technology infinity®
TRANSCRIPT
energy efficient - environmentally friendly - economicalEC MOTORS - diRECT dRivE - CuSTOM builT
ErP Compliant
infinity®
AIR VENTT E C H N O L O G Y
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 2
infinity® - ec motorINDEX
Selection Chart Page 3
Internal & External Acoustic Cabinet & Twin Fans - General Page 6
Performance - QSS-EC/EM-EC/QST-EC/EMT-EC 150s Page 7
Performance - QSS-EC/EM-EC/QST-EC/EMT-EC 200s Page 8
Performance - QSS-EC/EM-EC/QST-EC/EMT-EC 250s Page 9
Performance - QSS-EC/EM-EC/QST-EC/EMT-EC 310s Page 10
Performance - QSS-EC/EM-EC/QST-EC/EMT-EC 350s Page 11
Performance - QSS-EC/EM-EC/QST-EC/EMT-EC 450s Page 12
Performance - QSS-EC/EM-EC/QST-EC/EMT-EC 560s Page 13
Dimensions - QSS-EC/EM-EC - single Page 14
Dimensions - QST-EC/EMT-EC - twin Page 15
Heat Recovery Units - Internal & External: Side by Side & Stacked: EHB or LPHW heating coil - General Page 16
Performance - HRP1EC Page 17
Performance - HRP2EC Page 18
Dimensions - HRP1EC & HRP2EC Page 19
Performance - HRP3EC Page 20
Performance - HRP4EC Page 21
Performance - HRP5-1EC Page 22
Performance - HRP5-2EC Page 23
Performance - HRP5-3EC Page 24
Performance - HRP6-1EC Page 25
Performance - HRP6-2EC Page 26
Dimensions - HRP-ECs Internal - Side by side & Stacked Page 27
Dimensions - HRP-ECs External - Side by side & Stacked Page 28
Performance HRP350-1 Page 29
Performance HRP350-2 Page 30
Dimensions - HRP350s Page 31
Compact Air Handling Units - Internal & External: EHB or LPHW heating coil - General Page 32
Performance - IME/EME 12/15-ECs Page 33
Performance - IME/EME 20-ECs Page 34
Performance - IME/EME 25-ECs Page 35
Performance - IME/EME 31-ECs Page 36
Dimensions - IME/EME-ECs Page 37
Performance - IMW/EMW 12/15-ECs Page 38
Performance - IMW/EMW 20-ECs Page 39
Performance - IMW/EMW 25-ECs Page 40
Performance - IMW/EMW 31-ECs Page 41
Dimensions - IMW/EMW-ECs Page 42
Air Handling Units - Internal & External: EHB or LPHW heating coil - General Page 43
Performance - SPE/SRE1-ECs Page 44
Performance - SPE/SRE4-ECs Page 45
Performance - SPE/SRE6-ECs Page 46
Performance - SPE/SRE7-ECs Page 47
Dimensions - SPE/SRE-ECs - Internal & External Page 48
Performance - SPW/SRW1-ECs Page 49
Performance - SPW/SRW4-ECs Page 50
Performance - SPW/SRW6-ECs Page 51
Performance - SPW/SRW7-ECs Page 52
Dimensions - SPW/SRW-ECs - Internal & External Page 53
Controller, Grille and Damper Page 54
Ancillaries Page 55
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 3
QSS150
QSS200
QSS250
QSS310
QSS355
QSS450
QSS560
IME15
IME20
IME25
IME31
SPE1
SPE4
SPE6
SPE7
IMW15
IMW20
IMW25
IMW31
SPW1
SPW4
SPW6
SPW7
HRP1
HRP2
HRP3
HRP4
HRP5-1
HRP5-2
HRP5-3
HRP6-1
HRP6-2
HRP350-1
HRP350-2
0 0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1 1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
2 2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3 3.1
3.2
3.3
3.4
3.5
3.6
3.7
infinity® - ec motor
SELECTION CHART
Maximum Air Volume - all models (m3/sec)
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9 1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9 2
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9 3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 4
infinity® - ec motor
Air Vent Technology was founded in 1996 in order to
provide high quality products to the Heating and Venti-
lation market.
Since that date the Company has established a reputa-
tion throughout the UK, undertaking many high profile
contracts . The success of the Company has been, and
remains, attributable to a firm commitment to quality
and customer care. Commitment to quality was rein-
forced in 2001 by the introduction of the ISO9001 qual-
ity management system.
In 2007 AVT was brought under the Vectaire Group of
Companies and has since benefitted from over thirty
years' experience in the air movement industry, to-
gether with an innovative approach to product devel-
opment (with particular regard to energy efficient
products which have a high performance/energy ratio).
AVT aims to supply ventilation solutions which
provide the best in energy efficiency, comfort and
design for every segment of the market, and to en-
sure that its responsibility to the environment is a
prime feature in designs for ventilation schemes.
AVT solutions to ventilation problems also reflect
a proper combination of cost effectiveness and en-
ergy efficiency
AVT's highly trained field sales force covers the
whole of the United Kingdom and can provide
quality local support with technical expertise on
products.
AVT can design ventilation schemes from small to
large providing a total, compatible package, thus
guaranteeing a quality ventilation solution.
All AVT products are designed and produced in the
UK to the highest standards. Ventilation/heat re-
covery/air handling systems can be custom built to
solve any specification requirement whilst comply-
ing with all the latest building regulations.
AVT has now developed a rangeof products specifically intendedto ensure the maximum energysaving efficiency by using EC
motors - infinity®
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 5
infinity® - ec motor
The infinity® range has been designed to encompass
a comprehensive range of energy efficient, environmen-
tally friendly and economical products.
infinity® fans all have integral trickle and boost con-
trollers to allow them to run continuously at their most
effective supply/extract capacity. The user can boost to
maximum airflow as and when required by means of a
variety of remote switches
The infinity® range includes cabinet fans, both single
and twin fans, direct drive air handling units with airflows
from 0.001 to 1.57 m3/sec for EHB or LPHW heating,
and direct drive heat recovery units - again for EHB or
LPHW heating delivering up to .93 m3/sec. All of these
models are available for internal or external installation
AVT can supply a complete range of accessories includ-
ing silencers, attenuators, pressure switches, filters, anti-
vibration mounts etc, as well as step control panels and
electric heater batteries.
To complete the infinity® rangeAVT has developed a series of lowprofile, direct drive, heat recoveryunits. These products have all the
benefits of others in the infinity®range, but have the added advan-tage of having a maximum profileof only 350mm allowing heat re-covery units to be installed in thetightest of spaces.
The infinity® range allows compliance with all the lat-
est building regulations, and in particular are ErP Direc-
tive 2013 and 2015 Compliant. Every unit is built in
the UK using the latest technology and with EC motors
for the ultimate in energy saving and low specific fan
powers
All models are super quiet with high performance
acoustic linings.
• 7 sizes
• super quiet - high performance acoustic lining
• integral trickle and boost, and isolator
• airflow 3.5 m3/sec
• internal model cabinets from 0.9mm to 1.6mm thick gal-
vanised sheet steel lined with 25mm Barafoam"O" class
6mm barrier mat layer. External models with plastisol finish
• auto reset, thermal cut-out protection
• twin fan versions incorporate an integral auto-
changeover panel and backdraught shutters to prevent
circulation through un-used fan
• integral mounting points for easy installation
• units may be mounted vertically or horizontally with either
top or bottom access
• fan blades statically and dynamically balanced in accordance
with ISO 1940/1 and balancing quality G6.3
• motor/impellor assembly mounted on removable plate
for easy maintenance and cleaning
• motors are pre-wired to an external terminal box, speed
controller and isolator to ensure simple and quick installation
• external models discharge is via birdmesh protected cowl
• max air temperature 40ºC
• powder coating for externally mounted filter boxes is
available (Model No: FUV.../WP etc)
• single phase (450 and 560 models are 3-phase), 230v
• manufactured in UK to ISO 9001
energy efficient, environmentally friendly, economical
EC motors - ErP 2013 and 2015 Compliant
infinity® - ec motor
INTERNAL & EXTERNAL ACOUSTIC CABINET & TWIN FANS
QSS-EC, EM-EC, QST-EC, EMT-EC
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 6
QSS150
QSS200
QSS250
QSS310
QSS355
QSS450
QSS560
Max Air Volume (m3/sec)
0
0.5 1
1.5 2
2.5 3
3.5
infinity® - ec motor
INTERNAL & EXTERNAL ACOUSTIC CABINET & TWIN FANS
QSS-EC, EM-EC, QST-EC, EMT-EC
Technical Data - 150-ECs
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 7
400
375
350
325
300
275
250
225
200
175
150
125
100
75
50
25
0
External Pressure (PA)
Duty (m3/sec)0.000 0.025 0.050 0.075 0.100 0.125
100%80%60%40%
SFP - 0.4 W/L/S
SFP - 0.6 W/L/S
SFP - 0.8W/L/S
SFP - 1.0 W/L/S
SFP - 1.2W/L/S
Electrical Data
ModelsFan Power
WSupply
FLCamps
150 ECs 52 230V, 1Ph 0.40
150 ECsMid Octave Frequency band / Hz Total in Duct Breakout @ 1m Breakout @ 3m
63 125 250 500 1k 2k 4k 8k dB dB(A) dB(A) NR dB(A) NR
100%Inlet in duct dB 62 56 60 66 63 62 79 65 80 80
29 25 <20 <20Outlet in duct dB 65 59 63 69 66 65 82 68 83 83
80%Inlet in duct dB 57 52 55 61 58 57 71 57 72 73
23 <20 <20 <20Outlet in duct dB 60 55 58 64 61 60 74 60 75 76
60%Inlet in duct dB 50 46 50 56 62 50 58 47 65 64
<20 <20 <20 <20Outlet in duct dB 53 49 53 59 65 53 61 50 68 67
40%Inlet in duct dB 43 46 47 47 43 39 34 29 53 48
<20 <20 <20 <20Outlet in duct dB 46 49 50 50 46 42 37 32 56 51
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 8
infinity® - ec motor
INTERNAL & EXTERNAL ACOUSTIC CABINET & TWIN FANS
QSS-EC, EM-EC, QST-EC, EMT-EC
Technical Data - 200-ECs
400
375
350
325
300
275
250
225
200
175
150
125
100
75
50
25
0
External Pressure (PA)
0.000 0.025 0.050 0.075 0.100 0.125 0.150 0.175 0.200 0.225 0.250
40%
SFP - 0.4 W/L/S
SFP - 0.6 W/L/S
SFP - 0.8W/L/S
SFP - 1.0 W/L/S
SFP - 1.2W/L/S
100%80%60%
Electrical Data
ModelsFan Power
WSupply
FLCamps
200 ECs 70 230V, 1Ph 0.55
200 ECsMid Octave Frequency band / Hz Total in Duct Breakout @ 1m Breakout @ 3m
63 125 250 500 1k 2k 4k 8k dB dB(A) dB(A) NR dB(A) NR
100%Inlet in duct dB 63 69 72 68 67 65 63 71 77 74
38 37 29 26Outlet in duct dB 66 72 75 71 70 68 66 74 80 77
80%Inlet in duct dB 59 65 67 63 61 60 58 64 72 68
33 31 23 20Outlet in duct dB 62 68 70 66 64 63 61 67 75 71
60%Inlet in duct dB 52 58 60 56 54 52 52 51 65 61
26 23 <20 <20Outlet in duct dB 55 61 63 59 57 55 55 54 68 64
40%Inlet in duct dB 43 51 50 46 42 39 36 28 55 48
<20 <20 <20 <20Outlet in duct dB 46 54 53 49 42 42 39 31 58 51
Duty (m3/sec)
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 9
400
375
350
325
300
275
250
225
200
175
150
125
100
75
50
25
0
External Pressure (PA)
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40
infinity® - ec motor
INTERNAL & EXTERNAL ACOUSTIC CABINET & TWIN FANS
QSS-EC, EM-EC, QST-EC, EMT-EC
Technical Data - 250 ECs
40%
SFP - 0.4 W/L/S
SFP - 0.6 W/L/S
SFP - 0.8W/L/S
SFP - 1.0 W/L/S
SFP - 1.2W/L/S
100%80%60%
Duty (m3/sec)
Electrical Data
ModelsFan Power
WSupply
FLCamps
250 ECs 170 230V, 1Ph 1.40
250 ECsMid Octave Frequency band / Hz Total in Duct Breakout @ 1m Breakout @ 3m
63 125 250 500 1k 2k 4k 8k dB dB(A) dB(A) NR dB(A) NR
100%Inlet in duct dB 61 64 69 68 69 66 62 63 75 73
35 33 26 22Outlet in duct dB 64 67 72 71 72 69 65 66 78 76
80%Inlet in duct dB 55 58 63 62 63 61 57 57 69 68
29 27 20 <20Outlet in duct dB 58 61 66 65 66 64 60 60 72 71
60%Inlet in duct dB 47 51 55 54 55 53 49 48 62 60
21 <20 <20 <20Outlet in duct dB 50 54 58 57 58 56 52 51 65 63
40%Inlet in duct dB 36 39 42 42 41 39 35 29 48 46
<20 <20 <20 <20Outlet in duct dB 39 42 45 45 44 42 38 32 51 49
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 10
infinity® - ec motor
INTERNAL & EXTERNAL ACOUSTIC CABINET & TWIN FANS
QSS-EC, EM-EC, QST-EC, EMT-EC
Technical Data - 310 ECs
Duty (m3/sec)0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
400
375
350
325
300
275
250
225
200
175
150
125
100
75
50
25
0
External Pressure (PA)
40%
SFP - 0.4 W/L/S
SFP - 0.6 W/L/S
SFP - 0.8W/L/S
SFP - 1.0 W/L/S
SFP - 1.2W/L/S
100%80%60%
Electrical Data
ModelsFan Power
WSupply
FLCamps
310 ECs 510 230V, 1Ph 3.10
310 ECsMid Octave Frequency band / Hz Total in Duct Breakout @ 1m Breakout @ 3m
63 125 250 500 1k 2k 4k 8k dB dB(A) dB(A) NR dB(A) NR
100%Inlet in duct dB 66 71 82 81 81 76 73 68 87 85
48 47 38 37Outlet in duct dB 69 74 85 84 84 79 76 71 90 88
80%Inlet in duct dB 61 66 77 76 75 71 67 62 82 79
43 42 33 31Outlet in duct dB 64 69 80 79 78 74 70 65 85 82
60%Inlet in duct dB 55 59 70 69 68 63 60 54 74 72
36 34 26 23Outlet in duct dB 58 62 73 72 71 66 63 57 77 75
40%Inlet in duct dB 45 50 58 55 54 51 49 43 62 59
24 21 <20 <20Outlet in duct dB 48 53 61 58 57 54 52 46 65 62
Electrical Data
ModelsFan Power
WSupply
FLCamps
350 ECs 450 230V, 1Ph 2.90
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 11
infinity® - ec motor
INTERNAL & EXTERNAL ACOUSTIC CABINET & TWIN FANS
QSS-EC, EM-EC, QST-EC, EMT-EC
Technical Data - 350 ECs
Duty (m3/sec)0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2
400
375
350
325
300
275
250
225
200
175
150
125
100
75
50
25
0
External Pressure (PA)
40%
SFP - 0.4 W/L/S
SFP - 0.6 W/L/S
SFP - 0.8W/L/S
SFP - 1.0 W/L/S
SFP - 1.2W/L/S
100%80%60%
350 ECsMid Octave Frequency band / Hz Total in Duct Breakout @ 1m Breakout @ 3m
63 125 250 500 1k 2k 4k 8k dB dB(A) dB(A) NR dB(A) NR
100%Inlet in duct dB 68 78 80 79 71 68 70 57 85 80
47 45 37 36Outlet in duct dB 71 81 83 82 74 71 73 60 88 83
80%Inlet in duct dB 62 73 74 74 66 63 64 51 79 74
41 39 31 28Outlet in duct dB 65 76 77 77 69 66 67 54 82 77
60%Inlet in duct dB 53 64 64 65 57 55 54 43 70 65
31 28 21 <20Outlet in duct dB 56 67 67 68 60 58 57 46 73 68
40%Inlet in duct dB 45 52 50 50 45 44 40 33 57 52
<20 <20 <20 <20Outlet in duct dB 48 55 53 53 48 47 43 36 60 55
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 12
infinity® - ec motor
INTERNAL & EXTERNAL ACOUSTIC CABINET & TWIN FANS
QSS-EC, EM-EC, QST-EC, EMT-EC
Technical Data - 450 ECs
Electrical Data
ModelsFan Power
WSupply
FLCamps
450 ECs 1010 400V, 3ph 1.60
Duty (m3/sec)
400
375
350
325
300
275
250
225
200
175
150
125
100
75
50
25
0
External Pressure (PA
)
40%
SFP - 0.4 W/L/S
SFP - 0.6 W/L/S
SFP - 0.8W/L/S
SFP - 1.0 W/L/S
SFP - 1.2W/L/S
100%80%60%
450 ECsMid Octave Frequency band / Hz Total in Duct Breakout @ 1m Breakout @ 3m
63 125 250 500 1k 2k 4k 8k dB dB(A) dB(A) NR dB(A) NR
100%Inlet in duct dB 71 76 78 78 70 71 77 69 84 81
44 42 34 31Outlet in duct dB 74 77 80 82 82 77 78 69 88 86
80%Inlet in duct dB 65 70 73 72 65 66 70 63 79 75
39 37 29 26Outlet in duct dB 68 72 75 76 76 72 73 63 82 81
60%Inlet in duct dB 58 64 66 65 58 59 60 54 71 67
32 29 22 <20Outlet in duct dB 61 66 68 69 69 65 63 55 75 73
40%Inlet in duct dB 47 52 55 54 46 46 45 38 60 55
21 <20 <20 <20Outlet in duct dB 49 54 57 59 57 52 48 40 64 61
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 13
infinity® - ec motor
INTERNAL & EXTERNAL ACOUSTIC CABINET & TWIN FANS
QSS-EC, EM-EC, QST-EC, EMT-EC
Technical Data - 560 ECs
Electrical Data
ModelsFan Power
WSupply
FLCamps
560 ECs 3100 400V, 3ph 4.90
Duty (m3/sec)
400
375
350
325
300
275
250
225
200
175
150
125
100
75
50
25
0
External Pressure (PA)
40%
SFP - 0.4 W/L/S
SFP - 0.6 W/L/S
SFP - 0.8W/L/S
SFP - 1.0 W/L/S
SFP - 1.2W/L/S
100%80%60%
560 ECsMid Octave Frequency band / Hz Total in Duct Breakout @ 1m Breakout @ 3m
63 125 250 500 1k 2k 4k 8k dB dB(A) dB(A) NR dB(A) NR
100%Inlet in duct dB 78 82 86 83 79 77 75 68 90 85
53 51 43 42Outlet in duct dB 81 85 89 90 90 84 80 71 95 93
80%Inlet in duct dB 73 77 81 78 74 72 69 63 85 80
48 46 38 36Outlet in duct dB 76 80 84 85 85 78 75 66 90 88
60%Inlet in duct dB 65 70 75 71 67 65 62 55 78 73
41 39 31 28Outlet in duct dB 68 73 77 78 78 72 68 59 83 81
40%Inlet in duct dB 56 60 64 61 57 55 52 45 68 63
30 28 21 <20Outlet in duct dB 59 62 67 67 68 62 57 49 73 71
0.00 0.20 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25 3.50 3.75 4.00
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 14
infinity® - ec motor
INTERNAL & EXTERNAL ACOUSTIC CABINET & TWIN FANS
QSS-EC, EM-EC, QST-EC, EMT-EC
Dimensions
Single Internal and External
Model A B C D Ekg
Internal
kg
External
trickle
/boostIsolator
150-EC 250 250 300 150 185 9 10 yes yes
200-EC 350 250 400 200 220 14 15 yes yes
250-EC 450 350 550 250 270 26 27 yes yes
310-EC 550 400 600 310 315 32 33 yes yes
350-EC 650 550 650 350 345 45 47 yes yes
450-EC 750 650 975 450 430 74 80 yes yes
560-EC 900 800 1100 560 525 114 118 yes yes
Single Internal
Single External
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 15
infinity® - ec motor
INTERNAL & EXTERNAL ACOUSTIC CABINET & TWIN FANS
QSS-EC, EM-EC, QST-EC, EMT-EC
Dimensions
Twin Internal
Twin External
Twin Internal and External
Model A B C D Ekg
Internal
kg
External
trickle
/boost
Isola-
torDACOV8
ACO3-3PH
150-EC 450 250 400 150 160 20 21 yes yes yes no
200-EC 450 350 450 200 195 27 28 yes yes yes no
250-EC 600 450 550 250 245 40 42 yes yes yes no
310-EC 850 450 800 310 290 62 64 yes yes yes no
350-EC 950 550 900 350 320 80 83 yes yes yes no
450-EC 1200 650 1200 450 405 131 134 yes yes no yes
560-EC 1500 750 1500 560 495 217 222 yes yes no yes
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 54
0-10v Closed Loop Pressure Controller
This unit is a PI controller for use with EC fans for
maintaining constant pressure control. When it is
used with an appropriate differential pressure
sensor, it maintains the pre-programmed pressure
in ventilation systems by varying the fan speed in
relation to the system pressure.
Grilles
These grilles can incorporate a wide variety of
functions. With various activation modes such as
humidity, PIR, CO2 and VOC, the grilles can auto-
matically adjust the level of ventilation according to
the needs of the occupants. The airflow range can
be set at installation to adapt to special require-
ments, or to compensate for lack of pressure.
Commissioning is also facilitated by the presence
of an integrated pressure plug allowing connection
to a manometer.
In-Line Damper
In-line opposed blade dampers are available in a
variety of sizes to suit the application. Dampers
come with pre-fitted damper actuators. The
damper actuators can be activated through a vari-
ety of sensors, including, but not limited to, the an-
cillaries listed on the next page. These dampers can
be used in conjunction with the grilles shown above
to create a complete system solution.
infinity® - ec motorCONTROLLER, GRILLE AND DAMPER
Tel: 01264 356415 Fax: 01264 337854
Email: [email protected] Web: www.airventtechnology.co.uk
Page 55
Dynamic Remote Humidistat
This unit can be connected to an "Infinity" product
so that it will automatically switch on when the
percentage of humidity in the room reaches the
(adjustable) pre-set level. The unit will continue to
operate until the level of humidity falls below the
pre-set level.
Remote Passive Infra Red
This unit can be connected to an "Infinity" product
so that it will automatically switch on when the
sensor detects the presence of a person in the
room. The unit incorporates an over-run timer and
will continue operating the fan for a (adjustable)
pre-set length of time after the person has moved
away from the range of the sensor.
infinity® - ec motorANCILLIARIES - FOR TRICKLE BOOST OPERATION
Thermostat
This unit can be connected to an "Infinity" product
so that it will automatically switch on when the
temperature reaches the (adjustable) pre-set level.
It will then continue to operate until the tempera-
ture falls back to that level.
Air Quality Sensor
This unit can be connected to an "Infinity" product
so that it will automatically switch on when the
sensor detects that the level of pollution has
reached an unacceptable level (pre-set by the user).
The product will then continue to operate until the
pollution has been cleared and the atmosphere
reaches an acceptable level. The AQS incorporates
a switch for manual operation.
Air Vent Technology reserves the right to alter specifications as part of its policy of continuous development July2015/INF01am© E & O.E
AIR VENT TECHNOLOGY LTD 56 Reith Way Portway Industrial Estate Andover Hampshire SP10 3TY
Tel: +44(0)1264 356415 Fax: +44(0)1264 337854 Email: [email protected] Web: www.airventtechnology.co.uk Part of the Vectaire Group of Companies
Certificate No: GB9455