/8 3/4 5/8 1/2 1/4
8400 1 1/8 7/8 3/4 5/8 1/2 1/4
9600 1 1/8 1 1/8 7/8 3/4 5/8 1/4
10800 1 3/8 1 1/8 7/8 3/4 5/8 3/8
12000 1 3/8 1 1/8 7/8 3/4 5/8 3/8
18000 1 5/8 1 3/8 1 1/8 7/8 3/4 3/8
24000 2 1/8 1 5/8 1 3/8 1 1/8 7/8 3/8
36000 2 5/8 2 1/8 1 5/8 1 3/8 1 1/8 1/2
48000 2 5/8 2 1/8 1 5/8 1 3/8 1 1/8 1/2
60000 3 1/8 2 5/8 2 1/8 1 5/8 1 3/8 1/2
72000 3 5/8 2 5/8 2 1/8 1 5/8 1 3/8 1/2
-
7/31/2019 Tecumseh Refrigerant Piping
8/24
92 Chapter 5
Table 5-5: R-134a Refrigerant Line Sizes for Remote Systems Commercial Refrigeration
Cond. UnitCAPACITY
(BTU/Hr.)
SUCTION LINE SIZES
AT SYSTEMS EVAPORATOR DESIGN TEMPERATURE Liquid Line
Size-40F -20F 0F +20F +40F
1200 5/8 1/2 3/8 3/8 3/8 1/4
2400 3/4 5/8 1/2 1/2 3/8 1/4
3600 7/8 3/4 5/8 1/2 1/2 1/4
4800 1 1/8 7/8 3/4 5/8 1/2 1/4
6000 1 1/8 7/8 3/4 5/8 1/2 1/4
7200 1 3/8 1 1/8 7/8 3/4 5/8 1/4
8400 1 3/8 1 1/8 7/8 3/4 5/8 3/8
9600 1 5/8 1 1/8 7/8 3/4 5/8 3/8
10800 1 5/8 1 3/8 1 1/8 7/8 3/4 3/8
12000 1 5/8 1 3/8 1 1/8 7/8 3/4 3/8
18000 2 1/8 1 5/8 1 3/8 1 1/8 7/8 3/8
24000 2 5/8 2 1/8 1 3/8 1 3/8 1 1/8 1/2
36000 3 1/8 2 1/8 2 1/8 1 3/8 1 1/8 1/2
48000 3 5/8 2 5/8 2 1/8 1 5/8 1 3/8 1/2
60000 3 5/8 3 1/8 2 5/8 2 1/8 1 5/8 1/2
72000 4 1/8 3 1/8 2 5/8 2 1/8 1 5/8 1/2
-
7/31/2019 Tecumseh Refrigerant Piping
9/24
A LOOK AT SERVICE SAFETY
Installation and Replacement Information 93
III. Refrigerant Line Pressure Drops
Figure 5-2. Refrigerant line pressure drops for Freon 12 refrigerant (reprinted by permission of DuPontFluorochemicals).
.
2
.
3
.
4
.
6
.
8
2 3 4 6 8 1
0
2
0
3
0
4
0
6
0
8
0
1
00
2000
3000
4000
6000
8000
10
,000
BTU's Per HR
0.
2
0.
2
0.
3
0.
4
0.
6
0.
8 1 2 3 4 5 6 810
20
30
40
50
0.
3
0.
4
0.
6
0.
8 1 2 3 4 5 6 810
20
30
40
50
EXAMPLE:
5.5 Tons at -4 0C Evap. 85F Cond.
3 1/8" Suction Line Pressure Drop = 0.155 p.s.i./100 ft.3/4" Liquid Line Pressure Drop = 1.0 p.s.i./100 ft.
At 120F Condenser
At 100F Condenser
At 80F Condenser
61/8
"
51/8
"
41/8
"
35/8
"
31/8
"
21/8
"
15/8
"
11/8
"
7/8"
3/4"
5/8"
1/2"
3/8"
-60
F
Eva
pora
torT
empe
ratu
re
-40F
40F
Dis
char
geL
ines
80
F
Con
dens
er
100F
Con
dens
er
120
FC
onde
nser
Liqu
idL
ine
-20
F
20F
0F
13/8
"O.D.TypeLCo
pper
Tubing
25/8
"
Tons of Refrigeration
Pressure Drop In Lbs. Per Sq. In. Per 100 Ft.
NOTE: Pressure drops do notallow for pulsating flow. Ifflow is pulsating, use nextlarger pipe size. Liquidline determined at 0Fevap. & 80F cond.Discharge lines at 0Fevap. Other conditions donot appreciably changeresult. Vapor evap. outlet
assumed to be at 65F.
-
7/31/2019 Tecumseh Refrigerant Piping
10/24
94 Chapter 5
Figure 5-3. Refrigerant line pressure drops for Freon 22 refrigerant (reprinted by permission of DuPont
Fluorochemicals).
0.
2
0.
3
0.
4
0.
6
0.
8
1 2 3 4 6 8 10
20
30
40
60
80
100
2000
3000
4000
6000
8000
10
,000
BTU's Per HR
0.
2
0.2 0.3 0.4 0.6 0.8 1 2 3 4 5 8 10 20 30 40 506
0.
3
0.
4
0.
6
0.
8 1 2 3 4 5 6 810
20
30
40
50
At 80F Condenser
At 100F Condenser
At 120F Condenser
61/8
"
51/8
"
41/8
"
35/8
"
25/8"
15/8
"
11/8
"
7/8"
3/4"
5/8"
1/2"
3/8"
-60FE
vaporator
Temperature
-40F
13/8
"O.D.TypeL
Copper
Tubing
31/8
"
21/8
"
Tons of Refrigeration
Pressure Drop In Lbs. Per Sq. In. Per 100 Ft.
EXAMPLE:
5.5 Tons at -40F Evap. 85F Cond.
2 5/8" Suction Line Pressure Drop = 0.18 p.s.i./100 ft.
5/8" Liquid Line Pressure Drop = 1.7 p.s.i./100ft.
-20F
20F
40F
Dischargelin
es80F
Condenser
100F
Condenser
120FC
ondenser
Liquid
Line
0F
NOTE: Pressure drops do not allowfor pulsating flow. If flow ispulsating, use next largerpipe size. Liquid linedetermined at 0F evap. &80F cond. Discharge linesat 0F evap. Otherconditions do not
appreciably change result.Vapor evap. outlet assumedto be at 65F.
-
7/31/2019 Tecumseh Refrigerant Piping
11/24
A LOOK AT SERVICE SAFETY
Installation and Replacement Information 95
Figure 5-4. Refrigerant line pressure drops for Freon 502 refrigerant (reprinted by permission of DuPont
0.2
0.3
0.4
0.6
0.8
1 2 3 4 6 8 10
20
30
40
60
80
100
200
0
300
0
400
0
600
0
800
0
10,00
0
BTU's Per HR
0.2
0.2
0.3
0.4
0.6
0.8 1 2 3 4 6 81
020
30
40
50
2 3 4 5 6 810 20 30 40500.3 0.4 0.6 0.8 1
At 80F CondenserAt 100F Condenser
At 120F Condenser
71/8
"
61/8
"
51/8
"
41/8
"
35/8
"
31/8
"
25/8
"
21/8
"
15/8
"
13/8
"
11/8
"
7/8"
3/4"
1/2"
3/8"
5/8"O
.D.TypeL
Copp
erTubin
g
-60
FEva
pora
torT
empe
ratu
re
-40
F
Tons of Refrigeration
Pressure Drop In Lbs. Per Sq. In. Per 100 Ft.
EXAMPLE:
5.5 Tons at -40F Evap. 85F Cond.
Choose 2 5/8" Suction Line Pressure Drop = 0.3
Choose 3/4" Liquid Line Pressure Drop = 1.7
-20
F
20F
40F
Disch
arge
Lin
e
Liqu
idL
ine0
F
NOTE: Pressure drops do not allow forpulsating flow. If flow is pulsating,
use next larger pipe size.
-
7/31/2019 Tecumseh Refrigerant Piping
12/24
96 Chapter 5
Figure 5-5. Refrigerant line pressure drops for HP62 (404A) refrigerant (reprinted by permission of DuPont
Fluorochemeicals).
0.1
0.2
0.3
0.4
0.6
0.8
1 2 3 4 6 8 10
20
30
40
60
80
100
200
300
400
600
800
1000
0.0
10.4
0.6
0.8 1 2 3 4 6 81
0
0.0
80.1
0.2
0.3
0.0
2
0.0
2
0.0
3
0.0
4
0.0
6
0.0
80.1
0.2
0.3
0.4
0.6
0.8 1 2 3 4 6 81
0
0.0
3
0.0
4
0.0
6
At 30C Condenser
At 40C Condenser
At 50C Condenser
61/8
"O.D.TypeLCo
pper
Tub
ing
51/8
"
41/8
"
35/8
"
31/8
"
25/8
"
21/8"
15/8
"
13/8
"
11/8
"
7/8"
3/4"
5/8"
1/2"
3/8"
-50C
Evaporato
rTe
mpe
ratu
res
-40C
-20C
0C
-30C
-10C
10C
Dis
charge
Lin
es
Lines
Lin
es
Pressure Drop In Kpai Per Meter
Tons of Refrigeration
EXAMPLE:
15 kW at -40C Evap., 40C Cond.
2 1/8" Suction Line Pressure Drop = 0.11kPa/m5/8" Liquid Line Pressure Drop = 0.47 kPa/m
NOTE: Pressure drops do notallow for pulsating flow.If flow is pulsating, usenext larger pipe size.Liquid line and discharge
lines determined at -20Cevap. and 30C cond.Other conditions do notappreciably changeresult. Vapor at evap.
outlet assumed to be at 20C.
-
7/31/2019 Tecumseh Refrigerant Piping
13/24
A LOOK AT SERVICE SAFETY
Installation and Replacement Information 97
Figure 5-6. Refrigerant line pressure drops for HFC-134a refrigerant (reprinted by permission of DuPontFluorochemicals).
0.2
0.3
0.4
0.5
0.60.8 1 2 3 4 6 81
020
30
40
0.1
0.2
0.4
0.6
1 2 4 6 10
20
30
40
60
100
0.1
0.2
0.3
0.4
0.6
0.8 1 2 3 6 81
020
30
40
60
80
100
At 80F CondenserAt 100F Condenser
At 120F Condenser
61/8
"O.D.TypeL
Copp
erTu
bing
-60F
EvaporatorTe
mperatu
re
-40F
-20F
20F
40F
Dis
charg
eL
ines
Liquid
Lin
es
0F
51/8
"
41/8
"
35/8
"
31/8
"
25/8
"
21/8
"
15/8
"
13/8
"
11/8
"
7/8"
3/4"
5/8"
1/2"
3/8"
Pressure Drop In Psi Per 100 Ft.
Tons of Refrigeration
EXAMPLE:
25 Tons at -40F Evap. and 100F Cond.
2 5/8" Suction Line
Pressure Drop = 5.5 p.s.i./100 ft.
1 1/8" Liquid Line
Pressure Drop = 1.6 p.s.i./100 ft.
NOTE: Pressure drops do notallow for pulsating flow.If flow is pulsating, usenext larger pipe size.Liquid line and discharge
lines determined at 0Fevap. and 80F cond.Other conditions do notappreciably changeresult. Vapor at evap.
outlet assumed to be at 65F.
-
7/31/2019 Tecumseh Refrigerant Piping
14/24
98 Chapter 5
IV. Refrigerant Line Velocities
Figure 5-7. Refrigerant line velocities for Freon 12 refrigerant (reprinted by permission of DuPont
Fluorochemicals).
0.
1
0.
2
2000
3000
4000
6000
8000
10
,000
BTU's Per HR
0.
4
0.
6
1 2 4 6 10
20
40
60
100
15
20
30
40
50
60
70
80
100
150
200
300
400
500
600
1000
1500
2000
3000
4000
5000
6000
7000
8000
10
,000
800
700
15
20
30
40
50
60
70
80
100
150
200
300
400
500
600
1000
1500
2000
3000
4000
5000
6000
7000
8000
10
,000
800
700
At 80F Condenser
EXAMPLE:
5.5 Tons at -4 0F Evap. 85F Cond.
3 1/8" Suction Line Velocity = 1916 ft./min.3/4" Liquid Line Velocity = 94 ft./min.
At 100F Condenser
At 120F Condenser
61/8
"
-60FEvap
orator
Temperature
-40F
-20F
0F
20F
40F
80F
Condenser
51/8
"
41/8
"
35/8
"
13/8
"
3/4"
5/8"
31/8
"
25/8
"
21/8
"
15/8
"
11/8
"
7/8"
O.D.TypeLCo
pper
Tubing
1/2"
3/8"
Tons of Refrigeration
Velocity In Feet/Minute
100F
Condenser
LiquidLine
Discha
rgeLines12
0F
Conden
ser
NOTE: Liquid line determined at0F evap. and 80F cond.Discharge lines at 0Fevap. Net refrigeration for"Freon" 12 includessuction gas at 65F.
-
7/31/2019 Tecumseh Refrigerant Piping
15/24
A LOOK AT SERVICE SAFETY
Installation and Replacement Information 99
Figure 5-8. Refrigerant line velocities for Freon 22 refrigerant (reprinted by permission of DuPont Fluorochemicals).
0.
1
0.
2
0.
4
0.
6
1 2 4 6 10
20
40
60
100
200
0
300
0
400
0
600
0
800
0
10
,00
0
BTU's Per HR
15
15
20
30
40
60
80
100
150
200
300
400
600
800
1000
1500
2000
3000
4000
6000
8000
10
,000
20
30
40
60
80
100
150
200
300
400
600
800
1000
1500
2000
3000
4000
6000
8000
10
,000
At 80F CondenserAt 100F Condenser
At 120F Condenser
51/8
"
41/8
"
-60FEv
aporatorTe
mperatu
re
Discha
rgelin
es80F
Cond
enser
-40F
-20F
20F
40F
Liquid
Line
100F
Cond
enser
120F
Conden
ser
0F
35/8
"
31/8
"
25/8
"
21/8
"
15/8
"
13/8
"
11/8
"
7/8"O
.D.TypeLCo
pper
Tubing
5/8"
1/2"
3/8"
3/4"
Tons of Refrigeration
Velocity, Feet/M inute
EXAMPLE:
5.5 Tons at -40F Evap. 85F Cond.
2 5/8" Suction Line Velocity = 1718 ft./min.5/8" Liquid Line Velocity = 114 ft./min.
NOTE: Liquid line determinedat 0F evap. and 80Fcond. Discharge linesat 0F evap. Netrefrigeration for "Freon"22 includes suction gasat 65F.
-
7/31/2019 Tecumseh Refrigerant Piping
16/24
100 Chapter 5
Figure 5-9. Refrigerant line velocities for Freon 502 refrigerant (reprinted by permission of DuPont
Fluorochemicals).
0.1
0.2
0.4
0.6
1 2 4 6 10
20
40
60
100
2000
3000
4000
6000
8000
10,0
00
BTU's Per HR
15
20
30
40
50
60
80
100
150
200
300
400
500
600
800
1000
1500
2000
3000
4000
5000
6000
8000
10,0
00
15
20
30
40
50
60
80
100
150
200
300
400
500
600
800
1000
1500
2000
3000
4000
5000
6000
8000
10,0
00
At 80F CondenserAt 100F Condenser
At 120F Condenser
61/8
"
15/8
"
13/8
"
11/8
"
7/8"
3/4"
5/8"
1/2"
3/8"
51/8
"
41/8
"
35/8
"
31/8
"
25/8
"
21/8
"
-60FEv
aporator
Temperature
-40F
-20F
0F
20F
40F
Discha
rgeLines80
FConde
nser
100F
Conden
ser
120F
Cond
enser
Liquid
Line
Tons of Refrigeration
Velocity, Feet/Minute
EXAMPLE:
5.5 Tons at -40F Evap. 85F Cond.
2 5/8" Suction Line Velocity = 1555 ft./min.3/4" Liquid Line Velocity = 105 ft./min.
NOTE: Liquid line determined
at 0F evap. and 80Fcond. Discharge linesat 0F evap. Netrefrigeration for "Freon"502 includes suction gas
at 65F.
-
7/31/2019 Tecumseh Refrigerant Piping
17/24
A LOOK AT SERVICE SAFETY
Installation and Replacement Information 101
Figure 5-10. Refrigerant line velocities for HP62 (404A) refrigerant (reprinted by permission of DuPont
Fluorochemicals).
0.
1
0.
2
0.
3
0.
4
0.
6
0.
8
1 2 3 4 6 8 10
20
30
40
60
80
100
200
300
400
600
800
100
0.
1
0.
2
0.
3
0.
4
0.
6
0.
8 1 2 3 4 6 810
20
30
40
60
80
100
0.
2
0.
3
0.
4
0.
6
0.
8 1 2 3 4 6 810
20
30
40
60
80
100
At 30C Condenser
At 40C Condenser
At 50C Condenser
61
/8"O
.D.Typ
eLC
opperTu
bing
51
/8"
41
/8"
35
/8"
31
/8"
25
/8"
7/8"
3/4"
5/8"
3/8"1/
2"
21
/8"
15
/8"
11
/8"
13
/8"
-50C
EvaporatorTe
mperatu
res
-40C
-30
C
-20C
0C-1
0C
10C
Dis
charg
eL
ines
Liquid
Lin
es
Velocity In M/S
Kilowatts of Refrigeration
EXAMPLE:
55 kW at -40C Evap., 40C Cond.
2 1/8" Suction Line Velocity = 38 m/s1 3/8" Liquid Line Velocity = 0.55 m/s
NOTE: Liquid line and discharge lines determined at -20C evap.and 30C cond. Other conditions do not appreciably changeresult. Net refrigeration for HP-62 includes suction gas at 20 C.
-
7/31/2019 Tecumseh Refrigerant Piping
18/24
102 Chapter 5
Figure 5-11. Refrigerant line velocities for HFC-134a refrigerant (reprinted by permission of DuPont Fluorochemicals).
0.1
0.2
0.3
0.4
0.5
0.6
1 2 3 4 6 8 10
20
30
40
60
80
100
200
300
400
600
800
1000
0.2
0.1
0.2
0.3
0.4
0.6
0.8 1 2 3 4 6 81
020
30
40
60
80
100
0.3
0.4
0.6
0.8 1 2 3 4 6 81
020
30
40
60
80
100
At 30C Condenser
EXAMPLE:
45 kW at -30C Evap., 40C Cond.
3 1/8" Suction Line Velocity = 18 m/s1 3/8" Liquid Line Velocity = 0.37 m/s
NOTE: Liquid line determined at -20C evap. and 30C cond.
Discharge lines at -20C evap. Other conditions do not
appreciably change result. Net refrigeration forHFC-134a includes suction gas at 20C.
At 40C Condenser
At 50C Condenser
61/
8"O
.D.Typ
eLCoppe
rTu
bin
g
51/
8"
41/
8"
31/
8"
21/
8"3
5/8"
25/
8"
15/
8"
13/
8"
11/
8"
7/8"
3/4"
5/8"
1/2"
3/8"
-50C
EvaporatorTe
mperatu
res
-40C
-30C
-20
C
-10C
0C
10C
-40
C
Condenser
-50
C
Condenser
Liq
uid
Line
s
Dis
charg
eLin
es-
30C
Cond
ens
er
Kilowatts of Refrigeration
Velocity In M/S
-
7/31/2019 Tecumseh Refrigerant Piping
19/24
A LOOK AT SERVICE SAFETY
Installation and Replacement Information 103
V. Service Valves
As shipped with the compressors, the rotolock ser-vice valves have a small plastic dust plug inside thethreaded end. Be sure to remove this plug before
installing.Service valves on Tecumseh systems are frontseated by turning the valve stem clockwise. Thiscloses the valve and opens the gauge por t.
Turning the stem counter-clockwise back seats thevalve and t hu s opens th e system and closes the gaugeport.
If present, t he valve port t o th e system cont rol (highpressure cutout, low pressure control, fan controletc.) is always open regardless of the position of thevalve stem.
If it is desired to operate th e system with the servicegauge operating, it is necessary to crack the valvefrom its back seated position for the gauges to per-form. Before removing the gauges, close the gaugeport by return ing th e valves to t heir fully open posi-tion (back seated).
Remember to check the packing gland nut (ifpresent ) on the stem for snugness before leaving t he
job . Install t he cover n ut over th e valve stem as a sec-ond ary safeguard against leaks at th e stem.
VI. Processing the System
The performance and longevity of a refrigerationsystem is stron gly influen ced by h ow th e system wasprocessed, that is, how the system was prepared foroperation at the time of installation. The procedureis:
1. O n split systems, install the liquid and suction
line. See Refrigerant Line Sizes on pages 88-
92 for recommended line sizes. A properly
sized suction line accumulator is recom-
mended . See Accum ulator Selection D ata onpage 118 for accumulator sizing. Insulate the
suction line to reduce heat exchange and
excessive return gas temperatures to the com-
pressor.
2. To prevent oxidation and scale forming inside
the tubes, it is good practice to flow dry nitro-
gen through the tubing during the soldering
operations. A light flow of abou t 1/ 4 cub ic feet
per minu te is sufficient.
3. Install a filter in th e liquid line imm ediately
ahead of th e capillary tube or expansion valve.
A liquid line drier should also be installed.
4. A suction line filter/drier is recomm ended to
prot ect the comp ressor. A suction accumu lator
must be installed on those systems having
defrost cycles (heat pumps, low temperature
refrigeration) or the likelihood of periodic
floodbacks (bulk milk coolers, ice machines).
See Accum ulator Selection D ata on page 118
for accumu lator sizing.
5. Pressure test the system for leaks using the
safety precautions outlined in System Flush-
ing, Purging, and Pressure Testing for Leaks
on pages 4-5. D o not p ressurize the system
beyond 150 PSIG fi eld leak test pr essure.
6. Use a vacuum pum p (not a compressor) to
draw a vacuum of 1000 microns or less from
both sides of the system. It is a waste of time to
attempt to draw a vacuum on a system with
the pump connected only to the low side.
Entry must be made directly into the high
pressure side to properly evacuate that p ort ion
of the system. Use a good electronic gauge to
measure the vacuum. An accurate reading can-
not be made with a refrigeration gauge.
Remember 29 of mercury as read on a com-
pound gauge equals 23,368 microns of vac-
uum.
WARNING! Never use a compressor to
evacuate a system. Instead, use a high vac-
uum pump specifically designed for that pur-
pose.
Never start the compressor while it is under
deep vacuum. Always break a vacuum with
refrigerant charge before energizing the
compressor.
Failure to follow these instructions can dam-
age the hermetic terminal and may result in
terminal venting. As always, to reduce the
risk of serious injury or death from fire due
to terminal venting, never energize the com-
pressor unless the protective terminal cover
is securely fastened.
-
7/31/2019 Tecumseh Refrigerant Piping
20/24
104 Chapter 5
7. If a suction line accum ulator is present, charge
into the accumulator to prevent liquid refrig-
erant from reaching the compressor. If this is
not possible, then break the vacuum by allow-
ing refrigerant vapor to enter the low side at
the suction service valve. When the system
pressure reaches 60 psig for R-22 (70 psig for
R-502, 35 psig for R-12), start the compressor
and cont inue charging at rate not m ore than 5
pounds per minutes for the larger systems and
somewhat less for smaller systems. Follow the
safety precautions outlined in System Charg-
ing on p ages 5-6.
8. Ch eck fans and blowers for correct direction
of rotation, belt tension, and proper air flow
(CFM).
9. With th e protective terminal cover securely
fastened, run the compressor and allow the
system pressures and temperatures to stabilize.
Systems vary in their operating characteristics
bu t generally these approximations will apply:
10. Before leaving the job ru n the system for
awhile. Listen for abnormal noises. Feel the
bottom crankcase housing and d etermine th at
it is warm. Is the compressor upper housing
sweating indicating that liquid refrigerant is
reaching the compressor? Is the return gas
temperature at the compressor 65F or less
and not more than 80F? Recheck pressures,
amps, fan motors, belts, CFM, etc.
VII. System Cleanup and
Compressor Replacement
After Compressor Failure
Once you determine that a compressor needs to be
replaced you must then determine whether the sys-tem has been contaminated. C omp ressor m otor fail-ure can lead to such contamination. (Whilecomp ressor motor failure is sometimes referred to asmotor burnout, it does not mean that a fire actu-ally occurs inside a hermetic compressor.) Evensmall amounts of contamination must be removedfrom the system to avoid damaging the replacementcompressor. Therefore, it is important to thoroughlyclean a refrigeration/air conditioning system if sys-tem con tamination is present.
If a compressor motor failure has occurred,refrigerant or mixtures of refrigerant and oil inthe system can be acidic and cause chemicalburns. As always, to avoid injury, wear appro-priate protective eyewear, gloves and clothingwhen servicing an air conditioning or refrigera-tion system. If refrigerant or mixtures of refrig-erant and oil come in contact with skin or eyes,flush the exposed area with water and get medi-cal attention immediately.
The following outlines a process for compressorreplacement and system clean-up for a systemequipp ed with a Tecum seh comp ressor. You shouldrefer to the original equipment manufacturers(O EM ) service information.
A. Determine Extent of SystemContamination
Following the precautions in Refrigerants andOther Chemicals and Compressor Removal onpage 4, remove the compressor.
Use the following guidelines to determine whethercontamination, if any, is limited to the compressoror extends to t he system.
If the discharge line shows no evidence of contami-nation and t he suction stub is clean or has only lightcarbon deposits, then the contaminants are limitedto th e compressor hou sing (Com pressor H ousing
Table 5-6: Pressure and TemperatureStabilization
Pressure Temperature
Saturated Head
Pressure
Ambient temperature F + 25F for
air cooled condenser.
Water cooled Discharge water F + 10F
Saturated evaporator pressure
Air Conditioning Discharge air F - 20F
Medium
TemperatureProduct temperature -10F to -12F
Low Temperature Product temperature -6to -8F
! WARNING
-
7/31/2019 Tecumseh Refrigerant Piping
21/24
A LOOK AT SERVICE SAFETY
Installation and Replacement Information 105
Contamination). A single installation of liquid and
suction line filter-driers shou ld cleanup t he system.
If, however, the discharge line or the suction line
shows evidence of contamination, the compressor
was running at the time of the motor failure and
contaminants were pumped throughout the system
(System Con tamination). If System Con tamination
has occurred, several changes of the liquid and suc-
tion line filter-driers will be needed to cleanup the
system. In addition, the expansion device will need
to be replaced. If the system is a heat pump, t he four
way valve should be replaced.
B. Install Replacement Compressor and
Components1. Install the replacement compressor with new
external electrical components (capacitors,
relay, overload, etc., where applicable). Check
the contacts of the starting control or contac-
tor.
2. Install an oversized liquid line filter-drier.
3. Install a generously sized suction line filter-
drier imm ediately upstream of th e compr essor.
The drier when permanently installed in aclean system, or as initially installed in a dirty
system, must have a pressure drop not more
than that of Table 5-3. Pressure taps must be
supplied imm ediately before and after the suc-
tion filter-drier to permit the pressure drop to
be measured.
If a suction line accumulator is present and
System Contamination has occurred, it must
be thoroughly flushed to remove any trapped
sludge and thus prevent it from plugging the
oil return hole. The filter-drier should be
installed upstream of the accumulator and the
compressor.
In the case of Compressor Housing Contami-
nation, the filter-drier should be installed
between the compressor and the suction line
accumulator.
Rubber refrigeration hoses are not satisfactory
for temporarily hooking up th e suction line fil-
ter-drier to the system since the acid quickly
breaks down the rubber and plastic.
4. Follow the precautions in System Flushing,
Purging, and Pressure Testing for Leaks on
pages 4-5, to purge the system and pressure
test for leaks.
C. Evacuate the System
Evacuate the system to less than 1000 microns,
using a good vacuum pum p (not a compressor) and
an accurate high vacuum gauge. O perate the pu mp
at 10 00 microns, or less, for several hou rs to be sure
the vacuum is maintained.
An alternate method of removing moisture and non -
cond ensables from the system is:
1. Evacuate the system to 29 inches vacuum.
Break vacuum with refrigerant to be used for
final charging of system and vapor charge to
35-50 pounds gauge pressure. Leave vapor
charge in system for a minimum of five min-
utes. Reduce pressure to 0 gauge p ressure.
2 . Repeat step 1.
3. Evacuate system to 29 inches vacuum. Ch arge
system with the specified kind and quantity of
refrigerant.
WARNING! Never use a compressor to evacuate
a system. Instead, use a high vacuum pump specif-
ically designed for that purpose.
Never start the compressor while it is under deep
vacuum. Always break a vacuum with refrigerantcharge before energizing the compressor.
Failure to follow these instructions can damage
the hermetic terminal and may result in terminal
venting. As always, to reduce the risk of serious
injury or death from fire due to terminal venting,
never energize the compressor unless the protec-
tive terminal cover is securely fastened.
-
7/31/2019 Tecumseh Refrigerant Piping
22/24
106 Chapter 5
D. Charge the System and Check thePressure Drop
Charge the system and place in operation. Followthe safety precautions outlined in System Charg-ing on pages 5-6. Immediately after startup, checkthe pressure drop across the suction line filter-drier.This will serve two purposes:
Verify that the drier selection was correct; thatis, large enough.
Serve as a base point to wh ich subsequent pr es-sure checks can be compared.
Because the permissible pressure drop across thedrier is relatively small, it is suggested that a differ-ential pressure gauge be used for the measuremen t.
E. Measure the Pressure Drop
After the system has been operating for an hour orso, measure th e pressure d rop across the suction linefilter-drier.
In th e case of Com pressor Hou sing Con tamination,little change should be noted. The pressure dropwill, in m ost instances, be below t hat t olerable for apermanent installation (see Table 5-3).
On the other hand, where System Contaminationoccurred, an increased pressure drop will be mea-sured. Change the suction filter-drier an d the liquidline filter-drier whenever the pressure dropapproaches or exceeds that allowed for temporaryoperation during cleanup (see Table 5-4).
Keep changing both the suction and liquid line fil-ter-driers until th e pressure d rop stabilizes at a figureequal to or below that permitted for permanentoperation in a system (see Table 5-3). At t his point ,it is the service persons option as to whether to leavethe suction drier in the system or remove it from
operation.
If the system is to be opened to permit the perma-nent removal of the suction filter-drier then the liq-uid line filter-drier should be changed once more.
Table 5-3: Suggested Maximum Pressure Drop (PSI) for Permanent Suction Filter-Drier Installation
Application Air Cond. High Medium Low Low
Evaporator Range, F +55 to +32 +55 to +20 +30 to -10 +10 to -20 -20 to -40
R-12 2 2 1 1/2 1/2 1/2
R-22 3 3 2 1 1/2
R-502 3 3 2 1 1/2
Table 5-4: Suggested Maximum Pressure Drop (PSI) for Temporary Suction Filter-Drier InstallationDuring Cleanup
Application Air Cond. High Medium Low Low
Evaporator Range, F +55 to +32 +55 to +20 +30 to -10 +10 to -20 -20 to -40
R-12 9 9 6 2 3/4
R-22 15 15 9 3 1 1/2
R-502 15 15 9 3 1 1/2
-
7/31/2019 Tecumseh Refrigerant Piping
23/24
A LOOK AT SERVICE SAFETY
Installation and Replacement Information 107
F. Test for Acidity If Multiple Motor FailuresHave Occurred
If the system has suffered m ultiple motor failures, itis advisable that the oil of the replacement be testedafter Section E and judged acid free before the sys-tem is considered satisfactorily cleaned. An oil sam-ple may be taken from a hermetic system if at thetime the replacement com pressor was installed an oiltrap is installed in th e suction line (see Figure 5-12).W hen the trapped oil level appears in the sight glass(less than an ounce is needed) the oil may be slowlytransferred to the b eaker of th e acid t est kit as avail-able from several manufacturers. A reading of lessthan 0.05 acid nu mb er is an ind ication that the sys-
tem is free of acid. A reading of higher than 0.05means continued cleaning is required. Return to B2on page 105.
G. Monitor the System
The above procedure for the cleanup of hermeticsystems after motor failure through the use of suc-tion line filter-drier will prove satisfactory in mostinstancesprov id ed the system is monitored and keptclean by repeated drier changes, if such are needed.T he failure to follow th ese minimum cleanup recom-mendations will result in an excessive risk of repeatmotor failure.
Figure 5-12. Method of obtaining oil sample on hermetic system. After satisfactory oil test,Schrader valve may be capped and the oil sampler taken to next job.
Schrader Valve Vertically Downward
Female Schrader Valve Connection
1/2" Liquid Sight Glass
1/2" Shut Off Valve
2"
Minimum
At Least 6 Diameters
Suction Line
-
7/31/2019 Tecumseh Refrigerant Piping
24/24
VIII. Replacing Compressors in
Water-Utilizing Systems:
Preventing Explosions
In certain water-utilizing refrigeration systems,water can leak into the refrigerant side of th e system.This can lead to an explosion of system compo-nents, including b ut not limited to, the comp ressor.If such an explosion occurs, the resulting blast cankill or seriously injure anyone in the vicinity.
Water-utilizing systems that have single-wall heatexchangers may present a risk of explosion. Suchsystems may include:
water source heat pump/air conditioning sys-tems, and
water cooling systems, such as icemakers, watercoolers, and juice dispensers.
Water-utilizing systems that have single-wall heatexchangers present a risk of explosion unless theyhave either:
a high pressure cut-out which interrupts powerto ALL leads to the com pressor or
an external p ressure relief valve.
Before replacing a compressor in a water-utilizingsystem, read and follow Prevention of Water-Utiliz-ing System Explosions on pages 6-7.