technical note - tn 032: 2015 - transport for nsw · technical note - tn 032: 2015 . ... convention...

23
Technical Note - TN 032: 2015 For queries regarding this document [email protected] www.asa.transport.nsw.gov.au Technical Note - TN 032: 2015 Issued date: 12 June 2015 Effective date: 12 June 2015 Subject: Withdrawal of SPG 1250 Interface between Signalling and Control Systems This technical note is issued by the Asset Standards Authority as a notification to remove from use RailCorp document SPG 1250 Interface between Signalling and Control Systems, Version 1.7. SPG 1250 is a legacy document and shall be used for reference purposes only. ASA standard T HR SC 01250 SP Interface between Signalling and Control Systems, Version 1.0 supersedes this document. Authorisation: Technical content prepared by Checked and approved by Interdisciplinary coordination checked by Authorised for release Signature Name Omer Saricilar Peter McGregor John Paff Graham Bradshaw Position Principal Engineer Control Systems Lead Signals and Control Systems Engineer A/Chief Engineer Rail Principal Manager, Network Standards and Services © State of NSW through Transport for NSW Page 1 of 1

Upload: buidan

Post on 18-May-2018

221 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Technical Note - TN 032: 2015

For queries regarding this document

[email protected] www.asa.transport.nsw.gov.au

Technical Note - TN 032: 2015 Issued date: 12 June 2015

Effective date: 12 June 2015

Subject: Withdrawal of SPG 1250 Interface between Signalling and Control Systems

This technical note is issued by the Asset Standards Authority as a notification to remove from

use RailCorp document SPG 1250 Interface between Signalling and Control Systems,

Version 1.7.

SPG 1250 is a legacy document and shall be used for reference purposes only. ASA standard

T HR SC 01250 SP Interface between Signalling and Control Systems, Version 1.0 supersedes

this document.

Authorisation:

Technical content prepared by

Checked and approved by

Interdisciplinary coordination checked by

Authorised for release

Signature

Name Omer Saricilar Peter McGregor John Paff Graham Bradshaw

Position Principal Engineer

Control Systems

Lead Signals and

Control Systems

Engineer

A/Chief Engineer Rail Principal Manager,

Network Standards

and Services

© State of NSW through Transport for NSW Page 1 of 1

Page 2: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P

Engi

neer

ing

Spec

ifica

tion

2

Engineering Specification Signals and Control Systems Construction Specification

SPG 1250

INTERFACES BETWEEN SIGNALLING AND CONTROL

SYSTEMS

Version 1.7

Issued 21 March 2013

Owner: Chief Engineer Signals and Control Systems

Approved by:

Warwick Allison Chief Engineer Signals and Control Systems

Authorised by:

Stephen Templeton Principal Engineer Control Systems

Disclaimer This document was prepared for use on the RailCorp Network only. RailCorp makes no warranties, express or implied, that compliance with the contents of this document shall be sufficient to ensure safe systems or work or operation. It is the document user’s sole responsibility to ensure that the copy of the document it is viewing is the current version of the document as in use by RailCorp. RailCorp accepts no liability whatsoever in relation to the use of this document by any party, and RailCorp excludes any liability which arises in any manner by the use of this document. Copyright The information in this document is protected by Copyright and no part of this document may be reproduced, altered, stored or transmitted by any person without the prior consent of RailCorp.

UNCONTROLLED WHEN PRINTED Page 1 of 2

Page 3: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P RailCorp Engineering Specification — Signals and Control Systems — Construction Specification

Interfaces Between Signalling and Control Systems SPG 1250

© RailCorp Page 2 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

Document control

Version Date Summary of change 1.0 7 April 2009 New document 1.1 May 2010 Application of TMA 400 format.

1.2 9 September 2011 Added Signal Direction Indicator Inputs, added allocation strategy of input and outputs.

1.3 3 April 2012 Westlock is added as a CBI. Track Sequencing alarm’s indication and control are added.

1.4 3 January 2013 Added slip detector inputs to Appendix A page 18

1.5 5 February 2013

Added missing “Air System” equipment label to Appendix A page 14 Added Signal Key Switch to Appendix A page 15 Modified slip detector inputs to Appendix A page 18

1.6 11 March 2013 Added "emergency override" inputs page 17 Added reference to ESG100

1.7 21 March 2013 Added " Points Maintenance Isolating Switch " inputs page 17

Page 4: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P RailCorp Engineering Specification — Signals and Control Systems — Construction Specification

Interfaces Between Signalling and Control Systems SPG 1250

© RailCorp Page 3 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

Contents 1 Scope and Application ...........................................................................................................5 2 Applicable Standards .............................................................................................................5 3 Overview ..................................................................................................................................5 4 Indication and Control States ................................................................................................6

4.1 Indications..................................................................................................................6 4.2 Controls .....................................................................................................................6

5 Hardware Interface..................................................................................................................6 5.1 Equipment types ........................................................................................................6 5.2 Telemetry Equipment.................................................................................................7

5.2.1 SCADA 2000 ..............................................................................................7 5.2.1.1 Indications...................................................................................7 5.2.1.2 Indication Conditioning................................................................8 5.2.1.3 Controls.......................................................................................8

5.2.2 DUPLINE....................................................................................................8 5.2.2.1 Indications...................................................................................8 5.2.2.2 Indication Conditioning................................................................8 5.2.2.3 Controls.......................................................................................8

5.2.3 IMAC...........................................................................................................8 5.2.3.1 Indications...................................................................................9 5.2.3.2 Controls.......................................................................................9

5.2.4 KINGFISHER .............................................................................................9 5.2.4.1 Indications...................................................................................9 5.2.4.2 Controls.......................................................................................9

5.3 Computer Based Interlockings ..................................................................................9 5.3.1 SSI..............................................................................................................9

5.3.1.1 Indications...................................................................................9 5.3.1.2 Controls.....................................................................................10

5.3.2 Westlock...................................................................................................10 5.3.3 Microlok ....................................................................................................10

5.3.3.1 Indications.................................................................................10 5.3.3.2 Controls.....................................................................................10

5.4 Electrical Isolation....................................................................................................10 5.4.1 Relay Based Systems ..............................................................................11 5.4.2 Computer Based Systems .......................................................................11

6 Interface properties...............................................................................................................11 6.1 Naming Convention .................................................................................................11 6.2 Combining of Inputs.................................................................................................12

7 Expected Indications and Controls.....................................................................................12 8 Spare Indications or Controls..............................................................................................12 9 Allocation of Indications and Controls ...............................................................................12 10 Documentation of Interface..................................................................................................13 Appendix A Indications..............................................................................................................14

Page 5: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P RailCorp Engineering Specification — Signals and Control Systems — Construction Specification

Interfaces Between Signalling and Control Systems SPG 1250

© RailCorp Page 4 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

Appendix B Controls ..................................................................................................................21

Page 6: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P RailCorp Engineering Specification — Signals and Control Systems — Construction Specification

Interfaces Between Signalling and Control Systems SPG 1250

1 Scope and Application This document describes the interface requirements between the signalling system and the Signalling Control System.

For new interlockings this document shall be used as the interface requirements to the Signalling Control System. The interlocking design is expected to follow the naming convention and the meaning of the indications and controls as defined in this document.

For existing interlockings this document is intended to be used as the requirements for the signalling interface design if it is modified for remote control.

For some installations a separate maintenance system may be provided to capture diagnostic indications for maintainers. When this is provided, a reduced set of indications may be provided to the Signalling Control System. When this occurs, the interface is to be documented as described in Section . Mandatory indications and controls for the Signalling Control System are noted in and Appendix B respectively..

10Appendix A

The requirements detailed in this document do not reduce any requirements of the signal design principles or standards.

2 Applicable Standards

RailCorp Specifications ESG 007 Glossary of Signalling Terms ESG 100 Signal Design Principles SDG 001 Standard Signalling Circuits SPG 1230 Design Of Microlok II Interlockings SPG 0703 Signalling Documentation and drawings SPG 0713 Signalling Control Systems

Other Specifications SSI 8003-10 SSI Data Preparation Interlocking Railtrack PLC

3 Overview Figure 1 shows the interface between the signalling system and the signalling control system.

Signalling System(Vital InterlockingSystem – usually

Trackside)

Signaller

Interface between signalling system and signalling control system

Signalling Control System(Non-vital system

usually centralised)

Communications Link

© RailCorp Page 5 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

Page 7: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P RailCorp Engineering Specification — Signals and Control Systems — Construction Specification

Interfaces Between Signalling and Control Systems SPG 1250

© RailCorp Page 6 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

Figure 1 - Interface Overview

In this document “the interface” refers to the interface between the signalling system and Signalling Control System unless otherwise specified.

The physical interface usually takes the form of a serial communications link between field located interlocking equipment, & a remotely located control system.

This document identifies the types of signalling systems and interface equipment that the Signalling Control System connects to. It also defines the logic states of the indications and controls in terms of the electrical interface or protocol.

4 Indication and Control States This section defines the states of indications and controls that shall be used by the Signalling Control System.

4.1 Indications The signalling control system is required to be able to display each state as ON, OFF or UNKNOWN.

Where failure of the signalling equipment or components of the signalling equipment or telemetry equipment cannot be determined entirely from the communications link, equipment health indications shall be provided. For example if a Microlok field slave fails then the indications received from the Microlok master will need to be marked as unknown by the control system. A Slave_OK indication is required to achieve this, see Cardfile OK in Appendix A.

Health indications shall be associated with the indications they affect.

Health indications shall be processed before changes to their affected indication bits by the Control System.

4.2 Controls The Signalling Control System states of signalling controls shall be :

Steady OFF

Steady ON

Pulse ON – The output is set to ON then OFF

Pulse OFF – The output is set to OFF then ON

The type of control & the duration of the pulse shall depend on the hardware interface. See section 5.

5 Hardware Interface This section identifies the connection details for the signalling system and relates the physical interface to the states of the Signalling Control System indications and controls.

5.1 Equipment types The Signalling Control System interfaces shall include the capability to interface to signalling systems of the following interlocking types:

Page 8: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P RailCorp Engineering Specification — Signals and Control Systems — Construction Specification

Interfaces Between Signalling and Control Systems SPG 1250

© RailCorp Page 7 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

a) Relay

b) Microlok

c) SSI and Westlock

d) Westrace

The Signalling Control System interfaces to Relay interlocking shall include the following types of telemetry equipment:

a) SCADA 2000

b) Dupline

c) IMAC

d) Kingfisher Telemetry Systems

The Signalling Control System interfaces to signalling ancillary systems may also include the following types of equipment:

a) Power supply equipment – rectifiers, Switch mode supplies, Uninterruptible power supplies (UPS) including bypass on line, on battery etc, Emergency Change Over contactors (ECOs), Earth Leakage Detectors (ELDs), miscellaneous indications – voltage free relay contacts.

b) Air compressor systems – Control PLCs, pressure switches, compressor alarms and miscellaneous indications – serial data, USB or voltage free contacts.

c) Fire alarms.

d) Data Link switches, routers.

e) Trackside monitoring (e.g. dragging gear detection, etc.)

5.2 Telemetry Equipment The wiring connections from any telemetry system to the signalling system shall be included in the signalling design circuits.

5.2.1 SCADA 2000 The SCADA 2000 is a telemetry system, which can be duplicated to improve availability. The connections to the interlocking are via optoisolator boards.

5.2.1.1 Indications The input circuit may be a single contact, or a logic circuit of a number of contacts.

The Signalling Control System shall detect indications as:

ON: when the input circuit is closed and the required voltage is applied to the input terminal.

OFF: when the input circuit is open.

Vital Indication Optoisolators (VIO) may be used where an intermediate point of a vital circuit is required as an input, such as for RUZR indications. A circuit including the VIO then drives an input Optoisolator as per conventional inputs.

Page 9: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P RailCorp Engineering Specification — Signals and Control Systems — Construction Specification

Interfaces Between Signalling and Control Systems SPG 1250

© RailCorp Page 8 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

5.2.1.2 Indication Conditioning Indication conditioning is set by the Signalling Control System; there are no hardware interface requirements for indication conditioning.

5.2.1.3 Controls Controls shall have the following effect on outputs:

Steady ON: current is allowed to flow

Steady OFF: no current is allowed to flow.

For Pulse ON controls the output is set to ON and after 1 second set to OFF. This conversion is performed by the SCADA 2000 system. Pulse OFF controls are handled similarly.

Controls are only set ON by the master side. For the Standby side all controls are set OFF. On a change of mastership there will be an overlap where both sides are master to ensure that the signalling control outputs do not drop out.

5.2.2 DUPLINE Dupline is a telemetry system, which can be duplicated to improve availability.

5.2.2.1 Indications The input circuit may be a single contact, or a logic circuit of a number of contacts.

Indications shall be detected as:

ON: when the input circuit is closed and the required voltage is applied to the input terminal.

OFF: when the input circuit is open.

5.2.2.2 Indication Conditioning Dupline has no indication for input module failures

A hard-wired health indication shall be supplied per input module.

This input is wired directly to the indication bus voltage. If there is a failure of the module then all indications from the module will be set OFF, including the health indication. When this is detected all other inputs from the module are made UNKNOWN.

Dupline has two failure modes “ALL ON” and “ALL OFF” with only the “ALL OFF” failure mode being alarmed.

5.2.2.3 Controls No control shall be issued using Dupline telemetry systems.

5.2.3 IMAC IMAC is a telemetry system, which can be duplicated to improve availability.

Page 10: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P RailCorp Engineering Specification — Signals and Control Systems — Construction Specification

Interfaces Between Signalling and Control Systems SPG 1250

© RailCorp Page 9 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

5.2.3.1 Indications IMAC input modules use a sense current to determine if the input circuit is closed. For this reason one circuit or contact cannot be used for duplicated inputs. Two contacts, or duplicated input circuits are to be used for duplicated system. The input circuit may be a single contact, or a logic circuit of a number of contacts.

Indications shall be detected as:

ON: when the input circuit is closed.

OFF: when the input circuit is open.

IMAC input modules can be configured to invert the logic sense of the inputs using DIP switches. This feature is not used.

5.2.3.2 Controls No control shall be issued using IMAC telemetry systems.

5.2.4 KINGFISHER Kingfisher is a telemetry system that which can be duplicated to improve reliability.

5.2.4.1 Indications The input circuit may be a single contact, or a logic circuit of a number of contacts.

Indications shall be detected as:

ON: when the input circuit is closed and the required voltage is applied to the input terminal.

OFF: when the input circuit is open.

5.2.4.2 Controls Use of controls through Kingfisher is permissible in accordance with 5.2.1 above, however, receipt on both sides may be required for the application.

5.3 Computer Based Interlockings

5.3.1 SSI The Signalling Control System shall interface to SSI interlockings via a serial communications link using the BR1631 protocol.

The connection point shall be the RS422 ports provided by the Panel Processor Modules (PPM). Each SSI cubicle has two PPMs with one RS422 port per PPM for the interface.

5.3.1.1 Indications Indications are received via the protocol. The indication values shall be:

ON: SSI value of TRUE which is indicated by a ‘1’ in the protocol message.

OFF: SSI value of FALSE which is indicated by a ‘0’ in the protocol message.

Page 11: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P RailCorp Engineering Specification — Signals and Control Systems — Construction Specification

Interfaces Between Signalling and Control Systems SPG 1250

© RailCorp Page 10 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

5.3.1.2 Controls Requests shall only be sent by the master Signalling Control System side. On a change of mastership there will be an overlap where both sides are master.

Control values sent via the protocol are set to:

ON: SSI value of TRUE which is indicated by a ‘1’ in the protocol message.

OFF: SSI value of FALSE which is indicated by a ‘0’ in the protocol message.

5.3.2 Westlock The Signalling Control System shall interface to Westlock interlockings via a serial communications link using the RT/E/S/17503 protocol.

The connection point shall be the RS422 ports provided by the Control System Gateways (CSG). Each Westlock system has two CSGs. Each CSG can have multiple addresses with one RS422 port per address on each CSG.

The RT/E/S/17503 protocol is identical to the SSI BR1631 protocol. See section 5.3.1 for definitions of Indications and Controls.

5.3.3 Microlok The Signalling Control System shall interface to Microlok interlockings via serial communications links using the Genisys protocol. Two Genisys links shall be provided.

5.3.3.1 Indications The values of the indications received via the protocol shall be:

ON: Microlok value of TRUE which is indicated by a ‘1’ in the protocol message.

OFF: Microlok value of FALSE which is indicated by a ‘0’ in the protocol message.

5.3.3.2 Controls Controls values sent via the protocol are set to:

ON: Microlok value of TRUE via a ‘1’ in the protocol message.

OFF: Microlok value of FALSE via a ‘0’ in the protocol message.

Where Microlok requires controls to be pulsed ON or OFF, the duration shall be configurable in the Signalling Control System. The duration will typically be set to 1 second but shall not be greater than 2 seconds.

Controls shall be sent from both the master and the standby Signalling Control System side.

5.4 Electrical Isolation Signalling interlocking equipment shall be electrically isolated from control system equipment or communication equipment. This is to avoid lowering the electrical integrity of signalling systems & avoid the transference of electrical surge between systems.

Page 12: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P RailCorp Engineering Specification — Signals and Control Systems — Construction Specification

Interfaces Between Signalling and Control Systems SPG 1250

© RailCorp Page 11 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

5.4.1 Relay Based Systems All wiring connected to vital circuits shall conform to railway signalling standards for vital wiring. Equipment connected to such wiring is subject to Type Approval to ensure adequate isolation is provided between the vital & non-vital elements of the system.

5.4.2 Computer Based Systems All connections between vital computer systems & communication equipment, or control equipment shall be isolated.

6 Interface properties This section describes the properties of indications and controls.

6.1 Naming Convention The Signalling Control System I/O naming convention for existing interlockings shall be as per the function names used in the circuit book or data, with the addition of an interlocking abbreviation prefix to achieve unique names. The interlocking abbreviation shall be a unique two letter abbreviation of the interlocking name.

The interlocking abbreviation is not required in the interlocking data. The function names shall omit all characters that are added to identify repeats. See Standard Signalling Circuits SDG 001, sheet Z03.

Where multiple copies of the same function are provided to the Signalling Control Systems (e.g. at system interfaces), a suffix of ‘–n’ shall be added where n is the copy number starting from 1. The suffix for the first copy of the function may be omitted; subsequent copies shall be numbered starting from 2.

The naming conventions for SSI interlockings shall be as per the SSI source files. The naming convention is defined in SSI 8003-10.

For new works the naming convention shall be as defined by this document. The naming convention of this document follows that of Signalling Documentation and Drawings SPG 0703, Appendix B ; and Signalling Circuit Design Standards Standard Signalling Circuits SDG 001, sheets Z01, Z02.

In general the indication names may exclude the ‘R’ for relay at the end of the function name. The ‘R’ shall be omitted where it is commonly omitted in usage such as track circuit indications, as is done in Microlok data. The naming convention for equipment that is not included in the above documents shall follow the name used in the signalling circuits or computer based interlockings data or is a descriptive word in brackets.

For Microlok interlockings the bit names of the Microlok data are often prefixed with their communications port number, see SPG 1230, section 4.5.3. Where this is the case, the communications port prefix shall be removed from the name used by the Signalling Control System.

The IO names may contain alphanumeric characters (case sensitive) as well as the four characters “- _ ( )”. IO names shall not contain any space characters. The asterisk ‘*’ is reserved for use by intermediate terms within the Signalling Control System. The terms “TRUE” and “FALSE” are also reserved.

Page 13: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P RailCorp Engineering Specification — Signals and Control Systems — Construction Specification

Interfaces Between Signalling and Control Systems SPG 1250

© RailCorp Page 12 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

6.2 Combining of Inputs Inputs shall be provided for each indication separately except where combining of inputs is required to provide the single required function such as:

a) Route availability indications.

b) Certain alarm indications as may be agreed on a project basis.

7 Expected Indications and Controls This section identifies the expected indication and control connections that shall be provided by the signalling system to the Signalling Control System.

In the table the indications specified for Relay and Microlok interfaces are expressed in terms of relay contacts. For Microlok interfaces “contact” shall mean the functional equivalent.

For SSI the table lists the indications that are required as well as the latches that need to be provided.

This table represents the usual application. Some installations may vary in the logic required to provide the function.

For example, some signals may clear without train stop drive.

The Chief Engineer Signals and Control Systems may clarify specific situations upon request.

Where separate diagnostic systems are provided, those indications that are mandatory for the Signalling Control System are noted. These may also be provided to the diagnostic system.

The indication and control listings are in Appendix A and Appendix B.

8 Spare Indications or Controls Controls and indications shall be logically (numerically) arranged in order on the serial links. It is preferred that any new or altered spare indications or controls are added to the end of any listing rather than to readjust the predefined order in the bit stream. Once the bit listing is established minor modifications may have the spares at the end utilised for additional bits.

To facilitate the addition of extra bits, the listing shall include the initial allocation of an additional 15%– 20% bits nominated as spare over & above the required bit listing. Typically the additional spare bits may fill out the capacity of the addressing arrangements.

9 Allocation of Indications and Controls All indications and controls related to an item of signalling equipment shall be allocated in one telemetry system. For example all the IO for a signal including all indications and controls as well as associated A track indication for all routes from the signal shall be allocated to one telemetry system.

Indications shall be geographically contiguous in one telemetry system, i.e. If the signal and A track are indicated from System 1 and the B track is indicated from the next telemetry (2) then subsequent tracks C, D, etc. shall be indicated from system 2.

Page 14: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P RailCorp Engineering Specification — Signals and Control Systems — Construction Specification

Interfaces Between Signalling and Control Systems SPG 1250

© RailCorp Page 13 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

10 Documentation of Interface For any project implementation, the Signal Designer shall produce a detailed bit list for the interface for agreement by the control system designer. When this is agreed, any changes to the list shall require the agreement of both parties.

Page 15: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P

RailCorp Engineering Specification — Signals and Control Systems — Construction Specification Interfaces Between Signalling and Control Systems SPG 1250

Appendix A Indications

Equipment Indication Name Mandatory for Signalling Control System

Interface Type Relay / Microlok SSI

Starting of the lag compressor AIR_LAG_KR

Compressor failure AIR_FW_KR Dryer failure (if provided separate from compressor) AIR_DF_KR

Activation of any low pressure * AIR_LP_KR Activation of any high pressure AIR_HHH_KR Loss of either power supply either partially (e.g. loss of phase) or completely

AIR_PSN_KR AIR_PSE_KR

Activation of low pressure AIR_LLL_KR Failure of both compressors * AIR_F_KR

Air System

Loss of both power supplies * AIR_PSR_KR Normal Available * Front contact of _NORM LnameNORM Emergency Available * Front contact of _EMERG LnameEMERG Load Available * Front contact of _PSR LnamePSR ATS 1 Auto Selected ATS_ON_AUTO ATS 1 Normal Supply Available & On Line ATS_NOR

ATS 1 Emergency Supply Available ATS_EMERG ATS 1 Essential Switchboard 1 Supply Available ATS_ESS_NOR

UPS Healthy (drops out with any UPS alarm) UPS_NOR

AC Power Supply

UPS on Bypass UPS_BYPASS

© RailCorp Page 14 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

Page 16: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P

RailCorp Engineering Specification — Signals and Control Systems — Construction Specification Interfaces Between Signalling and Control Systems SPG 1250

Equipment Indication Name Mandatory for Signalling Control System

Interface Type Relay / Microlok SSI

UPS Load on Battery UPS_BATT UPS ON UPS_ON EC01 Supply Available & On Line EC01_NOR EC01 Bypass Supply Available EC01_BYPASS EC01 Essential Switchboard 2 Supply Available EC01_ESS_NOR

* Combination of front contact of HR or front contact of LsPR and front contact of VRR or front contact of RGKR

Combination of: - SnameT.asp0 .. asp2 LnameVRR – see train stop indications Rname.set Logic to perform combination shall be provided by interlocking designer.

Signal Reverse (RGK)

* Combination of back contact of HR or back contact of LsPR and front contact of VNR or front contact of NGPR

Combination of: - SnameT.asp0 .. asp2 LnameVNR – see train stop indications Latch for train stop suppression where required. Logic to perform combination shall be provided by interlocking designer.

Signal Normal (NGK)

Up direction Indicator (_UYR) _UYR na Down direction Indicator (_DYR) _DYR na

Signals

Signal Key Switch (_GZK) * _GZK _GZK

© RailCorp Page 15 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

Page 17: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P

RailCorp Engineering Specification — Signals and Control Systems — Construction Specification Interfaces Between Signalling and Control Systems SPG 1250

Equipment Indication Name Mandatory for Signalling Control System

Interface Type Relay / Microlok SSI

Signals Emergency Replacement * Front contact of ENR SnameT.auto

Controlled Signal Auto Re-clear * Front contact of (A)SR SnameT.auto *Note A1 Controlled Signal Approach Locked ( ALS ) * Front Contact of ALSR/ALSK in MLK SnameT.toal

Controlled Signal * Front Contact of LPR Either SnameT.ascon or LnameLPR latch Lever Control ( _LP )

DC Power Warning * Front contact of _WARN LnameWARN DC Power Supply DC Power Fail * Front contact of _FAIL LnameFAIL Up Direction ( UD ) * Front contact of UDKR or UDR LnameUDKR Direction Indicator Down Direction ( DD ) * Front contact of DDKR or DDR LnameDDKR

Timer Initiation * “Section and Direction Identifier” _PBR na Direction Override

* “Section and Direction Identifier” _SECTION_JR na Direction Override

Control Indicator * Front contact of _CONTROL Latch Dual Controls Control Repeater * Front contact of _CONTROLK Latch

Earth Leakage Detector Earth Leakage Front contact of _ELD LnameELD Emergency Shunt Function ESF Enabled * Front contact of ESF_ON LnameESF * Note A1

Fire Front contact of _FIRE_ALARM LnameFIREALARM Fire System Fire System Fault Front contact of _FIRE_FAULT LnameFIREFAULT Alarm Front contact of _FLOOD_ALARM na Warning Front contact of _FLOOD_WARNING na Flood Detector Override Front contact of _FLOOD_OVERRIDE na

Half Pilot Staff HPS In Lock * Front contact _HPS LnameHPS High Load Detectors Alarm * Front contact of _ALARM na

© RailCorp Page 16 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

Page 18: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P

RailCorp Engineering Specification — Signals and Control Systems — Construction Specification Interfaces Between Signalling and Control Systems SPG 1250

Equipment Indication Name Mandatory for Signalling Control System

Interface Type Relay / Microlok SSI

Health EquipmentOK * _OK na Warning * Front contact of _NO_CHARGE LnameCHARGE Alarm * Front contact of _LOW_BATTERY LnameBATTERY Crossing Normal Front contact of XNR na

Level Crossing Note A3

Crossing Control Front contact of XR na Local * Front contact of LCR na Remote * Front contact of RCR na Closing * Front contact of _CLOSING na

* Front contact of _OVERRIDE_OFF_CONT na Override control off

* Front contact of _OVERRIDE_AUTO_CONT na Override control auto

Override control forced * Front contact of _OVERRIDE_FORCED_CONT na

Local Control

Override enabled * Front contact of OVERRIDE_KR na Ready * A_ON_STANDBYK na Mastership Master On Line * A_MASTER_ONLINEK na

Non-Stopping Train Function Enabled * Front contact of non-stopping train function L-NON-STOP-TRAIN

Free WZ * Front Contact of WZR LnameWZ

Normal NWK * Front contact of NWKR Combination of: - Pname.cn and Pname.dn Points

Reverse RWK * Front contact of RWKR Combination of: - Pname.cr and Pname.dr

Points Maintenance Isolating Switch Points Maintenance Isolating Control off * Front contact of ZIR na

Normal Detected NK * Front contact of NKR/NWKR/NR LnameNKR Releasing Switches Normal Locked NL * Front contact of NLR LnameNLR

© RailCorp Page 17 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

Page 19: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P

RailCorp Engineering Specification — Signals and Control Systems — Construction Specification Interfaces Between Signalling and Control Systems SPG 1250

Equipment Indication Name Mandatory for Signalling Control System

Interface Type Relay / Microlok SSI

Release Reverse RL * Front contact of RLR LnameRLR

Normal Lock NL * Front contact of NLR Rname.set (to be inverted) Routes

* RUZK Combination of indications. Available RUZ

Machine In Use MUR * Front contact of MuR na Ring Circuit Note A5 Machine Finished FUP * Front contact of FnPR na

Security Alarm Front contact of _SEC_ALARM LnameSECALARM Security System Security Fault Front contact of _SEC_FAULT LnameSECFAULT

Signal Filament Group Filament Failure FCK * Front contact of FCKR na

Signal Lamp Group * Front contact of ECR, with qualification where required SnameT.lp Lamp Failure ECK

Slip detected * Front contact of SLIP NR LnameSLIPNR Slip (land) Detector Emergency Slip Override Switch * Front contact of SLIP ALARM R LnameSLIPALARMR

Tracks Unoccupied _T * Front Contact of TKR.

Combination of: - Tname.clear Tname.bar

Track Timers Expired _J * Front Contact of TJKR LTnameJ Normal VN Note A2 Front contact of VNR LnameVNR Train Stops Reverse VR Note A2 Front contact of VRR LnameVRR

Ventilation Lock Enabled Note A4 Front contact of VCKR na Track Sequencing Alarm Alarm LALM(line-location)

Treadle Treadle_Fault *

Miscellaneous

© RailCorp Page 18 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

see Note A6 SSI Interlocking Critical Fault * na Combination of: - nameStatus.newcrit nameStatus.ackcrit nameStatus.timeout

Page 20: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P

RailCorp Engineering Specification — Signals and Control Systems — Construction Specification Interfaces Between Signalling and Control Systems SPG 1250

Equipment Indication Name Mandatory for Signalling Control System

Interface Type Relay / Microlok SSI

nameStatus.disabled

* na Combination of: - nameStatus.newncrit nameStatus.ackncrit

SSI Interlocking Non-critical Fault

SSI Interlocking Disabled * na nameStatus.disabled Communications OK * Front contact of Comms_System_OK na Master On Line * A_MASTER_ONLINEK na

THIS_SIDE_OK OTHER_SIDE_OK DUAL_LINK_OK

na Dual Link Health

* <Location>LINK_A_FOMS_M1OK (for each location / cardfile) na LINK A FOMS M1OK_for each location

* <Location>LINK_B_FOMS_M1OK (for each location / cardfile) na LINK B FOMS M1OK_for each location

* <Location>LINK_A_FOMS_M3OK (for each location / cardfile) na LINK A FOMS M3OK_for each location

* <Location>LINK_B_FOMS_M3OK (for each location / cardfile) na LINK B FOMS M3OK_for each location

* <Location> OK (for each location / cardfile) na Cardfile OK Note A7.

* This <Location> OK (or A_OK) (for each location / cardfile) na This Cardfile OK (for dual systems)

* Other <Location> OK (or B_OK) (for each location / cardfile) na Other Cardfile OK (for dual systems)

On Line * A_ONLINE na On Standby * A_ONSTANDBY (or THIS_MLK_OK_OUT) na

© RailCorp Page 19 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

Page 21: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P

RailCorp Engineering Specification — Signals and Control Systems — Construction Specification Interfaces Between Signalling and Control Systems SPG 1250

Equipment Indication Name Mandatory for Signalling Control System

Interface Type Relay / Microlok SSI

Dual Link OK MP1 * MP1_DUAL_LINK OK na Dual Link OK MP2 * MP2_DUAL_LINK OK na MP1 Link <X> OK * MP1_PORT1 LINK OK Na MP2 Link <X> OK * MP2_PORT 1 LINK OK na Microlok Warning * MLK_WARNING na Microlok Diversity Link In Operation * _DIV_<LOCATION> <LINK> Na

RS400 / RS416 LOC_A1_RS400_OK LOC_A_DIAG_RS416_OK

Kingfisher

Table 1 - Indications

Note A1: It is preferred that these functions are performed wholly within the control system.

Note A2: These functions are only for intermediate train stops. Train stops at signals are to be combined with the NGK & RGK functions.

Note A3: Comprehensive level crossing monitoring is performed by the Cerberus systems.

Note A4: Only included in Signalling Control System if it impacts signals clearing.

Note A5: Only for existing relay based entrance – exit interlockings with Commence & Finish functions performed within the relay interlocking.

Note A6: Where Ethernet switches are used, equivalent indications for the device health are to be substituted.

Note A7: Different configurations may require variation to these status bits.

Note A8: <name> indicates the location name.

© RailCorp Page 20 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

Page 22: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P

RailCorp Engineering Specification — Signals and Control Systems — Construction Specification Interfaces Between Signalling and Control Systems SPG 1250

Appendix B Controls

Equipment Control Name Interface Type Relay / Microlok SSI

Enable A(F)R Note B1 Note B1 Auto Re-Clear Disable Normal A(FM)R OR Inverted A(T)R Note B1 Note B1 Set Auto EM_REP or EMRR Automatic Signals with

Emergency Replacement Replace Inverted EM(T)REP or Normal EM(FM)REP

Direction Override Set SECTION PB Accept ACPT_RSR Dual Controls Cancel ACPT_UNR

Emergency Shunt Function ESF Request ESF Note B1 Note B1

Commence (F)R Finish (F)R Entrance Exit Routes Cancel (FM)R Test _TEST High Load Detectors Cancel _CANCEL

Mastership Go Master CTR_SYS_MASTER Note B2 Enable NON_STOP_TRAIN_(R)R Non-Stopping Train

Function Disable NON_STOP_TRAIN_(N)R Request RSR pulsed QRname Note B3 One Control Routes Cancel UNR pulsed QXSname Centre (C)R steady QPnameKC Normal (N)R steady QPnameQN Points Reverse (R)R steady QPnameQR

Releasing Switches Lock (N)R steady

© RailCorp Page 21 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7

Page 23: Technical Note - TN 032: 2015 - Transport for NSW · Technical Note - TN 032: 2015 . ... convention and the meaning of the indications and controls as defined in this document

Sup

erse

ded

by T

HR

SC

012

50 S

P

RailCorp Engineering Specification — Signals and Control Systems — Construction Specification Interfaces Between Signalling and Control Systems SPG 1250

Equipment Control Name Interface Type Relay / Microlok SSI

Release (R)R steady

Track Sequencing Alarm Reset QSEQRESET

Note B1: It is preferred that these functions are performed wholly within the control system.

Note B2: Not to be used for new work.

Note B3: <name> indicates the location name.

© RailCorp Page 22 of 22 Issued 21 March 2013 UNCONTROLLED WHEN PRINTED Version 1.7