Quality EWC-QU-TS21 Technical Schedule Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22 Author: Warringtonfire Testing and Certification Limited Approved: P. Duggan Certification Manager Authorised: K. Prendergast Divisional Director, Certification Page 1 of 38 This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document. Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN Co. Reg. No. 11371436 TECHNICAL SCHEDULE TS21 THE CONTRIBUTION OF EDGE SEALS TO THE CONTROL OF SMOKE LEAKAGE VIA DOORSETS

Upload: others

Post on 10-Oct-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 1 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

TECHNICAL SCHEDULE

TS21

THE CONTRIBUTION OF EDGE SEALS TO THE CONTROL

OF SMOKE LEAKAGE VIA DOORSETS

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 2 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

CONTENTS

ISSUE STATUS AND AMENDMENT 3

FOREWORD 5

1. SCOPE 6

2. REFERENCES 8

3. DEFINITIONS 10

4. CLASSIFICATIONS 10

5. CERTIFICATION REQUIREMENTS 11

6. ASSESSMENT OF PRODUCTS 12

7. CERTIFICATE CONTENTS 12

8. IDENTIFICATION AND LABELLING 12

9. FACTORY PRODUCTION CONTROL 13

10. AUDIT PROCEDURES 14

ANNEX A Test Procedures 15

ANNEX B Guidance Notes 24

ANNEX C Universal Matrix 25

ANNEX D Certificate Template 28

ANNEX E Factory Production Control Checklist 30

ANNEX F Participating Organisations 39

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 3 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

ISSUE STATUS AND AMENDMENT

i. This is a controlled copy of the Technical Schedule. Scheme members to which it has been issued will be provided with details of any changes in accordance with the amendment procedure below.

ii. From here on in, references to Warringtonfire Testing and Certification Limited will be shown as Warringtonfire.

iii. Each page of the document is identified by a page number, issue number and date.

Where an amendment is made, the revised page will bear a new issue number and date of amendment.

iv. Where an amendment requires an extra page to be inserted, this is numbered with the

number of the preceding page but with the addition of a letter suffix, e.g. 10A will be inserted between pages 10 and 11 and 10B will follow 10A. The new pages are dated in the normal way.

v. Any amendment to this document will be identified on the Amendment Page, which will

be re-issued to holders of controlled copies with the amended sections/pages. Revised pages shall be inserted in place of existing pages or between existing pages and superseded pages shall be discarded. Where a significant number of amendments are made to this document the entire document will be re-issued under a new issue number. In such cases holders of the document shall destroy the previous issue.

vi. The Amendment Page and the relevant revised pages will be produced by Warringtonfire

following agreement with the Warringtonfire Sector Liaison Group, and issued to the holders of each controlled copy of the document, together with an acknowledgment slip (document transmittal) which shall be signed and returned to Warringtonfire to confirm that the document has been amended. It shall be the responsibility of the nominated representative of the organisation to ensure that the document is maintained in an up to date condition at all times.

vii. To ensure that a permanent record is available of all amendments, Warringtonfire

maintains a file of all superseded pages which are marked with the date of withdrawal. The record is held on file indefinitely in order to allow Warringtonfire to determine the past requirements of the scheme at any time.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 4 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

AMENDMENT PAGE

To ensure that each controlled copy of this Technical Schedule contains a complete record of amendments, the Amendment Page is updated and issued with each set of revised/new pages of the document. Details of the procedures for amending this document are given in section 1 of this document.

Amendment Discard Insert

No Date

*Sections Changed

Page(s) Issue no Page(s) Issue no

1 30.06.15 All- Updated to new

format, also to include

references to BS EN

ISO/IEC 17065 and ISO

9001. Management

Council renamed to

Impartiality Committee

All 2 All 3

2 22.04.16 Name change from WCL to Exova (UK) Limited

All 3 All 4

3 11.12.18 Name change to Warringtonfire Testing and Certification Limited

All 5 All 6

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 5 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

TECHNICAL SCHEDULE (TS)

THE CONTRIBUTION OF EDGE SEALS TO THE CONTROL OF SMOKE LEAKAGE VIA DOORSETS

FOREWORD

This Technical Schedule (TS) forms part of a series of controlled documents which comprise the CERTIFIRE product certification scheme. It has been prepared in accordance with the requirements of BS EN ISO/IEC 17065 for product certification bodies. In addition to this Schedule the other controlled documents relevant to CERTFIRE certification are:

TS00 - General Requirements for CERTIFIRE Certification of Passive Fire Protection Products/Systems

CERTIFIRE Quality Manual

Certificates in the CF000 series, together with any appendices

Documentation from the manufacturer

Rules for use of the CERTIFIRE logo

This CERTIFIRE scheme aims to provide confidence that smoke seals installed in smoke control doors will enable the doorset to achieve the required level of ambient smoke control and, where relevant, not detract from their fire resistance.

This document is intended for the certification of ambient door smoke seals. It has been prepared by the organisations listed in Annex F and agreed in accordance with the requirements of BS EN ISO/IEC 17065. Individual components can have a significant influence on the performance of smoke control and fire resistance of doors and doorsets. This TS incorporates criteria to help ensure that the doors will provide the requisite performance when correctly fitted with other CERTIFIRE approved components.

Smoke seals eligible for certification under this Technical Schedule will be designed to be fitted to doors required to comply with the ambient smoke control requirements of UK legislation based on the provisions of BS476: Part 31.1 or EN1634 - 3. The certification may also be appropriate to other jurisdictions where the same performance criteria apply. This version of TS21 supersedes previous versions and becomes effective from May 2010.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 6 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

1. SCOPE

1.1 This Technical Schedule defines the technical requirements via testing and appraisal for seals designed to contribute to the control of smoke leakage at ambient temperature around the perimeter of pedestrian doors.

1.2 Evaluation of smoke control performance is in accordance with BS476: Part 31.1. 1.3 Certification against European specifications is not possible under this TS. although

testing in accordance with EN1634-3 may be used in support of the seal’s performance. 1.4 A separate TS, based on European specifications will be drafted in due course. 1.5 Approval is applicable only to seals fitted to pedestrian doorsets that are hinged on one

vertical edge or pivoted as single or multiple leaves of single or double action configuration.

1.6 Certification is designed to be applicable to seals fitted to CERTIFIRE approved doors

but may also be applicable to others. 1.7 Certification will apply to a seal or range of seals based upon a given design and using

the same materials. When a company manufactures, or fabricates products from significantly different components and/or materials then a separate certificate may be required for each type of seal,

1.8 The detailed field of application in the Certificate of Approval will identify any limitations

applying to the use and interchangeability of smoke seals.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 7 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

1.9 Doors are classified as the following types:

a) Type TT: 20 minute doorsets that consist of non-metallic leaves in timber frames that do not contain intumescent materials in the frame to leaf gap.

b) Type ITT: 20 minute to 120 minute doorsets containing intumescent seals and

consisting of non-metallic faced and edged leaves hung in timber frames c) Type ITM: 20 minute to 120 minute doorsets containing intumescent seals and

consisting of non-metallic faced and edged leaves hung in metal frames. d) Type ITC: 20 minute to 120 minute doorsets containing intumescent seals and

consisting of non-metallic faced and edged leaves hung in proprietary composite frames, of which the principal material is other than timber or metal but which may include any other materials.

e) Type MM: 20 to 240 minute doorsets consisting of uninsulated or insulated metal

door assemblies in metal frames without intumescent seals f) Type IMM: 20 to 240 minute doorsets consisting of uninsulated or insulated metal

door assemblies in metal frames with intumescent seals g) Suffix G: 20 minute to 120 minute doorsets of any of the above constructions which

include more than 20% area of uninsulating glass have the appropriate code above with the suffix ‘G’. For example ‘ITTG’ and ‘ITMG’

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 8 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

2. REFERENCES

EN Standards are published by National Standards body and may include National Annexes.

For CERTIFIRE purposes the definitive version of any EN standard is that published by BSI

and prefixed ‘BS EN’.

References contained in TS 00 may also be relevant.

BS 476- 20 Fire tests on building materials and structures. Method for determination of the fire resistance of elements of construction (general principles)

BS 476- 22 Fire tests on building materials and structures. Method for determination of the fire resistance of non-loadbearing elements of construction

BS 476- 31.1 Fire tests on building materials and structures. Methods for measuring smoke penetration through doorsets and shutter assemblies. Method of measurement under ambient temperature conditions

BS 7352 Specification for strength and durability performance of metal hinges for side hanging applications and dimensional requirements for template drilled hinges

EN1634-1 Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Fire resistance test for door and shutter assemblies and openable windows

EN1634- 3 Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Smoke control test for door and shutter assemblies

BS EN ISO/IEC 17065 Conformity assessment. Requirements for bodies certifying products, processes and services

ISO 9001 Model for Quality Assurance in Design, Development, Production, Installation and Servicing

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 9 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

CERTIFIRE Technical Schedules

TS00 General Requirements for CERTIFIRE Certification of Passive Fire Protection Products/Systems

TS10 Fire Resisting Pedestrian Type Hinged or Pivoted Doorsets with Non-

metallic Leaves TS12 Fire Resisting Pedestrian Type Doorsets with Metallic Leaves and

Frames Including Optional Smoke Control TS21 The Contribution of Edge Seals to the Control of Smoke Leakage via

Door Assemblies TS23 Locks and Latches TS24 The Contribution of Single Axis Hinges to the Performance of Fire

Resisting Door Assemblies TS25 Fire Resistant Glass, Glazing Systems and Materials TS26 The Contribution of Panic Exit Devices Operated by a Horizontal Bar to

the Performance of Fire Resisting Door Assemblies TS30 Industrial Type Fire Resisting Doorsets TS31 The Contribution of Emergency Exit Devices to the Performance of

Fire Resisting Door Assemblies TS33 The Contribution of Door Coordinators to Fire Resisting Doorsets

TS34 The Contribution of Controlled Door Closing Devices and Accessories

to Fire Resisting Doorsets TS35 The Contribution of Intumescent Seals to the Fire resistance of Door

Assemblies TS42 Fire resisting doorsets and openable windows with fire resisting and/or

smoke control characteristics.

PFPF Guide PFPF Guide to Undertaking Assessments in lieu of Fire Tests

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 10 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

3. DEFINITIONS

Assessment The evaluation of the performance and other data against the requirements of this document conducted in accordance with the Passive Fire Protection Federation (PFPF) ‘Guide to undertaking Assessments In Lieu of Fire Test’, or other similar document for the relevant jurisdiction, and taking into account published extended application (EXAP) rules for the product. Also the evaluation, in accordance with the PFPF Guide or similar, of proposed changes to the tested specimen(s)

Factory Production Control The permanent internal control of production exercised by the manufacturer. All the elements, requirements and provisions adopted by the manufacturer shall be documented in a systematic manner in the form of written policies and procedures. This production control system documentation shall ensure a common understanding of quality assurance and enable the achievement of the required product characteristics and the effective operation of the production control system to be checked. (Definition ref. Construction Products Directive) Ambient Temperature A temperature of 25±15oC, representative of that normally found in buildings, (Taken from BS476:Part 31.1).

4 CLASSIFICATION

4.1 Evaluation against the requirements of this Schedule is designed to provide certification of product performance in accordance with the methods and procedures in BS 476: Part 31.1.

4.2 Smoke seals are designated as follows:

a) Type CD; Compression/Deflection seals which fit between the face of the leaf and the door stop

b) Type WS; Wiping seals which fit between the leaf edge and the frame of single acting doors

(When fitted to single action doors the seal in the hanging jamb is subjected to compression/deflection and shall satisfy the leakage rate criteria in this condition).

c) Type WD; Wiping seals which fit between the leaf edge and the frame of double

acting doors or the plain meeting stiles and overpanel junctions of single and double action door assemblies.

d) Type TS; Threshold seals which fit between the leaf edge and the threshold.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 11 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

5. CERTIFICATION REQUIREMENTS

5.1 General requirements 5.1.1 The general requirements for CERTIFIRE certification are contained in ‘TS00 – General

Requirements for CERTIFIRE Certification of Passive Fire Protection Products/Systems’ which should be read in conjunction with this TS.

5.1.2 To gain the maximum benefit from a product range, a manufacturer should test the most

onerous configuration and arrangement of smoke seals intended to be used. A number of different configurations may need to be tested in order to maximise the field of application of a particular product.

5.2 Smoke Control Test Requirements 5.2.1 The general requirements for testing are given in TS00. 5.2.2 The detailed testing procedure based on BS476: Part 31.1 is given in Annex A. 5.2.3 No performance determined’ is not an option for smoke control. 5.3 Fire Resistance 5.3.1 Whilst smoke control seals are not required to contribute to fire resistance unless part of

a combined fire and smoke seal they should nevertheless not detract from fire resistance. This should be evaluated by the inclusion of a set of smoke seals in a full scale fire test of a door in accordance with BS476: Part 22. Full details of the requirements are included in Annex A.

5.4 Durability 5.4.1 The durability of the smoke seal is designed to be evaluated by the enhancement to the

testing regime of BS476: Part 31.1 whereby the door with seals fitted is opened and closed 100000 times.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 12 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

6. ASSESSMENT OF PRODUCTS

6.1 The CERTIFIRE assessment shall determine the field of application of the product and be conducted in accordance with Annex A of this TS.

7. CERTIFICATE CONTENTS

7.1 The certificate shall carry a unique number issued by Warringtonfire. The certificate shall identify the product and any variations in the design. Seals will be classified as on the following types:

a) Type CD; Compression/Deflection seals which fit between the face of the leaf and the door stop

b) Type WS; Wiping seals which fit between the leaf edge and the frame of single acting doors

c) Type WD; Wiping seals which fit between the leaf edge and the frame of double acting doors or the plain meeting stiles and overpanel junctions of single and double action door assemblies.

d) Type TS; Threshold seals which fit between the leaf edge and the threshold The certificate will define the limitations applying to the use of the seal, including the

smoke control performance and the door types, configuration and if appropriate the specific CERTIFIRE approved doors with which the seals may be used. The field of application shall be given in the form of the universal matrix given in Annex C.

7.2 An example of a certificate is given in Annex D.

8. IDENTIFICATION AND LABELLING

8.1 The seals shall be clearly marked so that the scope of certification can be easily established. The marking shall include:

The CERTIFIRE name and or logo

The certificate number.

The manufacturers name

The month and year of manufacture and/or batch code

8.2 Marking should be on each length of seal. Where this is not possible the immediate packaging of the unit for sale shall be marked. Thus if the seal is sold in individual lengths it will be necessary to mark each length

8.3 No specific label or label design is specified or supplied by Warringtonfire. Certificate

holders are deemed to be licensed to label products in accordance with the above requirements and CERTIFIRE rules for use of the certification Mark.

8.4 The product shall be despatched with a data sheet that explains the principle of the

approval and how it only applies to the smoke seals and not the door into which it is fitted. This data sheet shall give clear fixing and maintenance instructions for the product

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 13 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

and make general recommendations as to how the smoke seals interact with the intumescent seals appropriate to the various levels of fire resistance. The literature shall show the product compatibility by means of the Universal Matrix (Annex C). The contents of the information sheet shall be agreed between the manufacturer and Warringtonfire.

The information sheet shall contain the following as a minimum:

The Certificate number

Storage and handling requirements

Identification of any components required to produce the fire resisting structure and not supplied by the manufacturer

Details of appropriate supporting constructions and fixing methods

The universal matrix for the field of application

Recommendations as to who should install the product e.g. FIRAS certificated installer

Technical support contact details

9. FACTORY PRODUCTION CONTROL

9.1 The manufacturer shall exercise control over the manufacture of the product 9.2 The general requirements for factory production control are contained in TS00

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 14 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

10. AUDIT PROCEDURES

10.1 Audit Fire Tests

10.2 Non-fire Audit Tests

10.3 Factory Surveillance Visits

10.3.1 The general requirements for independent inspection and surveillance of FPC are given in TS00

10.3.2 Manufacturers shall be subject to an annual FPC surveillance visit by a Warringtonfire

auditor.

10.3.3 The manufacturer is responsible for:

a) Advising Warringtonfire of who their ISO 9001 Certification Body is, and in

particular if it changes b) Making available copies of surveillance and reassessment reports from the CB c) Maintaining the manufacture of certificated products within their ISO 9001 scope d) Supplying a current ISO 9001 certificate and scope to Warringtonfire

10.3.4 The inspection shall be orientated to the production of the product in the same way as

inspection and surveillance of FPC for CE marking.

10.3.5 The inspection shall be separate from and additional to those conducted by the ISO 9001

certification body, except that if Warringtonfire is the ISO 9001 body or is the certification body for Attestation of Conformity for CE marking, the requirements of both will be covered concurrently.

[Note: the frequency of surveillance visits required by ISO 9001 and FPC for CE marking will generally be not less than annually.]

10.3.6 The checklist used for inspection and surveillance of FPC is included as Annex E

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 15 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

ANNEX A

TEST PROCEDURES A.1 Testing - General Appraisals shall be based upon information derived from appropriate tests are specified

in Clauses A.2 to A.5. The primary test evidence to be considered in support of an appraisal shall be generated

by UKAS approved laboratories or other laboratories acceptable to CERTIFIRE as detailed in CERTIFIRE’s ‘Regulations and Procedures Pertaining to Certification’.

In order that any test is performed in a manner that generates data directly applicable to

the door seal under consideration, it is necessary to restrict the test conditions or specimen design as indicated in clauses A.3 to A.5.

A.2 Test Evidence - General A.2.1 A test shall be performed in accordance with the procedures specified in BS 476: Part

31.1 on a test assembly of a design appropriate to the seal type being evaluated and which complies with the specified opening and closing resistances (see A.3 to A.5). The tested assembly shall satisfy the criteria for the leakage of ambient temperature smoke of 3m3/m/hr at a pressure of 25 Pa (see Note 2).

A.2.2 An assembly of the appropriate design when fitted with the seals to be CERTIFIRE

approved shall be subjected to the following opening and closing cycles; i) Single swing doors - through 10o of opening for 100,000 cycles; ii) Double swing doors - through an arc of 10o about the centre line of the assembly

for 50,000 cycles. The seal shall be deemed to have satisfied the test if it can be shown that: a) The closing resistance resulting from contact between the seal and the adjacent

surface does not exceed 17.5 or 21 Nm for latched and unlatched doors respectively when measured following reasonable cleaning and refurbishment of the test rig or its accessories.

b) The seals will continue to satisfy the 3m3/m/hr criteria when the assembly is

tested to BS 476: Part 31.1 for a second time. Light cleaning of the frame and the leaf edge is permitted.

A.2.3 The smoke seal shall have been included in a door assembly tested to BS 476: Part

20/22 or EN1634-1 in a manner than demonstrates that the fitting of the seal does not reduce the fire resistance of an assembly. Where possible a direct correlation shall exist to show how the door, together with its intumescent, is unaffected by the fitting of the seals. (see Note 3).

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 16 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

A.2.4 Any separate smoke seal (i.e. not a seal that incorporates an integral intumescent

material) that is not stop mounted shall not inhibit the fitting of ironmongery and heat activated seals. A maximum width for a CERTIFIRE approved smoke seal shall be 15mm unless the manufacturer’s literature gives clear guidance on the specification and the method of fitting ironmongery and heat activated seals.

A.3 Compression/Deflection Seals (C/D) and Wiping Seals for single acting doors (W-

S). A.3.1 Test Assembly The leaf shall be an all cellulosic leaf (type C) of between 800mm and 950mm width by

between 2000mm and 2100mm high and at least 43mm thick, consisting of either a solid laminated softwood strip core or a softwood framed flax board/chipboard core, faced with plywood, hardboard or chipboard. The frame shall be softwood or hardwood with no unsealed, ‘through’ joints at the corners. The frame shall be provided with a 12mm deep removable timber door stop screw fixed at 300mm nominal centres. The frame jambs shall be fixed back to the test surround with no less than 4 fixings per jamb, the upper and lower fixings being no more than 150mm from the jamb ends. The head shall be fixed with at least a single, central fixing.

The gap between the leaf edge and the frame head and jambs shall be between 3mm

and 4.5mm. The leaf and frame edges shall be rounded with a radius of 2.5±0.5mm. The threshold gap (between bottom of leaf edge and test frame member of threshold if fitted) shall be sealed in a manner that permits the leaf to move sufficiently to permit the door to break contact with the seal without causing the permissible resistance to closing forces to be exceeded.

The leaf shall be hung on 3 No (1½ Pairs) hinges such that with no smoke seals fitted the

resistance to closing is not more than 2Nm when the threshold is sealed as described above. The hinges shall comply with BS 7352: Class 6 with the addition of the requirement to satisfy the maximum frictional resistance of 2Nm, when hung as a set. These may be fitted conventionally or may be fitted as hinges fixed on the face. In the latter case the manufacturer’s data sheet supplied with the product shall clearly state how the seals are fitted with conventional hinges.

Whilst the assembly is being tested unlatched the opening stile and jamb shall be tested

in one the following conditions: a) With a forend plate and striker plate of the size and type specified in the

manufacturers product data sheet. b) With a forend plate fitted which is of the following minimum dimensions Height 175mm Width 25mm together with an appropriate striker plate as defined or specified for the product.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 17 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

c) With the seal fitted in a manner that stimulates the fitting of such components;

e.g. by leaving gaps in the seal where it would be interrupted by such ironmongery.

d) With plain stiles and jambs free from ironmongery but in this condition the

manufacturers literature shall clearly state how the seals are fitted to accommodate CERTIFIRE approved ironmongery components without negating the smoke sealing ability or without being interrupted by ironmongery.

If the seal is only suitable for fitting to unlatched doors, due to the resistance to closing

figures being too high to accommodate the additional resistance of the latch that is to be fitted, or due to the size or shape of the sealing system, then the need to incorporate or simulate the ironmongery may be omitted but the manufacturers product data sheet shall clearly state this restriction.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 18 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

A.3.2 Testing Regime a) Hang the leaf in the frame as described in clause A.3.1. b) Adjust the assembly until the moment required to open and close the door over

an arc of at least 30 degrees is not more than 2Nm. (The apparatus shown in Figure 2 is suitable for this purpose).

c) Fit the smoke seals to be evaluated to the head and jambs of the assembly. d) Open the door at least 3o and apply a closing moment of 14 Nm at the leaf

centroid and check that the leaf reaches its closed position i.e. contact with the stop and/or seal as appropriate for wiping and deflection seals or contact with the seal for compression seals. (i.e. at a position that would not prevent a latch bolt from engaging in the case of a latched door).

In the case where the above criteria are not complied with the closing moment

may be increased to 17Nm. If the seals comply with this requirement they may be allowed to be used only on unlatched door assemblies and this must be clearly stated in the manufacturer’s literature and in his product data sheet.

e) Apply an opening moment of 30Nm at the leaf centroid to ensure that the door

opens at least 3o. f) Apply and maintain a closing moment at the leaf centroid of 20Nm. g) Seal the threshold as described in A.3.1 or by means of the same seal as fitted

for evaluation as in Clause c) above. (See Note 4). h) Perform the leakage test described in BS 476: Part 31.1 or EN1634-3 at a

positive chamber pressure of 25Pa relative to the laboratory atmosphere and determine compliance with the criteria given in A.2.1. The assembly shall be tested from both sides unless it can be demonstrated that the test represents the most onerous condition, e.g. on an outward opening leaf in the case of a stop of a mounted seal.

i) Perform the cycling test described in A.2.2. A.3.3 If any adjustments are made to the seals during the course of the testing regime in order

to achieve any of the criteria the test shall be repeated from A.3.2.a).

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 19 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

A.3.4 Seals that satisfy the leakage criteria when subjected to the test specified in Clause 5.3 may be used on the head, frame jambs and hanging stiles of single swing, single and double leaf door assemblies. (See Note 6). The leaves of these assemblies may be latched with an ‘easy-action’ latch, i.e. requiring a maximum closing moment of 5Nm, if fitted, or unlatched unless an additional closing moment of 15Nm was required to close the door (see A.3.2). In this case the seals may only be used as part of an unlatched assembly.

A.4 Wiping Seals - Double acting doors and plain meeting stiles (W-D) A.4.1 Test Assembly The leaf shall be an all cellulosic leaf (type C) between 800mm and 950mm wide by

between 2000mm and 2100mm high and at least 43mm thick consisting of either a solid laminated softwood strip core or a softwood framed flaxboard/chipboard core, faced with plywood, hardboard or chipboard. The frame shall be softwood or hardwood with no unsealed through joints at the corner. The frame jambs shall be fixed back to the test surround with no less than 4 fixings per jamb, the upper and lower fixings being no more than 150mm from the jamb ends. The head shall be fixed with at least a single, central fixing.

The gap between the leaf edge and the frame head and jambs shall be between 3.5mm

and 4.5mm. The leaf and frame edges shall be rounded with a radius of 2.5±0.5mm. The threshold gap between bottom of the leaf edge and test frame member (or threshold, if fitted) shall be sealed in a manner that permits the leaf to move sufficiently to demonstrate the seals ability to tolerate movement without causing the permissible resistance to closing forces to be exceeded. The leaf shall be hung on an adjustable top centre and bottom pivot and strap such that with no smoke seals fitted the resistance to closing is not more than 2Nm when the threshold is sealed as described above.

Whilst the door is tested unlatched many double leaf single acting doors are fitted with

bolts and latches and some double acting doors are fitted with bolts and/or locks for security purposes.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 20 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

It is recommended that the door assembly above be tested in one of the following conditions: a) With a forend plate and striker plate, box keep and flush bolts (not engaged) of

the size and type specified in the manufacturers product data sheet. b) With a forend plate fitted which is of the following minimum dimensions: Height 155mm Width 25mm

together with an appropriate striker plate and keep as defined or specified for the product, and 2 No flush bolts of the following minimum dimensions:

Height 225mm Width 25mm c) With the seal fitted in a manner that simulates the fitting of such components; e.g.

by leaving gaps in the seal where it would be interrupted by such ironmongery. (See Note 5).

If none of the above items are fitted because the seals are only designed for use on

unlatched doors, or unsecured double acting doors this must be clearly stated in the manufacturers product data sheet.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 21 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

A.4.2 Testing Regime a) Hang the leaf in the frame on a pair of pivots as described in clause A.4.1 with

the leaf centre line in line with the centre line of the frame and, by means of an indicator, establish this as the datum.

b) Measure the opening moment applied at the centroid of the door leaf when

moving the leaf in either direction at least 15o each side of the centre line. It shall not require more than 2Nm to move the leaf away from or towards the datum position. Adjust assembly until the figure is achieved.

c) Fit smoke seals to be evaluated to the head and jambs of the assembly. d) Open door at least 3o and apply a closing moment at the leaf centroid of 17Nm

and check that the leaf achieves its central datum position from either direction of closing.

e) Apply an opening moment 30Nm at the leaf centroid when the door is at rest in

the datum position to ensure that the door opens at least 3o. This should be performed for both directions of opening and confirmed for each direction from which the leaf may come to rest.

f) Apply and maintain a closing moment against the direction of applied pressure at

the leaf centroid of 20Nm. This will require a limiting device at the datum position to restrain the door from opening into the pressure chamber.

g) Seal the threshold as described in A.4.1, or by means of the same seal as fitted

for evaluation as in clause c) above if appropriate. (See Note 4). h) Perform the leakage test described in BS 476: Part 31.1, at a positive chamber

pressure of 25Pa and determine compliance with the criteria given in A.2.1. i) Perform the cycling test specified in A.2.2. A.4.3 If any adjustments are made to the seals during the course of the testing regime in order

to achieve any of the criteria the test shall be repeated from A.4.2.a. A.4.4 Seals that satisfy the leakage criteria when subjected to the test specified in clause A.4

may be used on the head, jambs and meeting stiles of double swing, single and double leaf door assemblies, or the plain meeting stiles of single swing, double leaf assemblies.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 22 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

A.5 Threshold Seals (TS) A.5.1 Test Assembly The test shall be performed on either a single swing or a double swing, single leaf

assembly as appropriate to the seal under evaluation. In the case of a universal threshold seal a single swing assembly will be used.

The general assembly shall comply with the specifications given in A.3.1 and A.4.1

respectively. The gap between the leaf edges and the frame are not critical if it is only the threshold seal that is being evaluated as the other gaps will be sealed as described. The leaf edges and the edges of any timber threshold shall be rounded with a radius of 2.5± 0.5mm. The gaps down both jambs and across the frame head shall be sealed in a manner that permits the leaf to move sufficiently to demonstrate the seals ability to tolerate movement without causing the permissible resistance to closing forces to be exceeded.

The leaf shall be hung as described in A.3.1 or A.3.4 as appropriate to the assembly

under test. A.5.2 Testing Regime a) The testing regimes described in clauses A.3.2 and A.4.2 clause a) to +) should

be used as appropriate to the assembly under test except that the value of the moment used in clause d) shall be 3Nm for a double acting or unlatched door or 2.5Nm in the case of a latched door.

b) Seal the head and jambs as described in A.5.1 (See Note 7). c) Perform the leakage test described in BS 476: Part 31.1 at a positive chamber

pressure of 25Pa and determine compliance with the criteria given in A.2.1. d) Perform the cycling test specified in A.2.2. A.5.3 If any adjustment is made to the seals during the course of the testing regime in order to

achieve any of the criteria the test shall be repeated from A.5.2.a) A.5.4 Seals that satisfy the leakage criteria when subjected to the test specified in clause A.5

may be used on the threshold of single or double leaf door assemblies. Any restriction on use with respect to single or double swing shall be clearly stated in the manufacturer’s product data sheet.

Note 1: Whilst this Technical Schedule only addresses itself to establishing the suitability

of a seal to be used in conjunction with timber doors and leaves, the principles and methodology can be adapted and used, on an ad-hoc basis, to establish the suitability of seals for use on metal assemblies.

Note 2: The length of the leakage path to which the leakage criteria applies is the

perimeter of the leaf to which the seal being evaluated is fitted. In the case of

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 23 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

double leaf doorsets this includes the length of the meeting stiles. If a set of seals is being evaluated simultaneously including a threshold seal, then all four edges are to be included in establishing the criteria. Examples given below are based upon a 2040mm high by 826mm wide leaf hung as a single or double leaf.

SASD - no threshold seal in evaluation = (2040 x 2) + 826mm leakage path 4.91m SASA - no threshold seal in evaluation = (2040 x 3) + (2 x 826mm) leakage path = 7.77m SADD - with threshold seals = (2040 x 3) + (4 x 826mm) leakage path = 9.42m NB. SASD = Single acting (SA), single door (SD) SADD = Single action (SA), double door (DD) etc. Note 3: When making an assessment against this Technical Schedule on a combined

intumescent and smoke seal, then in addition to satisfying the leakage rate prescribed in the seal shall also have been evaluated on a doorset against the procedures described in BS 476: Part 22: Clauses 6 and 7 and obtained an integrity rating commensurate with the quantity of intumescent fitted, i.e. 30 minutes for a cross-section of 20mm2 and 60 minutes for a cross section of 40mm2.

Note 4: A method of satisfying this requirement is to fit a temporary stop at the threshold

to which is fitted a seal identical to that being evaluated on the head and jambs. In this case the length of this seal is incorporated in the calculations when determining the leakage rate/m of the seal.

Note 5: With a conventional timber door assembly it is unlikely to satisfy the required

leakage criteria with gaps in the seals to simulate ironmongery. Note 6: Symmetrical wiping seals evaluated in accordance with the recommendations

given in 5.3 may be assessed as being suitable for use on the head, jambs and meeting stiles of double acting door assemblies without performing the tests described in Clause A.4.

Note 7: It may be convenient to fit an inverted threshold seal at the head of assembly. The calculated leakage rate shall take the additional length of seal into account. In this case the jambs are required to be sealed in a manner that provides a continuous line contact without restraining the door movement.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 24 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

ANNEX B Within the series of Technical Schedules relating to the components which make up a fire resisting door assembly, it is sometimes necessary to sub-divide fire doors into different categories. These categories are given below:- Type C Door leaves where all parts of the construction are of timber or other cellulosic

material, e.g. flaxboard, chipboard, fibreboard etc, or leaves where inorganic or mineral based materials are surrounded by softwood or hardwood framing. The mineral based material may be in the form of a solid slab or as sub-facings either side of a void, with or without intermediate rails. The timber framing must be unprotected for not less than 40mm which includes any lipping. The framing may be reinforced by additional timber or similar material at the head or at lock blocks to product a larger frame to support ironmongery.

Type I-O Door leaves constructed primarily of inorganic, or mineral based materials where

the surrounding frame of timber is less than 40mm wide, including any lippings. Type H Door leaves where a type ‘C’ door leaf, normally all of cellulosic construction is

faced on both sides with an inorganic board or a rigid intumescent sheet material not less than 2mm thick, either as a facing or a sub-facing. This material will extend from leaf edge to leaf edge, excluding any lippings.

Type M Door leaves where the facings or sub-facings are of a steel construction and

where the edges are metal (excluding any seals fitted), including primarily glazed leaves where the structural leaf framing consist of metal sections.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 25 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

ANNEX C

UNIVERSAL MATRIX FOR EXPRESSING COMPONENTS COMPATIBILITY FOR FIREDOOR ASSEMBLIES

Door Assembly Type

ITT ITM MM

C H I-O C H I-O M

FD20

FD20 +o/panel or 2nd leaf

FD30

FD30 +o/panel or 2nd leaf

FD60

FD60 +o/panel or 2nd leaf

FD90

FD90 +o/panel or 2nd leaf

FD120

FD120 +o/panel or 2nd leaf

FD180

FD180 +o/panel or 2nd leaf

FD180

FD180 +o/panel or 2nd leaf

UNIVERSAL MATRIX FOR EXPRESSING COMPONENTS COMPATIBILITY FOR FIREDOOR ASSEMBLIES

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 26 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

* (1) - Used for W-D seals only * (2) - May only be filled in if test evidence to Part A - Section 2 is available (yet to be

prepared)

EXAMPLE OF HOW TO FILL IN MATRIX FOR ‘C/D’, ‘W-S’ AND ‘TS’ SMOKE CONTROL SEALS

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 27 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

* (1) - Used for ‘C/D’, ‘W-S’ and ‘TS’ seals * (2) - May only be filled in if test evidence to Part A - Section 2 is available (yet to be

prepared)

EXAMPLE OF HOW TO FILL IN MATRIX FOR W-D SMOKE CONTROL SEALS

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 28 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

ANNEX D CERTIFICATE TEMPLATE

(The data contained herein is fictitious and does not relate to any actual door)

CERTIFICATE OF APPROVAL

No. CF XXX

This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products

The undermentioned products of

DYANA DOORS LIMITED

Address

Tel: Fax:

Have been assessed against the requirements of the Technical Schedule(s) denoted below and are approved for use subject to the conditions

appended hereto:

____________________________________________________________________________

CERTIFIED PRODUCT TECHNICAL SCHEDULE Smoke Seals TS21 The Contribution of Edge Seals to the Control of Smoke Leakage via Door Assemblies

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 29 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

SMOKE SEALS

1. Dyana Doors smoke seals are used for sealing door assemblies against leakage of

ambient temperature smoke, as defined in BS 476: Part 31.1. They do not contain intumescent material.

2. This certification is designed to demonstrate compliance of the product or system

specifically with Approved Document B (England and Wales), Section 2 of the Technical Standards (Scotland), Technical Booklet E (N. Ireland). If compliance is required to other regulatory or guidance documents there may be additional considerations or conflict to be taken into account.’

3. Within BS 5588: Part 1, a fire door required to resist the passage of smoke at ambient

temperature conditions should, when tested in accordance with BS 476: Section 31.1 with the threshold taped and subjected to a pressure of XX Pa, have a leakage not exceeding X m3/m/h. The threshold gap should be sealed either by a seal either with a leakage rate not exceeding Xm3/m/h at XX Pa or just contacting the floor. Where this is impracticable the threshold gap should not exceed X mm at any point.

4. The door seals are approved on the basis of: i) Initial type testing ii) A design appraisal against TS21

iii) Certification of quality management systems to ISO9001 iv) Inspection and surveillance of factory production control.

5. This approval certifies that the above seals are suitable for use with single-acting door

assemblies required to restrict smoke leakage at ambient temperatures as defined in Appendix B of Approved Document B, ‘Fire Safety’ to the Building Regulations 1991. It is applicable to latched and unlatched, single-leaf assemblies consisting of timber faced and edged leaves with timber, cellulosic or mineral cores in timber frames with or without intumescent edge seals (Code ITT and TT respectively). It is only applicable to assemblies that have been approved, or have been shown by test, to achieve the required period of fire resistance.

6. The seals shall be uninterrupted and fixed around the head and vertical edges of the

frame. The seals may be provided in brown, black and white colours. 7. The approval relates to on-going production. Product and/or its immediate packaging is

identified with the manufacturers’ name, the product name or number, the CERTIFIRE name or name and mark, together with the CERTIFIRE certificate number and application where appropriate.

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 30 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

ANNEX E

FACTORY PRODUCTION CONTROL CHECKLIST In the course of this annual inspection the following criteria should be considered:

GENERAL QUESTIONS

Questions to be considered Q/M or Procedure

Ref

Inspector Comments:

1 Does the producer continue to apply a quality management system related to the technical specification?

Intumescent Seals TS35

CF No.(s)

2 Does the producer still apply a quality management system related to the technical specification?

If YES, is that proved by a valid certificate and by whom? (detail certificate no. & certification body)

Report any changes

3. Does the factory production control for the devices to be certified continue to form part of the quality management system? Is it still contained within the manual or in a second tier of management system below the manual – but referred to by the manual? Are factory production control procedures / work instructions still being issued to shop floor? Identify these? If possible verify that any updated procedures have been passed to shop floor.

4 Are all areas of the production operation still addressed by the factory production control system – from purchasing / delivery of raw materials through to storage & delivery of finished product? Identify any areas not covered

5 Does the producer continue to have direct control of the appropriate machinery and for the production of the products to be certified, or are key elements of the production with respect to the essential characteristics subcontracted to others on or off the site?

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 31 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

Questions to be considered Q/M or Procedure

Ref

Inspector Comments:

6 Is the maintenance of this machinery still carried out to written procedures at regular intervals?

Is this being carried out properly, regularly, and is this recorded / documented?

7 Have there been any alterations to personnel since the initial FPC visit?

Contact Person

Management Representative Quality/Production Teams

8 For the products to be certified, have there been any changes in the way the raw materials are purchased since the last visit? - are the same suppliers still used (intumescent

ISO)?

- do purchase orders still detail specific requirements for raw materials? - are certificates of analysis / conformance still being requested from suppliers as part of procedures?

are specifications still in place with certain suppliers (which are referred to by P/Os) to ensure consistency of materials?

9 Is the Inspection of the incoming raw materials still carried out and have there been any changes in the way or frequency of the checks?

Are any certificates of analysis / conformity received still reviewed filed?

10 Is traceability of the raw materials used still being maintained?

What evidence was reviewed to confirm this traceability was still effective?

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 32 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

Questions to be considered Q/M or Procedure

Ref

Inspector Comments:

11 Are batches / items of raw material still traceable through the production process and in finished products?

What evidence was reviewed to confirm this traceability is effective?

12 Are the personnel involved in the production continue to be sufficiently qualified and trained to operate and maintain the production equipment and carry out production line duties?

What records / evidence confirm this?

13 Has the form of the FPC process control instructions remained the same or have any changes been made?

14 Are all production processes and procedures still recorded at regular intervals? Who records the processes? (if applicable) Are these continuously (automatically) recorded?

How is the documentation organized?

15 Are MFC (Manufacturing Frequency Checks) still being carried out for each batch and type of intumescent material?

Is the same equipment still being used to carry out tests?

Is equipment as annex A TS35 or has another method been approved by CERTIFIRE?

Have there been any changes to the stated values for the product?

If yes have they been declared to CERTIFIRE?

Have the required independent annual audit tests been carried out?

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 33 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

Questions to be considered Q/M or Procedure

Ref

Inspector Comments:

16 Review test records on material used in current batches. Do the findings of this review of records correlate with the requirements laid down in the company’s technical specification for the product for type testing, and for testing for surveillance purposes of the FPC? Are ageing resistance test results available and do they meet requirements of TS35? If internally tested who sealed the test cabinet for CERTIFIRE? Is serviceability testing carried out? Identify any anomalies found.

Are procedures still in place to deal with any batches that fail the tests?

17 Are smoke seals included in company’s approved product range? Which code(s) apply to the seals? Does data sheet included with finished products the following: -

- Application(s) for which CERTIFIRE approval is granted for seals

- Explanation of the principle of the approval - Clear fixing instructions - General recommendations as to how SS/ImS

interact - Universal Matrix

Is packaging clearly marked with CERTIFIRE logo?

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 34 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

Questions to be considered Q/M or Procedure

Ref

Inspector Comments:

18 Is the inspection equipment (micrometer, tape rules etc.) still correctly maintained and calibrated on a continuous basis to ensure constant accuracy of the tests performed during factory production control and surveillance? Are calibration records still available to enable the accuracy of the items of test / inspection equipment to be traced to national / international standards? Are internal calibrations still carried out in addition to periodic external ones? – if so how carried out / what frequency? Ensure equipment used to carry out MFC checks is still included in calibration system.

19 Does the producer continue to apply an adequate documented system that allows the detection of defects and deviations quickly enough to identify unambiguously those products that are not in accordance with the product specification so that they are removed prior to delivery? How are any non-conforming products identified and how dealt with after sentencing? What investigation goes on into such problems, have any changes been made to the process as a result? What records are produced?

20 For the products to be certified, does the producer continue to apply an adequate documented system concerning product complaints received, and that is integrated into the factory production control? Does the system still include appropriate measures to avoid or correct these deficiencies? How many customer complaints have been received since the last audit? Have any changes been made to the process as a result?

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 35 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

Questions to be considered Q/M or Procedure

Ref

Inspector Comments:

21 Have any changes been made to the method of packaging since the last audit?

22 Are product batches still traceable to date of production and the raw materials used? What records / evidence confirm this?

23 Has there been any changes to the information provided either marked on the packaging labelling?

- explanation of the principles of approval (i.e. applies only to seal material not the door)?

- Clear fixing instructions? - Guide to how much material to use? - Reference to IFSA Info sheet No.1? - Any special requirements if needed? - Handling & storage provisions? - Contact details for technical support?

23 Has there been any changes to the information provided either marked on the product? This must include the following

- CERTIFIRE name - Certificate No. - Manufacturer’s name - Month and year of manufacturer (or batch

code)

Marking should be on each length of seal if not possible the immediate packaging of the unit for sale shall be marked. Thus is seal is sold in individual lengths it will be necessary to mark each length.

24 Where a seal is only approved for minimum scope by CERTIFIRE the following wording must be visible prior to the packaging being opened. These seals of size are suitable to be used with CERTIFIRE approved FD30 SL, SAL, or unlatched timber doors of max leaf size 2040x926mm and thickness of 42mm. If also approved for double leaf door the additional wording will be added. FD30DL, SA latched timber doors of max individual leaf size 2040x826mm and thickness 42mm

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 36 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

Questions to be considered Q/M or Procedure

Ref

Inspector Comments:

25 Are records still maintained of where the finished products are shipped? Is the production batch number traceability still being maintained once the products have been dispatched to assist in traceability should any complaints be made? What records / evidence confirm this?

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 37 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

Summary of Inspection Findings:

Observations / Recommendations:

List of Attachments: Non Conformances Raised:

Signed by Inspector:

Date:

Signed for client by:

Date:

Reviewed by: (Office use only)

Date:

Quality EWC-QU-TS21

Technical Schedule

Issue No: 6 Issue Date: 13.12.18 Effective Date: 13.12.18 Review Date: 12.12.22

Author: Warringtonfire Testing and

Certification Limited

Approved: P. Duggan

Certification Manager

Authorised: K. Prendergast

Divisional Director, Certification

Page 38 of 38

This document is the exclusive property of Warringtonfire Testing and Certification Limited. It shall not be reproduced, in part or as a whole, other than by authorised Company personnel. The current controlled copy of the master document is that held and viewable by means of the Company QMS or company website. Electronic or paper copies may be considered valid if the issue number matches that shown on the current controlled copy of the master document.

Warringtonfire Testing and Certification Limited Reg. Office: 10 Lower Grosvenor Place, London, United Kingdom, SW1W 0EN

Co. Reg. No. 11371436

ANNEX F

PARTICIPATING ORGANISATIONS

BODIES AUTHORISED TO OPERATE CERTIFICATION TO THE PROVISIONS OF THIS SCHEDULE

Warringtonfire Testing and Certification Limited

THIS SCHEDULE IS RATIFIED BY MEMBERS OF THE WARRINGTONFIRE IMPARTIALITY COMMITTEE

Association for Specialist Fire Protection (ASFP) British Automatic Fire Sprinkler Association (BAFSA) British Retail Consortium (BRC) British Woodworking Federation (BWF) Chief Fire Officers Association (CFOA) Construction Products Association (CPA) Department of Communities and Local Government (DCLG) Door and Hardware Federation (DHF) Fire Protection Association (FPA) Glass and Glazing Federation (GGF) Guild of Architectural Ironmongers (GAI) Institute of Fire Prevention Officers (IFPO) Institute of Fire Safety Manager (IFSM) London Underground Limited (LUL) Royal Institute of Chartered Surveyors (RICS) RISC Authority Secured By Design (SBD) Local Authority Building Control (LABC) Warringtonfire (WF) ‘Users of Warringtonfire documents are reminded that copyright exists in all CERTIFIRE publications. No part of this publication may be reproduced in any form without prior permission in writing from Warringtonfire. Permission to copy this document for internal use and promotional purposes only is automatically granted to companies holding CERTIFIRE certification. Such copies are uncontrolled and this status should be identified on each copy’