Technical specificationSoftware ver. MPD 6.20 Multi protocol and LON for FMC-400

Page 2: Technical specification - ООО "Свидпамп"swedepump.by/files/279223.pdf · Technical specification Software ver. MPD 6.20 Multi protocol and Lon for FMC-400 Data Product

Technical specification

Software ver. MPD 6.20 Multi protocol and Lon for FMC-400

Data

Product

FMC-400 MPD 6.20 is ITT Flygt´s standard RTU1 (remoteterminal unit) with multi-protocol and loncommunication for control and supervision ofwastewater pumping stations equipped with up to fourpumps.

The open architecture will interface with the mostcommon SCADA systems on the market. Totally there are180 different variables accessible in the directories. Theparameter-controlled standard software handles pumpcontrol, alarm function, running data, performancemonitoring and communication with the central systemand/or paging system.

The lon communication supports up to 8 nodes. Hence,the FMC RTU works as a central to communicate with 8FGC controllers. Trend and data collection, remotecontrol, alarm handling etc can be distributed via lon toFMC.

A number of different modem types can be connected inorder to receive utmost possible flexibility. Connectablemodems are TDK 5660 V.90 Global Class, Westermo TD-22 and TD-33. Besides this, there is an interface forRS232 with different communication speeds whereexternal communication equipment can be connectedand operated in fixed multidrop network, for instanceradio.

Denomination

40 500946 MPD 6.20 Multi protocol and Lon, Eng40 500948 MPD 6.20 Multi protocol and Lon, Swe

Requirements

FMC-400 pump controllerGateway2

Accessories

Level sensorSurge voltage protectionPower supplyBattery backup

Protocol

*) No dialled-up communication

1 Remote terminal unit

2 For Lon communication

Protocol Tele- Commentgram

Comli 0 Transfer of I/O-RAM status orregister values

1 Acknowledge2 Request of I/O-RAM status or

register values3 Transfer of status for one I/O-bit4 Request of status for one I/O-bitJ Transfer of date and timeQ Request of historical trendR Transfer of historical trend dataÅ Request of time stamped eventsÄ Transfer of time stamped events< Request of high registers= Transfer of high registers

Modbus *) 01 Read coil status02 Read input status03 Read holding registers04 Read input registers05 Force single coil06 Preset single register15 Force multiple coils16 Preset multiple registers

AquaCom WCA Alarm requestMCC Setpoint adjustmentMAS Transfer of analogue setpointsMAT Alarmcode filterWGS Transfer of status/remote ctrlWGD Transfer of periodical reportWGH Transfer of historical trendBRK BreakEBR Break (with acknowledgement)

2

Page 3: Technical specification - ООО "Свидпамп"swedepump.by/files/279223.pdf · Technical specification Software ver. MPD 6.20 Multi protocol and Lon for FMC-400 Data Product

Technical specification

Software ver. MPD 6.20 Multi protocol and Lon for FMC-400

Communication channels

Front panel

The front panel features indicators for pump status,important alarms and RTU status. Five push-buttonsensure ease of control. LED display reports interactionwith software.

Front panel, FMC-200

Interface Description of functions

COM1 - Dialled-up connection GSM modemRS232 Siemens TC35

- Dialled-up connection external modem- Dialled-up connection Westermo TD33- Radio communication ”Transparent mode”- Radio communication ”Controlled mode”- Dedicated and dialled-up modem Westermo TD-22 V.23Bis, V.22- Dedicated line RS232/RS485

COM2 - ServiceRS232

COM3 - Dialled-up modem TDK 5660 V.34,PC-card V.22

- Dialled-up modem TDK 2814 V.34, V.22

COM4

IndicationsStarting level, P1-P4Capacity measurement in progressPump P1-P4, starting outputPump P1-P4, running

Key setSwitch, read or write modeThree buttons for writing/reading parameters and setvaluesAlarm acknowledgement

Alarm panelThe alarms are displayed by LEDs on the annunciatorpanel as follows.

Overflow alarm

Power failure

High level

Low level

Pump P1, motor protection tripped

Pump P2, motor protection tripped

Pump P3, motor protection tripped

Pump P4, motor protection tripped

Pump P1, capacity fault

Pump P2, capacity fault

Pump P3, capacity fault

Pump P4, capacity fault

Personnel alarm

Spare alarm

Spare

General alarm

3

Page 4: Technical specification - ООО "Свидпамп"swedepump.by/files/279223.pdf · Technical specification Software ver. MPD 6.20 Multi protocol and Lon for FMC-400 Data Product

Technical specification

Software ver. MPD 6.20 Multi protocol and Lon for FMC-400

www.flygt.com

The manufacturer reserves the right to alter performance,specification or design without notice.

Functions

MPD

6.2

0 04

.01

Eng.

06.

02

8942

94

System functionsTime and dateRemote serviceAlarm distribution to AquaViewAlarm distribution from FGCAlarm distribution to SMS, numeric and text pagingStatus and inversion of digital input signalsAlarm log with 1000 alarms

Pump control functions4 pump controlStart and stop level controlMaximum running pumps at the same timeStart and stop delaysHigh and low level float backup runPump alternation on every start.Number of alternating pumpsRandom start levelRemote control of pumpsRemote reset of motor protector

Extra functionsEnergy consumptionCalibrated level measurement.Level sensor supervisionRain calculationPersonnel supervision and alarmPower failure controlService interval for individual pumpsIndividual pump capacity calculationInflow and pumped volume calculationPump sump definitionOverflow alarm logCleaning valve control

ReportsRuntime and starts for individual pumpsPumped volumeOverflow time, number of and volumeEnergy consumptionRain meter

TrendsLevel of sumpLevel in each FGCOverflowCapacity for individual pumpsInflowPrecipitation

I/O listComli and modbus adress listAddresses of signals translated to be used directly inexternal SCADA system

By interest please contact ITT Flygt for technicalinformation about software ver. GNC 150-24 M forFMC-150 to monitor and control up to 24 FGC pumpcontrollers.