technical drawings from aiw - melbourne waterproofing ......1.2 m centres 5x5 mm min. fillet or...
TRANSCRIPT
![Page 1: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/1.jpg)
Technical Drawings from AIWto assist with understandingAS4654.2 Waterproofing membranes forexternal above-ground use.Design and installation.
![Page 2: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/2.jpg)
Detail of metal post support
![Page 3: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/3.jpg)
Detail of horizontal membrane penetration
![Page 4: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/4.jpg)
Detail of one way movement joint
![Page 5: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/5.jpg)
Detail of one way construction joint
![Page 6: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/6.jpg)
Drainage detail for exposed membrane
![Page 7: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/7.jpg)
Detail of overflow pipe through parapet
![Page 8: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/8.jpg)
Vertical upward termination – overflashing profile
![Page 9: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/9.jpg)
Vertical upward termination – overflashing terminated in reglet and sealed
![Page 10: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/10.jpg)
Vertical downward termination – balcony edge detail
![Page 11: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/11.jpg)
Vertical downward termination – pressure seal
![Page 12: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/12.jpg)
Edge protection of sheet membrane over parapet
![Page 13: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/13.jpg)
Membrane termination at a cavity parapet
![Page 14: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/14.jpg)
Gutter termination detail
![Page 15: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/15.jpg)
Membrane termination at external opening doors
![Page 16: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/16.jpg)
Membrane termination at wall openings
![Page 17: Technical Drawings from AIW - Melbourne Waterproofing ......1.2 m centres 5x5 mm min. fillet or backing to be placed in corner Via cove or similar](https://reader035.vdocuments.us/reader035/viewer/2022081622/613642450ad5d2067647e820/html5/thumbnails/17.jpg)
Vertical penetration detail using collar