Data Sheet Revision: 1.1
Low pressure regulator
TECNIX FV M26 adjustable model
Code: CB52921 Comap Page: 1 de 2
COMAP DO BRASIL LTDA. Avenida Rudolf Dafferner, 601, Bloco F - Alto da Boa Vista - CEP: 18085-005 - Sorocaba - SP
CNPJ: 01.527.508/0001-05 / Telefone: (15)3218 1222 - Fax: (15)3218 1299 / site: www.clesse.com.br/e-mail: [email protected]
Uma subsidiria da CLESSE INDUSTRIES e COMAP S.A.
Pressure regulator for natural gas with 4 m
3
/h nominal flow considering 0,6 (air = 1) density. Including fullrelief valve according to NTC3727.
TECNIX FV - M26 x 1/2"
CLESSE
16
16,6
17,2
17,8
18,4
19
19,6
20,2
20,8
21,4
22
22,6
23,2
23,8
24,4
25
25,6
26,2
26,8
27,4
28
0 0,5 1 1,5 2 2,5 3 3,5 4
Flow m/h (Natural Gas)
OutletPress
ure(mbar)
PE: 0,21 bar
Inle P.: 0,35 bar
Inle P.: 0,5 bar
Material:
Body and cover made in aluminium die cast (UNI5076 DIN 1725/2); seat disc and diaphragm made in
nitrilic rubber (NBR); internal components made in steel, aluminium, brass and plastic.
Full relief valve:relief valve with full vent incorporated to regulator, concept and performance according to
NTC3727. The outlet pressure is limited in 1300 mmca 10% with inlet pressure up to 4,0 barg.
P.s.: Without Over Pressure Shut Off.
Features TECNIX FV (CB52921)
Working temperature -20oC to +60
oC
Maximum inlet pressure 11 barg (157 psi)
Inlet pressure range 0,21 to 0,5 barg (3 to 7 psi )
Nominal outlet pressure 20,5 mbar
Outlet pressure range 1,6 to 2,5 kPa ( 16 to 25 mbarg )
Relief pressure According to NTC 3727
Flow rate 4 m3/h of natural gas (for P. inlet 0,21 barg)
Inlet connection M26 x 1,5 male
Outlet connection 1/2" NPT female
Surface finishing Components made in steel are zinc plated.
-
8/10/2019 Tecnix_FV REGULADOR.pdf
2/2
Data Sheet Revision: 1.1
Low pressure regulator
TECNIX FV M26 adjustable model
Code: CB52921 Comap Page: 2 de 2
COMAP DO BRASIL LTDA. Avenida Rudolf Dafferner, 601, Bloco F - Alto da Boa Vista - CEP: 18085-005 - Sorocaba - SP
CNPJ: 01.527.508/0001-05 / Telefone: (15)3218 1222 - Fax: (15)3218 1299 / site: www.clesse.com.br/e-mail: [email protected]
Uma subsidiria da CLESSE INDUSTRIES e COMAP S.A.
General comments:
1. For a better performance is recommended to apply a filter inlet the regulator;
Warning Dirties can damage the regulators seat;
2. Clean the piping before install the regulator;3. Is recommended to install this regulator outdoor;4. For a good performance the inlet and outlet pressure have to be inside the pressure range (according to
the data table above);
5. The outlet pressure can be adjusted by the adjustment disc (removing the plastic cap);6. For a good connection sealing, use a correct product and correct quantity;7. Dont put an over torque in the connections;8. FV Full Vent (full relief valve).
Pressure units (international system): 1 bar = 1,02 Kgf/cm2 1 Kgf/cm298 kPa 14,2 psi (lb/pol2)