Teck Cable
P O W E R I N G T H E I N D U S T R I A L S E C T O R
Our Commitment
Our commitment to our customers is simple - we deliver even when others can’t.
As one of Canada’s largest wire, cable and data communication distributors for over 35 years, Texcan supplies solutions for automotive, power distribution, control, industrial automation, commercial, residential, premise wiring and networking applications. Our commitment to superior customer service is the number one reason customers keep coming back.
Our parent company, Sonepar, is a major global electrical distributor, with divisions in 36 countries, 5 continents, over 36,000 associates and 2,200 branches.
Dedicated to Our Customers
Texcan understands that business is done between people. We consider a job finished when the customer is completely satisfied. This approach highlights our commitment to quality and our high level of customer service. This winning combination focuses on a personalized approach to our customers.
Product Expertise and Specialized Services
Texcan has five stocking locations in Western Canada. With over 200 employees, Texcan is able to provide product application expertise, specialized technical assistance and superior sales service to meet our customers’ needs.
We constantly strive to bring value to our customers. We provide:
• An extensive range of stock wire products • Computerized order processing • Regionalized bar coded warehousing • Competitive pricing • Inventory tracking technology • JIT inventory
Strategic Partnerships
Texcan has worked hard to develop partnerships with customers and vendors and continues to be committed to developing such strategic alliances. These partnerships provide Texcan with a successful and proven record with some of the largest customers in the pulp and paper, mining, petrochemical, transportation, and communication industries.
Thanks to our relationships with key vendors such as: General Cable, Southwire, Belden, Prysmian Group, Shawflex, Nexans, AmerCable and Deca, Texcan is able to offer its customers a diverse selection of quality products.
We are confident we can continue to be your successful partner now and in the future.
Over 35 Years of Service
Table of Contents
Universal Toll Free Phone: 1.800.665.1025 | 3
Page No.
Teck Cable 4
Standard Design Features 5
Armoured Control 600V 6
Teck Multiconductor 600V - 14 AWG 7
- 12 AWG 8
- 10 AWG 9
Teck Composite 600V - 14 AWG 10
- 12 AWG 10
Teck 1C 1000V 11
Teck 2C 1000V 12
Teck 3C 1000V 13
Teck 4C 1000V 14
Teck Unshielded - 1C 5kV 15
- 3C 5kV 16
Teck Shielded - 1C 100% 5kV 17
- 3C 100% 5kV 18
- 1C 133% 5KV (aka 100% 8kV) 19
- 3C 133% 5KV (aka 100% 8kV) 20
- 3C 133% 8kV 21
- 1C 133% 15kV 22
- 3C 133% 15kV 23
- 1C 133% 25kV 24
- 3C 133% 25kV 25
- 1C 133% 28kV 26
- 3C 133% 28kV 27
- 1C 100% 35kV 28
- 3C 100% 35kV 29
Teck Connectors 30-31
Technical Information - Metric Conversions 32
- Installation Data 33
To Place an Order - For many of the products in the catalogue, you will find everything that you need to place an order. Should you need any assistance or require special orders, please contact your sales representative. A complete list of our sales offices can be found on the back cover of this catalogue.
Teck Cable
4 | Universal Toll Free Phone: 1.800.665.1025
IntroductionTeck cable, a flexible armoured cable originally designed for use in Canadian mines, has become a key component for the distribution of electricity through a broad range of industrial, commercial and manufacturing facilities.
Teck cable’s combination of interlocking flexible armour with two layers of PVC jacket provide a rugged, compact and flexible cable that is resistant to corrosion, water and mechanical abuse. It is designed for use in wet or dry locations with a maximum conductor temperature of 90˚C and a low temperature rating of -40°C.
ApplicationsTeck cable is used extensively by the pulp and paper, chemical, mining, petrochemical and manufacturing industries in a broad range of applications, especially where cable may be subjected to mechanical damage and corrosive chemicals. Commercial applications for Teck cable include apartment buildings and commercial complexes. Teck cable is also an economical alternative as the need for conduits or ducts and pull boxes is eliminated.
Teck cable is approved for use; in wet and dry locations, indoor and outdoor, in exposed and concealed wiring, in ventilated, non-ventilated and ladder type cable trays, for direct earth burial and for service entrance installations, above and below ground. It is ‘HL’ rated for use in all hazardous locations when used with optional ‘HL’ approved connectors.
Specifications• CSA FT1 & FT4• CSA C22.2 No. 131 for Teck cables rated up to and including 5kV• CSA C68.10 for shielded Teck cables rated 5kV and above (C68.10 pending)• CSA C22.2 No. 0.3 Clause 4.11.4 FT4 flame test• CSA C22.2 No. 174 for use in the following hazardous locations (HL):
- Class 1 Group A, B, C, D. Division 1 & 2 - Class II Group E, F, G. Division 1 & 2 - Class III
• ICEA S-66-524 / NEMA WC7 for Teck cables rated above 5kV• IEEE 383 &1202 (70,000 BTU/hr) flame test• ICEA T-29-520 (210,000 BTU/hr) Vertical Cable Tray Flame Test• ICEA T-30-520 (70,000 BTU/hr) Vertical Cable Tray Flame Test *Refer to CE Code for details
C A U T I O N N O T I C E
In case of fire, well maintained early warning smoke detectors will give an alarm long before non-metallic coverings become combustible.However, the Electrical and Electronic Manufacturers Association of Canada has suggested that all purchasers of PVC insulated / jacketed products be advised of the following:
• Non-metallic coverings of electrical cables can burn and may transmit fire when ignited.• Burning non-metallic coverings may emit acid gases which are toxic and may generate dense smoke.• Emission of acid gases may corrode metal in the vicinity e.g. sensitive instruments and reinforcing rods in cement.
The installer and/or user assumes all liability for the consequences of the installation and/or use of any of the products in violation of any applicable law, regulation, or code.
Standard Design Features
Universal Toll Free Phone: 1.800.665.1025 | 5
Conductors – Class B compact or compressed concentric stranded soft drawn bare copper per ASTM, conforming to CSA C68.3. Conductor Shielding – A thermoset semi-conducting shield is extruded over the conductor on all cables rated over 1kV. Minimum thickness in accordance with CSA C68.3, Table 2. Insulation – Cross-linked polyethylene (XLPE), meeting the requirements of CSA RW90 for cables rated up to and including 1kV. For cables rated 5kV and above, the TR-XLPE insulation meets the requirements of CSA Standard C68.3 M92. Metallic Shield – A 15% gapped copper tape shield meeting the requirements of CSA C68.3 is helically applied to the insulated conductors in three conductor shielded cables rated 5kV and above. In single conductor cables, the concentric ground serves as the metallic shield and bonding conductor. Bonding (Ground) Conductor – Class B stranded soft bare copper conductor, in accordance with CSA C68.3 and CSA C22.2 No. 131, is included in the assembled cable for multiconductor cables. In single conductor cables, the concentric ground serves as the metallic shield and bonding conductor. Fillers and Core Binder Tape – Where required, suitable fillers to make round and core binders may be used. Inner Jacket – Flame-retardant and moisture resistant PVC Jacket is applied over the core in accordance with CSA C22.2 No. 131. Armour – An interlocking aluminum armour is applied over the inner jacket meeting the requirements of CSA C22.2 No. 131, Clause 5.11. Outer Jacket – A low temperature (-40°C), flame-retardant, moisture and sunlight resistant PVC jacket is applied over the armour in accordance with CSA C22.2 No. 131. Minimum thickness in accordance with CSA 68.3, Table 21. Complete cable FT4 rated. Accessories• Non-hazardous Teck connectors• Explosion proof (hazardous location) cable connectors• High voltage termination and splice kits• Compression lugs and sleeves
INSULATION
BONDCONDUCTOR
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
FILLERS
INNER JACKET
CONDUCTOR
COPPERTAPE
INSULATIONSHIELD
TAPE
Colour CodeTECK 90 CABLES:• 2 conductor cables are colour coded black and white• 3 conductor cables are colour coded black, red and blue• 4 conductor cables are colour coded black, red, blue and white• 5 or more conductor cables are black and alpha numeric coded
ARMOURED CONTROL:• Conductor #1 is white, the remaining conductors are black
and numbered Options• Aluminum phase conductor and bonding conductor• Ethylene-propylene rubber (EPR) insulation for shielded Teck
cables rated 5kV and above• Overlapping copper tape shield• Sequential marking on outer jacket• Special ground wire requirements: 50% of phase conductor or
more than one ground conductor• Fully filled core for multiconductor Teck cables rated 5kV and above• Galvanized steel interlocked armour (GSIA) for multiconductor
Teck cables• Coloured outer jacket• Vertical riser Teck• Variable frequency drive (VFD)• Other constructions available upon request
22000-02-040 2 16 16 0.336 0.536 0.650 177 264
22000-03-040 3 16 16 0.356 0.556 0.670 196 291
22000-04-040 4 16 16 0.386 0.586 0.700 217 323
22000-05-040 5 16 16 0.420 0.620 0.730 241 358
22000-06-040 6 16 16 0.446 0.686 0.798 264 393
22000-07-040 7 16 16 0.482 0.722 0.834 276 411
22000-08-040 8 16 16 0.545 0.785 0.897 300 447
22000-10-040 10 16 16 0.597 0.797 0.920 373 555
22000-12-040 12 16 16 0.626 0.826 0.950 407 605
22000-15-040 15 16 16 0.673 0.873 0.990 459 683
22000-20-040 20 16 16 0.749 0.949 1.070 545 811
22000-25-040 25 16 16 0.888 1.123 1.220 730 1086
22000-30-040 30 16 16 0.942 1.172 1.280 811 1206
22000-40-040 40 16 16 1.045 1.275 1.380 974 1449
22000-50-040 50 16 16 1.149 1.379 1.480 1141 1697
SPECIFIC ATIONS CONSTRUC TION
Armoured Control 16 AWG 600V XLPE/PVC/AIA/PVC
Conductor: Bare copper Class B compressed stranded
Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature and moisture resistant Polyvinyl Chloride (PVC), blue
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request
• CSA FT4
• CSA C22.2 No. 239
• CSA C22.2 No. 174
• CSA C22.2 No. 38
*Refer to CE Code for details
OUTER JACKET
ARMOUR
CONDUCTOR
INSULATION
BONDCONDUCTOR
INNER JACKET
FILLERS
TAPE
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
HL
16 AWG
Part Number No. of Conductors
AWG Size Approximate Diameter (Over)
Net Weight w/ Armour
Cond. Bond Wire Inner Jacket (in.) Armour (in.)Outer Jacket
(in.)LB/MFT KG/KM
Armoured Control
6 | Universal Toll Free Phone: 1.800.665.1025
CO
NTR
OL
AR
MO
UR
ED
CO
NT
RO
L
05001-01-010 2 14 14 0.030 0.130 0.360 0.580 0.670 39 58 195 290
05001-02-010 3 14 14 0.030 0.130 0.380 0.600 0.690 52 78 226 336
05001-03-010 4 14 14 0.030 0.130 0.420 0.640 0.720 68 101 256 381
05001-04-010 5 14 14 0.030 0.130 0.460 0.680 0.760 81 121 290 432
05001-05-010 6 14 14 0.030 0.130 0.500 0.720 0.800 95 142 316 471
05001-06-010 7 14 14 0.030 0.130 0.520 0.740 0.820 104 155 338 503
05001-07-010 8 14 14 0.030 0.130 0.570 0.790 0.870 117 174 373 555
05001-09-010 10 14 14 0.030 0.130 0.660 0.880 0.960 149 222 451 671
05001-11-010 12 14 14 0.030 0.130 0.680 0.900 0.990 176 262 511 761
05001-14-010 15 14 14 0.030 0.130 0.740 0.960 1.040 217 323 586 872
05001-19-010 20 14 14 0.030 0.130 0.910 1.130 1.210 285 424 789 1174
05001-24-010 25 14 14 0.030 0.130 1.000 1.220 1.300 337 502 958 1426
05001-29-010 30 14 14 0.030 0.130 1.060 1.280 1.360 402 599 1015 1511
05001-31-010 40 14 14 0.030 0.130 1.180 1.400 1.480 531 791 1234 1837
05001-33-010 50 14 14 0.030 0.130 1.300 1.520 1.600 661 984 1463 2178
Teck 90 Armoured Power
Universal Toll Free Phone: 1.800.665.1025 | 7
CO
NTR
OL
60
0V
MU
LTI
14 AWG
Part Number
No. of Conductors
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over)
Copper Content
Net Weight w/ Armour
Cond. Bond WireInsul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
SPECIFIC ATIONS CONSTRUC TION
Multiconductor 14 AWG 600V XLPE/PVC/AIA/PVC
Conductor: Bare copper Class B compressed stranded
Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
OUTER JACKET
ARMOUR
CONDUCTOR
INSULATION
BONDCONDUCTOR
INNER JACKET
FILLERS
TAPE
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
05002-01-010 2 12 14 0.030 0.150 0.400 0.620 0.700 55 82 228 340
05002-02-010 3 12 14 0.030 0.150 0.430 0.650 0.730 75 112 254 378
05002-03-010 4 12 14 0.030 0.150 0.470 0.690 0.770 96 143 293 436
05002-04-010 5 12 14 0.030 0.150 0.510 0.730 0.810 116 173 350 521
05002-05-010 6 12 14 0.030 0.150 0.590 0.810 0.890 137 204 416 619
05002-06-010 7 12 14 0.030 0.150 0.610 0.830 0.910 157 234 443 660
05002-07-010 8 12 14 0.030 0.150 0.640 0.860 0.940 177 264 492 732
05002-09-010 10 12 14 0.030 0.150 0.730 0.950 1.040 219 326 555 826
05002-11-010 12 12 14 0.030 0.150 0.790 1.010 1.100 261 389 653 972
05002-14-010 15 12 14 0.030 0.150 0.850 1.070 1.160 322 480 757 1127
05002-19-010 20 12 14 0.030 0.150 1.010 1.230 1.320 424 631 986 1468
05002-24-010 25 12 14 0.030 0.150 1.110 1.330 1.420 527 785 1210 1801
05002-29-010 30 12 14 0.030 0.150 1.180 1.400 1.490 630 938 1320 1965
05002-31-010 40 12 14 0.030 0.150 1.320 1.540 1.640 837 1246 1725 2567
05002-49-010 50 12 14 0.030 0.150 1.450 1.670 1.770 1044 1553 2055 3058
Teck 90 Armoured Power
8 | Universal Toll Free Phone: 1.800.665.1025
CO
NTR
OL
60
0V
MU
LTI
SPECIFIC ATIONS CONSTRUC TION
Multiconductor 12 AWG 600V XLPE/PVC/AIA/PVC
Conductor: Bare copper Class B compressed stranded
Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
OUTER JACKET
ARMOUR
CONDUCTOR
INSULATION
BONDCONDUCTOR
INNER JACKET
FILLERS
TAPE
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
12 AWG
Part Number
No. of Conductors
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over)
Copper Content
Net Weight w/ Armour
Cond. Bond WireInsul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
05003-01-010 2 10 12 0.030 0.180 0.450 0.670 0.750 87 130 275 410
05003-02-010 3 10 12 0.030 0.180 0.480 0.700 0.780 119 177 327 487
05003-03-010 4 10 12 0.030 0.180 0.555 0.740 0.830 150 223 413 615
05003-04-010 5 10 12 0.030 0.180 0.600 0.820 0.910 184 274 473 704
05003-05-010 6 10 12 0.030 0.180 0.660 0.880 0.960 217 323 515 766
05003-07-010 8 10 12 0.030 0.180 0.710 0.930 1.020 282 420 613 912
05003-09-010 10 10 12 0.030 0.180 0.860 1.080 1.160 348 518 828 1232
05003-11-010 12 10 12 0.030 0.180 0.930 1.150 1.230 414 617 916 1363
05003-14-010 15 10 12 0.030 0.180 1.000 1.220 1.300 512 762 1084 1613
05003-19-010 20 10 12 0.030 0.180 1.140 1.360 1.440 675 1005 1316 1958
05003-24-010 25 10 12 0.030 0.180 1.250 1.470 1.550 835 1243 1612 2399
05003-29-010 30 10 12 0.030 0.180 1.330 1.550 1.650 998 1493 1821 2709
05003-31-010 40 10 12 0.030 0.180 1.490 1.710 1.810 1321 1966 2278 3390
05003-33-010 50 10 12 0.030 0.180 1.650 1.870 1.970 1648 2453 2820 4196
SPECIFIC ATIONS CONSTRUC TION
Multiconductor 10 AWG 600V XLPE/PVC/AIA/PVC
Conductor: Bare copper Class B compressed stranded
Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
OUTER JACKET
ARMOUR
CONDUCTOR
INSULATION
BONDCONDUCTOR
INNER JACKET
FILLERS
TAPE
HL
Teck 90 Armoured Power
Universal Toll Free Phone: 1.800.665.1025 | 9
CO
NTR
OL
60
0V
MU
LTI
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
10 AWG
Part Number
No. of Conductors
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over)
Copper Content
Net Weight w/ Armour
Cond. Bond WireInsul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
05030-01-010 14 12 14 0.300 0.560 0.780 0.860 114 170 356 530
05030-02-010 14 10 12 0.300 0.590 0.810 0.890 158 235 416 619
05030-03-010 14 8 10 0.450 0.690 0.950 1.000 208 310 541 805
05030-04-010 14 6 8 0.450 0.740 0.990 1.200 338 503 696 1035
05030-05-010 14 4 8 0.450 0.890 1.140 1.250 485 722 972 1446
05030-07-010 14 2 6 0.450 1.020 1.270 1.390 747 1112 1295 1927
05030-08-010 14 1 6 0.550 1.140 1.390 1.500 911 1356 1539 2290
05030-09-010 14 1/0 6 0.550 1.220 1.470 1.590 1117 1662 1798 2676
05030-10-010 14 2/0 6 0.550 1.320 1.570 1.710 1378 2051 2150 3199
05030-12-010 14 4/0 4 0.550 1.550 1.800 1.940 2167 3225 3080 4583
14 AWG
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Control Power Bond Wire Inner Jacket (in.) Armour (in.) Outer Jacket
(in.)LB/
MFTKG/ KM
LB/ MFT
KG/ KM
Teck 90 Armoured Power
10 | Universal Toll Free Phone: 1.800.665.1025
CO
NTR
OL
60
0V
CO
MP
OS
ITE
SPECIFIC ATIONS CONSTRUC TION
Control Composite 3 Power &3 Control Conductors 600V XLPE/PVC/AIA/PVC
Conductor: Bare copper Class B compressed stranded
Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
OUTER JACKET
ARMOUR
CONDUCTOR
INSULATION
BONDCONDUCTOR
INNER JACKET
FILLERS
TAPE
HL
05031-02-010 12 10 12 0.030 0.665 0.865 0.979 180.2 268.0 - 431 641
05031-03-010 12 8 10 0.040 0.755 0.955 1.071 250.7 373.0 544 809
05031-04-010 12 6 8 0.060 0.914 1.134 1.250 361.6 538.0 822 1223
05031-05-010 12 4 8 0.060 0.930 1.160 1.270 508.8 757.0 978 1455
05031-07-010 12 2 6 0.060 1.026 1.246 1.362 772.3 1149.0 1307 1944
05031-08-010 12 1 6 0.080 1.182 1.402 1.518 938.3 1396.0 1587 2361
05031-09-010 12 1/0 6 0.080 1.263 1.483 1.603 1143.3 1701.0 1840 2737
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
12 AWG
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Control Power Bond Wire Inner Jacket (in.) Armour (in.) Outer Jacket
(in.)LB/
MFTKG/ KM
LB/ MFT
KG/ KM
05018-13-010 4 6 0.060 0.350 0.490 0.730 0.810 211 314 410 610
05018-17-010 3 6 0.060 0.380 0.520 0.760 0.840 244 363 450 680
05018-21-010 2 6 0.060 0.420 0.560 0.780 0.870 286 426 510 760
05018-25-010 1 4 0.080 0.490 0.660 0.880 0.960 390 581 680 1010
05019-01-010 1/0 4 0.080 0.530 0.690 0.910 1.000 458 682 760 1130
05019-05-010 2/0 4 0.080 0.580 0.710 0.950 1.040 544 810 860 1280
05019-09-010 3/0 3 0.080 0.630 0.810 1.030 1.120 685 1020 1080 1610
05019-13-010 4/0 3 0.080 0.690 0.860 1.080 1.170 820 1220 1270 1890
05020-01-010 250 2 0.090 0.750 0.990 1.210 1.290 980 1459 1490 2210
05020-05-010 300 2 0.090 0.770 1.040 1.280 1.370 1112 1655 1920 2857
05020-09-010 350 1 0.090 0.815 1.120 1.360 1.445 1340 1994 1910 1910
05020-13-010 400 1 0.090 0.850 1.155 1.395 1.480 1499 2231 2088 3107
05020-21-010 500 1/0 0.090 0.925 1.200 1.475 1.560 1841 2604 2510 3740
05020-25-010 600 1/0 0.090 1.005 1.305 1.545 1.655 2173 3234 2877 4281
05020-41-010 750 2/0 0.090 1.160 1.370 1.590 1.690 2570 3825 3510 5230
05021-01-010 1000 2/0 0.090 1.310 1.590 1.810 1.900 3340 4970 4430 6590
SPECIFIC ATIONS CONSTRUC TION
Single Conductor 1000V XLPE/PVC/AIA/PVC
Conductor: Bare copper Class B compact or compressed stranded
Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
Ground (Bonding) Conductor: Concentric serving of solid bare copper wires applied over the insulation
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Other coloured outer jacket and constructions available upon request
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
OUTER JACKET
ARMOUR
CONDUCTOR
CONCENTRIC COPPERBOND CONDUCTOR
INSULATIONINNER JACKET
TAPE
HL
Teck 90 Armoured Power
Universal Toll Free Phone: 1.800.665.1025 | 11
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
CO
NTR
OL
1K
V T
EC
K
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
05015-01-010 14 14 0.045 0.170 0.430 0.650 0.730 39 58 219 326
05016-01-010 12 14 0.045 0.180 0.470 0.690 0.770 55 82 255 380
05017-01-010 10 12 0.045 0.210 0.510 0.730 0.810 86 128 291 433
05018-02-010 8 10 0.045 0.240 0.600 0.820 0.900 137 204 392 584
05018-10-010 6 8 0.060 0.310 0.720 0.940 1.020 215 320 556 827
05018-14-010 4 8 0.060 0.350 0.850 1.070 1.160 312 464 744 1107
05018-18-010 3 6 0.060 0.380 0.930 1.150 1.230 415 618 905 1347
05018-22-010 2 6 0.060 0.420 0.980 1.200 1.280 502 747 1030 1533
05018-26-010 1 6 0.080 0.490 1.120 1.340 1.420 612 911 1235 1838
05019-02-010 1/0 6 0.080 0.530 1.230 1.450 1.530 740 1101 1425 2120
05019-06-010 2/0 6 0.080 0.580 1.280 1.500 1.580 922 1372 1660 2470
05019-10-010 3/0 4 0.080 0.630 1.370 1.590 1.690 1190 1771 1995 2969
05019-14-010 4/0 4 0.080 0.690 1.480 1.700 1.790 1466 2182 2350 3497
05020-02-010 250 4 0.090 0.750 1.620 1.840 1.930 1709 2543 2779 4135
05020-06-010 300 4 0.090 0.760 1.765 2.005 2.115 2018 3003 3341 4972
05020-10-010 350 3 0.090 0.860 1.870 2.090 2.180 2373 3561 3650 5431
05020-14-010 400 3 0.090 0.850 1.945 2.185 2.295 2687 3999 4147 6171
05020-22-010 500 3 0.090 0.990 2.110 2.330 2.450 3316 4935 4895 7284
05020-42-010 750 1 0.090 1.160 2.450 2.670 2.790 4941 7353 6872 10226
05020-46-010 1000 1 0.090 1.310 2.760 2.980 3.100 6562 9766 8993 13382
Teck 90 Armoured Power
12 | Universal Toll Free Phone: 1.800.665.1025
SPECIFIC ATIONS CONSTRUC TION
Two Conductor 1000V XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
OUTER JACKET
ARMOUR
CONDUCTOR
INSULATION
BONDCONDUCTOR
INNER JACKET
FILLERS
TAPE
HL
CO
NTR
OL1K
V T
EC
K
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
Conductor: Bare copper Class B compact or compressed stranded
Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
05015-02-010 14 14 0.045 0.170 0.470 0.670 0.760 52 77 261 388
05016-02-010 12 14 0.045 0.180 0.510 0.720 0.800 75 112 299 445
05017-02-010 10 12 0.045 0.210 0.590 0.790 0.880 124 185 374 557
05018-03-010 8 10 0.045 0.240 0.630 0.860 0.940 189 281 486 723
05018-11-010 6 8 0.060 0.310 0.780 1.030 1.130 300 447 724 1078
05018-15-010 4 8 0.060 0.350 0.910 1.160 1.250 447 665 970 1444
05018-19-010 3 6 0.060 0.380 0.970 1.220 1.300 582 866 1136 1691
05018-23-010 2 6 0.060 0.420 1.020 1.280 1.370 710 1056 1311 1951
05018-27-010 1 6 0.080 0.490 1.210 1.440 1.540 866 1288 1593 2371
05019-03-010 1/0 6 0.080 0.530 1.290 1.560 1.680 1069 1590 1906 2837
05019-07-010 2/0 6 0.080 0.580 1.380 1.650 1.770 1327 1974 2225 3311
05019-11-010 3/0 4 0.080 0.630 1.490 1.750 1.870 1670 2485 2666 3967
05019-15-010 4/0 4 0.080 0.690 1.600 1.860 1.980 2109 3138 3207 4772
05020-03-010 250 4 0.090 0.750 1.800 2.050 2.170 2470 3675 3800 5655
05020-07-010 300 4 0.090 0.760 1.885 2.125 2.235 2961 4406 4460 6637
05020-11-010 350 3 0.090 0.860 2.010 2.260 2.400 3437 5114 4979 7409
05020-15-010 400 3 0.090 0.850 2.075 2.315 2.455 3948 5875 5719 8511
05020-23-010 500 3 0.090 0.990 2.270 2.520 2.660 4839 7200 6586 9798
05020-28-010 600 2 0.090 1.005 2.410 2.650 2.790 5868 8733 7948 11828
05020-43-010 750 2 0.090 1.160 2.760 2.890 3.030 7225 10751 9267 13790
05021-03-010 1000 1 0.090 1.310 3.080 3.280 3.440 9612 14303 12184 18130
SPECIFIC ATIONS CONSTRUC TION
Three Conductor 1000V XLPE/PVC/AIA/PVC
Conductor: Bare copper Class B compact or compressed stranded
Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
OUTER JACKET
ARMOUR
CONDUCTOR
INSULATION
BONDCONDUCTOR
INNER JACKET
FILLERS
TAPE
HL
Teck 90 Armoured Power
Universal Toll Free Phone: 1.800.665.1025 | 13
CO
NTR
OL1
KV
TE
CK
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
05015-03-010 14 14 0.045 0.170 0.500 0.720 0.800 68 101 290 430
05016-03-010 12 14 0.045 0.180 0.570 0.790 0.880 96 143 357 531
05017-03-010 10 12 0.045 0.210 0.630 0.850 0.930 150 223 455 677
05018-04-010 8 10 0.045 0.240 0.700 0.920 1.000 241 359 548 816
05018-12-010 6 8 0.060 0.310 0.930 1.150 1.250 383 570 907 1350
05018-16-010 4 8 0.060 0.350 1.040 1.260 1.350 579 862 1168 1738
05018-20-010 3 6 0.060 0.380 1.090 1.310 1.400 748 1113 1373 2043
05018-24-010 2 6 0.060 0.420 1.150 1.370 1.460 919 1368 1583 2356
05018-28-010 1 6 0.080 0.490 1.380 1.600 1.720 1128 1679 2032 3024
05019-04-010 1/0 6 0.080 0.530 1.470 1.690 1.810 1398 2081 2365 3520
05019-08-010 2/0 6 0.080 0.580 1.570 1.790 1.910 1742 2593 2745 4085
05019-12-010 3/0 4 0.080 0.630 1.690 1.910 2.030 2223 3308 3398 5057
05019-16-010 4/0 4 0.080 0.690 1.870 2.090 2.210 2769 4121 4170 6205
05020-04-010 250 4 0.090 0.750 2.010 2.230 2.350 3249 4835 4789 7126
05020-12-010 350 3 0.090 0.860 2.240 2.460 2.600 4528 6738 6307 9385
05020-24-010 500 3 0.090 0.990 2.540 2.760 2.900 6395 9516 8438 12556
05020-44-010 750 2 0.090 1.160 3.020 3.240 3.420 9564 14232 12411 18468
Teck 90 Armoured Power
14 | Universal Toll Free Phone: 1.800.665.1025
SPECIFIC ATIONS CONSTRUC TION
Four Conductor 1000V XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
OUTER JACKET
ARMOUR
CONDUCTOR
INSULATION
BONDCONDUCTOR
INNER JACKET
FILLERS
TAPE
HL
CO
NTR
OL1K
V T
EC
K
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
Conductor: Bare copper Class B compact or compressed stranded
Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
19001-01-060 6 8 0.090 0.390 0.540 0.760 0.850 143 213 370 550
19001-02-060 4 6 0.090 0.430 0.620 0.840 0.930 223 332 490 730
19001-04-060 2 6 0.090 0.490 0.670 0.890 0.980 301 448 590 890
19001-05-060 1 4 0.090 0.520 0.710 0.930 1.020 405 603 720 1060
19001-06-060 1/0 4 0.090 0.560 0.740 0.960 1.060 474 705 800 1190
19001-07-060 2/0 4 0.090 0.600 0.810 1.030 1.130 561 835 900 1350
19001-08-060 3/0 3 0.090 0.640 0.860 1.080 1.180 708 1054 1130 1680
19001-09-060 4/0 3 0.090 0.700 0.940 1.160 1.260 847 1261 1330 1970
19001-10-060 250 2 0.090 0.750 1.020 1.240 1.340 1012 1506 1530 2280
19001-11-060 300 2 0.090 0.805 1.075 1.315 1.405 1128 1679 1695 2522
19001-12-060 350 1 0.090 0.850 1.155 1.395 1.480 1345 2001 1960 2910
19001-13-060 400 1 0.090 0.895 1.200 1.440 1.530 1499 2231 2133 3174
19001-15-060 500 1/0 0.090 0.970 1.270 1.490 1.590 1548 2304 2570 3830
19001-16-060 600 1/0 0.090 1.055 1.355 1.595 1.705 2174 3235 2929 4359
19001-24-060 750 2/0 0.090 1.150 1.460 1.680 1.780 2243 3338 3900 5800
19001-25-060 1000 2/0 0.090 1.300 1.640 1.860 1.960 2819 4195 4930 7340
SPECIFIC ATIONS CONSTRUC TION
Unshielded Single Conductor90 MIL 5kV XLPE/PVC/AIA/PVC
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Ground (Bonding) Conductor: Concentric serving of solid bare copper wires applied over the insulation
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange
Options: Other coloured outer jacket and constructions available upon request
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
CONDUCTOR
CONCENTRIC COPPERBOND CONDUCTOR
INSULATIONINNER JACKET
TAPE
HL
Teck 90 Armoured Power
Universal Toll Free Phone: 1.800.665.1025 | 15
CO
NTR
OL
5K
V U
NS
HIE
LDE
D
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
19003-02-060 6 8 0.090 0.390 1.050 1.270 1.370 301 448 927 1380
19003-03-060 4 8 0.090 0.430 1.150 1.370 1.470 442 658 1138 1694
19003-04-060 2 6 0.090 0.490 1.270 1.490 1.590 703 1046 1476 2197
19003-05-060 1 6 0.090 0.520 1.370 1.590 1.690 970 1444 1752 2607
19003-06-060 1/0 6 0.090 0.560 1.450 1.670 1.770 1082 1610 2012 2994
19003-07-060 2/0 6 0.090 0.600 1.540 1.760 1.860 1343 1999 2334 3473
19003-08-060 3/0 4 0.090 0.640 1.650 1.870 1.970 1720 2560 2835 4219
19003-09-060 4/0 4 0.090 0.700 1.760 1.980 2.080 2315 3445 3328 4952
19003-10-060 250 4 0.090 0.750 1.930 2.150 2.250 2469 3684 3910 5819
19003-11-060 300 4 0.090 0.805 1.980 2.220 2.330 2961 4406 4616 6869
19003-12-060 350 3 0.090 0.850 2.140 2.360 2.490 3476 5173 5102 7592
19003-13-060 400 3 0.090 0.895 2.170 2.410 2.550 3948 5875 5836 8685
19003-15-060 500 2 0.090 0.970 2.400 2.620 2.750 4837 7198 6721 10001
19003-16-060 600 2 0.090 1.051 2.530 2.750 2.890 5868 8733 8110 12069
19003-20-060 750 2 0.090 1.150 2.790 3.010 3.140 7224 10750 9469 14090
19003-25-060 1000 1 0.090 1.300 3.170 3.390 3.540 9715 14458 13790 20520
Teck 90 Armoured Power
16 | Universal Toll Free Phone: 1.800.665.1025
SPECIFIC ATIONS CONSTRUC TION
Unshielded Three Conductor90 MIL 5kV XLPE/PVC/AIA/PVC
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
OUTER JACKET
ARMOUR CONDUCTOR
INSULATION
BONDCONDUCTOR
INNER JACKET
FILLERS
TAPE CONDUCTORSHIELD
HL
CO
NTR
OL
5K
V U
NS
HIE
LDE
D
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
Teck 90 Armoured Power
Universal Toll Free Phone: 1.800.665.1025 | 17
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
CONDUCTOR
CONCENTRIC COPPERBOND CONDUCTOR
INSULATIONINNER JACKET
TAPE
19002-02-060 6 8 0.090 0.390 0.680 0.900 0.990 144 214 510 770
19002-03-060 4 6 0.090 0.430 0.720 0.940 1.030 224 333 590 880
19002-04-060 2 6 0.090 0.490 0.780 1.030 1.120 302 449 750 1120
19002-05-060 1 4 0.090 0.520 0.810 1.000 1.150 406 604 870 1300
19002-06-060 1/0 4 0.090 0.560 0.880 1.130 1.220 475 707 1010 1500
19002-07-060 2/0 4 0.090 0.600 0.920 1.170 1.260 562 836 1120 1670
19002-08-060 3/0 3 0.090 0.640 0.970 1.220 1.310 709 1055 1300 1930
19002-09-060 4/0 3 0.090 0.700 1.020 1.270 1.360 843 1255 1470 2180
19002-10-060 250 2 0.090 0.750 1.100 1.380 1.480 1013 1508 1680 2500
19002-12-060 350 1 0.090 0.850 1.240 1.520 1.620 1389 2067 2120 3150
19002-14-060 500 1/0 0.090 0.970 1.340 1.620 1.720 1928 2869 2770 4130
19002-16-060 750 2/0 0.090 1.150 1.540 1.830 1.930 2820 4197 3780 5760
19002-17-060 1000 2/0 0.090 1.300 1.760 2.050 2.150 3607 5368 5010 7460
SPECIFIC ATIONS CONSTRUC TION
Shielded Single Conductor90 MIL 100% 5kV TR-XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Ground (Bonding/Shield) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange
Options: Other coloured outer jacket and constructions available upon request
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
Teck 90 Armoured Power
18 | Universal Toll Free Phone: 1.800.665.1025
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
19008-02-060 6 8 0.090 0.900 1.170 1.450 1.540 349 519 1120 1670
19008-03-060 4 8 0.090 0.430 1.260 1.540 1.630 503 749 1350 2010
19008-04-060 2 6 0.090 0.490 1.390 1.670 1.770 771 1147 1740 2590
19008-05-060 1 6 0.090 0.520 1.450 1.730 1.830 939 1397 1960 2920
19008-06-060 1/0 6 0.090 0.560 1.530 1.810 1.910 1148 1708 2290 3410
19008-07-060 2/0 6 0.090 0.600 1.620 1.910 2.010 141 2104 2620 3900
19008-08-060 3/0 4 0.090 0.640 1.780 2.070 2.170 1798 2668 3210 4780
19008-09-060 4/0 4 0.090 0.700 1.900 2.190 2.290 2212 3292 3720 5530
19008-10-060 250 4 0.090 0.750 2.010 2.300 2.430 2583 3844 4300 6400
19008-11-060 300 4 0.090 0.890 2.115 2.355 2.495 3058 4551 4980 7411
19008-12-060 350 3 0.090 0.906 2.210 2.450 2.590 3569 5311 5638 8390
19008-13-060 400 3 0.090 0.960 2.315 2.555 2.695 4054 6033 6202 9230
19008-14-060 500 2 0.090 0.970 2.480 2.770 2.900 4998 7438 7130 10610
19008-16-060 600 2 0.090 1.115 2.645 2.885 3.025 5991 8916 8471 12606
19008-20-060 750 2 0.090 1.150 2.980 3.270 3.420 7440 11072 10330 15370
19008-25-060 1000 1 0.090 1.300 3.310 3.600 3.750 9860 14674 13080 19460
SPECIFIC ATIONS CONSTRUC TION
Shielded Three Conductor90 MIL 100% 5kV TR-XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Metallic Shield: Helically applied 15% gapped copper tape
Ground (Bonding) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request Helically applied 20% overlapped copper tape shield
INSULATION
BONDCONDUCTOR
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
FILLERS
INNER JACKET
CONDUCTOR
COPPERTAPE
INSULATIONSHIELD
TAPE
HL
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
CONDUCTOR
CONCENTRIC COPPERBOND CONDUCTOR
INSULATIONINNER JACKET
TAPE
Teck 90 Armoured Power
Universal Toll Free Phone: 1.800.665.1025 | 19
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
19012-02-060 6 8 0.115 0.440 0.730 0.950 1.040 145 216 550 820
19012-03-060 4 6 0.115 0.480 0.770 0.990 1.080 225 335 680 1010
19012-04-060 2 6 0.115 0.540 0.830 1.080 1.170 303 451 840 1250
19012-05-060 1 4 0.115 0.570 0.910 1.160 1.250 407 606 960 1430
19012-06-060 1/0 4 0.115 0.610 0.940 1.190 1.280 453 674 1060 1570
19012-07-060 2/0 4 0.115 0.650 0.980 1.230 1.320 476 708 1170 1740
19012-08-060 3/0 3 0.115 0.700 1.030 1.310 1.400 563 838 1350 2000
19012-09-060 4/0 3 0.115 0.750 1.080 1.360 1.450 710 1057 1520 2260
19012-10-060 250 2 0.115 0.800 1.160 1.440 1.530 849 1263 1730 2580
19012-12-060 350 1 0.115 0.940 1.290 1.570 1.670 1169 1740 2170 3230
19012-14-060 500 1/0 0.115 1.020 1.410 1.690 1.790 1390 2069 2860 4260
19012-16-060 750 2/0 0.115 1.200 1.600 1.890 1.990 2821 4198 3940 5860
19012-17-060 1000 2/0 0.115 1.350 1.810 2.100 2.200 3608 5369 5090 7570
SPECIFIC ATIONS CONSTRUC TION
Shielded Single Conductor115 MIL 133% 5kV (aka 100% 8kV)
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Ground (Bonding/Shield) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange
Options: Other coloured outer jacket and constructions available upon request
(Per AEIC)
TR-XLPE/PVC/AIA/PVC
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
19018-03-060 4 8 0.115 0.480 1.370 1.650 1.750 505 752 1500 2230
19018-04-060 2 6 0.115 0.540 1.500 1.780 1.880 744 1152 1930 2870
19018-05-060 1 6 0.115 0.570 1.570 1.860 1.960 943 1403 2150 3200
19018-06-060 1/0 6 0.115 0.610 1.650 1.940 2.040 1151 1713 2430 3620
19018-07-060 2/0 6 0.115 0.650 1.800 2.090 2.190 1417 2109 2890 4300
19018-08-060 3/0 4 0.115 0.700 1.900 2.190 2.290 1796 2673 3360 5000
19018-09-060 4/0 4 0.115 0.750 2.010 2.300 2.430 2215 3296 3940 5860
19018-10-060 250 4 0.115 0.800 2.130 2.420 2.550 2583 3844 4470 6650
19018-11-060 300 4 0.115 0.920 2.225 2.465 2.605 3064 4560 5155 7671
19018-12-060 350 3 0.115 0.940 2.430 2.720 2.850 3572 5316 5650 8400
19018-14-060 500 2 0.115 1.020 2.640 2.930 3.060 5004 7447 7440 11070
SPECIFIC ATIONS CONSTRUC TION
Shielded Three Conductor115 MIL 133% 5kV (aka 100% 8kV)
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
INSULATION
BONDCONDUCTOR
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
FILLERS
INNER JACKET
CONDUCTOR
COPPERTAPE
INSULATIONSHIELD
TAPE
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Metallic Shield: Helically applied 15% gapped copper tape
Ground (Bonding) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request Helically applied 20% overlapped copper tape shield
Teck 90 Armoured Power
20 | Universal Toll Free Phone: 1.800.665.1025
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
(Per AEIC)
TR-XLPE/PVC/AIA/PVC
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
INSULATION
BONDCONDUCTOR
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
FILLERS
INNER JACKET
CONDUCTOR
COPPERTAPE
INSULATIONSHIELD
TAPE
19014-01-012 6 8 0.140 0.495 1.405 1.645 1.755 403 600 1434 2134
19014-04-012 4 8 0.140 0.535 1.490 1.730 1.840 513 763 1619 2409
19014-02-012 2 6 0.140 0.590 1.610 1.850 1.960 783 1165 2127 3165
19014-05-012 1 6 0.140 0.621 1.735 1.975 2.085 951 1415 2482 3694
19014-06-012 1/0 6 0.140 0.658 1.815 2.055 2.165 1160 1726 2769 4121
19014-07-012 2/0 6 0.140 0.702 1.910 2.150 2.260 1426 2122 3137 4668
19014-08-012 3/0 4 0.140 0.749 2.010 2.250 2.390 1759 2618 3679 5475
19014-09-012 4/0 4 0.140 0.801 2.125 2.365 2.505 2226 3313 4258 6337
19014-10-012 250 4 0.140 0.843 2.215 2.455 2.595 2595 3862 4716 7018
19014-13-012 300 4 0.140 0.896 2.325 2.570 2.710 3069 4567 5330 7932
19014-11-012 350 3 0.140 0.940 2.425 2.665 2.810 3583 5332 5977 8895
19014-14-012 400 3 0.140 0.985 2.520 2.760 2.900 4065 6049 6551 9749
19014-12-012 500 2 0.140 1.065 2.685 2.925 3.065 4935 7344 7590 11295
19014-15-012 600 2 0.140 1.140 2.920 3.160 3.330 6001 8390 9143 13606
19014-16-012 750 2 0.140 1.235 3.125 3.365 3.535 7438 11069 10891 16208
19014-17-012 1000 1 0.140 1.385 3.455 3.695 3.865 9868 14685 13765 20485
Teck 90 Armoured Power
Universal Toll Free Phone: 1.800.665.1025 | 21
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
SPECIFIC ATIONS CONSTRUC TION
Shielded Three Conductor140 MIL 133% 8kV TR-XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Metallic Shield: Helically applied 15% gapped copper tape
Ground (Bonding) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request Helically applied 20% overlapped copper tape shield
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
19020-04-032 2 6 0.220 0.760 1.090 1.340 1.430 286 426 1028 1530
19020-05-032 1 4 0.220 0.790 1.120 1.370 1.460 391 582 1170 1740
19020-06-032 1/0 4 0.220 0.830 1.160 1.410 1.500 459 683 1270 1890
19020-07-032 2/0 4 0.220 0.860 1.200 1.450 1.540 546 813 1390 2060
19020-08-032 3/0 3 0.220 0.910 1.250 1.500 1.590 693 1031 1570 2340
19020-09-032 4/0 3 0.220 0.960 1.300 1.580 1.680 830 1235 1780 2650
19020-10-032 250 2 0.220 1.020 1.380 1.660 1.760 989 1472 2010 2990
19020-11-032 350 1 0.220 1.120 1.500 1.780 1.880 1228 1827 2490 3700
19020-12-032 500 1/0 0.220 1.240 1.650 1.940 2.040 1896 2821 3220 4790
19022-12-032 750 2/0 0.220 1.420 1.890 2.180 2.280 2766 4116 4390 6530
19022-25-032 1000 2/0 0.220 1.570 2.050 2.340 2.480 3552 5286 5550 8260
Teck 90 Armoured Power
22 | Universal Toll Free Phone: 1.800.665.1025
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
SPECIFIC ATIONS CONSTRUC TION
Shielded Single Conductor220 MIL 133% 15kV TR-XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
CONDUCTORINSULATION
CONCENTRIC COPPERBOND CONDUCTOR
INSULATIONSHIELD
INNER JACKET
TAPE
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Ground (Bonding/Shield) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), red
Options: Other coloured outer jacket and constructions available upon request
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
19022-01-032 2 6 0.220 0.760 2.020 2.310 2.430 793 1180 2665 3966
19022-02-032 1 6 0.220 0.790 2.100 2.370 2.490 964 1435 3089 4597
19022-03-032 1/0 6 0.220 0.830 2.170 2.460 2.580 1175 1749 3300 4900
19022-04-032 2/0 6 0.220 0.860 2.260 2.550 2.670 1438 2140 3650 5430
19022-05-032 3/0 4 0.220 0.910 2.360 2.650 2.770 1821 2710 4140 6160
19022-06-032 4/0 4 0.220 0.960 2.470 2.760 2.880 2248 3345 4680 6960
19022-07-032 250 4 0.220 1.020 2.590 2.880 3.000 2607 3880 5275 7850
19022-08-032 350 3 0.220 1.120 2.900 3.190 3.330 3597 5353 6842 10181
19022-11-032 500 3 0.220 1.240 3.160 3.450 3.590 5022 7474 8513 12668
19022-16-032 750 2 0.220 1.420 3.570 3.850 4.000 7452 11090 11507 17122
Teck 90 Armoured Power
Universal Toll Free Phone: 1.800.665.1025 | 23
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
SPECIFIC ATIONS CONSTRUC TION
Shielded Three Conductor220 MIL 133% 15kV TR-XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Metallic Shield: Helically applied 15% gapped copper tape
Ground (Bonding) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), red
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request Helically applied 20% overlapped copper tape shield
INSULATION
BONDCONDUCTOR
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
FILLERS
INNER JACKET
CONDUCTOR
COPPERTAPE
INSULATIONSHIELD
TAPE
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
19023-02-012 1 4 0.320 0.990 1.365 1.605 1.715 385 573 1386 2063
19023-03-012 1/0 4 0.320 1.026 1.415 1.655 1.765 453 674 1568 2333
19023-04-012 2/0 4 0.320 1.066 1.455 1.695 1.805 538 801 1634 2432
19023-05-012 3/0 3 0.320 1.113 1.490 1.730 1.840 685 1019 1970 2932
19023-06-012 4/0 3 0.320 1.185 1.560 1.800 1.910 818 1217 2136 3179
19023-08-012 250 2 0.320 1.218 1.640 1.880 1.990 974 1449 2366 3521
19023-10-012 350 1 0.320 1.315 1.800 2.040 2.150 1343 1999 2966 4414
19023-12-012 500 1/0 0.320 1.454 1.940 2.180 2.290 1866 2777 3654 5438
19023-14-012 750 2/0 0.320 1.620 2.105 2.350 2.485 2642 3932 4677 6960
19023-15-012 1000 3/0 0.320 1.770 2.235 2.475 2.615 3491 5195 5665 8430
Teck 90 Armoured Power
24 | Universal Toll Free Phone: 1.800.665.1025
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
SPECIFIC ATIONS CONSTRUC TION
Shielded Single Conductor320 MIL 133% 25kV TR-XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
CONDUCTORINSULATION
CONCENTRIC COPPERBOND CONDUCTOR
INSULATIONSHIELD
INNER JACKET
TAPE
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Ground (Bonding/Shield) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Other coloured outer jacket and constructions available upon request
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
19026-02-012 1 6 0.320 0.990 2.530 2.820 2.940 985 1466 3690 5490
19026-03-012 1/0 6 0.320 1.030 2.650 2.940 3.060 1193 1775 4110 6120
19026-06-012 2/0 6 0.320 1.070 2.740 3.030 3.150 1460 2173 4490 6680
19026-04-012 3/0 4 0.320 1.120 2.910 3.190 3.330 1842 2741 5270 7840
19026-05-012 4/0 4 0.320 1.170 3.020 3.310 3.440 2261 3365 5840 8700
19026-08-012 250 4 0.320 1.220 3.150 3.430 3.580 2629 3912 6440 9590
19026-11-012 350 3 0.320 1.370 3.440 3.730 3.880 3615 5380 7720 11490
19026-12-012 500 2 0.320 1.454 3.625 3.865 4.035 5096 7584 9943 14797
Teck 90 Armoured Power
Universal Toll Free Phone: 1.800.665.1025 | 25
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
SPECIFIC ATIONS CONSTRUC TION
Shielded Three Conductor320 MIL 133% 25kV TR-XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Metallic Shield: Helically applied 15% gapped copper tape
Ground (Bonding) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request Helically applied 20% overlapped copper tape shield
INSULATION
BONDCONDUCTOR
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
FILLERS
INNER JACKET
CONDUCTOR
COPPERTAPE
INSULATIONSHIELD
TAPE
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
19031-02-012 1 4 0.345 1.035 1.385 1.625 1.735 387 576 2477 3686
19031-03-012 1/0 4 0.345 1.076 1.465 1.705 1.815 453 674 1565 2329
19031-04-012 2/0 4 0.345 1.116 1.505 1.745 1.855 538 801 1841 2740
19031-05-012 3/0 3 0.345 1.160 1.525 1.765 1.875 678 1009 1982 2950
19031-06-012 4/0 3 0.345 1.215 1.605 1.845 1.955 818 1217 2204 3280
19031-08-012 250 2 0.345 1.255 1.645 1.885 1.995 975 1451 2397 3567
19031-10-012 350 1 0.345 1.365 1.850 2.090 2.200 1343 1999 3058 4551
19031-12-012 500 1/0 0.345 1.506 1.990 2.230 2.340 1868 2780 3729 5549
19031-14-012 750 2/0 0.345 1.620 2.105 2.345 2.485 2723 4052 4758 7081
19031-15-012 1000 2/0 0.345 1.810 2.280 2.520 2.660 3491 5195 5740 8542
Teck 90 Armoured Power
26 | Universal Toll Free Phone: 1.800.665.1025
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
SPECIFIC ATIONS CONSTRUC TION
Shielded Single Conductor345 MIL 133% 28kV TR-XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
CONDUCTORINSULATION
CONCENTRIC COPPERBOND CONDUCTOR
INSULATIONSHIELD
INNER JACKET
TAPE
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Ground (Bonding/Shield) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Other coloured outer jacket and constructions available upon request
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
19027-01-012 1 6 0.345 1.040 2.680 2.970 3.100 988 1470 3980 5930
19027-02-012 1/0 6 0.345 1.080 2.760 3.050 3.180 1200 1786 4360 6490
19027-03-012 2/0 6 0.345 1.120 2.920 3.210 3.360 1466 2182 4950 7370
19027-04-012 3/0 4 0.345 1.170 3.020 3.310 3.460 1848 2750 5490 8160
19027-05-012 4/0 4 0.345 1.220 3.140 3.430 3.580 2264 3369 6090 9060
19027-06-012 250 4 0.345 1.270 3.260 3.550 3.700 2635 3921 6660 9910
19027-08-012 350 3 0.345 1.420 3.560 3.850 4.000 3621 5389 7960 11840
19027-10-012 500 2 0.345 1.506 3.740 3.900 4.150 2893 3980 8008 11917
Teck 90 Armoured Power
Universal Toll Free Phone: 1.800.665.1025 | 27
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
SPECIFIC ATIONS CONSTRUC TION
Shielded Three Conductor345 MIL 133% 28kV TR-XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Metallic Shield: Helically applied 15% gapped copper tape
Ground (Bonding) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request Helically applied 20% overlapped copper tape shield
INSULATION
BONDCONDUCTOR
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
FILLERS
INNER JACKET
CONDUCTOR
COPPERTAPE
INSULATIONSHIELD
TAPE
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
CONDUCTORINSULATION
CONCENTRIC COPPERBOND CONDUCTOR
INSULATIONSHIELD
INNER JACKET
TAPE
19030-02-010 1/0 4 0.345 1.076 1.465 1.705 1.815 453 674 1565 2329
19030-03-010 2/0 4 0.345 1.116 1.505 1.745 1.885 538 801 1841 2740
19030-04-010 3/0 3 0.345 1.160 1.525 1.765 1.875 678 1009 1982 2950
19030-05-010 4/0 3 0.345 1.215 1.605 1.845 1.955 818 1217 2204 3280
19030-06-010 250 2 0.345 1.255 1.645 1.885 1.995 975 1451 2397 3567
19030-08-010 350 1 0.345 1.365 1.850 2.090 2.200 1343 1999 3058 4551
19030-10-010 500 1/0 0.345 1.506 1.990 2.230 2.340 1868 2780 3729 5549
19030-12-010 750 2/0 0.345 1.620 2.105 2.345 2.485 2723 4052 4758 7081
19030-15-010 1000 2/0 0.345 1.810 2.280 2.520 2.660 3491 5195 5740 8542
Teck 90 Armoured Power
28 | Universal Toll Free Phone: 1.800.665.1025
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
SPECIFIC ATIONS CONSTRUC TION
Shielded Single Conductor345 MIL 100% 35kV TR-XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Ground (Bonding/Shield) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Other coloured outer jacket and constructions available upon request
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
19028-02-010 1/0 6 0.345 1.080 2.760 3.050 3.180 1200 1786 4360 6488
19028-03-010 2/0 6 0.345 1.120 2.920 3.210 3.360 1466 2182 4950 7366
19028-04-010 3/0 4 0.345 1.170 3.020 3.310 3.460 1848 2750 5490 8170
19028-05-010 4/0 4 0.345 1.220 3.140 3.430 3.580 2264 3369 6090 9063
19028-06-010 250 4 0.345 1.270 3.260 3.550 3.700 2635 3921 6660 9911
19028-08-010 350 3 0.345 1.420 3.560 3.850 4.000 3621 5389 7960 11846
19028-11-010 500 3 0.345 1.510 3.740 3.980 4.250 2893 4305 10133 15083
Teck 90 Armoured Power
Universal Toll Free Phone: 1.800.665.1025 | 29
CO
NTR
OL
ME
DIU
M V
OLT
AG
ES
HIE
LDE
D
SPECIFIC ATIONS CONSTRUC TION
Shielded Three Conductor345 MIL 100% 35kV TR-XLPE/PVC/AIA/PVC
• CSA FT1 & FT4
• CSA C22.2 No. 131 & 174
• CSA C68.10
• IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
• ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
• ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
*Refer to CE Code for details
HL
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice.
* See pages 30 & 31 for corresponding connector.
Conductor: Bare copper Class B compact or compressed stranded
Conductor Shield: Extruded thermoset semi-conducting shield
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded thermosetting semi-conducting shield
Metallic Shield: Helically applied 15% gapped copper tape
Ground (Bonding) Conductor: Stranded bare copper conductor
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armour (GSIA) Other coloured outer jacket and constructions available upon request Helically applied 20% overlapped copper tape shield
INSULATION
BONDCONDUCTOR
CONDUCTORSHIELD
OUTER JACKET
ARMOUR
FILLERS
INNER JACKET
CONDUCTOR
COPPERTAPE
INSULATIONSHIELD
TAPE
Part Number
AWG SizeInsulation Thickness
(in.)
Approximate Diameter (Over) Copper Content Net Weight
w/ Armour
Cond. Bond Wire Insul.(in.)
Inner Jacket (in.)
Armour (in.)
Outer Jacket (in.)
LB/ MFT
KG/ KM
LB/ MFT
KG/ KM
Teck Connector
30 | Universal Toll Free Phone: 1.800.665.1025
TMC2 Connector
Hub Size(in.)
Part Number Cable Armour Diameter (in.)
Cable Jacket DiameterOverall OD (in.)
Aluminum Min Max Min Max
1 0.50 18-TMC2-050A075 0.420 0.630 0.500 0.750
2 0.50 18-TMC2-050A099 0.600 0.890 0.690 0.990
1A 0.75 18-TMC2-075A075 0.420 0.630 0.500 0.750
2A 0.75 18-TMC2-075A099 0.600 0.890 0.690 0.990
3 0.75 18-TMC2-075A118 0.790 1.100 0.870 1.180
3A 1.00 18-TMC2-100A118 0.790 1.100 0.870 1.180
4 1.00 18-TMC2-100A137 0.940 1.280 1.020 1.370
4A 1.25 18-TMC2-125A137 0.940 1.280 1.020 1.370
5 1.25 18-TMC2-125A162 1.220 1.500 1.300 1.620
6 1.25 18-TMC2-125A190 1.490 1.720 1.570 1.900
5A 1.50 18-TMC2-150A162 1.220 1.500 1.300 1.620
6A 1.50 18-TMC2-150A190 1.490 1.720 1.570 1.900
7 1.50 18-TMC2-150A200 1.570 1.880 1.650 2.000
8 1.50 18-TMC2-150A233 1.790 2.210 1.910 2.330
7A 2.00 18-TMC2-200A200 1.570 1.880 1.650 2.000
8A 2.00 18-TMC2-200A233 1.790 2.210 1.910 2.330
9 2.00 18-TMC2-200A272 2.140 2.610 2.270 2.720
9A 2.50 18-TMC2-250A272 2.140 2.610 2.270 2.720
10 3.00 18-TMC2-300A325 2.490 2.970 2.620 3.250
10A 3.50 18-TMC2-350A325 2.490 2.970 2.620 3.250
11 3.50 18-TMC2-350A376 2.950 3.540 3.160 3.760
11A 4.00 18-TMC2-400A376 2.950 3.540 3.160 3.760
12 4.00 18-TMC2-400A425 3.520 3.940 3.700 4.250
Standard: Aluminum connectors
Options: Also available in nickel plated brass and stainless steel connectors
Locknuts: Aluminum connectors up to 1” hub size - steel locknut included Aluminum connectors above 1” hub size - sold separately Nickel plated connectors - all sizes sold separately Stainless steel connectors - all sizes sold separately
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice
Hub Size(in.)
Part Number Cable Armour Diameter (in.)
Cable Jacket DiameterOverall OD (in.)
Aluminum Min Max Min Max
1 0.50 18-TMC2X-050AX075 0.420 0.630 0.500 0.750
2 0.50 18-TMC2X-050AX099 0.600 0.890 0.690 0.990
1A 0.75 18-TMC2X-075AX075 0.420 0.630 0.500 0.750
2A 0.75 18-TMC2X-075AX099 0.600 0.890 0.690 0.990
3 0.75 18-TMC2X-075AX118 0.790 1.100 0.870 1.180
3A 1.00 18-TMC2X-100AX118 0.790 1.100 0.870 1.180
4 1.00 18-TMC2X-100AX137 0.940 1.280 1.020 1.370
4A 1.25 18-TMC2X-125AX137 0.940 1.280 1.020 1.370
5 1.25 18-TMC2X-125AX162 1.220 1.500 1.300 1.620
6 1.25 18-TMC2X-125AX190 1.490 1.720 1.570 1.900
5A 1.50 18-TMC2X-150AX162 1.220 1.500 1.300 1.620
6A 1.50 18-TMC2X-150AX190 1.490 1.720 1.570 1.900
7 1.50 18-TMC2X-150AX200 1.570 1.880 1.650 2.000
8 1.50 18-TMC2X-150AX233 1.790 2.210 1.910 2.330
7A 2.00 18-TMC2X-200AX200 1.570 1.880 1.650 2.000
8A 2.00 18-TMC2X-200AX233 1.790 2.210 1.910 2.330
9 2.00 18-TMC2X-200AX272 2.140 2.610 2.270 2.720
8B 2.50 18-TMC2X-250AX233 1.790 2.210 1.910 2.330
9A 2.50 18-TMC2X-250AX272 2.140 2.610 2.270 2.720
9B 3.00 18-TMC2X-300AX272 2.140 2.610 2.270 2.720
10 3.00 18-TMC2X-300AX325 2.490 2.970 2.620 3.250
10A 3.50 18-TMC2X-350AX325 2.490 2.970 2.620 3.250
11 3.50 18-TMC2X-350AX376 2.950 3.540 3.160 3.760
11A 4.00 18-TMC2X-400AX376 2.950 3.540 3.160 3.760
12 4.00 18-TMC2X-400AX425 3.520 3.940 3.700 4.250
TMC2X Connector
EDITOR’S NOTE: Texcan has made every effort to ensure the accuracy of the information in this catalogue. Information contained herein neither constitutes endorsement of theproduct nor does Texcan make any claims or guarantees as to the accuracy or the completeness of the information. All information is subject to change without notice and suggestionsmade are not to be understood as recommendations to use any products in violation of any regulation or laws relating to any material or its intended use.
Universal Toll Free Phone: 1.800.665.1025 | 31
Teck Connector
Note: All dimensions are nominal and are subject to normal manufacturing tolerance. Specifications are subject to change without prior notice
Standard: Aluminum connectors
Options: Also available in nickel plated brass and stainless steel connectors
Locknuts: All sizes sold separately RapidEX Sealer Included with Connector
Note: On single conductor cables above 600 volts, please contact a Texcan Representative.
28 0.08
26 0.13
24 0.20
22 0.32
20 0.52
18 0.82
16 1.31
Metric Conversions
32 | Universal Toll Free Phone: 1.800.665.1025
AWG to Metric Conversion Chart
Length Conversions
Mass Conversions
Length & Mass Conversions
Temperature Conversions
AWG mm2
From To Multiply By
From To Multiply By
From To Multiply By
From To Multiply By
From To Multiply By
From To Multiply By
AWG mm2AWG mm2 AWG mm2
14 2.08
12 3.31
10 5.26
8 8.37
6 13.30
4 21.15
3 26.66
2 33.63
1 42.41
1/0 53.51
2/0 67.44
3/0 85.03
4/0 107.22
250 126.68
300 152.01
350 177.35
400 202.68
500 253.35
600 304.02
750 380.03
1000 506.71
Kilometers Miles 0.06214
Meters Feet 3.2808
Meters Inches 39.3701
Meters Yards 1.0936
Centimeters Inches 0.3937
Centimeters Feet 0.03281
Millimeters Inches 0.03937
Millimeters Mils 39.3701
Mils Inches 0.001
Miles Kilometers 1.6093
Yards Meters 0.9144
Feet Meters 0.3048
Feet Centimeters 30.48
Inches Meters 0.0254
Inches Centimeters 2.54
Inches Millimeters 25.4
Inches Mils 1000.0
Mils Millimeters 0.0254
Kilograms Pounds 2.205
Kilograms Short Tons 0.0011
Grams Grains 15.4323
Grams Ounces 0.0352
Pounds Kilograms 0.4535
Short Tons Kilograms 907.1848
Grains Grams 0.0647
Ounces Grams 28.3495
KG/KM LBS/MFT 0.6719
LBS/MFT KG/KM 1.488
Celsius Fahrenheit (ºC x 9/5 ) + 32
Fahrenheit Celsius (ºF - 32) x 5/9
Installation Data
Universal Toll Free Phone: 1.800.665.1025 | 33
Bending Radius Pulling Tension
Power Cables Without Metallic Shielding or Armour The minimum bending radii for both single and multiconductor non-shielded cables without metallic shielding or armour are as follows:
Power Cables Over 600V, Unshielded,UnarmouredThe minimum bending radius for all cables is six times theoverall cable diameter.
Power Cables Over 600V, ShieldedThe minimum bending radius for all cables is twelve times theoverall cable diameter.
Interlocked Armoured Cable, All VoltagesFor unshielded Teck cables, the minimum bending radius issix times the armour outside diameter (as per rule 12-614).For shielded Teck cables, the minimum bending radius is twelvetimes the diameter (as per Table 15 of the C.E.C.).
*Please refer to the C.E.C. for additional information.
Note: Bending radius refers to the inner surface of the cable at the bend and not at the axis of the cable.
The following recommendations are based on a study sponsored by ICEA. These recommendations may be modified if experience and more exact information so indicate.
A. Maximum Pulling Tension on Cable (maximum 10,000 lbs) 1. With pulling eye attached to copper conductors:
TM = 0.008 x n x CM where: TM = maximum tension, lbs
n = number of conductors CM= circular mil area of each conductor
2. With cable grip over lead sheath: TM = 4712 t (D - t) where: TM = maximum tension, lbs
t = sheath thickness, inches D = overall diameter of cable, inches
3. With cable grip over non-leaded cable, the maximum pulling tension should not exceed 1000 lbs or the maximum obtained using TM = 0.008 x n x CM.
4. When more than three conductors are pulled together, the maximum pulling tension should be reduced by 20%.
B. Maximum Permissible Pulling Length LM = (TM) / (f x W) where: LM = pulling length, feet (straight section)
TM = maximum tension, lbs f = coefficient of friction (usually 0.5) W = weight of cable, lbs/ft
C. Pulling Tension Requirements in Ducts / Raceway (refer to rule 12-902 in CE Code) 1. For straight sections:
TS = L x W x f where: TS = tension at pulling end of straight section, lbs
L = length of straight section, ft W = weight of cable, lbs/ft f = coefficient of friction (usually 0.5)
2. For curved sections: TC = T1efa where: TC = cable tension at pulling end of curved section, lbs
T1 = cable tension at feeding end of curved section, lbs e = naperian logarithm base (2.718) f = coefficient of friction (usually 0.5) a = angle of bend, radians (1 radian = 57.3º)
.169 and Less 4 5 6
.170 - .310 5 6 7
.311 and Over - 7 8
Thickness ofConductorInsulationin Inches
Minimum Bending Radiusas a Multiple of Cable Diameter
Overall Diameter of Cable in Inches
1.000and Less
1.001to 2.000
2.001and Over
34 | Universal Toll Free Phone: 1.800.665.1025
Notes
Universal Toll Free Phone: 1.800.665.1025 | 35
Notes
36 | Universal Toll Free Phone: 1.800.665.1025
Notes
Universal Toll Free Phone: 1.800.665.1025 | 37
Notes
38 | Universal Toll Free Phone: 1.800.665.1025
Notes
Cable Management Program• Competitive contract pricing• Customer specified tagging requirements• Customer specified reel sizes• Custom cut lengths• Long lengths capability• Timely product releases
(reduces on-site storage space and costs)• Product on-site scheduling• Custom packing slips• Bar coded product labels• Weatherproof reel tags• Expediting and progress reports
Specialized Technical Assistance• Technical expertise on cable applications,
installation procedures, ampacities, bending radii, terminations and cable selection
Customized Cable Solutions• Special constructions built to customer
specifications when requested
International Export Services• Specialized export services, packaging, labeling,
freight consolidation, customs advisory services and adherence to Incoterms 2010
Paralleling• Offers a contractor a significant installation advantage
in a single reel containing multiple phase conductors
Lagging• A safe method of protecting cables that must be
transported through rough terrain involving 2” x 4” lumber ‘lags’ which are fastened across the flanges encasing the cable reel
Pulling Eyes and Bolts• A pulling line can be attached to the cable when
requested to aid in the installation of cables into conduit, tray or duct
Just-In-Time (JIT)• Just-in-time shipments to job sites across
North America through our network of distribution warehouses
• Our stocking, cutting and shipment expertise ensure that your wire and cable requirements are satisfied and project delays eliminated
After Hours, Emergency Service• We understand that our customers’ needs don’t
always fall within the course of a normal business day, therefore we provide 24/7 service
Our Value Added Services
Quality Service is Our Source of Pride
wire and cable specialists since 1978VANCOUVER (Head Office)10449 120th Street (Scott Rd.)Surrey, BC V3V 4G4Tel: 604.528.3600Fax: 604.528.3790Toll Free: 1.800.665.1025Toll Free Fax: 1.877.606.1090
EDMONTON11330 - 189 Street NW Edmonton, AB T5S 2V6 Tel: 780.944.9331 Fax: 780.486.3182 Toll Free: 1.800.252.7545 Toll Free Fax: 1.877.486.3182
CALGARY#105 – 10710 - 25 Street NE Calgary, AB T3N 0A1 Tel: 403.717.3900 Fax: 403.717.3910 Toll Free: 1.855.717.3900 Toll Free Fax: 1.855.717.3910
Email [email protected] www.texcan.com
SASKATOON3403 Faithfull Avenue Saskatoon, SK S7K 8H6 Tel: 306.385.3800 Fax: 306.385.3810 Toll Free: 1.855.385.3800 Toll Free Fax: 1.855.385.3810
WINNIPEG25 Meridian DriveWinnipeg, MB R2R 1J4Tel: 204.982.9290Fax: 204.661.8459Toll Free: 1.800.665.2491Toll Free Fax: 1.877.661.8459
TCK 0416