Technical Description FBP FieldBusPlug
V6
PDP21-FBPPROFIBUS DP-V0 FieldBusPlug
PDP22-FBPPROFIBUS DP-V1 FieldBusPlug
Coupler,Bus master
Control system CPU
Power supply 24 V
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
Contents Page
1. PROFIBUS DP, Introduction 31.1 ISO/OSI model 31.2 Typical Bus Topologies 31.3 Overview of transferred data 41.4 PROFIBUS DP-V0 <---> PROFIBUS DP-V1 51.5 PROFIBUS DP Master Class 1, PROFIBUS DP Master class 2 71.6 Profiles, short overview 8
2. PROFIBUS built with PDP21 and PDP22 92.1 Slaves with FieldBusPlug 92.2 Important Features of Bus Lines Created with PDP21 / PDP22 92.3 Building a PROFIBUS DP line with FieldBusPlugs 102.4 Topology examples 112.5 Topologies with Repeater 142.6 Topologies with Optical Link 162.7 Power Supply, INT / EXT 162.8 Power Supply via Bus Cable, Calculation 172.9 Grounding, Shielding 19
3. Data Structure, Addressing 213.1 Communication between FieldBusPlug and Device 213.2 Slave with DP-V0 or DP-V1 FieldBusPlug, Data Overview 213.3 Configuration of a PROFIBUS line with FBP slaves in the bus master 223.4 Addressing 26
4. Technical Data 274.1 Bus Cable and Bus Length 274.2 PDP21, PDP22, Pin Assignement 284.3 PDP21, PDP22, Indicators on the Front Plate 294.4 PDP21, PDP22, Technical Data 304.5 PDP21, PDP22, Ordering data 314.6 PDP21, PDP22, Dimensions 324.7 Accessories 33
FieldBusPlug / 03.2010 PROFIBUS DP
Fieldbus configurations with the PROFIBUS FieldBusPlug PDP21 and PDP22 are easy to project and fast to install. Failures e.g. due to poor connection, termination resistors on wrong positions etc. are avoided.
PROFI-BUS
Master
24 V0 V
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
1. PROFIBUS DP, Introduction
1.1 ISO/OSI model
──
──
──
1.2 Typical Bus Topologies
ISO/OSI
Application layer
Data-link layer
For the application layer there are also different versions possible e.g. PROFIBUS DP-V0, PROFIBUS DP-V1 but also others that are not regarded here.
Transmission medium (physical)
Physical layer
Layer 1
PROFIBUS DP is actual the most common fieldbus for industrial applications worldwide and is standardized in IEC61158 together with other fieldbus protocols.
Fieldbus systems normally use only three of them:
Indeed it is possible and common to use conventional cables but also optical fibers as physical layer for the PROFIBUS DP or have a mixture of both in a single bus configuration.
One basis is the ISO/OSI layer model that represents an ordering and description scheme for data transmission systems. It divides the way between the CPU interface and the physical medium into seven layers.
Transmitting CPU
Application layer
Data-link layer
Physical layer
Access (to the line) control, telegram (start,length,.) data security (e.g. CRC=Cyclic Redundancy Code)
Receiving CPU
The definition of the PROFIBUS is based on the experience concerning data transmission collected during long years.
Interface to the application program (CPU) with application oriented commands (read, write)
Definition of the medium (Twinax, optical fiber, ..), coding ("1"= -4V), transmission speed (baud rate)..
Layer 7
Layer 2
As a result of the ISO/OSI layer model each layer can be defined separately and (nearly) independent of the other layers.
Typical field bus topologies
Party Line
trunc
bran
chdrop
Party Line with branch and drop
Ring
The PROFIBUS DP realized with PDP21 or PDP22 represents a real Party Line topology that supports high baud rates up to 12 Mbit/s best possible.
Branches and Drops cause refexions which results a dramatic reduction of the max. baud rate. With repeaters this influence can be equalized partially.
FieldBusPlug / 03.2010 PROFIBUS DP 3
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
1. PROFIBUS DP, Introduction (continued)
1.3 Overview of transferred data
* The quantities of bytes / words are defined by the connected device.**
In the programming tool 07AC1131 used for the CPU 07KT98 the parameter´s value is 'Ignore Block Parameters' or 'Use Block Parameters' resp. in the PDP22 parameter part.
Block parameters are transferred during power-up.The PDP22 (PROFIBUS DP-V1) allows to suppress the block parameter transfer (executed e.g. during power-up) by setting the appropriate parameter. This parameter "Block-Parameter" is not sent to the device and cannot be set via the device, but has to be configured within the parameter area for the PDP22 itself.
Direction
DP/V1 only read / write
Group Type / example *
Qty. of DI, DO,...+product code..
Configuration,Identification
Cyclic data exchange
other basic data transfer
Monitored signals (inputs)
Commands (outputs)
DI = digital inputAI = analog input
DO=digital outputAO=analog output
Faults and warnings
Control function… trip class …
Control function… trip class …
Diagnosis
Block parameters**
Single parameters
baud rate, time -out..Bus specific data
Acyclic data exchange
read / write
readread
writewrite
read
write
read / write
Comment
DP/V0and
DP/V1
Device
Data exchange on the PROFIBUS
Control System
Example of a slave with PROFIBUS FieldBusPlug
FieldBusPlug / 03.2010 PROFIBUS DP 4
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
1. PROFIBUS DP, Introduction (continued)
1.4 PROFIBUS DP-V0 <---> PROFIBUS DP-V1
Commands and monitoring signals
Command and monitoring telegrams represent the cyclic data transfer.
Diagnosis
Complete Diagnosis telegram:
The Diagnosis telegram delivers detailed information if there is any problem, particularly in the process. A trip caused by overload of a motor is an example. Diagnosis data are automatically read by the PROFIBUS master if it gets a general fault info within a monitoring telegram.
Remark: Due to compatibility reasons the DP-V1 plug PDP22 can handle the DP-V0 diagnosis telegram also. Use the parameter 'DPV0 Diagnosis Format' (default) or 'DPV1 Diagnosis format' in the PDP22 parameter part.
The transfer of Commands and Monitoring signals is the essential task of the fieldbus and the connected units. They control and inform mainly about the process, e.g. start a motor and inform if it runs correctly, and are the same for DP-V0 and DP-V1.
Data is processed by the Profibus-Master, so the user is not able to access the data directly.
Diagnosis of PDP21/22 itself:
Length of user specific diagnosis including this lengthbyte.
Communication status: 0: Communication FBP <-> Device running1: Communication lostDiagnostic data received from device; refer to device manual
Data is processed by the Profibus-Master, so the user is not able to access the data directly.
Statusspecific = 0 (no further specification)
Communication status:0: Kommunikation zw. FBP und Gerät läuft1: Kommunikation gestört
Diagnostic data received from device; refer to device manual
Diagnosis of PDP21/22 itself:Length of user specific diagnosis including this lengthbyte.
Diagnosis-Type = 0x81 fix (Status Message)
Slot = 0 (fix)
6 bytes
PROFIBUS standard diagnosis
data
n+2 bytes
User-specific
diagnosis data
Üblich
1 byte length of slave diag.
mit PDP21/22
6 bytes
PROFIBUS standard diagnosis
data
6 bytes
PROFIBUS standard diagnosis
data
n+5 bytes
User-specific
diagnosis data
PROFIBUS DP-V1
mit PDP22
6 bytes
PROFIBUS standard diagnosis
data
PROFIBUS DP-V0
Üblich
n bytesdevice specific
diag.
n bytesdevice specific
diag.
1 byte length of slave diag.
1 byte communicationstatus
1 byte
1 byte
1 byte
1 byte
diag.-type
slot (=0)
statusspecific
communicationstatus
FieldBusPlug / 03.2010 PROFIBUS DP 5
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
1. PROFIBUS DP, Introduction (continued)
1.4 PROFIBUS DP-V0 <---> PROFIBUS DP-V1 (continued)
Configuration, Identification and other data
Additionally some general data such as Baud rate and Time-out are transferred.
Parameters
Parameters can also include service oriented data such as 'Operation hours'.
All slaves compare the expected configuration with their real configuration and confirm if they agree as a supposition to start the data exchange.
E.g. for the device UMC22 the parameter 'Set current' that has to be set correctly to enable the UMC22 to protect the connected motor perfectly against overload.
Parameters are necessary to adapt the device to the process.
Configuration, Identification and other data are necessary to start the operation and communi-cation with the PROFIBUS DP slave. These data are created during configuring/selecting the bus line including the slaves/devices and are sent to the FieldBusPlugs directly after power-up.
FieldBusPlug / 03.2010 PROFIBUS DP 6
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
1. PROFIBUS DP, Introduction (continued)
1.4 PROFIBUS DP-V0 <---> PROFIBUS DP-V1 (continued)
DP-V0 only allows to write the complete parameter set in one block.
DP-V1 offers reading and writing single parameters.
Note: In all cases only the bus master can start the data exchange on the PROFIBUS DP bus.
In addition it is not guaranteed that the parameter block is accepted by the slave.
In former times a separate master class 2 was needed to read and write single parameters. Actually most of the control systems offer a class 1 master capable to perform acyclic DP-V1 services to read and write all data types.
The possibility to read single parameters is an important advantage: If e.g. during commissioning the 'Set current' for a motor is modified locally by the electrician, then the control system must be able to read this value to back it up it into its data base.
Warning: When DP-V1 is used sending block parameters during normal operation can cause faults. The slave changes to the wait status until it receives the next cyclic data telegram. Following this can cause e.g. temporarily motor switch off.
The main difference between the PROFIBUS DP versions DP-V0 and DP-V1 is:
The appropriate parameter is 'Ignore V0 Parameters' or 'Use V0-Parameters' resp. and is available in the .GSD file for DP-V1, see chapter "3. Data Structure, Addressing", "3.3 Configuration of a PROFIBUS line with FBP slaves in the bus master".
The appropriate parameter is evaluated in the PDP21 / PDP22 and is not sent to the device and cannot be set via the device.
The PDP22 (PROFIBUS DP-V1) also allows to suppress the block parameter transfer. This avoids that the parameters are overwritten during power-up of the slave / device.
The bus master sends the parameter block to the slave during power-up of the slave/device. Some control systems also allow to send the parameter block during normal operation.
Parametersonly as block
DP/V0 master
DP/V0slave
DP/V1 master
DP/V1slave
Parametersas single
or as block
Configuration
Diagnosis
Commands Monitorings
Configuration
Diagnosis
Commands Monitorings
FieldBusPlug / 03.2010 PROFIBUS DP 7
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
1. PROFIBUS DP, Introduction (continued)
1.5 PROFIBUS DP Master Class 1, PROFIBUS DP Master class 2
PROFIBUS DP Master Class 1(usually a control system / station):─ continuous cyclic data transfer to all (or selected) slaves ─ transfer of other basic data - write and read bus specific data ( baud rate, time-out,....) - write configuration data - write block parameters - read diagnosis dataSome Master Class 1 are able to─ read and write single parameters (acyclic data transfer)
PROFIBUS DP Master Class 2(usually an operator station / PC)─ gets access to one slave after request (initiate) for a limited time,─ reads and writes acyclic dataSome Master Class 2 are able to─ read cyclic data
Slave Slave Slave Slave Slave
PROFIBUS DP Master Class 2
PROFIBUSDP Master
Class 1CPU
Control System
PROFIBUS DP Master Class 1 /Class 2
FieldBusPlug / 03.2010 PROFIBUS DP 8
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
1. PROFIBUS DP, Introduction (continued)
1.6 Profiles, short overview
There are two main groups of Profiles:
- General Application Profiles
- Specific Application Profiles
However, a profile helps for better understanding of specific slaves. The FieldBusPlug system as an universal bus connection system supports different profiles, depending on the device type.E.g. the UMC22 uses the bit assembly of Motor Managing Starters defined in the Low Voltage Switch Gear profile. But not all bits are used as well as additional (manufacturer specific) information is provided.
But due to the increasing complexity of the different slaves that offer more and more intelligence it is not fully possible (e.g. due to manufacturer specific data).
General Application Profiles describe functions and characteristics that relate to more than just one application. They also can be used together with specific application profiles.One examle is PROFIsafe that is used to support safety-related applications. (Note:The FieldBusPlugs PDP21 and PDP22 do not support PROFIsafe)
Specific Application Profiles are defined for a lot of applications such as encoders, panel devices etc.The scope of the profiles is to provide the possibiliy to replace a slave from one manufacturer by a similar slave from another manufacturer without modifying other parts of an installation.
FieldBusPlug / 03.2010 PROFIBUS DP 9
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
2. PROFIBUS built with PDP21 and PDP22
2.1 Slaves with FieldBusPlug
Examples:
2.2 Important Features of Bus Lines Created with PDP21 / PDP22
1) The PDP21 / PDP22 represents a tee unit.
2) All PDP21 / PDP22 connected to a bus line are supplied via the bus cable.
For more info see chapter "Supply" and the description of the devices.
3) A bus line built with PDP21 / PDP22 is a real party line without branches or drops.
4) The contacts - pins and jacks - are gold plated.
The main feature of the FieldBusPlug system is that all device types with the neutral FBP interface can be connected to several fieldbuses using the appropriate FieldBusPlug type.This means that a PROFIBUS DP-V0 slave (or DeviceNet, ... slave) is built up of a device with the neutral interface and the PROFIBUS DP-V0 FieldBusPlug PDP21-FBP.
One of the most important tasks during commissioning is to adjust the correct slave address carefully. Commands sent to the wrong slave can cause severe problems. For more details see the approriate chapter in this document.
This means: If the bus node built in the PDP21 / PDP22 fails all remaining FieldBusPlugs are still connected with the bus master.
This means: To supply the FieldBusPlugs a power supply unit is necessary that is situated best near the bus master. This is not a disadvantage because without bus master the data transmission is not possible.The advantage is that - under some circumstances - it is possible to supply the devices via the bus cable with 24 VDC saving local supplies.
This means: The max. baud rate 12 Mbit/s is possible, supposed the termination on both ends is done correctly and the max. bus length is not exceeded.
This means: Concerning the contacts the PDP21 / PDP22 avoid that faults caused by loose or bad contacts.
FieldBusPlug,e.g. PDP21
Device: e.g.Universal Motor Controller UMC22
neutral interface
Device: e.g.Softstarter PST
FieldBusPlug / 03.2010 PROFIBUS DP 10
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
2. PROFIBUS built with PDP21 and PDP22 (continued)
2.2 Important Features of Bus Lines Created with PDP21 / PDP22 (continued)
5) Only at the ends of the bus line termination resistors are possible.
2.3 Building a PROFIBUS DP line with FieldBusPlugs
Installation of the PROFIBUS line step by step:
■ Connect PDA11 (Adapter Cable Dsub9-M12) to the bus master.■ Do not forget to set the termination switch on the PDA11 (green) to ON.■ Connect the red and blue strand of the PDA11 with a 24 V DC power supply (+ red, ─ blue).■ Connect the first PDP21 or PDP22 to the PDA11, then the next PDP21 or PDP22 and so on.
■ Do not forget to mount the PDR11 (active PROFIBUS termination unit).
At the Dsub9 connector mounted on the bus master the termination resistor set has to be switched ON and at the other end of the bus line the termination unit must to be mounted.
Regarding the situation that 80 - 90% of the problems in conventional wired PROFIBUS lines are caused by loose contact or wrong termination, the FieldBus Plug system guarantees a faultless data transmission line between the master and the slaves.
This means: In the standard topology as shown below only at the ends of the line terminations are possible.
Attention: Observe precautions for handling electrostatic discharge when mounting / dismounting the plug.
Tighten the knurled knob carefully. The roughness felt during tightening shall result in resistance to vibration.
Standard Topology, only FieldBusPlugs as slaves
PDA11:PROFIBUS DP-Adapter CableDsub9-M12
PDR11:PROFIBUS DP Active Termination Unit
Switch (green)must be set to ON
PDP21 or PDP22PROFIBUS DP-V0 orPROFIBUS DP-V1FieldBusPlug(different length available)
PROFI-BUS
Master
24 V0 V
FieldBusPlug / 03.2010 PROFIBUS DP 11
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
2. PROFIBUS built with PDP21 and PDP22 (continued)
2.3 Building a PROFIBUS DP line with FieldBusPlugs (continued)
For more than 32 stations repeaters or RS485 to optical fiber converters can be used.
2.4 Topology examples
Feed-in if the bus cable is long
If the distance between the bus master and the slaves is longer it may be necessary to feed in 24 VDC for the FieldBusPlugs on a second place. Check with: "Supply Calculation" scheme.
A fault free and stable data transmission urgently requests the perfect termination of the bus line on both ends and nowhere else.This has to be regarded also when repeaters or optical converters are used.
The max number of stations per segment is 32 limited physically by the RS485 standard line drivers and receivers. This includes also repeaters and similar components.
Another limit is set by the max. number 125 of slave addresses. The available range is 1 through 125. More details see chapter "3. Data Structure, Addressing!", sub clause "3.4 Addressing"
PDA11:PROFIBUS DP-Adapter CableDsub9-M12
Switch (green)must be set to ON
PDX11PROFIBUS DP Extension Cable
PDV12PROFIBUS DP-Feed-In Connector (tee unit + 1 connector)
supplied Slaves
supplied Slaves
Feed-in if the bus cable is long
Power supply24VDC
PROFI-BUS
Master
24 V0 V
FieldBusPlug / 03.2010 PROFIBUS DP 12
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
2. PROFIBUS built with PDP21 and PDP22 (continued)
2.4 Topology examples (continued)
Even when slaves other than FieldBusPlugs are used the termination must be made correctly.
Topology if only one or few FBP slaves are connected
Bus master FBP Slave Slaves with Dsub9 connector
PDA11(PROFIBUS DP adaptercable Dsub9-M12 with feed-in, length 0,5 m)
PDM11(PROFIBUS DP Cable with male connector, length 0,5 m. Brown and blue cores not used.(Dsub9 connector not included)
Standard PROFIBUS DP cable and connector, customer prepared/mounted
off off off
PROFI-BUS
Master
24 V0 V
PROFI-BUS-Slave
PROFI-BUS-Slave
PROFI-BUS-Slave
PROFI-BUS-Slave
ONON
Topology if also other PROFIBUS slaves are connected
FBP Slave
Bus master FBP Slave
Slaves with Dsub9 connector
ON
off off
PROFI-BUS
Master
24 V0 V
PROFI-BUS-Slave
PROFI-BUS-Slave
socket
PROFI-BUS-Slave
ON
plug
PDA11(PROFIBUS DP adaptercable Dsub9-M12, with feed-in, length 0,5 m)
PDA12(PROFIBUS DP adapter cable M12-Dsub9-M12, (length 0,5 m / 0,5 m.The supply is fed through)
PDM11(PROFIBUS DP cablewith male connector).(Dsub9 connector is not included)
FieldBusPlug / 03.2010 PROFIBUS DP 13
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
2. PROFIBUS built with PDP21 and PDP22 (continued)
2.4 Topology examples (continued)
Topology if only one FBP slave distant from the bus master is connected
PDF11(PROFIBUS DP cable with plug, length 0,5 m. Brown and blue cores not used.Dsub9 connectornot included.
Standard PROFIBUS DP cable and connector, customer prepared/mounted
PDM11(PROFIBUS DP cable with socket,length 0,5 m. Brown and blue cores not used.Dsub9 connector not included
PDV12PROFIBUS DP-Feed-In Connector: T-unit + 1 connector)
If only one FBP slave is connected thepower supply of the UMC22 can be used.
Bus master FBP SlaveSlaves with Dsub9 connector
off off
PROFI-BUS
MasterPROFI-BUS-Slave
PROFI-BUS-Slave
PROFI-BUS-Slave
ONON
Power supply24VDC
FieldBusPlug / 03.2010 PROFIBUS DP 14
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
2. PROFIBUS built with PDP21 and PDP22 (continued)
2.5 Topologies with Repeater
Repeaters are necessary when:- the number of stations (bus master + slaves) is higher than 32 or- branches are necessary or- a longer bus length is required.
Note:-
- Each segment can have the allowed bus length referring chapter "4. Technical Data"-
-
-
- Keep unshielded cores as short as possible.- Take care for perfect grounding of the shields.
Repeaters have to be calculated as physical stations also within the max. number 32 stations per segment. Thus only 30 slaves can be connected to a segment.
Regard termination carefully. Repeaters normally have built in termination that can be switched on. Consult manufacture's instruction.Do not use more repeaters than necessary. Repeaters decrease the stability of the whole field bus system and make it more sensitive for electromagnetic influence.
Set baud rate on the repeater carefully according to the manufacturer's instruction. Most of the repeaters do not support baud rates up to 12 Mbit/s.
Power supply24VDC
Repeater at the end of segment 1 and at the beginning of the segment 2
Repeater
PROFI-BUS
Master
Power supply24VDC
**unshieldedsignal lines as short as possible
Termination=ON
PDM11(PROFIBUS DP cable with plug,
length 0,5 m. Brown and blue cores not used
PDF11(PROFIBUS DP cable with socket,length 0,5 m.
Termination=ON
**
Segment 1 Segment 2
FieldBusPlug / 03.2010 PROFIBUS DP 15
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
2. PROFIBUS built with PDP21 and PDP22 (continued)
2.5 Topologies with Repeater (continued)
2.6 Topologies with Optical Link
Together with optical links several aspects need to be regarded:- Type of fiber -glass or plastic, distances, laying procedure etc.- Connector types and the method to mount on plastic fibers and glass fibers- Topologies - line, star, ring etc.
Only a simple topology example is shown:
The optical link with the two converters has a behaviour similar to a repeater.
Termination example: two segments
termination termination termination termination
segment 1 segment 2
Repeater
termination no termination termination
trunc
termination
termination
no termination termination termination
bran
ch
segment 1 segment 2
segment 3
Repeater
Repeater
Termination example: two segments + branch
terminationtermination
fiber optic (two directions)termination termination
segment 1 segment 2
electro-optical converter
Optical link example: connection of two segments
electro-optical converter
FieldBusPlug / 03.2010 PROFIBUS DP 16
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
2. PROFIBUS built with PDP21 and PDP22 (continued)
2.7 Power Supply, INT / EXT
Some devices allow to be supplied externally (via terminals) or internally (via bus cable) setting the EXT/INT switch to EXT or INT resp. Consult documentation of the device.
When the signal contacts connected to DI0 - DI5 are distant to the UMC22 or the wiring to these contacts can not be surveyes well the EXT = external supply should be provided urgently.If INT = internal supply (via the bus cable) is used a short circuit 24V<---0V on the inputs circuits of the UMC22 can cause the complete failure of the PROFIBUS.
The supply of the FieldBusPlug is always made via the bus cable. This enables the FieldBusPlug to monitor the actual -e.g.faulty- status to the control station even when it is removed from the device or when power down appears on the device.
Larger devices cannot be supplied via the bus line, the supply current per device should not exeed 200 mA. Max. current per bus line total 4 A.
Additional it is possible to supply simple components such as proximity switches or the devices MSD11 and MSR22 via the bus cable of the FieldBusPlug.
24V
0V
UMC22
11
24V
24V
12 13 14 15
DI2
16 17 18
DI4
DI5
DI0
DI1
DI3
EX
T
INT
SWITCH
10
0V
DOC
5 6
DOC
DO0
7
DO2
9
DO1
8
max.70 mA
FieldBusPlug
24 V0 V
24 V0 V
0V 24Vif EXT supply
24Vto supply
inputs
DI1 DI2 DI3 DI4 DI5DI0
UMC22, INT/EXT supply possibilities
FieldBusPlug / 03.2010 PROFIBUS DP 17
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
2. PROFIBUS built with PDP21 and PDP22 (continued)
2.7 Power Supply, INT / EXT (continued)
-
-
-
Supply of FBP-Line must be protected by external fuse 4 A max.
2.8 Power Supply via Bus Cable, Calculation
Supply voltage: 19,2 V 24 V 31,2 VSupply current typ. 46 mA 37 mA 31 mA
The recommended power supply unit can be adjusted to 28 VDC:
Power Supply 24V / 5A adjustable Order code: 1SVR423416R0100 Type: CP-24/5.0
The calculation with the calculation scheme below takes into account: - The most distant slave - situated at the end of the scheme - needs at least: VDC- Line resistance (0.5 mm²) (can be changed): Ohm/m
Additional info:max. output voltage of above recommended supply unit 28 V
To be noticed:
All slaves even the slave most distant from the supply unit need to be supplied with min. 19.2VDC including ripple. That means that the power supply unit at the beginning of the line has toprovide a higher voltage to compensate the loss due to the line resistance.
Remark: The max. number of physical stations on one bus segment is 32, defined by the RS485 standard. That means: For more than 31 slaves an additional segment (coupled with repeater) has to be provided that needs normally a separate supply unit. In accordance with this fact the calculation below provides max 31 slaves + one master. Normally each repeater and RS485 / fiber-optic converter represent also one physical station each on the RS485 bus line.
To simplify the calculation the scheme below uses the highest of the currents but - on the other hand - does not regard the increased copper resistance and voltage loss for higher environment temperatures.
Check carefully whether the switches of the devices are set to EXT before delivering to the installation site.
Check the supply situation using the calculation scheme in the chapter below. Don't forget to check the total bus length.
Supposed all devices are supplied externally, the supply has to feed the PDP21 or PDP22connected to the bus. The supply current depends on the voltage (typical values):
Prefer separate supply units or separately fused supply circuits for the FieldBusPlug line and thedevices.
19,20,075
S S S S S S S
Master
Power supplyS S S S
line length to the most distant slave
average line length between 2 slaves
FieldBusPlug / 03.2010 PROFIBUS DP 18
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
Supply (continued)
2.8 Power Supply via Bus Cable, Calculation (continued)
Calculation procedure
1. Define number of slaves, e.g. including 10% spare slaves:Example: 25 slaves ---> Master at the row of the 26th slave.
2. Define average length of the bus line between the slaves: mThe total length appears in the row of the master, green cell.
Individual length can be filled in the green cells near the slaves.
3. Fill in current of the slaves: mAIndividual currents can be filled in in the yellow cells near the slaves.
Result: Voltage in the row of the master to be delivered by the power supply,total Current and total Bus Length.
Single Lengths Single Current Sum Voltage onNumber of (can be fixed (can be fixed the Slave
Slaves individually) individually) | | |
| V VMaster V 1 Slave ─┐ m mA mA V
│ mMaster 31 1 Slave ─┤ m mA mA V
│ mMaster 30 1 Slave ─┤ m mA mA V
│ mMaster 29 1 Slave ─┤ m mA mA V
│ mMaster 28 1 Slave ─┤ m mA mA V
│ mMaster 27 1 Slave ─┤ m mA mA V
│ mMaster 26 1 Slave ─┤ m mA mA V
│ mMaster 25 1 Slave ─┤ m mA mA V
│ mMaster 24 1 Slave ─┤ m mA mA V
│ mMaster 4 1 Slave ─┤ m mA mA V
│ mMaster 3 1 Slave ─┤ m mA mA V
│ mMaster 2 1 Slave ─┤ m mA mA V
│ mMaster 1 1 Slave ─┘ m mA mA min V
Results - The power supply unit has to deliver min. 23,7 V incl. ripple and tolerancesoft this - The power supply unit has to deliver min. 1200 mAexample - The bus length is 100 m. Note: Consider length and baud rate.
Current
4,0
4,0
4,0
4,0
4,0
4,0
4,0
4,0
It is necessary to consider also the max. length of the signal lines, see chapter "4. Technical Data".
46
25
4,0
46
104,0
96,0
92,0 46 1104
4,0
4,0
4,019,2192
138
184
460,0 46
46
46
46
8,0
4,0
12,0
24,80
| |
V26,04
24,04
19,20
19,24
19,28
1426
124,0 46 1472
120,0
108,0 46 1288 24,42
46 1242
100,0 46
116,0 46 1380 25,20
112,0 46 1334
1196 23,69
46 1150 23,34
23,01
V
25,62
SumBus
Length|
| |
V
4,0
som
e lin
es a
re h
idde
n / "
For
mat
", "
Row
s",
"unh
ide"
FieldBusPlug / 03.2010 PROFIBUS DP 19
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
2. PROFIBUS built with PDP21 and PDP22 (continued)
2.9 Grounding, Shielding
Grounding Principles
It is urgently recommended to connect the shield to ground:
- at the PROFIBUS DP master and- when entering / leaving a cabinet and- every third or forth FieldBusPlug and-
Efficient grounding of the shield
Painted surfaces inside the cabinet or aluminium plates hinder proper connection.
The PROFIBUS FieldBusPlug cable as well as the standard PROFIBUS cable is equipped with a perfect shield: Aluminium coated foil and braided litz.
According to IEC60204 / EN60204 (chapter 6.3.3) all metallic parts must be grounded to avoid that they - in case of an insulation fault, unexpected and unobserved - are connected to a dangerous voltage.
Regarding EMC, laboratory measurements have proved that grounding is not necessary when the PROFIBUS DP is built up with PDP21 / PDP22 only, normal industrial environment supposed.
Also long litz wire connecting the shield to the cabinet wall results in bad EMC data. For the litz wire
with the length up to length 10 cm the flexible lead should have minimum 6 mm2.
when connecting other - non FieldBusPlug slaves - in accordance with the manufacturer's instruction.
Best workmanship is to remove the sheath partially and to fix the shield directly onto a metallic rail or surface with a clip or a saddle:
The rail must be mounted directly on the metallic part of the cabinet. Zinc plated parts and plates are to be preferred inside the cabinets.
The grounding rail must be close to the cable lead-in in the cabinet wall and should be zinc or nickel plated for proper long term connection.
particular grounding clamp, available from all known terminal producers,to be hooked into the rail
grounding railclose to cable lead-in in the cabinet wall,bare copper or zinc or nickel plated, directly connected to metallic part of the cabinet.
FieldBusPlug / 03.2010 PROFIBUS DP 20
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
2. PROFIBUS built with PDP21 and PDP22 (continued)
2.9 Grounding, Shielding (continued)
Particularely in installations outside of cabinets where IP65 is used the grounding with tube clip can be used:
Wide spread or distant parts of an installation may have different grounding potential if there is not a good metallic connection between. The voltage difference is low but the equalizing current can be high.
Because of the the small cross section the shield of bus cables is not able to lead large equalizing currents. Therefore it is mandatory to add in these cases a equipotential bonding conductor with a cross section of at least 25 mm².
Control cabinet 1 Control cabinet 2
PROFIBUS Station
PROFIBUS Station
equipotential bonding conductor min 25 mm²
Equipotential bonding
Connection to grounded metallic parts of the installation not longer than 25 cm, cross section min. 10 mm²(or 10 cm / 4 mm²)
Grounding with tube clip
FieldBusPlug / 03.2010 PROFIBUS DP 21
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
3. Data Structure, Addressing
3.1 Communication between FieldBusPlug and Device
Direct mode (parallel communication)Signals are exchanged directly via the connections of the field bus-neutral interface.
Serial mode (serial communication)Signals are exchanged using a serial data protocol via the field bus-neutral interface.
Note: Nearly all devices connected to PROFIBUS DP-V0 and DP-V1 use the serial mode.
3.2 Slave with DP-V0 or DP-V1 FieldBusPlug, Data Overview
* DP-V0 and DP-V1 ** DP-V1 only
Scope of data: max. 1 command (digital output) and 2 monitoring signals (digital inputs). If the FieldBusPlug does not receive any telegram from the terminal device during power-up, this mode of data exchange will be set.
This table shows the maximum of data that can be handled by the PDP21/PDP22. Devices use only a part of these quantities, see the UMC22 as an example in the right column.
If the configuration created in the bus master and sent to the PDP21/PDP22 meets the confi-guration from the device, the PDP21 / PDP22 informs the busmaster that the communication can be started.
Binary, analog, parameter and diagnostic data are sent and received. As soon as the FieldBusPlug receives a valid telegram from the device, this mode of data exchange will be set non-volatile.
The data exchange between the PROFIBUS FieldBusPlugs and the device can be performed in two ways:
This mode is used only for very simple devices e.g. proximity switches.
In all cases the PDP21 and PDP22 behave as an input and output module even when the serial mode is active. In the following the serial mode is regarded.
During the initialization phase, the device sends its specific configuration data to the PDP21/22: Quantity of Commands, Monitoring signals, Diagnosis bytes and Parameters.
Type / exampleMax. quantity / presentation
on the Direct-
tionDI = digital inputAI = analog input
DO=digital outputAO=analog output
0 – 16 bytes (128 bits)0 – 16 words
0 – 16 bytes (128 bits)0 – 16 words
readread
writewrite
Faults and warnings
Control function… trip class …
1 byte from PDP21/PDP220 – 8 bytes from device
0 - 236 bytes
read
write
Control function… trip class …
Example:UMC22
1 word2 bytes
02 bytes
1 byte +4 bytes
42 bytes
26read / write
0 - 255, 1 - 4 bytes each
Baud rate, Time-out,...
adjusted during configuratn, transferred during power-up
read / write autom.
Group
Monitored signals (inputs)
Commands (outputs)
Diagnosis
block parameters
single parameters
Bus specific dataMaster to FBP only
Cyclic data*
Other basic
functions*
Acyclic data**
Qty. of DI, DO,...+ product code...
automatically defined and transferred during power up
read / write autom.
Configuration,Identification
FieldBusPlug / 03.2010 PROFIBUS DP 22
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
3. Data Structure, Addressing (continued)
3.3 Configuration of a PROFIBUS line with FBP slaves in the bus master
Following few hints (in brackets: for the ABB CPU 07KT89 and the programming tool 07AC1131)
a) Preparation of the control system programming tool:- Install PROFIBUS DP configurator if not available (in 07AC1131 available)- Read the actual .GSD file using the appropriate menu (copy to ....\AC1131\Library\PLCConf)
PDP21: ABB_078F.GSDPDP22: ABB_082D.GSD
To find out whether the .GSD file fits to the selected device consult the header:
b) Configuration of the Bus Master and the Bus Line:- Busmaster - separate coupler or CPU with PROFIBUS DP interface (07KT98 - DPM) - Bus line (baud rate, time out.....) if other than default or calculated values are desired.
But when connecting a PROFIBUS DP to a control system problems may appear. But they have a general reason and are not caused particularly by the FielBusPlug version of the PROFIBUS DP.
Indeed a field bus line built partly or completely equipped with FieldBusPlug slaves meets definitely the PROFIBUS DP standard. The certificate for the PROFIBUS DP-V0 is available.
Additional requirements appear when PROFIBUS DP/V1 is used. Some control systems require e.g. a Device Type Manager (DTM) or other supplemets depending on the engineering system to offer a comfortable interface.
Different control systems with built in PROFIBUS DP interfaces have different behaviour and need more or less different measures in configuring the slaves and in starting the data exchange.
FieldBusPlug / 03.2010 PROFIBUS DP 23
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
3. Data Structure, Addressing (continued)
3.3 Configuration of a PROFIBUS line with FBP slaves in the bus master( continued)
c) Parametrization of the PROFIBUS DP slaves PDP21 / PDP22 itself:
Select the FieldBusPlug PDP21-FBP or PDP22-FBP resp.The PDP21 does not require any particular parameters.
Block transfer / single transfer of parameters
'Use Block Parameters': PDP22 transfers block parameters to the device (Default)
Diagnosis format DP-V0 / DP-V1
Refer to the file ABB_082D.GSD that is valid for the PDP22 and contains:
Example for 07AC1131 / 07KT98
If e.g. during commissioning the 'Set current' for a motor is modified locally by the electrician the control system must be able to read this value to back up it in the data base.
'Ignore Block Parameters': PDP22 does not hand over the block parameters to the device.
The PDP22 (PROFIBUS DP-V1) offers to transfer single parameters. To suppress the block transfer during power-up a parameter can be set:
Due to compatibility reasons the DP-V1 plug PDP22 can handle the DP-V0 diagnosis telegram also. Use the parameter 'DPV0 Diagnosis Format' (default) or 'DPV1 Diagnosis format' in the PDP22 parameter part.
The PROFIBUS DP-V1 and , therefore, the PDP22 offers the possibility to read and write single parameters. This is an important advantage:
Block transfer is automatically executed during power-up. This means: Modified parameters are overwritten during power-up.
FieldBusPlug / 03.2010 PROFIBUS DP 24
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
3. Data Structure, Addressing (continued)
3.3 Configuration of a PROFIBUS line with FBP slaves in the bus master( continued)
d) Parametrization of the Device (Block Transfer)
Single Parameter Transfer
One important example is the DTM = Device Type Manager.
The possibility to read and write single parameters with PDP22 allows to create more comfortable tools for the commissioning phase that are more or less control system specific.
Example: UMC22 connected to CPU 07KT98, Programming tool 07AC1131
Example: UMC22 connected to CPU 07KT98, Programming tool 07AC1131
FieldBusPlug / 03.2010 PROFIBUS DP 25
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
3. Data Structure, Addressing (continued)
3.3 Configuration of a PROFIBUS line with FBP slaves in the bus master( continued)
e) Assignment of the Commands/Monitoring signals to control system internal variables
Example: Assignement with the 07AC1131
Automatic Definition of the other Variables
f) Prepare Diagnosis monitoring with dedicated function blocks07AC1131 / 07KT89 offers dedicated function blocks:
RUN REVERSE**not used**Motor Current, High ByteMotor Current, Low ByteRUN REVERSE**not used**not used**not used**
** lowest bit as example (UMC22)
/2 /2
Inputto PLC
(Monitor)
OutputfromPLC
(Com- mands)
%IW1.4
%IW1.5
%QW1.8
%QW1.9
%IB1.8%IB1.9%IB1.10%IB1.11%QB1.16%QB1.17%QB1.18%QB1.19
%IX1.4.0...1.4.7%IX1.4.8...1.4.15%IX1.5.0...1.5.7%IX1.5.8...1.5.15%QX1.8.0...1.8.7%QX1.8.8...1.8.15%QX1.9.0...1.9.7%QX1.9.8...1.9.15
Diag-nosis
to PLC
%MW0.0
%MW0.1
%MB0.0%MB0.1%MB0.2%MB0.3
%QX0.0.0...0.0.7%QX0.0.8...0.0.15%QX0.1.0...0.1.7%QX0.1.8...0.1.15
not used**Relay 0 check-back fault**not used**Byte: Parameter number
1 4 48
Coupler slot
Meaning Byte or lowest bitTel. Data Word Byte Bit
FieldBusPlug / 03.2010 PROFIBUS DP 26
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
3. Data Structure, Addressing (continued)
3.4 Addressing
Address Range
The PDP21 and PDP22 are adjusted to the address 100 by default from factory.
Address Adjustment
1.
2.
-
-
If the address adjusted in the device is higher than 125 the PDP21 / PDP22 uses the address stored in its EEPROM.
Address 126 is a default address that does not allow data exchange. If one - only one - slave with address 126 is on the bus line the bus master can change it to a valid address (but never reverse), supposed the bus master is able to do so.Remark: Be aware that a FieldBusPlug line allow only 32 stations per line due to the standard RS485 drivers/receivers. To connect more stations repeaters are necessary.
The valid address range is 1 to 125 and can be used for masters or slaves. Normally only one or two bus masters are connected and they should preferably use the lowest valid addresses 0, 1 or 2).
If the connected device does not offer means to adjust the address: This is typical for very simple devices e.g. proximity switches and also for the MSD11-FBP. In this case the address in the FieldBusPlug can be set:
Use the CAS21-FBP.0 (Addressing Set for PROFIBUS, DeviceNet, etc.).
Connect the FieldBusPlug to another device that has e.g.address switches and preset to the desired address. With switching on the FieldBusPlug receives and saves the address.
Adjustment of the addresses has to be done carefully. Sending commands to the wrong device can cause quite severe problems in the installation or machine.
Some particular devices can be parametrized not to start when the addresses in the FieldBusPlug and in the device are different. Check the technical desription of the device.
In all cases the address adjusted in the device is dominating. With this address the combination FieldBusPlug and device starts operation and communication immediately with power on.
The FieldBusPlug does not contain switches or other means to adjust the address. There are different possibilities to set the address:
The particular advantage is that the slave address is assigned to the device, not to the FieldBusPlug even when it stores the address as well.
The connected device contains address switches or other equivalent means. This is the normal situation for devices prepared to be connected to the PROFIBUS.
The address 126 can only be adjusted with the CAS21-FBP.0 (Addressing Set for PROFIBUS, DeviceNet, etc.). It consists of a small interface unit and a small PC software.
Control panel(from UMC22)
Address switchese.g. from MSR22
FieldBusPlug / 03.2010 PROFIBUS DP 27
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
4. Technical Data
4.1 Bus Cable and Bus Length
Bus Cable
The actual FieldBusPlug-PROFIBUS cable contains
a) Two cores for the bus signals N/A = green = connector pin 2 P/B = red = connector pin 4 (Dsub9 connector: N/A = pin 8, P/B = pin 3)
Characteristic wave impedance: 150 Ohm +/- 15 Ohm(for 3...20 MHz)Cross section: 0.22 mm² = ca. AWG 24Capacity typ.: 30 nF/kmInsulation: PE foamShielded with: metallized film
b) Two cores to supply the plugs +24 V = brown = connector pin 1 0 V = blue = connector pin 3
Cross section: 0.5 mm² = ca. AWG 20Resistance: 38,9 Ohm/kmInsulation: PE
c) Outer shield and jacket braided screen + drain wire = connector pin 5for both signal and supply cores
Drain wire 0.5 mm² = ca. AWG 20Jacket PU, pink, colour ca. RAL4001Bending radius (fixed installation) 10 times jacket diameterTemperature range (fixed inst.) -30°C ... + 80°C
Attention: Exchange of bus signal lines whith supply lines can cause destruction of the plug.
Bus length versus Data rate
The max. data rate depends directly on the bus length:
*
80 80
max. Drop length* [m] * * * * * 6.6 0
12000
Bus length [m] 800 800 800 800 650 300 160 80
500 1500 3000 600019.2 45.45 93.75 187.5Data rate [kBit/s] 9.6
Regarding the supply - voltage loss etc. - see chapter "2. PROFIBUS built with PDP21 and PDP22" sub clause "2.8 Power Supply via Bus Cable, Calculation".
0
The max drop length is defined by the standard only for 500 kBit/s but for lower data rates higher drop lengths are possible. Higher data rates do not allow drop lines.
0 0
view to pins(X13 of the PDP21/22)
mechanicalA coding
12
3 45
outer sheat: PUR, pink (RAL 4001)braided screen
0VDC: PUR or PE (blue)metallized plastic foilbus N/A: PE-foam (green)bus P/B: PE-foam (red)
shield litz (bare, left or right of the brown litz)24VDC: PUR or PE (brown)
FieldBusPlug / 03.2010 PROFIBUS DP 28
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
4. Technical Data (continued)
4.2 PDP21, PDP22, Pin Assignement
Field bus neutral interface to the terminal device(socket)
Pin assignment for parallel mode: 1 +24V (standard power supply unit) 2 digital input (DI 1) 3 0 V (standard power supply unit) 4 digital input (DI 0) 5 digital output (DO 0)
Pin assignment for serial mode: 1 +24V (standard power supply unit) 2 Diagnosis pin 3 0 V (standard power supply unit) 4 Serial data 5 Serial data
Passive plug at the cable end, to previous FieldBusPlug or to bus master
SocketX12
Socket X12
PROFIBUS DP/V0(PDP21) orPROFIBUS DP/V1(PDP22) slave circuitry
PROFIBUS interface. Here the passive plug of the next FieldBus-Plug is plugged in.
At the end of the bus line the termination unit PDR11 must be mounted for correct termination.
Pin assignment:1 +24 V DC (brown)2 Bus-N = A (green)3 0 V DC (blue)4 Bus-P = B (red)5 Shield (bare)
Passive plug / cableof the next FieldBusPlug
EXT = external supply
3
2
1
4
0 V
24 VDC
Signal P/B
PDP21, PDP22 DeviceExample: UMC22
Internal potential separation
Signal N/A
Plug X13
FieldBusPlug / 03.2010 PROFIBUS DP 29
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
4. Technical Data (continued)
4.3 PDP21, PDP22, Indicators on the Front Plate
Meaning of the LED’s
Note:
Error: cannot be remedied, e.g. incorrect checksum in the flash. Exchange plug.
Plug is waiting for configuration data, to be sent from the device (number of input/output bytes, number of parameter bytes, internal baud rate etc.).
If no data has been sent by the terminal device within 3 s, the plug switches to the parallel mode.
flashes
off
off On
On off
off
flashes
flashes
Error: can be remedied, e.g. connection to the terminal device is broken.
flashes
flashes
On
flashes
On
off
flashesoff
offPlug is under self-test during power-up
The device parameters received from The bus master are formal incorrect, e.g. of other length.
Status / Cause
Power supply is missing
Normal data exchange to the terminal device.
off
Normal data exchange to the PROFIBUS DP master.
Connection to the bus master lis interrupted longer than the time-out set by the bus master before interruption.
Possible errors: - No connection to the bus master, e.g. PROFIBUS not operating.- The PDP21 / PDP22 has a slave address that is not configured in the bus master.- Parameter length and slave address are correct but I/O configuration of the slave does not meet the configuration sent by the bus master.
On
LED red H4
Device statusLED green
H3
PROFIBUS statusLED green
H1LED red
H2off off
On flashes
PROFIBUS status
device status
H1 and H2 display the PROFIBUS status
H3 and H4 display the device statusFastening screw (provided on delivery)
Label for writing down the address setting
FieldBusPlug / 03.2010 PROFIBUS DP 30
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
4. Technical Data (continued)
4.4 PDP21, PDP22, Technical Data
Supply voltage
Safety insulation PELV according to EN60950
Current consumption
at 19.2 V 46 mAat 24,0 V 37 mAat 31.2 V 31 mA
Mounting
min. 10 ms
Recommended power supply unit Type: CP-24/5.0 adj.Order number: 1SVR 423 416 R0100can be adjusted to max. voltage 28 V DC
Bus termination
parallel and serial
Scope of data according to PROFIBUS DP specificationsConstruction of the FieldBusPlug cable round cable, black, 2 x 0.34 mm2 for supply voltage
2 x 0.25 mm2 for data lines
2 connected shields
PDP21, PDP22 pin assignement 1 +24 V DC (brown)2 Bus-N = A (green)3 0 V DC (blue)4 Bus-B = A (red)5 Shield (bare)
Warning:
Load capacity of plugs and cables max. 4 ADegree of protection
Ambient temperaturestorage -20...+70 °Coperation 0...+60 °C
Dimensions see followingTotal power dissipation PDP21, PDP22 max. 0.9 W
Weight plug with cable 0.25 m 0.09 kgplug with cable 0.5 m 0.10 kgplug with cable 1 m 0.13 kgplug with cable 5 m 0.35 kg
Bus address setting - with address switches or similar on the terminal device
- with addressing set CAS21-FBPAddress range 1 to 126, recommended 3 to 125
0 to 2 and 126 to 128 are reserved for particular tasksDiagnosis with LEDs see chapter "PDP21, PDP22, Indicators on the Front Plate"
24 V DC + 30% / - 20% (19.2 … 31.2 V DC)protected by external fuse 4 A max.
on the terminal device, fixed with a screw (provided on delivery) or by M12 box nut fixing
Exchange of bus signal lines whith supply lines can cause destruction of the plug.
IP 65, if M12 box nut fixing is used at the terminal device (e.g. sensor)
IP 20, if mounting is performed using the supplied fastening screw (e.g. for UMC22-FBP)
Modes of data communication between FieldBusPlug and device
Power line failure bridging time, to be performed by the power supply unit
active bus-Iine terminator 150 at both ends of the bus, the bus master units (or repeaters) offen offer a bus-Iine terminator at the start of the bus line.
21
4 35
12
3 45
pin socket
FieldBusPlug / 03.2010 PROFIBUS DP 31
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
4. Technical Data (continued)
4.5 PDP21, PDP22, Ordering data
Ordering Data: PROFIBUS DP/V0Type Description Order numberPDP21-FBP.025 PROFIBUS DP-V0 FieldBusPlug 0,25 m 1SAJ240000R0003PDP21-FBP.050 PROFIBUS DP-V0 FieldBusPlug 0,5 m 1SAJ240000R0005PDP21-FBP.100 PROFIBUS DP-V0 FieldBusPlug 1 m 1SAJ240000R0010PDP21-FBP.200 PROFIBUS DP-V0 FieldBusPlug 2 m 1SAJ240000R0020PDP21-FBP.500 PROFIBUS DP-V0 FieldBusPlug 5 m 1SAJ240000R0050
Ordering Data: PROFIBUS DP/V1Type Description Order numberPDP22-FBP.025 PROFIBUS DP-V1 FieldBusPlug 0.25 m 1SAJ240100R1003PDP22-FBP.050 PROFIBUS DP-V1 FieldBusPlug 0.5 m 1SAJ240100R1005PDP22-FBP.100 PROFIBUS DP-V1 FieldBusPlug 1 m 1SAJ240100R1010PDP22-FBP.500 PROFIBUS DP-V1 FieldBusPlug 5 m 1SAJ240100R1050
FieldBusPlug / 03.2010 PROFIBUS DP 32
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
4. Technical Data (continued)
4.6 PDP21, PDP22, Dimensions
FieldBusPlug / 03.2010 PROFIBUS DP 33
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
4. Technical Data (continued)
4.7 Accessories
Type Description Order number
PDX11-FBP.100 PROFIBUS DP Extension Cable 1m 1SAJ924001R0010PDX11-FBP.300 PROFIBUS DP Extension Cable 3m 1SAJ924001R0030PDX11-FBP.500 PROFIBUS DP Extension Cable 5m 1SAJ924001R0050
PDF11-FBP.050 PROFIBUS DP Cable with Female Connector 1SAJ924002R0005PDM11-FBP.050 PROFIBUS DP Cable with Male Connector 1SAJ924003R0005
PDC11-FBP.999 PROFIBUS DP Round Cable 100 m 1SAJ924004R1000
PDM11-FBP.0 PROFIBUS DP Male Assembling Connector 1SAJ924005R0001PDF11-FBP.0 PROFIBUS DP Female Assembling Connector 1SAJ924006R0001Note: Mount carefully. Loose contact causes communication problems. Instruction see below.
PDR11-FBP.150 PROFIBUS DP Termination Unit 1SAJ924007R0001
PDV11-FBP.0 PROFIBUS DP Feed-In Connector Code B-A 1SAJ924008R0001PDV12-FBP.0 PROFIBUS DP Feed-In Connector Code A-A 1SAJ924011R0001
1
4
23
1
4
23
1
4
23
PDV12
all M12code A
PDV11 M12 code A
M12 code B
M12code A
12345
12345
1 2 3 4
24 VDC (brown) 0 VDC (blue)
Bus-N = A (green)0 VDC (blue)
Bus-P = B (red)
Bus-N = A (green)
Bus-P = B (red)
24 VDC (brown)
Shield wireShield
PDV11,PDV12,Circuitdiagram
FieldBusPlug / 03.2010 PROFIBUS DP 34
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
4. Technical Data (continued)
4.7 Accessories (continued)
Type Description Order number
PDA11-FBP.050 PROFIBUS DP Adapter Cable Dsub9-M12 1SAJ924009R0005PDA12-FBP.050 PROFIBUS DP Adapter Cable M12-Dsub9-M12 1SAJ924010R0005
24 V
0 V
socket
switch for termination resistor set
additional connection of test unit etc.
PDA11
plug socket
switch for termination resistor set
PDA12
PDA11, PDA12, Circuit Diagrams
M12, view to socket Dsub9, view to socket
0 V (blau / blue)
Bus-P = B (rot / red)
Bus-N = A (grün / green)
+24 VDC ( braun /brown)
1 2
345 3
8
PDA11
PDA12 M12, view to pins Dsub9, view to socket M12, view to socket
2 1
35
4
1 2
4 35
0 V (blau / blue)Bus-P = B (rot / red)
+24 VDC ( braun /brown)
Bus-N = A (grün / green)
38
FieldBusPlug / 03.2010 PROFIBUS DP 35
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
4. Technical Data (continued)
4.7 Accessories (continued)
PDM11, PDF11, Mounting instruction
1. Stripping the insulation:
Distance between notch and cable end: 30 mm
Type of the shown insulation-stripping tool:PSM-STRIP-FC/PROFIB (PHOENIX)Part No.2744623
2. Remove the sheath3. Cut the shield carefully, the shield wire must not be cut4. Remove the aluminium shield layer5. Strip the insulation from the cores at a length of 10 mm6. Put-on and crimp the wire-end ferrules
7. Shorten wire-end ferrules (metallic part ca. 5 mm)8. Put the rubber O-ring in the notch9. Stick the plug parts on to the cable10.
11. Connect shield wire to pin 5 and pull the sleeve over it 12. Remove the 7 mm piece of sheath
13.
14. Screw together the front parts of the plug15.
16. Screw-on the clamp-type sleeve, done
Cable juts out 18 mm from the shown tool. Thus a piece of 7 mm in lengh is pre-notched.
Shorten the shield wire, stick the sleeve on to the shield wire
Fold the braided shield to the back part of the plug (with the O-ring)
Connect the PROFIBUS DP cores (green and red) to pin 2 and 4
Gummi-o-RingRubber o-ring
TülleSleeve
7-mm-Mantelstück7 mm of sheath
Gummi-o-RingRubber o-ring
SchirmgeflechtBraided shield
FieldBusPlug / 03.2010 PROFIBUS DP 36
PDP21-FBP PROFIBUS DP-V0 FieldBusPlugPDP22-FBP PROFIBUS DP-V1 FieldBusPlug
V6 Technical Description
FieldBusPlug / 03.2010 PROFIBUS DP 37
Man
ual N
o.
ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82 Postfach 10168069123 Heidelberg 69006 HeidelbergGermany Germany
Telephone +49 (0) 6221 701- 0 Telefax +49 (0) 6221 701- 240E-mail [email protected] http://www.abb.de/stotz-kontakt
2CD
C19
0 00
1 D
0209
03
.201
0