Technical specificationSoftware ver. MPD 6.20 Multi protocol and LON for FMC-400
Technical specification
Software ver. MPD 6.20 Multi protocol and Lon for FMC-400
Data
Product
FMC-400 MPD 6.20 is ITT Flygt´s standard RTU1 (remoteterminal unit) with multi-protocol and loncommunication for control and supervision ofwastewater pumping stations equipped with up to fourpumps.
The open architecture will interface with the mostcommon SCADA systems on the market. Totally there are180 different variables accessible in the directories. Theparameter-controlled standard software handles pumpcontrol, alarm function, running data, performancemonitoring and communication with the central systemand/or paging system.
The lon communication supports up to 8 nodes. Hence,the FMC RTU works as a central to communicate with 8FGC controllers. Trend and data collection, remotecontrol, alarm handling etc can be distributed via lon toFMC.
A number of different modem types can be connected inorder to receive utmost possible flexibility. Connectablemodems are TDK 5660 V.90 Global Class, Westermo TD-22 and TD-33. Besides this, there is an interface forRS232 with different communication speeds whereexternal communication equipment can be connectedand operated in fixed multidrop network, for instanceradio.
Denomination
40 500946 MPD 6.20 Multi protocol and Lon, Eng40 500948 MPD 6.20 Multi protocol and Lon, Swe
Requirements
FMC-400 pump controllerGateway2
Accessories
Level sensorSurge voltage protectionPower supplyBattery backup
Protocol
*) No dialled-up communication
1 Remote terminal unit
2 For Lon communication
Protocol Tele- Commentgram
Comli 0 Transfer of I/O-RAM status orregister values
1 Acknowledge2 Request of I/O-RAM status or
register values3 Transfer of status for one I/O-bit4 Request of status for one I/O-bitJ Transfer of date and timeQ Request of historical trendR Transfer of historical trend dataÅ Request of time stamped eventsÄ Transfer of time stamped events< Request of high registers= Transfer of high registers
Modbus *) 01 Read coil status02 Read input status03 Read holding registers04 Read input registers05 Force single coil06 Preset single register15 Force multiple coils16 Preset multiple registers
AquaCom WCA Alarm requestMCC Setpoint adjustmentMAS Transfer of analogue setpointsMAT Alarmcode filterWGS Transfer of status/remote ctrlWGD Transfer of periodical reportWGH Transfer of historical trendBRK BreakEBR Break (with acknowledgement)
2
Technical specification
Software ver. MPD 6.20 Multi protocol and Lon for FMC-400
Communication channels
Front panel
The front panel features indicators for pump status,important alarms and RTU status. Five push-buttonsensure ease of control. LED display reports interactionwith software.
Front panel, FMC-200
Interface Description of functions
COM1 - Dialled-up connection GSM modemRS232 Siemens TC35
- Dialled-up connection external modem- Dialled-up connection Westermo TD33- Radio communication ”Transparent mode”- Radio communication ”Controlled mode”- Dedicated and dialled-up modem Westermo TD-22 V.23Bis, V.22- Dedicated line RS232/RS485
COM2 - ServiceRS232
COM3 - Dialled-up modem TDK 5660 V.34,PC-card V.22
- Dialled-up modem TDK 2814 V.34, V.22
COM4
IndicationsStarting level, P1-P4Capacity measurement in progressPump P1-P4, starting outputPump P1-P4, running
Key setSwitch, read or write modeThree buttons for writing/reading parameters and setvaluesAlarm acknowledgement
Alarm panelThe alarms are displayed by LEDs on the annunciatorpanel as follows.
Overflow alarm
Power failure
High level
Low level
Pump P1, motor protection tripped
Pump P2, motor protection tripped
Pump P3, motor protection tripped
Pump P4, motor protection tripped
Pump P1, capacity fault
Pump P2, capacity fault
Pump P3, capacity fault
Pump P4, capacity fault
Personnel alarm
Spare alarm
Spare
General alarm
3
Technical specification
Software ver. MPD 6.20 Multi protocol and Lon for FMC-400
www.flygt.com
The manufacturer reserves the right to alter performance,specification or design without notice.
Functions
MPD
6.2
0 04
.01
Eng.
06.
02
8942
94
System functionsTime and dateRemote serviceAlarm distribution to AquaViewAlarm distribution from FGCAlarm distribution to SMS, numeric and text pagingStatus and inversion of digital input signalsAlarm log with 1000 alarms
Pump control functions4 pump controlStart and stop level controlMaximum running pumps at the same timeStart and stop delaysHigh and low level float backup runPump alternation on every start.Number of alternating pumpsRandom start levelRemote control of pumpsRemote reset of motor protector
Extra functionsEnergy consumptionCalibrated level measurement.Level sensor supervisionRain calculationPersonnel supervision and alarmPower failure controlService interval for individual pumpsIndividual pump capacity calculationInflow and pumped volume calculationPump sump definitionOverflow alarm logCleaning valve control
ReportsRuntime and starts for individual pumpsPumped volumeOverflow time, number of and volumeEnergy consumptionRain meter
TrendsLevel of sumpLevel in each FGCOverflowCapacity for individual pumpsInflowPrecipitation
I/O listComli and modbus adress listAddresses of signals translated to be used directly inexternal SCADA system
By interest please contact ITT Flygt for technicalinformation about software ver. GNC 150-24 M forFMC-150 to monitor and control up to 24 FGC pumpcontrollers.