technical manual - gnet.co.rs · typically over 1200, in conformity with the iec896-2. important...

26
An Invensys company Technical Manual OPzV

Upload: lyquynh

Post on 25-Apr-2018

219 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

An Invensys company

Technical Manual

OPzV

Page 2: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

1

I/ The principle of the gas recombination tubular gel battery1 - Operating principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 - Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 - Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 - The OPzV range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

II/ Application and use of the OPzV batteries1 - Standby applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 - Battery cycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 - Effect of temperature on battery capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 - Temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 - Effect of temperature on life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

III/ Electrical performance at 20°C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 to 16

IV/ Battery calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

V/ Installation of the battery1 - Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182 - Unpacking the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183 - Setting up the battery stands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184 - Connection of the cells . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225 - General recommandations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226 - Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227 - Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

VI/ Battery storage1 - Calculating the storage time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232 - Storage conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233 - Storage times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234 - Recharging stored batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235 - State of charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

VII/ Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

VIII/ Maintenance/checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Contents

Page

Page 3: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

The principle of gas recombination, which limits the release of gas, allows thebatteries to be installed in the widest possible range of sites and in contact withmodern technology.

The purpose of this operating guides is to provide you with technical information togain a better understanding of the gas-recombination battery OPzV range and willenable you to use it more effectively.

Introduction

2

Page 4: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

3

1 - Operating principleIn a traditional lead – acid battery, overcharging leads toa release of hydrogen and oxygen, a certain amount ofwater is lost and has to be replaced regularly by toppingup.

In a gas recombination battery, the internal design of thecell allows the oxygen produced at the positive plates todiffuse toward the negative plates :

- The oxygen reacts chemically with the spongy leadof the active material to form lead oxide.

- The sulphuric acid of which the electrolyte iscomposed then reacts with this lead oxide to formlead sulphate and water.

- The lead sulphate thus formed is transformedelectro-chemically into lead, to return sulphuricacid.

- As long as the battery remains fully charged, thisequilibrium is maintained.

Schematically, we then have the following reactions :

2 - ConclusionDue to the gas recombination reaction in the Hawker OPzVcells, water is recombined nearly at the same rate as it isconsumed under float charge conditions and no toppingup water during the lifetime of the cells is required.

I/ The principle of the gas recombination tubular gel battery

Conventional cell

Oxygen and Hydrogenescape to the atmosphere

OPzV

Oxygen evolved frompositive platetransfers to negativeand recombines toform water.

At the end of the charge or ifovercharging, oxygen gas isreleased at the positive plate.

H2O ➞ 2H+ + 1/2O2 + 2e-

The oxygen diffuses across thegelled electrolyte and themicro-porous separator to thenegative plate.

The oxygen reacts chemicallywith the spongy lead of thenegative plate to form leadoxide.The sulphuric acid reacts withthis lead oxide, giving leadsulphate and water.Part of the spongy lead is thuschemically discharged to thelead sulphate state and thewater consumed at the positiveplate is regenerated.

Pb + 1/2O2 ➞ PbO

PbO + H2SO4 ➞ PbSO4 + H2O

The spongy lead which waschemically discharged at thenegative plate is rechargedchemically.

PbSO4 + 2H+ + 2e-

➞ Pb + H2SO4

H2

O2

Electrolyte

Separator

+

- -+

O2

O2

Page 5: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

4

3 - ConstructionThese reactions can take place only by using :

- plates composed of a special lead calcium alloy whichprovides the grids with high mechanical strength and ahigh level of hydrogen overtension.

- microporous separators

- A capillary network gelled electrolyte :

To retain the electrolyte in a thixotropic gelTo help oxygen penetration into the negative plate.

- A pressure relief valve which allows gas to be releasedif necessary in the case of an accidental overcharge.

Lid in ABS

Separator

Flat negativeplate

Pressure relief valve

Colored negativepolarity washer (blue)

Container in ABS

Positive grid coating

Diecast tabs of positive grid

Terminals with brass insertfor improved conductivity

Colored positive polarity washer (red)

Tubular positive plates

Page 6: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

5

4 - The OPzV rangeComprises 14 cells with capacities from 200 Ah to 3000 Ah.

4 OPzV 200 1 200 215 210 190 170 130 0.92 2266 103 206 403 19.5 4 OPzV 200

5 OPzV 250 1 250 265 260 235 210 160 0.74 2803 124 206 403 23.5 5 OPzV 250

6 OPzV 300 1 300 320 310 285 255 195 0.63 3317 145 206 403 28.0 6 OPzV 300

5 OPzV 350 1 350 385 375 340 305 230 0.57 3630 124 206 520 31.0 5 OPzV 350

6 OPzV 420 1 420 465 450 410 365 275 0.49 4271 145 206 520 36.5 6 OPzV 420

7 OPzV 490 1 490 540 525 475 430 320 0.43 4883 166 206 520 42.0 7 OPzV 490

6 OPzV 600 1 600 705 680 615 545 395 0.55 3796 145 206 695 50.0 6 OPzV 600

8 OPzV 800 2 800 940 910 820 730 525 0.40 5200 210 191 695 68.2 8 OPzV 800

10 OPzV 1000 2 1000 1170 1135 1020 910 655 0.32 6460 210 233 695 82.0 10 OPzV 100

12 OPzV 1200 2 1200 1410 1370 1225 1090 790 0.27 7675 210 275 695 97.0 12 OPzV 120

12 OPzV 1500 2 1500 1580 1530 1395 1260 890 0.28 7510 210 275 845 120.0 12 OPzV 1500

16 OPzV 2000 3 2000 2110 2040 1855 1680 1190 0.21 10048 212 397 820 165.0 16 OPzV 2000

20 OPzV 2500 4 2500 2640 2550 2320 2100 1485 0.17 12606 212 487 820 200.0 20 OPzV 2500

24 OPzV 3000 4 3000 3170 3065 2785 2525 1785 0.14 14964 212 576 820 240.0 24 OPzV 3000

Type

designation

No

of

terminal

per pole

CapacityAh

acc. toDIN 40742

Capacity Ah

C10 C8 C5 C3 C1

at final voltage

1.80V 1.75V 1.77V 1.75V 1.67V

Dimensions (mm)Internalresistance(m ohm

/cell)

Short circuitcurrent

Weight (kg) cell Type

Length Width Overallheight

All dimensions and weights shown are subject to the usual manufacturing tolerances

4 OPzV 200 -6 OPzV 600

18 OPzV 1800 -12 OPzV 1500

16 OPzV 2000 20 OPzV 2500 -24 OPzV 3000

Page 7: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

6

1 - Standby applications1-1 Float voltage :The specific gravity of the gelled electrolyte is 1.260,

which allows for float charging theses OPzV batteries atthe same operating conditions as conventional floodedlead acid batteries.The float charge voltage is 2.23 V/cell.Therefore conventional vented Hawker OPzS ( tubular

lead- acid batteries) can be replaced by valve regulatedHawker OpzV batteries whithout charger modifications.The batteries are kept under a floating voltage of 2.23

volts per cell at a temperature of 20 °C.This float voltage should be set to match the prevalling

temperature, in accordance with the following table.

Due to the phenomena of gas recombination adifference of ± 2.5 % for an individual cell voltage can beobserved.However the total voltage of the battery shall be withinthe limits stated above.

1 - Application stationnaire1.2 Discharging : End of discharge voltageaccording to the discharge time

Although the tables of characteristics show end voltagesdown to 1.60 volts, the voltage values shown above arerecommended in order to avoid a too-deep discharge ofthe battery.

The application possibilities are multiple - as back–up supplies in telecom-munications, telephony, power generating stations and distribution systems, railway,airport or seaport signalling, computing, lighting, the armed forces, in the medicalfield, etc. - giving independent operation between 1 hour and 24 hours to suchinstallations.

II/ Application and use of the OPzV batteries

Temperature (C°) Float voltage (volt)

0°C10°C20°C30°C35°C

2.35 V2.28 V2.23 V2.20 V2.19 V

(Référence T°C)

Discharge Time (t) End voltage (volt)

1 h < t < 5 h

5 h < t < 8 h

8 h < t < 24 h

1.70 V

1.75 V

1.80 V

Page 8: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

7

1.3 Recharging :The battery should be recharged by using a uniquefloating and recharge voltage at 2.23V/cell at 20 °C.Nocurrent limitation is required in the majority ofapplication cases.

geIf the battery has to be charged more quickly, a rechargevoltage of 2.35 volts per cell can be used with currentlimited to 0.4C10

1.4 Ripple current :Unacceptable levels of ripple current from the charger ofthe load can cause permanent damage and a reductionin service life.It is recommended to limit the continuous

ripple current to 0.05 C10 (in amperes) as recommendedvalue, never exceed 0.1 C10.

* Note :If the charger does not permit anadjustement of the float voltage in relationwith the temperature, it is possible to set afloat voltage value in recharging voltagevalue according to the temperature rangesas indicated in the table hereafter.

Mean charging time in accordance with percentage discharge and recharging voltageper cell with current limited to 0.4C10

Recharging voltage according to temperature :

Percentagedischarge

Rechargingvoltage

State of charge

50% 60% 70% 80% 90% 95% 100%

-

-

2.23V

2.35V10%

-

-

-

-

-

-

-

-

2h00

1h45

12h00

7h00

-

-

2.23V

2.35V30%

-

-

-

-

1h15

1h00

4h00

3h00

8h00

6h00

24h00

14h00

-

-

2.23V

2.35V50%

0h45

0h30

1h30

1h15

4h00

3h00

8h30

5h30

15h00

10h00

38h00

22h00

1h00

1h00

2.23V

2.35V80%

1h30

1h30

3h00

2h30

7h00

5h00

13h00

9h15

25h00

15h00

56h00

34h00

2h00

2h00

2.23V

2.35V100%

2h30

2h30

4h30

4h00

10h00

7h15

20h00

14h00

35h00

24h00

80h00

50h00

Temperature (C°) Charging voltage (volt)

0°C10°C20°C30°C35°C

2.45 V2.40 V2.35 V2.32 V2.30 V

Temperature(C°)

Float voltage(Vpc)

Recharging voltage(Vpc)

-10°C to 5°C

5°C to 15°C

15°C to 30°C

30°C to 45°C

2.40 V

2.30 V

2.25 V

2.20 V

2.50 V

2.40 V

2.35 V

2.30 V

Page 9: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

8

2 - Battery cycling

Definition

Battery cycling implies use in a regular cycle, with fulldischarge followed by re-charging on a daily or weeklybasis for example.

The number of such cycles which can be obtained istypically over 1200, in conformity with the IEC896-2.

Important note : For all applications which use theOPzV type battery in a cycling system, it is recommendedthat the technical department of the Hawker companybe contacted so that the technical parameters can bespecified for the precise cycling programme in question.

3 - Effect of temperatureon battery capacity

The temperature has an effect on the battery capacityavailable. The following table gives the relevant details fora temperature of 20°C.

4 - Temperature rangeThe ideal ambient temperature for OPzV batteries is 20°C± 5°CThe operating temperature shall be in the range of 10 and 35°C

The maximum permissible temperature is 45°C

5 - Effect of temperature on lifeOperation of valve regulated batteries at temperatureshigher than 20°C will reduce life expectancy.Highertemperature increases the speed of chemical reactionsresulting in reduction of service life.A temperature increaseof 10 °C decreases the service life to half (law of Arrhenius)

Correction factor for capacity calculation according to temperature(the reference temperature is 20°C)Discharge time

(hours)End voltage

(volt)-10°C -5°C 0°C 5°C 10°C 15°C 20°C 25°C 30°C

1.671

1.753

1.775

0.39 0.49 0.59 0.69 0.8 0.9 1 1.03 1.05

0.55 0.62 0.7 0.77 0.85 0.92 1 1.02 1.05

0.58 0.65 0.72 0.79 0.86 0.93 1 1.02 1.04

0.6 0.67 0.74 0.81 0.87 0.94 1 1.02 1.041.8010

Page 10: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

9

III/ Electrical performances at 20°C

Constant current discharge in amperes Voltage end of discharge : 1.60 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 298 213 131.0 79.0 57.2 45.7 38.1 33.0 28.9 26.1 21.3 19.3 11.0 4 OPzV 200

5 OPzV 250 373 266 164.0 98.0 71.5 57.1 47.6 41.3 36.1 32.6 26.6 24.2 13.8 5 OPzV 250

6 OPzV 300 447 319 197.0 118.0 85.8 68.6 57.2 49.5 43.3 39.2 32.0 29.0 16,5 6 OPzV 300

5 OPzV 350 463 358 237.0 142.0 103.0 82.8 69.1 59.6 51.6 46.9 38.6 33.5 19.3 5 OPzV 350

6 OPzV 420 556 429 284.0 170.0 124.0 99.4 82.9 71.5 61.9 56.3 46.3 40.2 23.1 6 OPzV 420

7 OPzV 490 849 501 331.0 198.0 144.0 116.0 96.7 83.4 72.2 65.7 54.0 46.9 27.0 7 OPzV 490

6 OPzV 600 726 599 425.0 255.0 187.0 150.0 125.0 108.0 93.3 85.3 71.3 61.1 35.1 6 OPzV 600

8 OPzV 800 968 798 566.0 340.0 249.0 200.0 167.0 144.0 124.5 114.0 95.1 81.4 46.8 8 OPzV 800

10 OPzV 1000 1210 996 708.0 425.0 312.0 250.0 208.0 180.0 155.6 142.0 119.0 101.8 58.5 10 OPzV 1000

12 OPzV 1200 1452 1198 850.0 510.0 374.0 300.0 250.0 216.0 186.7 171.0 143.0 122.1 70.2 12 OPzV 1200

12 OPzV 1500 1509 1305 982.0 593.0 431.0 341.0 283.0 244.0 211.7 191.0 158.0 137.8 79.2 12 OPzV 1500

16 OPzV 2000 2012 1740 1309.0 790.0 574.0 455.0 377.0 325.0 282.3 255.0 211.0 183.7 105.6 16 OPzV 2000

20 OPzV 2500 2515 2175 1636.0 988.0 718.0 569.0 471.0 406,0 352.9 319,0 264.0 229.7 132.0 20 OPzV 2500

24 OPzV 3000 3018 2610 1964.0 1185.0 861.0 683.0 566.0 488.0 423.4 383.0 317.0 275.6 158.4 24 OPzV 3000

Constant power in watts per cell Voltage end of discharge : 1.60 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 490 368 235 146 108 87 72 63 55 49 41 37 21 4 OPzV 200

5 OPzV 250 613 460 294 182 135 109 90 78 69 62 51 47 27 5 OPzV 250

6 OPzV 300 736 552 353 218 162 130 108 94 82 74 62 56 32 6 OPzV 300

5 OPzV 350 760 612 423 261 194 156 131 113 98 89 74 65 37 5 OPzV 350

6 OPzV 420 912 734 508 313 233 188 157 136 118 107 89 78 45 6 OPzV 420

7 OPzV 490 1064 857 592 365 272 219 183 158 137 125 104 91 52 7 OPzV 490

6 OPzV 600 1170 999 732 464 349 281 235 204 176 161 136 117 67 6 OPzV 600

8 OPzV 800 1560 1332 976 618 465 374 314 272 235 215 182 156 90 8 OPzV 800

10 OPzV 1000 1950 1665 1220 773 581 468 391 340 294 268 227 195 112 10 OPzV 1000

12 OPzV 1200 2340 1998 1464 928 697 562 470 408 353 323 273 235 135 12 OPzV 1200

12 OPzV 1500 2430 2130 1638 1076 796 635 532 461 400 363 303 265 152 12 OPzV 1500

16 OPzV 2000 3240 2840 2184 1435 1060 848 709 614 534 483 405 353 203 16 OPzV 2000

20 OPzV 2500 4050 3550 2730 1794 1326 1060 885 767 667 604 507 441 253 20 OPzV 2500

24 OPzV 3000 4860 4260 3276 2153 1590 1273 1064 922 800 724 609 529 304 24 OPzV 3000

Page 11: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

10

Constant current discharge in amperes Voltage end of discharge : 1.65 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 274 205 131.0 79.0 57.2 45.7 38.1 33.0 28.9 26.1 21.3 19.3 11.0 4 OPzV 200

5 OPzV 250 343 256 163.0 98.0 71.5 57.1 47.6 41.3 36.1 32.6 26.6 24.2 13.8 5 OPzV 250

6 OPzV 300 411 307 196.0 118.0 85.8 68.6 57.2 49.5 43.3 39.2 32.0 29.0 16.5 6 OPzV 300

5 OPzV 350 422 338 235.0 142.0 103.0 82.8 69.1 59.6 51.6 46.9 38.6 33.5 19.3 5 OPzV 350

6 OPzV 420 506 405 282.0 170.0 124.0 99.4 82.9 71.5 61.9 56.3 46.3 40.2 23.1 6 OPzV 420

7 OPzV 490 590 473 329.0 198.0 144.0 116.0 96.7 83.4 72.2 65.7 54.0 46.9 27.0 7 OPzV 490

6 OPzV 600 657 552 407.0 255.0 187.0 150.0 125.0 108.0 93.3 85.3 71.3 61.1 35.1 6 OPzV 600

8 OPzV 800 876 736 542.0 340.0 249.0 200.0 167.0 144.0 124.5 114.0 95.1 81.4 46.8 8 OPzV 800

10 OPzV 1000 1095 920 678.0 425.0 312.0 250.0 208.0 180.0 155.6 142.0 119.0 101.8 58.5 10 OPzV 1000

12 OPzV 1200 1314 1104 814.0 510.0 374.0 300.0 250.0 216.0 186.7 171.0 143.0 122.1 70.2 12 OPzV 1200

12 OPzV 1500 1355 1189 925.0 593.0 431.0 341.0 283.0 244.0 211.7 191.0 158.0 137.8 79.2 12 OPzV 1500

16 OPzV 2000 1807 1585 1233.0 790.0 574.0 455.0 377.0 325.0 282.3 255.0 211.0 183.7 105.6 16 OPzV 2000

20 OPzV 2500 2259 1981 1541 988.0 718.0 569.0 471.0 406.0 352.9 319.0 264.0 229.7 132.0 20 OPzV 2500

24 OPzV 3000 2711 2378 1850.0 1185.0 861.0 683.0 566.0 488.0 423.4 383.0 317.0 275.6 158.4 24 OPzV 3000

Constant power in watts per cell Voltage end of discharge : 1.65 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 464 336 235 146 108 87 72 63 55 49 41 37 21 4 OPzV 200

5 OPzV 250 580 420 294 182 135 109 90 78 69 62 51 47 27 5 OPzV 250

6 OPzV 300 696 504 353 218 162 130 108 94 82 74 62 56 32 6 OPzV 300

5 OPzV 350 705 583 422 261 194 156 131 113 98 89 74 65 37 5 OPzV 350

6 OPzV 420 846 700 506 313 233 188 157 136 118 107 89 78 45 6 OPzV 420

7 OPzV 490 987 816 591 364 272 219 183 158 137 125 104 91 52 7 OPzV 490

6 OPzV 600 1098 936 720 463 349 281 235 204 176 161 136 117 67 6 OPzV 600

8 OPzV 800 1464 1248 960 618 465 374 314 272 235 215 182 156 90 8 OPzV 800

10 OPzV 1000 1830 1560 1200 772 581 468 391 340 294 268 227 195 112 10 OPzV 1000

12 OPzV 1200 2196 1872 1440 926 697 562 470 408 353 323 273 235 135 12 OPzV 1200

12 OPzV 1500 2238 1980 1605 1076 796 635 532 461 400 363 303 265 152 12 OPzV 1500

16 OPzV 2000 2984 2640 2140 1435 1060 848 709 614 534 483 405 353 203 16 OPzV 2000

20 OPzV 2500 3730 3300 2675 1794 1326 1060 885 767 667 604 507 441 253 20 OPzV 2500

24 OPzV 3000 4476 3960 3210 2153 1590 1273 1064 922 800 724 609 529 304 24 OPzV 3000

Page 12: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

11

Constant current discharge in amperes Voltage end of discharge : 1.70 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 250 192 129.0 78.0 57.2 45.7 38.1 33.0 28.86 26.1 21.3 19.3 11,0 4 OPzV 200

5 OPzV 250 313 240 161.0 97.5 71.5 57.1 47.6 41.3 36.07 32.6 26.6 24.2 13,8 5 OPzV 250

6 OPzV 300 375 288 194.0 117.0 85.8 68.6 57.2 49.5 43.29 39.2 32.0 29.0 16.5 6 OPzV 300

5 OPzV 350 380 313 224.0 141.0 103.0 82.8 69.1 59.6 51.57 46.9 38.6 33.5 19.3 5 OPzV 350

6 OPzV 420 456 376 269.0 169.0 124.0 99.4 82.9 71.5 61.89 56.3 46.3 40.2 23.1 6 OPzV 420

7 OPzV 490 532 438 314.0 197.0 144.0 116.0 96.7 83.4 72.2 65.7 54.0 46.9 27.0 7 OPzV 490

6 OPzV 600 575 494 378.0 251.0 187.0 150.0 125.0 108.0 93.84 85.3 71.3 61.1 35.1 6 OPzV 600

8 OPzV 800 767 659 504.0 335.0 249.0 200.0 167.0 144.0 124.5 114.0 95.1 81.4 46.8 8 OPzV 800

10 OPzV 1000 958 823 630.0 418.0 312.0 250.0 208.0 180.0 155.6 142.0 119.0 101.8 58.5 10 OPzV 1000

12 OPzV 1200 1150 988 756.0 502.0 374.0 300.0 250.0 216.0 186.7 171.0 143.0 122.1 70.2 12 OPzV 1200

12 OPzV 1500 1199 1061 851.0 585.0 428.0 341.0 283.0 244.0 211.7 191.0 158.0 137.8 79.2 12 OPzV 1500

16 OPzV 2000 1598 1415 1135.0 780.0 570.0 455.0 377.0 325.0 282.3 255.0 211.0 183.7 105.6 16 OPzV 2000

20 OPzV 2500 1998 1769 1419.0 975.0 713.0 569.0 471.0 406.0 352.9 319.0 264.0 229.7 132.0 20 OPzV 2500

24 OPzV 3000 2397 2122 1703.0 1170.0 855.0 683.0 566.0 488.0 423.4 383.0 317.0 275.6 158.4 24 OPzV 3000

Constant power in watts per cell Voltage end of discharge : 1.70 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 425 326 232 144 107 86 72 63 55 49 41 37 21 4 OPzV 200

5 OPzV 250 532 408 290 180 134 108 90 78 69 62 51 47 27 5 OPzV 250

6 OPzV 300 638 490 349 216 160 129 108 94 82 74 62 56 32 6 OPzV 300

5 OPzV 350 646 532 403 261 193 156 131 113 98 89 74 65 37 5 OPzV 350

6 OPzV 420 775 639 484 313 232 188 157 136 118 107 89 78 45 6 OPzV 420

7 OPzV 490 904 745 565 364 270 219 183 158 137 125 104 91 52 7 OPzV 490

6 OPzV 600 978 840 677 462 348 280 235 204 176 161 136 117 67 6 OPzV 600

8 OPzV 800 1304 1120 902 616 463 374 314 272 235 215 182 156 90 8 OPzV 800

10 OPzV 1000 1629 1399 1128 769 580 466 391 340 294 268 227 195 112 10 OPzV 1000

12 OPzV 1200 1955 1680 1353 924 696 560 470 408 353 323 273 235 135 12 OPzV 1200

12 OPzV 1500 2038 1812 1523 1076 796 635 532 461 400 363 303 265 152 12 OPzV 1500

16 OPzV 2000 2717 2416 2032 1435 1060 848 709 614 534 483 405 353 203 16 OPzV 2000

20 OPzV 2500 3397 3020 2540 1794 1326 1060 885 767 667 604 507 441 253 20 OPzV 2500

24 OPzV 3000 4075 3624 3048 2153 1590 1273 1064 922 800 724 609 529 304 24 OPzV 3000

Page 13: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

12

Constant current discharge in amperes Voltage end of discharge : 1.75 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 219 174 121.0 76.7 56.5 45.6 38.1 33.0 28.9 26.0 21.3 19.3 11.0 4 OPzV 200

5 OPzV 250 274 218 151.0 95.9 70.6 57.0 47.6 41.3 36.1 32.5 26.6 24.2 13.8 5 OPzV 250

6 OPzV 300 329 261 182.0 115.0 84.8 68.4 57.2 49.5 43.3 39.0 32.0 29.0 16.5 6 OPzV 300

5 OPzV 350 335 281 209.0 136.0 102.0 82.8 69.1 59.6 51.6 46.9 38.5 33.5 19.3 5 OPzV 350

6 OPzV 420 402 337 251.0 163.0 122.0 99.4 82.9 71.5 61.9 56.3 46.2 40.2 23.1 6 OPzV 420

7 OPzV 490 469 393 293.0 190.0 143.0 116.0 96.7 83.4 72.2 65.7 53.9 46.9 27.0 7 OPzV 490

6 OPzV 600 500 435 344.0 238.0 182.0 149.0 125.0 108.0 93.3 85.3 71.3 61.1 35.1 6 OPzV 600

8 OPzV 800 667 580 459.0 317.0 243.0 199.0 167.0 144.0 124.5 114.0 95.1 81.4 46.8 8 OPzV 800

10 OPzV 1000 833 725 573.0 397.0 303.0 248.0 208.0 180.0 155.6 142.0 119.0 101.8 58.5 10 OPzV 1000

12 OPzV 1200 1000 870 688.0 476.0 364.0 298.0 250.0 216.0 186.7 171.0 143.0 122.1 70.2 12 OPzV 1200

12 OPzV 1500 1036 931 762.0 546.0 421.0 338.0 283.0 244.0 211.7 191.0 158.0 137.8 79.2 12 OPzV 1500

16 OPzV 2000 1381 1241 1016.0 728.0 561.0 451.0 377.0 325.0 282.3 255.0 211.0 183.7 105.6 16 OPzV 2000

20 OPzV 2500 1726 1551 1270.0 910.0 701.0 564.0 471.0 406.0 352.9 319.0 264.0 229.7 132.0 20 OPzV 2500

24 OPzV 3000 2072 1862 1524 1092.0 842.0 677.0 566.0 488.0 423.4 383.0 317.0 275.6 158.4 24 OPzV 3000

Constant power in watts per cell Voltage end of discharge : 1.75 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 383 305 223 143 107 86 72 63 55 49 41 37 21 4 OPzV 200

5 OPzV 250 480 382 278 178 133 108 90 78 69 62 51 47 27 5 OPzV 250

6 OPzV 300 576 457 335 214 160 129 108 94 82 74 62 56 32 6 OPzV 300

5 OPzV 350 586 492 385 253 193 156 131 113 98 89 74 65 37 5 OPzV 350

6 OPzV 420 704 590 462 303 231 188 157 136 118 107 89 78 45 6 OPzV 420

7 OPzV 490 821 688 539 353 270 219 183 158 137 125 104 91 52 7 OPzV 490

6 OPzV 600 875 761 630 440 342 280 235 204 176 161 136 117 67 6 OPzV 600

8 OPzV 800 1167 1015 840 586 457 374 314 272 235 215 182 156 90 8 OPzV 800

10 OPzV 1000 1458 1269 1049 734 570 466 391 340 294 268 227 195 112 10 OPzV 1000

12 OPzV 1200 1750 1523 1259 881 684 560 470 408 353 323 273 235 135 12 OPzV 1200

12 OPzV 1500 1813 1629 1356 1010 791 635 532 461 400 363 303 265 152 12 OPzV 1500

16 OPzV 2000 2417 2172 1808 1347 1055 848 709 614 534 483 405 353 203 16 OPzV 2000

20 OPzV 2500 3021 2714 2260 1684 1318 1060 885 767 667 604 507 441 253 20 OPzV 2500

24 OPzV 3000 3626 3259 2712 2020 1583 1273 1064 922 800 724 609 529 304 24 OPzV 3000

Page 14: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

13

Constant current discharge in amperes Voltage end of discharge : 1.80 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 188 153 111.0 72.2 54.5 44.3 37.4 32.5 28.6 25.8 21.3 19.3 11.0 4 OPzV 200

5 OPzV 250 235 191 139.0 90.3 68.1 55.4 46.8 40.6 35.7 32.3 26,6 24.2 13.8 5 OPzV 250

6 OPzV 300 282 230 167.0 108.0 81.8 66.5 56.1 48.8 42.9 38.7 32.0 29.0 16.5 6 OPzV 300

5 OPzV 350 286 246 187.0 126.0 96.9 79.1 66.8 58.4 50.4 46.7 38.5 33.5 19.3 5 OPzV 350

6 OPzV 420 343 295 224.0 151.0 116.0 94.9 80.2 70.1 60.4 56.0 46.2 40.2 23.1 6 OPzV 420

7 OPzV 490 400 344 262.0 176.0 136.0 111.0 93.5 81.8 70.5 65.4 53.9 46.9 27.0 7 OPzV 490

6 OPzV 600 422 374 302.0 218.0 171.0 140.0 119.0 104.0 90.9 83.5 70.4 61.1 35.1 6 OPzV 600

8 OPzV 800 563 499 403.0 291.0 228.0 187.0 159.0 139.0 121.1 111.0 93.9 81.4 46.8 8 OPzV 800

10 OPzV 1000 703 623 503,0 363.0 285.0 233.0 198.0 173.0 151.4 139.0 117.0 101.8 58.5 10 OPzV 1000

12 OPzV 1200 844 748 604.0 436.0 342.0 280.0 238.0 208.0 181.7 167.0 141.0 122.1 70.2 12 OPzV 1200

12 OPzV 1500 860 794 660.0 489.0 387.0 319.0 272.0 238.0 205.7 191.0 158.0 137.8 79.2 12 OPzV 1500

16 OPzV 2000 1147 1059 880.0 652.0 516.0 425.0 362.0 317.0 274.3 254.0 211.0 183.7 105.6 16 OPzV 2000

20 OPzV 2500 1434 1324 1100.0 815.0 645.0 531.0 453.0 396.0 342.9 318.0 264.0 229.7 132.0 20 OPzV 2500

24 OPzV 3000 1721 1589 1320.0 978.0 774.0 638.0 543.0 476.0 411.4 381.0 317.0 275.6 158.4 24 OPzV 3000

Constant power in watts per cell Voltage end of discharge : 1.80 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 338 275 205 135 104 84 71 62 55 49 41 37 21 4 OPzV 200

5 OPzV 250 423 344 257 169 129 105 89 77 68 62 51 47 27 5 OPzV 250

6 OPzV 300 508 414 309 202 155 126 107 93 82 74 62 56 32 6 OPzV 300

5 OPzV 350 515 443 346 235 184 150 127 111 96 89 74 65 37 5 OPzV 350

6 OPzV 420 617 531 414 282 220 180 152 134 115 107 89 78 45 6 OPzV 420

7 OPzV 490 720 619 485 329 258 211 178 156 135 125 104 91 52 7 OPzV 490

6 OPzV 600 760 673 556 405 323 265 225 198 173 159 135 117 67 6 OPzV 600

8 OPzV 800 1013 898 742 541 431 353 301 264 230 211 180 156 90 8 OPzV 800

10 OPzV 1000 1265 1121 926 675 539 440 374 329 288 264 225 195 112 10 OPzV 1000

12 OPzV 1200 1519 1346 1111 811 646 529 450 395 345 317 271 235 135 12 OPzV 1200

12 OPzV 1500 1548 1429 1214 910 731 603 514 452 391 363 303 265 152 12 OPzV 1500

16 OPzV 2000 2065 1906 1619 1213 975 803 684 602 521 483 405 353 203 16 OPzV 2000

20 OPzV 2500 2581 2383 2024 1516 1219 1004 856 752 651 604 507 441 253 20 OPzV 2500

24 OPzV 3000 3098 2860 2429 1819 1463 1206 1026 904 782 724 609 529 304 24 OPzV 3000

Page 15: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

14

Constant current discharge in amperes Voltage end of discharge : 1.85 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 154 129 96.1 64.9 48.7 40.4 34.3 29.9 26.3 23.9 20.1 17.5 10.0 4 OPzV 200

5 OPzV 250 193 161 120.0 81.1 60.9 50.5 42.9 37.4 32.9 29.9 25.1 21.8 12.6 5 OPzV 250

6 OPzV 300 231 194 144.0 97.4 73.1 60.6 51.5 44.9 39.4 35.9 30.2 26.2 15.1 6 OPzV 300

5 OPzV 350 223 203 160.0 112.0 86.7 71.6 61.2 53.6 47.1 43.1 36.6 31.8 18.3 5 OPzV 350

6 OPzV 420 267 244 192.0 134.0 104.0 85.9 73.4 64.3 56.5 51.7 43.9 38.2 22.0 6 OPzV 420

7 OPzV 490 312 285 224.0 156.0 121.0 100.0 85.7 75.0 65.9 60.3 51.2 44.6 25.6 7 OPzV 490

6 OPzV 600 332 308 253.0 190.0 153.0 127.0 109.0 95.7 84.0 77.2 65.4 56.9 32.7 6 OPzV 600

8 OPzV 800 443 411 337.0 253.0 204.0 169.0 145.0 128.0 112.0 103.0 87.2 75.9 43.6 8 OPzV 800

10 OPzV 1000 553 513 422.0 317.0 255.0 212.0 182.0 160.0 140.0 129.0 109.0 94.8 54.5 10 OPzV 1000

12 OPzV 1200 664 616 506.0 380.0 306.0 254.0 218.0 191.0 168.0 154.0 131.0 113.8 65.4 12 OPzV 1200

12 OPzV 1500 671 650 550.0 419.0 339.0 284.0 245.0 215.0 187.4 174.0 147.0 127.6 73.3 12 OPzV 1500

16 OPzV 2000 895 866 733.0 558.0 452.0 378.0 326.0 287.0 249.8 232.0 196.0 170.1 97.8 16 OPzV 2000

20 OPzV 2500 1119 1083 916.0 698.0 565.0 473.0 408.0 359.0 312.3 290.0 245.0 212.6 122.2 20 OPzV 2500

24 OPzV 3000 1343 1299 1100.0 837.0 678.0 567.0 489.0 431.0 374.7 348.0 294.0 255.2 146.6 24 OPzV 3000

Constant power in watts per cell Voltage end of discharge : 1.85 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 285 239 181 123 94 78 66 58 51 46 39 34 20 4 OPzV 200

5 OPzV 250 357 298 226 154 117 97 83 72 63 58 49 43 25 5 OPzV 250

6 OPzV 300 427 359 271 185 140 116 99 87 76 69 59 51 30 6 OPzV 300

5 OPzV 350 413 376 301 213 166 137 118 103 91 83 72 62 36 5 OPzV 350

6 OPzV 420 496 451 362 255 200 165 142 124 109 100 86 75 43 6 OPzV 420

7 OPzV 490 578 527 422 296 232 192 165 145 127 116 100 87 50 7 OPzV 490

6 OPzV 600 614 570 473 359 292 243 209 184 161 148 128 111 64 6 OPzV 600

8 OPzV 800 818 760 630 478 390 323 278 246 215 198 170 148 85 8 OPzV 800

10 OPzV 1000 1023 949 789 599 487 405 349 307 269 248 213 185 106 10 OPzV 1000

12 OPzV 1200 1228 1140 946 718 584 485 419 367 323 296 255 222 128 12 OPzV 1200

12 OPzV 1500 1241 1203 1029 792 647 542 470 413 360 334 287 249 143 12 OPzV 1500

16 OPzV 2000 1656 1602 1371 1055 863 722 626 551 480 445 382 332 191 16 OPzV 2000

20 OPzV 2500 2070 2004 1713 1319 1079 903 783 689 600 557 478 415 238 20 OPzV 2500

24 OPzV 3000 2485 2403 2057 1582 1295 1083 939 828 720 668 573 498 286 24 OPzV 3000

Page 16: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

Constant current discharge in amperes Voltage end of discharge : 1.87 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 136 118 89.0 60.8 46.1 38.0 32.4 28.2 24.8 22.6 18.8 16.8 9.5 4 OPzV 200

5 OPzV 250 170 147 111.2 76.0 57.6 47.5 40.5 35.3 31.0 28.3 23.9 21.0 11.9 5 OPzV 250

6 OPzV 300 203 177 133.2 91.2 69.1 57.1 48.6 42.4 37.2 34.0 28.7 25.2 14.3 6 OPzV 300

5 OPzV 350 195 182 148.0 104.4 81.0 67.2 57.6 50.5 44.4 40.9 34.8 30.6 17.4 5 OPzV 350

6 OPzV 420 234 219 177.2 124.8 97.2 80.6 69.1 60.6 53.3 49.1 41.7 36.7 20.9 6 OPzV 420

7 OPzV 490 274 255 206.8 145.6 113.0 93.9 80.7 70.6 62.2 57.3 48.7 42.8 24.4 7 OPzV 490

6 OPzV 600 292 276 232.2 175.6 142.2 118.6 102.2 89.9 79.1 73.0 62.0 54.6 31.0 6 OPzV 600

8 OPzV 800 389 368 309.4 233.8 189.6 158.2 136.2 120.0 105.5 97.4 82.7 72.8 41.4 8 OPzV 800

10 OPzV 1000 486 459 387.2 293.0 237.0 198.0 170.4 150.4 131.8 121.8 103.4 90.9 51.7 10 OPzV 1000

12 OPzV 1200 583 552 464.4 351.2 284.4 237.6 204.4 179.8 158.2 145.6 124.2 109.1 62.1 12 OPzV 1200

12 OPzV 1500 591 578 502.4 385.8 314.6 265.6 230.2 202.2 176.6 164.4 139.4 122.2 69.5 12 OPzV 1500

16 OPzV 2000 788 770 669.4 514.0 419.2 353.6 306.4 269.8 235.5 219.2 186.0 162.9 92.6 16 OPzV 2000

20 OPzV 2500 985 963 836.8 642.8 524.2 442.2 383.2 337.4 294.3 274.0 232.6 203.6 115.8 20 OPzV 2500

24 OPzV 3000 1182 1156 1004.4 771.0 628.8 530.6 459.8 405.0 353.2 328.8 279.2 244.3 139.0 24 OPzV 3000

Constant power in watts per cell Voltage end of discharge : 1.87 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 253 220 169 116 89 73 63 55 48 44 37 33 19 4 OPzV 200

5 OPzV 250 317 274 211 145 111 92 78 68 60 55 47 41 23 5 OPzV 250

6 OPzV 300 380 330 252 174 133 110 94 82 72 66 56 49 28 6 OPzV 300

5 OPzV 350 365 345 280 199 156 129 111 98 86 79 68 60 34 5 OPzV 350

6 OPzV 420 438 414 336 238 187 155 134 117 103 95 82 72 41 6 OPzV 420

7 OPzV 490 511 484 392 278 218 181 156 137 120 111 96 84 48 7 OPzV 490

6 OPzV 600 544 519 437 334 273 227 197 173 152 141 121 107 61 6 OPzV 600

8 OPzV 800 725 693 583 444 363 303 262 231 203 188 162 142 81 8 OPzV 800

10 OPzV 1000 906 865 729 557 454 380 328 289 254 235 202 178 101 10 OPzV 1000

12 OPzV 1200 1088 1038 875 667 545 456 393 346 305 281 243 213 121 12 OPzV 1200

12 OPzV 1500 1102 1079 946 733 603 509 443 389 340 317 272 239 136 12 OPzV 1500

16 OPzV 2000 1470 1438 1261 977 804 678 589 519 454 422 363 318 181 16 OPzV 2000

20 OPzV 2500 1838 1798 1576 1222 1005 848 737 649 567 528 454 398 226 20 OPzV 2500

24 OPzV 3000 2206 2157 1892 1465 1205 1017 884 779 681 634 545 477 271 24 OPzV 3000

15

Page 17: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

16

Constant current discharge in amperes Voltage end of discharge : 1.90 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 108 101 78.3 54.6 42.1 34.5 29.5 25.7 22.6 20.7 17.0 15.8 8.8 4 OPzV 200

5 OPzV 250 135 126 97.9 68.3 52.6 43.1 36.9 32.1 28.3 25.9 22.0 19.7 11.0 5 OPzV 250

6 OPzV 300 162 151 117.0 81.9 63.2 51.8 44.3 38.6 33.9 31.1 26.4 23.6 13.2 6 OPzV 300

5 OPzV 350 154 154 130.0 92.9 72.4 60.5 52.2 45.8 40.5 37.7 32.1 28.7 16.1 5 OPzV 350

6 OPzV 420 185 185 155.0 111.0 86.9 72.6 62.6 55.0 48.6 45.2 38.5 34.5 19.3 6 OPzV 420

7 OPzV 490 216 216 181.0 130.0 101.0 84.7 73.1 64.1 56.7 52.8 44.9 40.2 22.5 7 OPzV 490

6 OPzV 600 231 231 201.0 154.0 126.0 106.0 92.0 81.3 71.7 66.7 57.0 51.1 28.5 6 OPzV 600

8 OPzV 800 308 308 268.0 205.0 168.0 142.0 123.0 108.0 95.7 88.9 76.0 68.1 38.0 8 OPzV 800

10 OPzV 1000 385 385 335.0 257.0 210.0 177.0 153.0 136.0 119.6 111.0 95.0 85.1 47.6 10 OPzV 1000

12 OPzV 1200 462 462 402.0 308.0 252.0 213.0 184.0 163.0 143.5 133.0 114.0 102.1 57.1 12 OPzV 1200

12 OPzV 1500 470 470 431.0 336.0 278.0 238.0 208.0 183.0 160.5 150.0 128.0 114.1 63.7 12 OPzV 1500

16 OPzV 2000 627 627 574.0 448.0 370.0 317.0 277.0 244.0 213.9 200.0 171.0 152.1 85.0 16 OPzV 2000

20 OPzV 2500 784 784 718.0 560.0 463.0 396.0 346.0 305.0 267.4 250.0 214.0 190.1 106.2 20 OPzV 2500

24 OPzV 3000 941 941 861.0 672.0 555.0 476.0 416.0 366.0 320.9 300.0 257.0 228.1 127.4 24 OPzV 3000

Constant power in watts per cell Voltage end of discharge : 1.90 V/cell

Type 15’ 30’ 1h 2h 3h 4h 5h 6h 7h 8h 10h 12h 24h Type

4 OPzV 200 206 192 150 105 82 67 57 50 44 40 33 31 17 4 OPzV 200

5 OPzV 250 257 239 187 132 102 83 72 62 55 50 43 39 22 5 OPzV 250

6 OPzV 300 308 287 224 158 123 100 86 75 66 61 52 47 26 6 OPzV 300

5 OPzV 350 293 298 249 179 140 117 101 89 79 73 63 57 32 5 OPzV 350

6 OPzV 420 352 357 297 214 168 140 121 107 95 88 76 68 38 6 OPzV 420

7 OPzV 490 410 418 347 251 196 164 142 125 110 103 88 79 44 7 OPzV 490

6 OPzV 600 439 443 384 296 243 205 178 157 139 129 112 100 56 6 OPzV 600

8 OPzV 800 586 591 512 394 324 274 237 208 186 172 149 133 75 8 OPzV 800

10 OPzV 1000 732 739 640 493 405 342 295 262 232 215 186 167 93 10 OPzV 1000

12 OPzV 1200 878 885 768 591 486 411 355 315 278 258 223 200 112 12 OPzV 1200

12 OPzV 1500 893 893 823 645 537 459 401 353 311 291 251 224 125 12 OPzV 1500

16 OPzV 2000 1191 1191 1096 860 714 612 535 471 415 388 335 298 167 16 OPzV 2000

20 OPzV 2500 1490 1490 1371 1075 894 764 668 589 519 485 419 373 208 20 OPzV 2500

24 OPzV 3000 1788 1788 1645 1290 1071 919 803 706 623 582 504 447 250 24 OPzV 3000

Page 18: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

17

The following calculations will enable you todetermine which unit in the OpzV range you requirein order to supply the power you need, and in thespecified temperature conditions :

Where discharge includes current surges, please consultour commercial department.

Constant discharge case

- Power required : 23.7 kW- Minimum voltage : 376 volts- Maximum voltage : 484 volts- Back up time required : 4 hours

For a temperature of 20°C,

the float charge voltage is 2.23 volts percell.

- Maximum number of 2V cells : 484 V/2.23 V = 217

- Discharge current : 23700 W/376V = 63A

- Minimum voltage per 2 V cell : 376/217 = 1.74 V

Refer to the table of electrical performancecharacteristics of the OPzV cells for an end voltage of1.75 volts.

- For a discharge current of 63A or more and a dischargetime of 4 hours, we find 68.4V A for the cell 6 OPzV300

- Type of battery : 217 cells 6 OPzV300 (320Ah in C10 for1.80 V)

For a temperature of O°C :

the float charge voltage is 2.35 volts percell.

- Maximum number of 2 V cells : 484V/2.35 V = 206.

- Discharge current : 23700 W/376 V = 63A

- Minimum voltage per 2 V cell : 376V/206=1.83 V

- Now refer to the section on the use of the OpzVaccumulators, at the paragraph entitled " Effect oftemperature on battery capacity, to find thecapacity correction factor- in this case it proves tobe 0.74.

- The equivalent discharge current will be : 63/0.74 = 85 A

- Now go to the table of electrical performancecharacteristics of the OPzV range for an end voltageof 1.85 volts.

- For a discharge current of 85 amps or more, the cellin the OPzV range which corresponds to a 4 hourdischarge time is the 6 OPzV420.

- The battery is thus made up of 206 cells of type6 OPzV420 (560 Ah at C10 for 1.80 V end voltage).

Important note :

In a case where the ambient temperature varies, thecalculations should be performed on the basis of thelowest temperature

Example : For 11 months of use at 20 °C and 1 month at0°C, calculate the number of cells with a float voltage of2.23 volts per cell, and find the correspondingaccumulator with the loss of capacity transferred to thedischarge current.

IV/ Battery calculations

Page 19: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

18

1 - WarningThe cells of the EG battery are already charged whendelivered, and are fitted with a protective cap oneach terminal. They should be unpacked with care.

Avoid short-circuiting terminals of opposite polarity,because these units are capable of discharging at a veryhigh current, even if the lid or the container happens tobe damaged.

2 - Unpacking the batteryEach shipment of OpzV batteries is accompanied by apacking list and installation instructions.

The packing list should be checked, and the SalesDepartment-Standby Batteries should be toldimmediately of any missing items.

The markings on the lid should be read carefully :

- The type of cell

- The voltage in volts

- The capacity in ampere hours

- The storage limit date

- The float charge voltage at 20-25 ° C

- The arrow must always point upwards if thebatteries are placed in the prone position.

Note : The symbol indicates that the accumulatoris of the recyclable type.

3 - Setting up the battery standsConstruction : Theses stands are in plastic-coveredsteels, and are notable for their :

- mechanical strength

- their adaptability

- their ease of assembly.

The standard stretchers of 600,750,900,1200 and 1500mm are designed to result in space- saving installations.

V/ Installation of the battery

Page 20: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

19

Stand models : There are two ranges of stands to suit theposition in which the accumulators are to be placed :

3.1 - Standard standsfor vertical cells

See also the appendix on page 20. The various assemblyoptions are dependent on :

- The number of cells of which the battery is composed

- The floor area available

3.2 - Stands for horizontal cells(see appendix page 20)

Stand in a 4 and 6 levels are availableConnexion in front of the stand for easier maintenance.

Importante note :

The floor must possess the necessary load-bearingcharacteristics.

Assembly of battery stands :

- The structure should be assembled in accordance withthe exploded view and instructions supplied with theequipment.

- Check the correct fixing ot the chassis after fistchecking the squareness.

- Take up any irregularity in floor surface using shims.

- The uprights of 2 or 3 level stands for vertical cells andthe 4 and 6 level stands for horizontal cells are bestmounted on a well.

- These plastic-covered metal stands are electricallyinsulated and require no connection to the buildingearth.

- For the installation of cells in the horizontal position,always ensure that the arrow on the lid of each unit ispointing upward.

1 and 2 levels

With

- 1 row

- 2 rows flat

- 3 rows flat

- 2 rows

- Special design-consult ourSales Department

3 levels

Page 21: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

20

Met

allic

sta

nds

size

s

Type

of

cells

W H

4 O

PzV

200

5 O

PzV

250

6 O

PzV

300

5 O

PzV

350

6 O

PzV

420

7 O

PzV

490

6 O

PzV

600

8 O

PzV

800

10 O

PzV

100

0

12 O

PzV

120

0

12 O

PzV

150

0

16 O

PzV

200

0

20 O

PzV

250

0

24 O

PzV

300

0

Spec

ial s

tudie

s, p

leas

e se

e w

ith

our

sal

es d

epar

tmen

ts.

*C

om

puls

ory

wal

l fix

ing

W H21

557

743

057

764

557

728

515

8250

015

8250

014

3050

019

70*

215

577

430

577

645

577

285

1582

500

1582

500

1430

500

1970

*21

557

721

569

321

569

321

569

321

586

721

586

729

086

729

086

929

010

1843

099

458

099

4

430

577

430

693

430

693

430

693

430

867

430

867

580

867

580

869

580

1018

645

577

645

693

645

693

645

693

645

867

645

867

285

1582

285

1698

285

1698

285

1698

285

1872

*28

518

72*

285

1872

*36

018

74*

360

2023

*50

019

99*

500

1582

500

1698

500

1698

500

1698

500

1872

*50

018

72*

650

1872

*65

018

74*

650

2023

*

500

1908

*50

020

24*

500

2024

*50

020

24*

500

1430

650

1430

650

1430

650

1430

822

1430

822

1430

822

1430

822

1430

930

1430

500

1970

*65

019

70*

650

1970

*65

019

70*

822

1970

*82

219

70*

822

1970

*82

219

70*

930

1970

*

W H W H W H W H W H W H W H W H W H W H W H W H W H

Ver

tica

l ass

emblin

g

V1

V2

V3

V4

V5

V6

H1

H2

Hori

zont

al a

ssem

blin

g

Page 22: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

21

Standard stands for vertical cells :

Length of the stand is determined bythe combination of 5 differentlongitudinal beams (Length 600 mm,750, 900, 1200 and 1500 mm) in relationwith the total length of cells.

Standard stands for horizontal cells :

Length of the stand is determined bythe combination of 5 differentlongitudinal beams (Length 600 mm,750, 900, 1200 and 1500 mm) in relationwith the total length of cells.

Caution : Take into account the in-between pillars.

Page 23: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

22

5 - General recommendations- Do not wear clothing in synthetic materials, to avoid

the generation of static potentials.

- Discharge any possible static electricity from clothesby touching an earth connected part.

- Handle the battery cells with special implementsprovided (never lift the cells by their terminals).

- Use insulated tools.

- Place the cells beginning with the least accessiblerows, spacing the cells as shown in the figure.

- Always ensure that the arrow on the cell lid ispointing upward if the cell is placed in thehorizontal position.

- Consult the drawing for the correct position of thecell poles (positive = red washer, negative = bluewasher).

- Before attaching the inter-cell flexible cables, checkthat all terminals are in the correct position.

- The battery cells are connected in series, that is witha positive pole connected to a negative pole.

- Clean the cells with nothing other than a dampenedcotton cloth.

- The tightening torque for connections is 23 Nm(2.3 Mkg) to a 25 Nm (2.5Mkg).

This maximum value must not be exceeded.

6 - SafetyAll installation and ventilation must comply with thecurrent regulations and norms

(In France : norm NFC15-100)

Batteries must be installed in accordance with EN 50272- 2standard

7 - StandardsThe OPzV range complies with the international standard :IEC 896-2

Classified as “long life” according to the EUROBAT Guide1999

Hawker production facilities worlwide are certified toISO 9001

Low ventilation requirement according to EN 50272-2

The OPzV conforms to draft of DIN standard 40742

4 - Connecting of the cellsin series :

The number of cells in series will determine the totalfloat voltage :

U = V x N

U = total float voltage V = float voltage for one cellN = number of cells

In parallel :

OPzV cells of the same ampere hour rating may beconnected in parallel to give higher currentcapability.This connection in parallel will be preferablycarried out through an equipotential wiring for an equalcurrent distribution in each string.

These is no technical reason for limiting the number ofstrings but for practical installation reasons, it isrecommended not to exceed 4 strings in parallelespecially if the battery is used in high discharge rates(standby time lower than 1 hour.).

Page 24: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

23

1 - Calculating the storage timeThe storage time is indicated on the battery lid. This takesinto account the shipping time of equipment, frequentlyquite lengthy (in the case of exports in particular).

2 - Storage conditionsThe battery should be stored away from any moisture orsource of heat.

3 - Storage timesThe self-discharge of OPzV batteries as a function oftemperatures is as follows :

In order to ensure that the battery can be charged easilyafter a long period of storage, it is recommended thatbatteries should not be stored fore more than thefollowing periods without recharging :

Failure to comply with these recommendations maycompromise the life expectancy of the battery.

4 - Recharging stored batteriesThe batteries should be recharged at the float chargevoltage to suit the temperature (2.23 volts at 20 °C percell for example) with a current limit of 0.4 C10 and for aminimum period of 96 hours.

The battery will be charged when the charging currenthas remained constant for a period of 3 hours.

5 - State of chargeThe battery state of charge can be determinedapproximately by measuring the open circuit voltageafter the battery has been at rest for a minimum of24 hours.

The necessity of a refreshing charge can also bedetermined by measuring the open circuit voltage of astored battery.

Refreshing charge is advised if the voltage drops below2.07 V/cell.

VI/ Battery storage

2% per month at 20°C

4% per month at 30°C

8% per month at 40°C

6 per month at 20°C

4 per month at 30°C

2 per month at 40°C

State of charge Voltage

100%70%50%20%

2.13V/cell2.09V/cell2.06V/cell2.02 V/cell

Page 25: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

24

Before bringing them into service, the batteries must becharged at a constant regulated voltage to match

the prevailing temperature, for a minimum period of48 hours.

VII/ Commissioning

- Every month, check the total floating voltage at thebattery terminals.It should be N x 2.23 volts at atemperature of 20 °C, where N is the number of cells inthe battery.

- Once each year, effect a reading of the voltage of cellsconstituting the battery.

- A difference of plus or minus 2.5 % between theseindividual floating voltages and the average voltagemay be observed. This is due to the gas recombinationprocess.

- A check on capacity ( independent operation on load)can be performed once a year.

SafetyWhen carrying out any work on the battery, theapplicable safety standards should be followed.

Note : Keep a logbook battery in which the measuredvalues can be noted as well as power cuts, dischargetests( current, time, T°…) etc.

The main factors causing reductionin the life expectancy of OPzV cells- Deep discharges

- Poor regulation of the float voltage

- Poor quality (smoothing) of the charging current

- High ambient temperatures

VIII/ Maintenance/checks

Page 26: Technical Manual - gnet.co.rs · typically over 1200, in conformity with the IEC896-2. Important note : For all applications which use the OPzV type battery in a cycling system, it

DC

E 10

02G

-08/

01 -

Sub

ject

to

tech

nica

l mod

ifica

tion

wit

hout

pri

or n

otic

e.

Hawker S.A.

Rue Alexander Fleming ZI EST BP 962

62033 Arras Cedex France

Tel: + 33 3 21 60 25 25 Fax: + 33 3 21 73 16 51

www.hawker.invensys.com

E-mail : [email protected]

Please refer to the website address for details of your nearest Hawker office

Hawker Worldwide Marketing

Rake Lane Clifton Junction Swinton

Manchester M27 8LR, UK

Tel: +44 (0)161 794 4611 Fax: +44 (0)161 793 6606

www.hawker.invensys.com