Technical Data TD027002EN Effective March 2014 Contents Description Page Voltage regulation with bypassing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Mobile MITS application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Natural gas extraction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Utility substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Portable power application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Small substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Residential area substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Lightning damaged substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Rural substation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Modular integrated transportable substation (MITS)

Upload: dotuyen

Post on 16-Mar-2018

220 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Technical Data TD027002EN Modular integrated …pub/@electrical/... · Cable Connection Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, ... DIFF. Protection Relay

Technical Data TD027002EN Effective March 2014

ContentsDescription Page

Voltage regulation with bypassing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Mobile MITS application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Natural gas extraction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Utility substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Portable power application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Small substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Residential area substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Lightning damaged substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Rural substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Modular integrated transportable substation (MITS)

Page 2: Technical Data TD027002EN Modular integrated …pub/@electrical/... · Cable Connection Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, ... DIFF. Protection Relay

2

Technical Data TD027002ENEffective March 2014

Modular integrated transportable substation (MITS)

eaton www.eaton.com

Voltage regulation with bypassing

Value proposition

Single-point contact for project management, plug-and-play installation, on-board fluid containment, and resolved voltage regulation with an aesthetically pleasing design.

A waste water treatment facility in the northeast United States found that poor voltage regulation was a significant problem for their equipment. The facility decided to remedy the situation with a voltage regulation MITS, resulting in fewer equipment issues and improved reliability.

34.5 kV FusedDisconnect Switch

Regulators (3)345 kVA34.5 kV, 100A,FR3 Fluid Filled

34.5 kV FusedDisconnect Switch

34.5 kVBypassSwitch

10 kVA Station ServiceTransformer W/VFIHV: 34,500V DeltaLV: 120/240VFR3 Fluid Filled

S

L

Figure 1. System Schematic

10'-1.0"

8'-11.8"

43'-11.4"34.5 kV Fused Disconnect Switch

34.5 kV Fused Disconnect Switchand 34.5 kV Bypass Switch

4-Inch Containment WallAbove Deck (Typical All Around)

FR3 Fluid Volume = 173 Gals.

Voltage Regulator34.5 kV, 100AFR3 Fluid Volume = 470 Gals.10 kVA Control Power Transformer

34.5 kV, 240/120V

Figure 2. System Layout and Dimensions

Page 3: Technical Data TD027002EN Modular integrated …pub/@electrical/... · Cable Connection Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, ... DIFF. Protection Relay

3

Technical Data TD027002ENEffective March 2014

Modular integratedtransportable substation (MITS)

eaton www.eaton.com

Mobile MItS application

Value proposition

Improved reaction time in emergency situations, completely mobile, integrated connection interface, and simple design.

This application involves a dedicated mobile application for the customer. Fueled by the need to respond and react to potential emergency situations, this mobile MITS provides the customer the ability to transform voltage. Used in conjunction with a mobile genset, voltage is generated at 480V and stepped up to a voltage of either 4160Y/2400 or 2400V delta to supply power on an emergency basis.

480V Junction Boxfor Generator Cable Connection

Transformer2400/4160Y/2400–480VStep Up Application2500 kVA, FR3 Fluid, 65°C

5 kV Cableson Trailer

Figure 3. System Schematic

2500 kVA2400/4160Y/2400480V 5.73% IZ

480V NEMA 4Junction Boxwith TransitionBusbars

480V 7–500 kcmilMetal-Clad Armor Cables

Ground CableStorage Box

Spare Tire/Cover,Near and Far Side

Flip Down/UpLadder

5 kV, 350 kcmil Jacketed Cable, 100 Ft

12" Galvanized Steel Cablewith Turnbuckle

Rails, Sideand Back

11'-4"

8'-6"

40'-10.0"

Steel Diamond Plate Deck

Figure 4. System Layout and Dimensions

Page 4: Technical Data TD027002EN Modular integrated …pub/@electrical/... · Cable Connection Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, ... DIFF. Protection Relay

4

Technical Data TD027002ENEffective March 2014

Modular integratedtransportable substation (MITS)

eaton www.eaton.com

natural gas extraction

Value proposition

Fifty percent savings on future relocation costs, 15 percent savings over conventional design, 25 percent savings in space, and increase in cash flow due to a quickly commissioned substation.

Configured for supplying electrical loads for sites that extract ground water embedded with natural gas, this MITS application is a different way of building substations for the mining industry. Using a skid-based platform, the MITS reduces the footprint and can provide a cost savings over a typical installation. Eaton’s modular substation is designed to be relocated to a new site after its service is completed at the existing site. The ability to move the entire substation without complete disassembly can provide customers with substantial benefits over conventional substation installations.

Viewing loads and status of equipment in harsh, remote environments often requires a long drive across difficult terrain. Eaton provides RTU cabinets populated with IEDs and SCADA equipment to meet most specifications. This contributes to cost and time savings for maintaining valuable equipment.

50 kVA StationService TransformerHV: 14,440GYLV: 240/120V

VFI Switchgear—Main25 kV, 900A

VFI Switchgear #225 kV, 900A, Four Feeders

VFI Switchgear #125 kV, 900A, Four Feeders

Primary MeteringCompartment14,400–120V VTs

Primary MeteringCompartment14,400–120V VTs

Source 1 Source 2

MeteringCTs

Figure 5. System Schematic

Feeder Switchgear #2 Feeder Switchgear #1Main Switchgear

1'-9"

Distribution Panel

Relay CabinetSpecified Metering and SCADA EquipmentFeeder Protection Relays

50 kVA Station Service Transformer

Voltage Transformer25 kV Padmounted Switchgear

7'-3"

8'-6.0"

38'-0"

Figure 6. System Layout and Dimensions

Page 5: Technical Data TD027002EN Modular integrated …pub/@electrical/... · Cable Connection Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, ... DIFF. Protection Relay

5

Technical Data TD027002ENEffective March 2014

Modular integratedtransportable substation (MITS)

eaton www.eaton.com

Utility substation

Value proposition

Modular design can be used at many locations, is completely integrated, provides on-board spill containment, and is transportable.

Driven by the need to cut the cost of installed substations and to create a modular design concept, this customer turned to Eaton’s MITS solution. The conventional substation consisted of overhead distribution, transformation, and feeder protection. In addition, each substation required the site to be prepared for oil containment in the event of a leak. In this example, Eaton provided solutions to the customer’s requirements and allowed the use of this modular solution at several sites throughout the electrical grid.

S

L

Substation Transformer9375/10,500–12,468/13,965 kVAHV: 22.9 kV DeltaLV: 13.8Y/7.97 kV55/65°C, ONAN/ONAF

Regulator and Recloser Bypass15 kV Model 10T RVAC Switchgear2 Source / 2 Taps with Tie SwitchVisible Break on All Sources and Taps

Regulators (3)500 kVA7620V, 656A(Operated at 7970V)

15 kV Recloser (1)Three-Phase NOVA(Solid Dielectric)Tamper-Resistant Outdoor Enclosure

15 kVA StationServiceTransformerHV: 13,800GYLV: 120/240V

Figure 7. System Schematic

120/240V Distribution Panel 15 kVA StationService Transformer

Recloser15 kV, 600ATamper-Resistant Enclosure

Regulators656A, 7.97 kVCL-6A Controls

Switchgear15 kV, 600A RVAC Model 10T

Substation Transformer9375 kVAHV: 22.9 kV DeltaLV: 13.8Y/7.97 kV

34'-5.9"

8'-6.0"

7'-8.4"

10'-11.0"

15'-1.5"

13'-1.3"

Weep Holes, Typ.

Access Hatch

Locking PumpAccess forOil Removal

Access Hatch

Weep HolesLocated DirectlyUnder Fins

Radiators

Locking PumpAccess for OilRemoval

LVC

abin

et

ControlBox

HV

Cab

inet

Figure 8. System Layout and Dimensions

Page 6: Technical Data TD027002EN Modular integrated …pub/@electrical/... · Cable Connection Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, ... DIFF. Protection Relay

6

Technical Data TD027002ENEffective March 2014

Modular integratedtransportable substation (MITS)

eaton www.eaton.com

Portable power application

Value proposition

Quick delivery, fully integrated, transportable, and a single point of contact for project management.

Furnished for the U.S. government, this MITS skid provides quick and reliable portable power for emergency applications. The need for this project was to step up voltage supplied by generators from 3.6 kV to 11 kV. The application has a variety of self-protecting features, and is quick to install and commission.

52

52

52

52

52

52

52

Metal-Enclosed Switchgear(3) 5 kV; 1200A Fused Load Interrupter SwitchesMetal-Clad Switchgear(1) 5 kV, 1200A Drawout Breaker

Metal-Clad Switchgear(5) 15 kV, 1200A Drawout Breakers

Substation Transformer5000/6250 kVAHV: 11.0Y/6.35 kVLV: 3.6 kV55/65°C, KNAN/KNAF

Notes:1. All Breakers Controlled by: Feeder Protection Relays2. Differential Protection Scheme for Transformer:Relay

Figure 9. System Schematic

H3H2H1H0

X3X2X1

73000 Lbs

15 kV ClassSwitchgear Lineup

5 kV ClassSwitchgear Lineup

Substation Transformer5000/6250 kVAHV: 11,000Y/6350VLV: 3600V Delta

10'-1.9"

8'-2.8"

37'-11.4"

Horn

Figure 10. System Layout and Dimensions

Page 7: Technical Data TD027002EN Modular integrated …pub/@electrical/... · Cable Connection Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, ... DIFF. Protection Relay

7

Technical Data TD027002ENEffective March 2014

Modular integratedtransportable substation (MITS)

eaton www.eaton.com

Small substation

Value proposition

Substantial saving over conventional substation design, 25 to 30 percent savings in project management, and over 60 percent smaller footprint than conventional substation design.

Installed in the western part of the U.S., this application combines two MITS skids that will provide dual functionality. Initially, the skids will step up voltage from 13.2 kV to 34.5 kV, and distribute voltage onto the transmission lines. At some point in the future, the customer plans to use these skids in the reverse fashion and step 34.5 kV down to 13.2 kV. Included with each skid is an Eaton differential protection relay used to trip the NOVA recloser and an upstream device.

Transformer5000 kVAHV: 34.5Y/19.9 kVLV: 13.2Y/7.62 kV55°C, ONAN

Primary MeteringCompartmentPTs and CTs

Recloser (1)35 kV, 200AThree-Phase NOVA (Solid Dielectric)Tamper-Resistant Outdoor Enclosure

87

15 kVA StationService TransformerHV: 34.5GY/19.9 kVLV: 120/240V

48 Vdc Battery Systemwith AC Charger

DIFF. Protection Relay

Figure 11. System Schematic

48 Vdc Battery System

30'

8'-6.0"

8'-6.3"

15 kVA Station Service Transformer

Transformer ControlCabinet with Relay Transformer

5000 kVA HV: 34.5Y/19.9 kVLV: 13.2Y/7.62 kV Primary

MeteringCabinet

Recloser35 kV Three-PhaseNOVA Mounted inTamper-Resistant Enclosure

Figure 12. System Layout and Dimensions

Page 8: Technical Data TD027002EN Modular integrated …pub/@electrical/... · Cable Connection Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, ... DIFF. Protection Relay

8

Technical Data TD027002ENEffective March 2014

Modular integratedtransportable substation (MITS)

eaton www.eaton.com

Residential area substation

Value proposition

Significantly smaller footprint than conventional substation design, safe and secure design requires no fencing, and one point of contact for entire substation.

The heavily wooded terrain of a 13.2 kV to 4 kV metro area provided challenges to the utility that served local estate homes. Unit substations serving the area were several decades old, had become heavily loaded, and lacked needed and overlooked maintenance. A new Eaton MITS was the best option.

L

S

Transformer

4 kV Recloser

13 kV Recloser

Regulators (3)250 kVA7620V, 328A

25 kVAStation ServiceTransformerHV: 13,200GY/7620LV: 240/120

Figure 13. System Schematic

18.5

8'-6.5"

40'

8'-6"

6" Typ.

DistributionPanel

Metering Enclosure 3.75 MVA Transformer

15 kVA StationService Transformer

13 kV Recloser

250 kVA Regulators (3)

4 kV Recloser

Figure 14. System Layout and Dimensions

Page 9: Technical Data TD027002EN Modular integrated …pub/@electrical/... · Cable Connection Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, ... DIFF. Protection Relay

9

Technical Data TD027002ENEffective March 2014

Modular integratedtransportable substation (MITS)

eaton www.eaton.com

Lightning damaged substation

Value proposition

Twenty-five percent savings on installed cost, and rapid and efficient installation and recovery time.

This design offers the perfect solution for a customer needing to replace a 5 MVA storm-damaged substation…fast. Eaton mounted and pre-wired a 5 MVA transformer, three pad-mounted regulators, a station service transformer, switchgear, and controls on a single structural steel platform. The customer pre-installed the ground grid, the MITS foundation, the incoming circuits, and the outgoing circuits. Total field install time of the MITS assembly was less than four hours.

Power to a town and surrounding community was restored in record time, and at a total installed cost 25 percent below conventional methods.

CL-6

SA

SB S

LLB

LA

VFI

Transformer34,500–12,470Y/7200V5000 kVA, ONAN 65ºC

H1A/H1B

Regulators (3)250 kVA7620V, 328A

Sectionalizing Cabinet 15 kVA

Station ServiceTransformerSingle-PhaseHV: 7620GYLV: 240/120V

15 kV Reclosers (3)

Figure 15. System Schematic

15 kVA ServiceStation Transformer

Sectionalizing Cabinet

Control Service Enclosure

15 kV Reclosers

250 kVARegulators

5 MVATransformer

40'-0"

8'-6"

9'-7.5"

Figure 16. System Layout and Dimensions

Page 10: Technical Data TD027002EN Modular integrated …pub/@electrical/... · Cable Connection Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, ... DIFF. Protection Relay

10

Technical Data TD027002ENEffective March 2014

Modular integratedtransportable substation (MITS)

eaton www.eaton.com

Rural substation

Value proposition

Quick implementation with minimal disruption to the customer and the existing landscape.

A substation was needed to serve a remote industrial load. Because of the unique transformer design, it was acquired through a third party and installed on a separate structural steel platform along with a high-side recloser, which serves as a switch and protection device.

To achieve cooling requirements, fans were required on the transformer. (The external transformer cooling fans no longer make the assembly tamper-proof; therefore, fencing is required.) A second structural steel platform was used to pre-install and test three single-phase, pad-mounted voltage regulators, switchgear, a control center, and a station service transformer. The platforms were interconnected at the job site and the completed assembly, as an integrated whole, did not affect the integrity of this finished product.

Surface grading to level the area would have been required for a concrete foundation. Instead of the concrete foundation, steel pillars were installed at weight-bearing points under the entire MITS assembly to elevate the structure from ground level.

15 kV Recloser

Skid 1

LB SBLA

L S

SA

H1A/H1B

S

T2

T1 VB1SW1SW2 VB2

VB3 SW3

Skid 2

Type PWVE25 kV Reclosers (2)

Type RVAC-13A25 kV Switchgear

250 kVARegulators (3)

Auto-Transformer10 MVAHV: 24,940Y/14,400VLV: 13,800Y/7960V

25 kVAStation Service TransformerHV: 24,940Y/14,400VLV: 240/120V

Figure 17. System Schematic

8'-6"

25'-0"

10'-3"

11'-9.5"

Skid 1Skid 2

37'-0"

Type PWVE25 kV Reclosers (2)

25 kVA Station Service TransformerHV: 24,940Y/14,400VLV: 240/120V

RVAC 13A25 kV Switchgear

Control Service Enclosure

PWERecloser

250 kVA Regulators (3)

Figure 18. System Layout and Dimensions

Page 11: Technical Data TD027002EN Modular integrated …pub/@electrical/... · Cable Connection Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, ... DIFF. Protection Relay

11

Technical Data TD027002ENEffective March 2014

Modular integratedtransportable substation (MITS)

eaton www.eaton.com

Page 12: Technical Data TD027002EN Modular integrated …pub/@electrical/... · Cable Connection Transformer 2400/4160Y/2400–480V Step Up Application 2500 kVA, ... DIFF. Protection Relay

Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton.com