ZERO-LATENCY DATA CENTER
TECHNICAL SPECIFICATION
ISO 9001:2015 ISO 27001:2013
CDLAN® srl - via Caldera 21 - 20153 Milan (IT)
+39 02 6706800@[email protected]
Caldera21® Cold Aisle Containment
POWERGRID
POWERGRID
TANK STORAGEPATH A PATH B
TRAFO
PDU PDU
TRAFO
GENERATORSWITCHGEAR
MECHANICALSWITCHGEAR
UTILITYSWITCHGEAR
DATAHALL
DATAHALL
UTILITYSWITCHGEAR
CDZCDZ +1
POWER GENERATORS
UPS UPS UPS UPS
Utility Power Supply capacity of 6 MW
2,4 MW of Critical IT power
1.400m2 of fully-fitted colocation space
400 racks 48U 800x1000
Slab Floor
2N Power System
N+1 Cooling System
High Power Density of up to 6kW/m2
DATA CENTER HIGHLIGHTS
Ground floor First floor
BUILDING
• 3 storey building with long-term lease secured• 3,100m2 of gross space• 1,400m2 of customer space• Slab MAX load 800 kg/m2• Control Room, Meeting Rooms, Storage Room
POWER
• 23kV utility supply up to 6MW dual feed (1MW single feed to date)• 2N+1 MEP design Tier IV-equivalent• 6 x 1MVA GE backup (2 installed to date)• 72h of autonomy with SLA on refueling• 2N+1 UPS redundancy• 100% availability SLA• Full range of AC and DC output currents
DATA HALL
• High power density configurations of up to 24kW IT per cabinet• Standard socket supply AC230V 32Amp A+B• Power cabling overhead• Cold Aisle Containment• From 4 Units up to a Full Cabinet
COOLING• Minimum N+1 CRAC redundancy per room DX system• Average Supply T 24°C +/-5°C as per ASHRAE standards 2011• Humidity: 25 - 75% as per ASHRAE standards 2011
CONNECTIVITY
• Dedicated campus fiber ring• Dual fiber entry point• Redundant Carrier Rooms and Meet-Me-Rooms• Three fiber paths connecting MIX data hall (200+ Carriers/ISPs)• Milan Internet Exchange on-site• Data cabling overhead• Fibre and copper in separate trays• Ethernet Connectivity supplied by Layer 2 Managed Network
SUPPORT• Hands and Eyes• On site engineers and support: 24x7
FIRE PROTECTION• VESDA detection systems• Hi-Fog fire suppression system• Fire separation walls
MONITORING
• BMS Monitoring System• SLAs on temperature and humidity in line with ASHRAE recommendation• Entire facility infrastructure monitored 24x7 (Chiller, CRAC, Fire Panels, Generator, UPS, data hall doors)
SECURITY
• Trained security staff on-site (24x7)• Multiple physical security layers (contactless keycards, CCTV, man trap)• 24x7 controlled access• ISO 27001-certified information security management systems
DATA CENTER FACT SHEETZERO-LATENCY DATA CENTER