technical catalog for ju/jw engine series
TRANSCRIPT
-
Technical Catalog
for JU/JW Engine Series
(with English to German Translator Pages) (Mit Englisch zu Deutsch Ubersetzung Seiten)
(with English to Spanish Translator Pages) (Traductor del Ingls al Espaol)
(with English to French Canadian Translator Pages) (Traducteur Anglais > Franais canadien)
This manual covers John Deere Series engines prepared by Clarke for fire pump service
Clarke UK, Ltd. Clarke Fire Protection Products, Inc. Unit 1, Grange Works 3133 E. Kemper Road
Lomond Road Cincinnati, OH 45241 Coatbridge U.S.A. ML5 2NN
United Kingdom TELE: +44(0)1236 429946 FAX: +44(0)1236 427274
TELE: +1.513.771.2200 FAX: +1.513.771.0726
www.clarkefire.com
C13965 rev P
-
This page intentionally left blank
-
CONTENTS SUBJECT Document No. English to German I&O Data Translator for German (Englisch zu Deutsch I&O Daten Ubersetzer fr Deutsch) C13973
English to Spanish I&O Data Translator for Spanish (Traductor del Ingls al Espaol) C13986
English to Spanish I&O Data Translator for French (Traducteur Anglais > Franais) C131051
JU4H-UF10/12 (USA) C13663
JU4H-UF10/12 (UK) C131234
JU4H-UF14 (USA) C131262
JU4H-UF14 (UK) C131263
JU4H-UF20/22 (USA) C13611
JU4H-UF20/22 (UK) C131235
JU4H-UF24 (USA) C131264
JU4H-UF24 (UK) C131265
JU4H-UF30/32 (USA) C13664
JU4H-UF30/32 (UK) C131228
JU4H-UFH8 (USA) C131398
JU4H-UFH0 (USA) C131397
JU4H-UFH2 (USA) C131396
JU4H-UF34 (USA) C131266
JU4H-UF34 (UK) C131267
JU4H-UF40/42 (USA) C13665
JU4H-UF40/42 (UK) C131229
JU4H-UF50/52 (USA) C13612
JU4H-UF50/52 (UK) C131230
JU4H-UF54 (USA) C131270
JU4H-UF54 (UK) C131271
JU4R-UF09&11 (USA) C131407
JU4R-UF09&11 (UK) C131651
JU4R-UF13 (USA) C131409
JU4R-UF13 (UK) C131652
JU4R-UF19 & UF21 (USA) C131408
JU4R-UF19 & UF21 (UK) C131653
JU4R-UF23 (USA) C131410
JU4R-UF23 (UK) C131654
JU4R-UF40 (USA) C131411
JU4R-UF40 (UK) C131655
JU4R-UF49 & UF51 (USA) C131412
JU4R-UF49 & UF51 (UK) C131656
-
JU4R-UF53 (USA) C131413
JU4R-UF53 (UK) C131657
JU6H-UFD0 C131394
JU6H-UFD2 C131393
JU6H-UF30/32 (USA) C13507
JU6H-UF30/32 (UK) C131231
JU6H-UFG8 C131392
JU6H-UFM8 C131391
JU6H-UFM0 C131390
JU6H-UFM2 C131389
JU6H-UF34 (USA) C131274
JU6H-UF34 (UK) C131275
JU6H-UF50/52 (USA) C13508
JU6H-UF50/52 (UK) C131232
JU6H-UF54 (USA) C131276
JU6H-UF54 (UK) C131277
JU6H-UF58 C131388
JU6H-UF60/62 (USA) C13509
JU6H-UF60/62 (UK) C131223
JU6H-UF68 C131387
JU6H-UF84 (USA) C131278
JU6H-UF84 (UK) C131279
JW6H-UF38 (USA) C131386
JW6H-UF30 (USA) C13426
JW6H-UF30 (UK) C132031
JW6H-UF48 (USA) C131385
JW6H-UF40 (USA) C13427
JW6H-UF40 (UK) C132032
JW6H-UF58 (USA) C131384
JW6H-UF50 (USA) C13613
JW6H-UF50 (UK) C132033
JW6H-UFH8 (USA) C132024
JW6H-UF60 (USA) C13614
JW6H-UF60 (UK) C132034
JU4H-NL14 C131253
JU4H-NL20/22 C13735
JU4H-NL24 C131254
-
JU4H-NL34 C131255
JU4H-NL50/52 C13738
JU4H-NL54 C131257
JU4R-NL09/11 C132009
JU4R-NL13 C132010
JU4R-NL19/21 C132011
JU4R-NL23 C132012
JU4R-NL40 C132013
JU4R-NL49/51 C132014
JU4R-NL53 C132015
JU6H-NL30/32 C13739
JU6H-NL34 C131259
JU6H-NL50/52 C13742
JU6H-NL54 C131260
JU6H-NL60 C13743
JU6H-NL74 C131383
JU6H-NL84 C131261
JW6H-NL30 C13997
JW6H-NL40 C13998
JW6H-NL50 C13999
JW6H-NL60 C131000
JU4H-LP20 C131244
JU4H-LP24 C131252
JU4H-LP50 C131245
JU4H-LP54 C131249
JU6H-LP50 C131246
JU6H-LP54 C131251
JU6H-LP60 C131247
JU6H-LP84 C131248
JU4H-AP50 C132129
JU4H-AP54 C132184
JU6H-AP30 C132130
JU6H-AP34 C131286
JU6H-AP50 C132131
JU6H-AP54 C131287
JU6H-AP60 C132132
JU6H-AP84 C131288
-
English to French Translator for C13977 (Traducteur Anglais > Franais) C131052
NFPA 20 Cooling Loop Piping Detail C13977
NFPA 20 Exhaust Piping Detail C06918
English to Spanish Translator for C07575 (Traductor del Ingls al Espaol) C13995
English to French Translator for C07575 (Traducteur Anglais > Franais) C131060
NFPA 20 and FM Engine Gauge Panel (DC Voltage) JU Engines C07575
English to German Translator for C07602 (Englisch zu Deutsch bersetzung fr C07602) C13969
English to Spanish Translator for C07602 (Traductor del Ingls al Espaol) C13987
English to French Translator for C07602 (Traducteur Anglais > Franais) C131062
NFPA 20 and FM Engine Gauge Panel (DC Voltage) JW Engines C07602
English to Spanish Translator for C07591 (Traductor del Ingls al Espaol) C13994
English to French Translator for C07591 (Traducteur Anglais > Franais) C131061
Engine Kim Jacket Water Heater (AC Voltage) (JU Engines) C07591
English to German Translator for C07651 (Englisch zu Deutsch bersetzung fr C07651) C13972 English to Spanish Translator for C07651 (Traductor del Ingls al Espaol) C13988
English to Frech Translator for C07651(Traducteur Anglais > Franais) C131053
Engine Jacket Water Heater (AC Voltage) (JW/JD Engines) C07651
Parts Illustration (JU Engines) C13513
Parts Illustration (JW/JD Engines) C13340
-
Page 1 of 2
Clarke Installation and Operation Datasheets English to German I&O Data Translator
English Text
Basic Engine Description Engine Manufacturer
Iveco Aifo Ignition Type
Compression (Diesel) Number of Cylinders
Bore and Stroke Displacement Compression Ratio
Valves per Cylinder - Intake - Exhaust Combustion System
Direct Injection Engine Type
In-Line, 4 Stroke Cycle Aspiration
Natural Firing Order (CW Rotation) Charge Air Cooling Type Raw Water Cooled Rotation (Viewed from Front) Clockwise Clockwise Standard Counter-Clockwise
Not Available Engine Crankcase Vent System
Closed Installation Drawing Cooling System Heat Exchanger
Engine H20 Heat Engine Radiated Heat Heat Exchanger Minimum Flow
Raw H20 Heat Exchanger Maximum Cooling H20
Inlet Pressure Flow
Thermostat, Start to Open C (F) Fully Opened Engine Coolant Capacity Coolant Pressure Cap Maximum Engine H20 Temperature Minimum Engine H20 Temperature Cooling System Radiator
Engine H20 Heat Engine Radiated Heat Radiator Minimum Ventilation Flow
Thermostat, Start to Open Fully Opened Engine Coolant Capacity Coolant Pressure Cap Maximum Engine Temperature Minimum Engine Temperature Electric System DC System Voltage (Nominal)
Battery Capacity for Ambients Above 0
Voltage (Nominal) Qty. per Battery Bank
SAE size per Reserve Capacity Minutes Battery Cable Circuit*, Max Resistance - ohm Battery Cable Minimum Size
Circuit* Length Charging Alternator Output Amp Starter Cranking Amps *Positive and Negative Cables Combined Length
Clarke Betriebs-und Wartungshandbuch Englisch zu Deutsch I&O Daten Ubersetzer
German Text
Grundlegende Motorbeschreibung Motorhersteller
Iveco Aifo Art der Zndung
Verdichtung (Diesel) Anzahl der Zylinder Zylinderbohrung und Hub Verdichtungsverhltnis Druck Verhltniss Ventile pro Zylinder Ansaugen
Abgas Verbrennungssystem
Direkteinspritzung Motortyp
Reihenbauweise, Hubzyklus Ansaugung
Direkt Zndfolge (Drehung im Uhrzeigersinn) Luft Khlung Typ Roh Wasser Khlung Drehung (von vorn gesehen)
Im Uhrzeigersinn Standard Im Gegenuhrzeigersinn
Nicht verfgbar Belftungssystem Kurbelwellengehuse
Geschlossen Installationszeichnung
Khlsystem - Wrmetauscher Motor H20 Wrme Vom Motor abgestrahlte Wrme Mindeststrmung Wrmetauscher
Roh H20 Maximalkhlung Wrmetauscher H20
Eingangsdruck Strmung
Thermostat Starten zum ffnen C (F) degrees Voll geffnet
Motorkhlmittelmenge Khlmitteldruckdose Maximalmotor H20 temperatur Mindestmotor H20 temperatur
Khlsystem Khler Motor H20 Wrme Vom Motor abgestrahlte Wrme Khler Mindestluftstrom Thermostat Starten zum ffnen
Voll geffnet Motorkhlmittelmenge Khlmitteldruckdose Maximalmotortemperatur Mindestmotortemperatur
Elektrosystem Gleichstrom Systemspannung (Nennspannung) Batteriekapazitt fr Ambient uber** 0 Degress Umgebungsbedingungen
Spannung (Nennspannung) Menge pro Batteriespeicher
SAE Gre pro Reservekapazitt Minuten
Batteriekabelkreis* - Maximaler Widerstand Ohm Mindestgre Batteriekabel Stromkreis*lnge Ausgang Ladealternator - Ampere Ampere Anlasserkurbel
*Gesamtlnge positive nd negative Kabel
-
Page 2 of 2
Clarke Installation and Operation Datasheets English to German I&O Data Translator
English Text
(Continued) NOTE: This engine is Intended for Indoor Installation Or In a Weatherproof Enclosure. Exhaust System Exhaust Flow Exhaust Temperature Maximum Allowable Back Pressure Minimum Exhaust Pipe Dia. Fuel System
Fuel Consumption Fuel Return Total Supply Fuel Flow Fuel Pressure Minimum Line Size Supply Maximum Line Size Return Maximum Allowable Fuel Pump Suction With Clean Filter Maximum Allowable Fuel Head above Fuel Pump, Supply or Return
Fuel Filter Micron Size Heater System Jacket Water Heater
Optional Wattage (Nominal) Voltage AC, 1P Optional Voltage AC, 1P
Lube Oil Heater Wattage (Required Option When Ambient is Below)
Induction Air System Air Cleaner Type
Canister Dry Type Drip Proof Air Intake Restriction Maximum Limit
Dirty Air Cleaner Clean Air Cleaner
Engine Air Flow Maximum Allowable Temperature (Air to Engine Inlet)
Lubrication System
Oil Pressure normal In Pan Oil Temperature Oil Pan Capacity High Total Oil Capacity with Filter
Performance BMEP Piston Speed Sound Pressure Level Power Curve
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherence To System Limitations. (Minimum Exhaust pipe Diameter is based on 1m of flexible section, 2m of rigid section, 1 90 elbow, and a silencer (as supplied by Clarke). *** Review for Power Deration If Air Entering Engine Exceeds 25C (77 F)
Clarke Betriebs-und Wartungshandbuch Englisch zu Deutsch I&O Daten Ubersetzer
German Text
Fortsetzung HINWEIS: Diese Maschine ist fr Installation im Raum oder in einem wettergeschtzten Gehuse bestimmt. Abgassystem Abgasstrom Abgastemperatur Maximal zulssiger Gegendruck
Mindestauspuffrohrdurchmesser Kraftstoffsystem Kraftstoffverbrauch Kraftstoffrckfluss Gesamtzufuhrstrmung Kraftstoff Kraftstoffdruck Mindestleitungsgre Zufuhr Maximalleitungsgre Rcklauf Maximal zulssige Kraftsstoffpumpensaugkraft mit sauberem Filter
Maximal zulssiger Kraftstoffdruck ber der Kraftstoffpumpe, Zufuhr oder Rcklauf Mikrongre Kraftstofffilter
Erhitzersystem Mantelwassererhitzer
Optional Wattleistung (Nennwert) Spannung Wechselstrom, 1P Optionale Spannung Wechselstrom, 1P
Schmierlerhitzer Wattleistung (erforderliche Option wenn Umgebungsbedingungen darunter liegen)
Induktionsluftsystem Luftfiltertyp
Kanister-Trockentyp tropfsicher Maximalgrenze fr Ansaugluftbegrenzung Schmutziger Luftfilter Sauberer Luftfilter Motorluftdurchsatz
Maximal zulssige Temperatur (Luft zum Motoreingang)
Schmiersystem ldruck normalen ltemperatur in der Wanne lwannenkapazitt hoch Gesamtlmenge mit Filter
Leistung BMEP Kolbendrehzahl Schalldruckpegel Leistungskurve
*Basierend auf Nennsystem. Strmungsanalyse muss durchgefhrt werden, um Einhaltung der Systembegrenzungen zu gewhrleisten. (Mindestauspuffrohrdurchmesser basiert auf 1 m flexiblem Stck, 2 m starrem Stck, einem 90 Krmmer und einem Schalldmpfer (wie von Clarke geliefert). *** Prfe auf Leistungsabminderung wenn die in den Motor eindringende Luft berschreitet
C13973 rev A
-
Page 1 of 2
Clarke Installation and Operation Datasheets English to Spanish I&O Data Translator
English Text
Basic Engine Description Engine Manufacturer
Iveco Aifo Ignition Type
Compression (Diesel) Number of Cylinders
Bore and Stroke Displacement Compression Ratio
Valves per Cylinder - Intake - Exhaust Combustion System
Direct Injection Engine Type
In-Line, 4 Stroke Cycle Aspiration
Natural Firing Order (CW Rotation) Charge Air Cooling Type Raw Water Cooled Rotation (Viewed from Front) Clockwise Clockwise Standard Counter-Clockwise
Not Available Engine Crankcase Vent System
Closed Installation Drawing Cooling System Heat Exchanger
Engine H20 Heat Engine Radiated Heat Heat Exchanger Minimum Flow
Raw H20 Heat Exchanger Maximum Cooling H20
Inlet Pressure Flow
Thermostat, Start to Open C (F) Fully Opened Engine Coolant Capacity Coolant Pressure Cap Maximum Engine H20 Temperature Minimum Engine H20 Temperature Cooling System Radiator
Engine H20 Heat Engine Radiated Heat Radiator Minimum Ventilation Flow
Thermostat, Start to Open Fully Opened Engine Coolant Capacity Coolant Pressure Cap Maximum Engine Temperature Minimum Engine Temperature Electric System DC System Voltage (Nominal)
Battery Capacity for Ambients Above 0
Voltage (Nominal) Qty. per Battery Bank
SAE size per Reserve Capacity Minutes Battery Cable Circuit*, Max Resistance - ohm Battery Cable Minimum Size
Circuit* Length Charging Alternator Output Amp Starter Cranking Amps *Positive and Negative Cables Combined Length NOTE: This engine is Intended for Indoor Installation Or In A Wetherproof Enclosure.
Hoja de Datos de Instalacin y Operacin de Clarke Traductor de Datos de I&O del Ingls al Alemn
Texto en Espaol
Descripcin de Motor Bsico Fabricante del Motor
Iveco Aifo Tipo de Ignicin
Compresin (Diesel) Nmero de Cilindros Dimetro y Carrera Desplazamiento Relacin de Compresin Vlvulas por Cilindro - Admisin
- Escape Sistema de Combustin
Inyeccin Directa Tipo de Motor
En Lnea, Ciclo de Carrera Aspiracin
Natural Orden de Encendido (Rotacin en sentido contrario a las manecillas del reloj)
Rotacin (Vista desde la parte delantera) Estndar Sentido contrario a las manecillas del reloj No Disponible Sistema de Ventilacin del Crter del Motor Cerrado Diagrama de Instalacin Sistema de Enfriamiento - Intercambiador de Calor Calor de Motor Calor Irradiado por el Motor Flujo Mnimo del Intercambiador de Calor No Tratado Enfriamiento Mximo del Intercambiador de Calor Presin de Entrada Flujo Termostato, Inicio de Abertura Totalmente Abierto Capacidad de Refrigerante del Motor Tapn de Presin del Refrigerante Temperatura Mxima del Motor Temperatura Mnima del Motor Sistema de Enfriamiento - Radiador Calor del Motor Calor Irradiado por el Motor Flujo de Ventilacin Mnimo del Radiador Termostato Inicio de Abertura Totalmente Abierto Capacidad de Refrigerante del Motor Tapn de Presin de Refrigerante Temperatura Mxima del Motor Temperatura Mnima del Motor Sistema Elctrico - DC Voltaje de Sistema (Nominal) Capacidad de Batera para Ambientes que exceden el Voltaje (Nominal) Cantidad por Banco de Bateras Tamao SAE por Capacidad de Reserva - Minutos Circuito de Cable de Batera*, Resistencia Mxima - ohm Tamao Mnimo de Cable de Batera Largo de Circuito* Salida del Alternador - Amp Amperaje de Giro del Arrancador *Largo Combinado de los Cables Positivo y Negativo* NOTA: El motor es para instalacin en interiores o en una Cubierta a Prueba de Intemperie.
-
Page 2 of 2
Clarke Installation and Operation Datasheets English to Spanish I&O Data Translator
English Text
(Continued) Exhaust System Exhaust Flow Exhaust Temperature Maximum Allowable Back Pressure Minimum Exhaust Pipe Dia. Fuel System
Fuel Consumption Fuel Return Total Supply Fuel Flow Fuel Pressure Minimum Line Size Supply Maximum Line Size Return Maximum Allowable Fuel Pump Suction With Clean Filter Maximum Allowable Fuel Head above Fuel Pump, Supply or Return
Fuel Filter Micron Size Heater System Jacket Water Heater
Optional Wattage (Nominal) Voltage AC, 1P Optional Voltage AC, 1P
Lube Oil Heater Wattage (Required Option When Ambient is Below)
Induction Air System Air Cleaner Type
Canister Dry Type Drip Proof Air Intake Restriction Maximum Limit
Dirty Air Cleaner Clean Air Cleaner
Engine Air Flow Maximum Allowable Temperature (Air to Engine Inlet)
Lubrication System
Oil Pressure normal In Pan Oil Temperature Oil Pan Capacity High Total Oil Capacity with Filter
Performance
BMEP Piston Speed Sound Pressure Level Power Curve
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherence To System Limitations. (Minimum Exhaust pipe Diameter is based on 1m of flexible section, 2m of rigid section, 1 90 elbow, and a silencer (as supplied by Clarke). *** Review for Power Deration If Air Entering Engine Exceeds 25C (77 F)
Hoja de Datos de Instalacin y Operacin de Clarke Traductor de Datos de I&O del Ingls al Alemn
Texto en Espaol
(Contina) Sistema de Escape Flujo de Escape Temperatura de Escape Contrapresin Mxima Permitida Dimetro mnimo de Tubo de Escape Sistema de Combustible Consumo de Combustible Retorno de Combustible Flujo Total de Suministro de Combustible Presin de Combustible Tamao Mnimo de Lnea - Suministro Tamao Mximo de Lnea - Retorno Mxima Succin Permitida de la Bomba de Combustible Con Filtro Limpio
Mxima Presin Permitida del Combustible Permitida de la Bomba, Suministro o Retorno
Tamao en Micras del Filtro de Combustible Sistema Calentador Calentador de Agua de Chaqueta Opcional Wattaje (Nominal) Voltaje - A.C., 1P Voltaje Opcional - AC, 1P Wattaje de Calentador de Aceite Lubricante (Opcin Requerida cuando el Ambiente es Inferior a) Sistema de Aire de Induccin Tipo de Purificador de Aire De Tipo Seco de Recipiente - A Prueba de Escurrimiento Lmite Mximo de Restriccin de Aire Purificador de Aire Sucio Purificador de Aire Limpio Flujo de Aire de Motor Temperatura Mxima Permitida (Entrada de Aire al Motor) Sistema de Lubricacin Presin de Aceite - Normal Temperatura de Aceite del Colector Capacidad del Colector de Aceite - Alta Capacidad Total de Aceite con Filtro Operacin BMEP Velocidad de Pistones Nivel de Presin de Sonido Curva de Potencia **Basado en un Sistema Nominal - El anlisis del flujo deber analizarse para asegurarse que hay apego a las limitaciones del sistema. (El dimetro mnimo de tubo de escape se basa en 1m de seccin flexible, 2m de seccin rgida, 1 codo de 900 y un silenciador (suministrado por Clarke). ***Revise la reduccin de potencia si el aire que ingresa al motor excede
C13986 rev A
-
Page 1 sur 2
Clarke Installation and Operation Datasheets Fiches techniques dinstallation et dutilisation de Clarke English to French-Canadian I&O Data Translator Traducteur Anglais > Franais des donnes d'installation et d'utilisation
English Text Basic Engine Description
Engine Manufacturer John Deere Co.
Ignition Type Compression (Diesel)
Number of Cylinders Bore and Stroke Displacement Compression Ratio
Valves per Cylinder - Intake - Exhaust Combustion System
Direct Injection Engine Type
In-Line, 4 Stroke Cycle Aspiration
Naturally Aspirated Turbocharged
Firing Order (CW Rotation) Charge Air Cooling Type
None Raw Water Cooled
Jacket Water Cooled Rotation (Viewed from Front) Clockwise
Standard Counter-Clockwise
Not Available Engine Crankcase Vent System
Open Installation Drawing Cooling System
Engine Heat Engine Radiated Heat Heat Exchanger Minimum Flow
Raw Heat Exchanger Maximum Cooling
Inlet Pressure Flow
Thermostat, Start to Open Fully Opened Engine Coolant Capacity Coolant Pressure Cap Maximum Engine Temperature Minimum Engine Temperature Electric System DC System Voltage (Nominal)
Battery Capacity for Ambients Above Voltage (Nominal)
Qty. per Battery Bank SAE size per J537 Reserve Capacity Minutes Battery Cable Circuit*, Max Resistance - ohm Battery Cable Minimum Size
Circuit* Length Charging Alternator Output Amp Starter Cranking Amps *Positive and Negative Cables Combined Length NOTE: This engine is Intended for Indoor Installation Or In A Weatherproof Enclosure. (Continued)
Texte en franais canadien
Description lmentaire du moteur Fabricant du moteur
John Deere Co. Type dallumage
Compression (Diesel) Nombre de cylindres
Alsage et course Cylindre Rapport de compression
Soupapes par cylindre - Admission - chappement Systme de combustion
Injection directe Type de moteur
En ligne 4 temps Aspiration
Aspiration naturelle Turbocompresseur
Ordre dallumage (rotation anti-horaire) Type de refroidissement air
Aucun Refroidissement eau brute
Refroidissement eau chemise Rotation (vue de lavant) Sens des aiguilles dune montre
Standard Sens inverse des aiguilles dune montre
Non disponible Systme de respiration du carter de moteur
Ouvert Plan dinstallation Systme de refroidissement
Chaleur du moteur Chaleur mise par le moteur coulement minimal de lchangeur de chaleur
Brut Refroidissement maximal de lchangeur de chaleur
Pression dentre coulement
Thermostat, Dbut douverture Ouverture totale Capacit de liquide de refroidissement du moteur Bouchon de radiateur Temprature maximale du moteur Temprature minimale du moteur Systme lectrique courant continu Tension du systme (nominale)
Capacit de la batterie pour les conditions ambiantes ci-dessus Tension (nominale)
Qt. par jeu de batteries Taille SAE selon J537 Capacit de rserve minutes Circuit de cblage de la batterie*, rsistance maximale ohms Taille minimale des cbles de batterie
Longueur du circuit* Courant de sortie de lalternateur de charge ampres Courant de lancement du dmarreur * Longueurs combines des cbles positif et ngatif REMARQUE : Ce moteur est prvu pour une installation en intrieur ou dans un caisson protg des intempries. (suite)
-
Page 2 sur 2
Clarke Installation and Operation Datasheets Fiches techniques dinstallation et dutilisation de Clarke English to French-Canadian I &O Data Translator Traducteur Anglais>Franais des donnes d'installation et d'utilisation
English Text Exhaust System Exhaust Flow Exhaust Temperature
Maximum Allowable Back Pressure Minimum Exhaust Pipe Dia. Fuel System
Fuel Consumption Fuel Return Total Supply Fuel Flow Fuel Pressure Minimum Line Size Supply Maximum Line Size Return Maximum Allowable Fuel Pump Suction With Clean Filter Maximum Allowable Fuel Head above Fuel Pump, Supply or Return
Fuel Filter Micron Size Heater System Jacket Water Heater
Optional Wattage (Nominal) Voltage AC, 1P Optional Voltage AC, 1P
Induction Air System Air Cleaner Type
Indoors Service Only - Washable Air Intake Restriction Maximum Limit
Dirty Air Cleaner Clean Air Cleaner
Engine Air Flow Maximum Allowable Temperature (Air to Engine Inlet)
Lubrication System
Oil Pressure normal In Pan Oil Temperature Oil Pan Capacity High - Low Total Oil Capacity with Filter
Performance
BMEP Piston Speed Mechanical Noise - Power Curve
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherence To System Limitations. (Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer pressure drop no greater than one half the max. allowable back pressure.)
*** Review for Power Deration If Air Entering Engine Exceeds
Texte en franais canadien
Systme dchappement Dbit dchappement Temprature dchappement
Contre-pression maximale admissible Diamtre minimal du tuyau dchappement Systme dalimentation en carburant
Consommation de carburant Retour du carburant Dbit du carburant dalimentation Pression du carburant Taille minimale des conduites alimentation Taille maximale des conduites retour Aspiration maximale admissible de la pompe carburant Avec filtre propre Hauteur de charge de carburant maximale admissible au-dessus de la pompe, alimentation ou retour
Taille du filtre carburant en microns Systme de rchauffage Rchauffage deau chemise
En option Puissance (nominale) Tension alternatif, monophas Tension en option alternatif, monophas
Systme dair dinduction Type de filtre air
Service en intrieur uniquement lavable Limite maximale de la restriction dentre dair
Filtre air sale Filtre air propre
Dbit dair du moteur Temprature maximale admissible (air dentre du moteur)
Systme de lubrification
Pression dhuile normale Temprature de lhuile dans le carter Capacit du carter dhuile niveau lev niveau bas Capacit dhuile totale avec le filtre
Performances
BMEP Vitesse du piston Bruit mcanique - Courbe de puissance
** Bas sur le systme nominal. Une analyse du dbit doit tre effectue pour assurer le respect des limitations du systme. (Le diamtre minimal du tuyau dchappement est bas sur 4,5 m (15 pieds) de tuyau, un coude et une chute de pression dans le silencieux infrieure la moiti de la contre-pression maximale admissible.)
*** Rviser la baisse si lair d'admission du moteur dpasse
C131051 revA
-
CLARKE Fire Protection Products
Basic Engine DescriptionJohn Deere Co.
Ignition Type....Compression (Diesel)Number of Cylinders..4Bore and Stroke - in.(mm)...4.19(106) x 5.00(127)Displacement - in.3 (L)....275 (4.5)Compression Ratio..17.0:1Valves per cylinder - Intake...1
Exhaust...1Combustion System..Direct InjectionEngine Type...Rotary, 4 Stroke CycleAspiration..Naturally AspiratedFiring Order (CW Rotation)...1-3-4-2Charge Air Cooling Type..NoneRotation (Viewed from Front) - Clockwise.Standard
Counter-Clockwise..Not AvailableEngine Crankcase Vent System...OpenInstallation Drawing.D-534Weight - lb (kg)910 (413)
Cooling System 1760 2100 2350 2600Engine H2O Heat -Btu/sec.(kW)...19 (20) 28 (30) 40 (42) 42 (44)Engine Radiated Heat - Btu/sec.(kW)..9 (10) 11 (12) 12 (13) 13 (14)Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)..6 (23) 7 (26) 8 (30) 9 (34)95F (35C) Raw H2O - gal/min. (L/min.)..8 (30) 9 (34) 10 (38) 11 (42)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...........4 (60) (400)Flow - gal./min (L/min.)........ 40 (151)
Thermostat, Start to Open - F (C).187 (86)Fully Opened - F (C)...196 (91)
Engine Coolant Capacity - qt. (L)...15 (14)Coolant Pressure Cap - lb./in.2(kPa)...10 (69)Maximum Engine H20 Temperature - F (C)...200 (93)Minimum Engine H20 Temperature - F (C)...160 (71)
Electric System - DCSystem Voltage (Nominal)...12 (Standard) 24 (Optional)Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)...12 24Qty. per Battery Bank.1 2SAE size per J537...4D-640 4D-640CCA @ 0F (-18C)...640 640Reserve Capacity - Minutes.....285 285
Battery Cable Circuit*, Max Resistance - ohm.......0.0012 0.0012Battery Cable Minimum Size
0 -120 in. Circuit* Length.00 00121 - 160 in. Circuit* Length..000 000161 - 200 in. Circuit* Length..0000 0000Charging Alternator Output - Amp.....40 40Starter Cranking Amps - @ 60F (15C)....380 250
JU4H-UF10 & JU4H-UF12INSTALLATION & OPERATION DATA
*Positive and Negative Cables Combined Length
Engine Manufacturer.
USA Production
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
-
CLARKE Fire Protection Products
Exhaust System 1760 2100 2350 2600Exhaust Flow - ft.3/min. (m3/min.). 379 (11) 415 (12) 469 (13) 531 (15)Exhaust Temperature - F (C)........740 (393) 918 (492) 1083 (584) 1055 (568)Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)Minimum Exhaust Pipe Dia. - in. (mm)**.. 3 (76)
Fuel SystemFuel Consumption - gal./hr. (L/hr.) 2.2 ( 8.3) 2.8 (10.6) 3.1 (11.7) 3.4 (12.9)Fuel Return - gal./hr. (L/hr.) 7.9 (29.9) 8.5 (32.2) 9.0 (34.1) 9.5 (36.0)Total Supply Fuel Flow - gal./hr. (L/hr.) 10.1 (38.2) 11.3 (42.8) 12.1 (45.8) 12.9 (48.9)Fuel Pressure - lb./in.2 (kPa).. 3-6 (21-41)
.50 Schedule 40 Steel PipePipe Outer Diameter in. (mm).......... .848 (0.33)
.375 Schedule 40 Steel PipePipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump SuctionWith Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m).. 4.5 (1.4)Fuel Filter Micron Size 5
Heater SystemJacket Water Heater
Wattage (Nominal)..1500Voltage - AC, 1P..115 (+5%, -10%)Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage(Required Option When Ambient is Below 40F (4C)
Induction Air SystemAir Cleaner TypeIndoors Service Only - WashableAir Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 140 (4.0) 155 (4.4) 166 (4.7) 186 (5.3)Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***. 130 (54)
Lubrication SystemOil Pressure - normal - lb./in.2 (kPa) 35-50 (241-345)In Pan Oil Temperature - F (C).. 220-245 (104-118)Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)Total Oil Capacity with Filter - qt. (L) 9 (8.5)
PerformanceBMEP - lb./in.2 (kPa). 67 (462) 70 (483) 67 (462) 65 (448)Piston Speed - ft./min. (m/min.) 1467 (447) 1750 (533) 1958 (597) 2167 (661)Mechanical Noise - dB(A) @ 1m...........Power Curve
Minimum Line Size - Return - (in.)........
pressure drop no greter than one half the max. allowable back pressure.)
*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)
JU4H-UF10 & JU4H-UF12INSTALLATION & OPERATION DATA (Continued)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations. (Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
C13905 (UF10) & C13906 (UF12)C13646 (UF10) & C13647 (UF12)
USA Production
Minimum Line Size - Supply - (in.)..........
C13663 revJDSP 25FEB08
-
CLARKE Fire Protection Products
Basic Engine DescriptionJohn Deere Co.Compression (Diesel)44.19(106) x 5.00(127) 4.5 (275)17.0:1
Valves per cylinder - 11Direct InjectionRotary, 4 Stroke CycleNaturally Aspirated1-3-4-2
Rotation (Viewed from Front) - StandardNot AvailableOpenD-545
Cooling System - 3 Pass 1760 2100 2350 260020 (19) 30 (28) 42 (40) 44 (42)
10.0 (9.0) 12.0 (11.0) 13.0 (12.0) 14.0 (13.0)
15 (4) 23 (6) 30 (8) 38 (10)
23 (6) 30 (8) 38 (10) 45 (12)
4 (60) (400)100 (26)
Thermostat, 86 (187)91 (196)14 (15)69 (10)93 (200)
71 (160)
Electric System - DC12 24
12 241 24D-640 4D-640640 640285 2850.0012 0.0012
0 -120 m 00 00121 - 160 m 000 000161 - 200 m 0000 0000
40 40380 250
JU4H-UF10 & JU4H-UF12 INSTALLATION & OPERATION DATA
*Positive and Negative Cables Combined Length
Engine Manufacturer....Ignition Type......................Number of Cylinders.............Bore and Stroke - mm (in.)..........Displacement - L (in.3)..........Compression Ratio............
Intake............Exhaust............
Combustion System............Engine Type..............Aspiration..............Firing Order (CW Rotation)..........
Clockwise........Counter-Clockwise..............
Engine Crankcase Vent System........Installation Drawing..........
Engine H2O Heat - kW (Btu/sec)..........Engine Radiated Heat - kW (Btu/sec).........Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
35C (95F) Raw H2O - L/min. (gal/min.)......
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........Flow - L/min. (gal./min)...........
Start to Open - C (F).........Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.)..........Coolant Pressure Cap - kPa (lb./in.2).......Maximum Engine H20 Temperature - C (F)......
Minimum Engine H20 Temperature - C (F).....
System Voltage (Nominal).........Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................Qty. per Battery Bank..........SAE size per J537............
UK Production
Starter Cranking Amps - @ 15C (60F).........
Circuit* Length............Circuit* Length.............Circuit* Length.............
Charging Alternator Output - Amp..........
CCA @ -18C (0F)..............Reserve Capacity - Minutes............
Battery Cable Circuit*, Max Resistance - ohm...........Battery Cable Minimum Size
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
-
CLARKE Fire Protection Products
Exhaust System 1760 2100 2350 260011.0 (379) 12.0 (415) 13.0 (469) 15.0 (531)393 (740) 492 (918) 584 (1083) 568 (1055)7.4 (30)76 (3)
Fuel System8.3 (2.2) 10.6 (2.8) 11.7 (3.1) 12.9 (3.4)
29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)38.2 (10.1) 42.8 (11.3) 45.8 (12.1) 48.9 (12.9)21-41 (3-6) .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).................. .033 (.848) .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).................. .026 (.675)
0.8 (31)1.4 (4.5)
5
Heater System
1500 115 (+5%, -10%) 230 (+5%, -10%)
Induction Air SystemIndoors Service Only - Washable
2.5 (10)1.2 (5)
4.0 (140) 4.4 (155) 4.7 (166) 5.3 (186)54 (130)
Lubrication SystemOil Pressure - normal - kPa (lb./in.2)....... 241-345 (35-50)In Pan Oil Temperature - C (F)......... 104-118 (220-245)Oil Pan Capacity - High - L (qt.)........ 8 (7.5)
Low - L (qt.).. 7 (6.5)Total Oil Capacity with Filter - L (qt.)... 9 (8.5)
Performance4.8 (67) 4.9 (70) 4.8 (67) 4.5 (65)
447 (1467) 533 (1750) 597 (1958) 661 (2167)
pressure drop no greater than one half the max. allowable back pressure.)
*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)
Mechanical Noise - dB(A) @ 1m.............Power Curve................
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations. (Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
Minimum Line Size - Return - (in.)................
Consult FactoryC131933 (UF10) C131934 (UF12)
Maximum Allowable Fuel Pump SuctionWith Clean Filter - m H20 (in. H20).........
Piston Speed - m/min. (ft./min.)..........
Engine Air Flow - m3/min. (ft.3/min.)........Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
Air Cleaner Type.........
BMEP - kg/cm2 (lb./in.2).............
Fuel Return - L/hr. (gal./hr.)...........Total Supply Fuel Flow - L/hr (gal./hr.)...........Fuel Pressure - kPa (lb./in.2)...........Minimum Line Size - Supply - (in.)..........
JU4H-UF10 & JU4H-UF12 INSTALLATION & OPERATION DATA (Continued)
UK Production
Fuel Consumption - L/hr. (gal./hr.).............
Exhaust Flow - m3/min. (ft.3/min.).............Exhaust Temperature - C (F)...............Maximum Allowable Back Pressure - kPa (in. H20)....Minimum Exhaust Pipe Dia. - mm (in.)**..........
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)....Fuel Filter Micron Size................
Jacket Water HeaterWattage (Nominal)..............
Air Intake Restriction Maximum LimitDirty Air Cleaner - kPa (in. H20)............Clean Air Cleaner - kPa (in. H20)...........
Voltage - AC, 1P.............Optional Voltage - AC, 1P..........
C131234 revF16AUG07 DSP
-
CLARKE Fire Protection Products
Basic Engine DescriptionJohn Deere Co.Compression (Diesel)4106 (4.19) x 127 (5.00)4.5 (275)17.0:1
Valves per cylinder - 11Direct InjectionRotary, 4 Stroke CycleNaturally Aspirated1-3-4-2
Rotation (Viewed from Front) - StandardNot AvailableOpenD-545
Cooling System - 3 Pass 2350 2600 2800 300032 (30) 34 (32) 36 (34) 38 (36)12 (13) 13 (14) 14 (15) 15 (16)
30 (8) 34 (9) 37 (10) 40 (11)38 (10) 42 (11) 45 (12) 48 (13)
4 (60) (400)100 (26)
Thermostat, 86 (187)91 (196)14 (15)69 (10)93 (200)71 (160)
Electric System - DC12 24
12 241 24D-640 4D-640640 640285 2850.0012 0.0012
0 -120 m 00 00121 - 160 m 000 000161 - 200 m 0000 0000
40 40380 250
UK Production
Starter Cranking Amps - @ 15C (60F).......
Circuit* Length.......Circuit* Length..........Circuit* Length..........
Charging Alternator Output - Amp.......
CCA @ -18C (0F)...........Reserve Capacity - Minutes........
Battery Cable Circuit*, Max Resistance - ohm.........Battery Cable Minimum Size
Battery Capacity for Ambients Above 0C (32F)Voltage (Nominal)...........Qty. per Battery Bank.........SAE size per J537...........
Coolant Pressure Cap - kPa (lb./in.2)......Maximum Engine H20 Temperature - C (F)......Minimum Engine H20 Temperature - C (F).....
System Voltage (Nominal)........
Flow - L/min. (gal./min).........Start to Open - C (F)......Fully Opened - C (F)......
Engine Coolant Capacity - L (qt.).........
15C (60F) Raw H2O - L/min. (gal/min.)....35C (95F) Raw H2O - L/min. (gal/min.)....
Heat Exchanger Maximum Cooling H2OInlet Pressure - bar (lb./in.2) (kPa).......
Installation Drawing.........
Engine H2O Heat - kW (Btu/sec)........Engine Radiated Heat - kW (Btu/sec).......Heat Exchanger Minimium Flow
Firing Order (CW Rotation).........Clockwise.......Counter-Clockwise.....
Engine Crankcase Vent System........
Exhaust...........Combustion System..........Engine Type............Aspiration.............
JU4H-UF14 INSTALLATION & OPERATION DATA
*Positive and Negative Cables Combined Length
Engine Manufacturer....Ignition Type.....................Number of Cylinders.............Bore and Stroke - mm (in.).........Displacement - L (in.3)..........Compression Ratio..........
Intake...........
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
-
CLARKE Fire Protection Products
Exhaust System 2350 2600 2800 300013 (469) 15 (531) 16 (581) 18 (630)
584 (1083) 568 (1055) 556 (1033) 543 (1010)7.5 (30)76 (3)
Fuel System11.7 (3.1) 12.9 (3.4) 13.6 (3.6) 14.8 (3.9)34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
45.8 (12.1) 48.9 (12.9) 51.1 (13.5) 53.8 (14.2) 21-41 (3-6) .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)............ .033 (.848) .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)............ .026 (.675)
0.8 (31) 1.4 (4.5) 2
Heater System
1500 115 (+5%, -10%) 230 (+5%, -10%)
Induction Air SystemIndoors Service Only - Washable
2.5 (10)1.2 (5)
4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)54 (130)
Lubrication SystemOil Pressure - normal - kPa (lb./in. 2).......... 241-345 (35-50)In Pan Oil Temperature - C (F)............. 104-118 (220-245)Oil Pan Capacity - High - L (qt.)........... 7.5 (8)
Low - L (qt.).... 6.5 (7)Total Oil Capacity with Filter - L (qt.)........ 8.5 (9)
Performance462 (67) 448 (65) 437 (63) 426 (62)
597 (1958) 661 (2167) 711 (2333) 762 (2500)Mechanical Noise - dB(A) @ 1m.............
UK Production
Consult FactoryC131943Power Curve..............
BMEP - kPA (lb./in.2)............Piston Speed - m/min (ft./min.).........
Engine Air Flow - m3/min. (ft. 3/min.)........Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
Air Cleaner Type...........Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)............Clean Air Cleaner - kPa (in. H20).........
Voltage - AC, 1P............Optional Voltage - AC, 1P.........
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)...Fuel Filter Micron Size...........
Jacket Water HeaterWattage (Nominal)............
Fuel Consumption - L/hr. (gal.hr).........Fuel Return - L/hr. (gal./hr.).......Total Supply Fuel Flow - L/hr. (gal./hr).......Fuel Pressure - kPa (lb./in.2)............Minimum Line Size - Supply - (in.).........
Minimum Line Size - Return - (in.)..........
Maximum Allowable Fuel Pump SuctionWith Clean Filter - m H 20 (in. H20).......
pressure drop no greater than one half the max. allowable back pressure.)
*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)
JU4H-UF14 INSTALLATION & OPERATION DATA (Continued)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations. (Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
Exhaust Flow - m3/min. (ft. 3/min.)........Exhaust Temperature - C (F)...........Maximum Allowable Back Pressure - kPa (in. H20)...Minimum Exhaust Pipe Dia. - mm (in.)**........
C131263 revF18DEC07 DSP
-
CLARKE Fire Protection Products
Basic Engine DescriptionJohn Deere Co.Compression (Diesel)4106 (4.19) x 127 (5.00)4.5 (275)17.0:1
Valves per cylinder - 11Direct InjectionRotary, 4 Stroke CycleNaturally Aspirated1-3-4-2
Rotation (Viewed from Front) - StandardNot AvailableOpenD-545
Cooling System - 3 Pass 2350 2600 2800 300032 (30) 34 (32) 36 (34) 38 (36)12 (13) 13 (14) 14 (15) 15 (16)
30 (8) 34 (9) 37 (10) 40 (11)38 (10) 42 (11) 45 (12) 48 (13)
4 (60) (400)100 (26)
Thermostat, 86 (187)91 (196)14 (15)69 (10)93 (200)71 (160)
Electric System - DC12 24
12 241 24D-640 4D-640640 640285 2850.0012 0.0012
0 -120 m 00 00121 - 160 m 000 000161 - 200 m 0000 0000
40 40380 250
UK Production
Starter Cranking Amps - @ 15C (60F).......
Circuit* Length.......Circuit* Length..........Circuit* Length..........
Charging Alternator Output - Amp.......
CCA @ -18C (0F)...........Reserve Capacity - Minutes........
Battery Cable Circuit*, Max Resistance - ohm.........Battery Cable Minimum Size
Battery Capacity for Ambients Above 0C (32F)Voltage (Nominal)...........Qty. per Battery Bank.........SAE size per J537...........
Coolant Pressure Cap - kPa (lb./in.2)......Maximum Engine H20 Temperature - C (F)......Minimum Engine H20 Temperature - C (F).....
System Voltage (Nominal)........
Flow - L/min. (gal./min).........Start to Open - C (F)......Fully Opened - C (F)......
Engine Coolant Capacity - L (qt.).........
15C (60F) Raw H2O - L/min. (gal/min.)....35C (95F) Raw H2O - L/min. (gal/min.)....
Heat Exchanger Maximum Cooling H2OInlet Pressure - bar (lb./in.2) (kPa).......
Installation Drawing.........
Engine H2O Heat - kW (Btu/sec)........Engine Radiated Heat - kW (Btu/sec).......Heat Exchanger Minimium Flow
Firing Order (CW Rotation).........Clockwise.......Counter-Clockwise.....
Engine Crankcase Vent System........
Exhaust...........Combustion System..........Engine Type............Aspiration.............
JU4H-UF14 INSTALLATION & OPERATION DATA
*Positive and Negative Cables Combined Length
Engine Manufacturer....Ignition Type.....................Number of Cylinders.............Bore and Stroke - mm (in.).........Displacement - L (in.3)..........Compression Ratio..........
Intake...........
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
-
CLARKE Fire Protection Products
Exhaust System 2350 2600 2800 300013 (469) 15 (531) 16 (581) 18 (630)
584 (1083) 568 (1055) 556 (1033) 543 (1010)7.5 (30)76 (3)
Fuel System11.7 (3.1) 12.9 (3.4) 13.6 (3.6) 14.8 (3.9)34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
45.8 (12.1) 48.9 (12.9) 51.1 (13.5) 53.8 (14.2) 21-41 (3-6) .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)............ .033 (.848) .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)............ .026 (.675)
0.8 (31) 1.4 (4.5) 2
Heater System
1500 115 (+5%, -10%) 230 (+5%, -10%)
Induction Air SystemIndoors Service Only - Washable
2.5 (10)1.2 (5)
4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)54 (130)
Lubrication SystemOil Pressure - normal - kPa (lb./in. 2).......... 241-345 (35-50)In Pan Oil Temperature - C (F)............. 104-118 (220-245)Oil Pan Capacity - High - L (qt.)........... 7.5 (8)
Low - L (qt.).... 6.5 (7)Total Oil Capacity with Filter - L (qt.)........ 8.5 (9)
Performance462 (67) 448 (65) 437 (63) 426 (62)
597 (1958) 661 (2167) 711 (2333) 762 (2500)Mechanical Noise - dB(A) @ 1m.............
UK Production
Consult FactoryC131943Power Curve..............
BMEP - kPA (lb./in.2)............Piston Speed - m/min (ft./min.).........
Engine Air Flow - m3/min. (ft. 3/min.)........Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
Air Cleaner Type...........Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)............Clean Air Cleaner - kPa (in. H20).........
Voltage - AC, 1P............Optional Voltage - AC, 1P.........
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)...Fuel Filter Micron Size...........
Jacket Water HeaterWattage (Nominal)............
Fuel Consumption - L/hr. (gal.hr).........Fuel Return - L/hr. (gal./hr.).......Total Supply Fuel Flow - L/hr. (gal./hr).......Fuel Pressure - kPa (lb./in.2)............Minimum Line Size - Supply - (in.).........
Minimum Line Size - Return - (in.)..........
Maximum Allowable Fuel Pump SuctionWith Clean Filter - m H 20 (in. H20).......
pressure drop no greater than one half the max. allowable back pressure.)
*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)
JU4H-UF14 INSTALLATION & OPERATION DATA (Continued)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations. (Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
Exhaust Flow - m3/min. (ft. 3/min.)........Exhaust Temperature - C (F)...........Maximum Allowable Back Pressure - kPa (in. H20)...Minimum Exhaust Pipe Dia. - mm (in.)**........
C131263 revF18DEC07 DSP
-
CLARKE Fire Protection Products
Basic Engine DescriptionJohn Deere Co.
Ignition Type....Compression (Diesel)Number of Cylinders..4Bore and Stroke - in.(mm)...4.19(106) x 5.00(127)Displacement - in.3 (L)....275 (4.5)Compression Ratio..17.0:1Valves per cylinder - Intake...1
Exhaust...1Combustion System..Direct InjectionEngine Type...Rotary, 4 Stroke CycleAspiration.. Naturally AspiratedFiring Order (CW Rotation)...1-3-4-2Charge Air Cooling Type..NoneRotation (Viewed from Front) - Clockwise.Standard
Counter-Clockwise..Not AvailableEngine Crankcase Vent System...OpenInstallation Drawing.D-534Weight- lb (kg)910 (413)
Cooling System 1760 2100 2350 2600Engine H2O Heat -Btu/sec.(kW)...19 (20) 28 (30) 40 (42) 42 (44)Engine Radiated Heat - Btu/sec.(kW)..13 (14) 15 (16) 16 (17) 17 (18)Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)..6 (23) 7 (26) 8 (30) 9 (34)95F (35C) Raw H2O - gal/min. (L/min.)..8 (30) 9 (34) 10 (38) 11 (42)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)....... 4 (60) (400)Flow - gal./min (L/min.).... 40 (151)
Thermostat, Start to Open - F (C).187 (86)Fully Opened - F (C)...196 (91)
Engine Coolant Capacity - qt. (L)...15 (14)Coolant Pressure Cap - lb./in.2(kPa)...10 (69)Maximum Engine H20 Temperature - F (C)...200 (93)Minimum Engine H20 Temperature - F (C)...160 (71)
Electric System - DCSystem Voltage (Nominal)...12(Standard) 24(Optional)Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)...12 24Qty. per Battery Bank.1 2SAE size per J537...4D-640 4D-640CCA @ 0F (-18C)...640 640Reserve Capacity - Minutes.....285 285
Battery Cable Circuit*, Max Resistance - ohm.......0.0012 0.0012Battery Cable Minimum Size
0 -120 in. Circuit* Length.00 00121 - 160 in. Circuit* Length..000 000161 - 200 in. Circuit* Length..0000 0000Charging Alternator Output - Amp.....40 40Starter Cranking Amps - @ 60F (15C)....380 250
JU4H-UF20 & JU4H-UF22INSTALLATION & OPERATION DATA
*Positive and Negative Cables Combined Length
Engine Manufacturer.
USA Production
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
-
CLARKE Fire Protection Products
Exhaust System 1760 2100 2350 2600Exhaust Flow - ft.3/min. (m3/min.). 379 (11) 415 (12) 469 (13) 531 (15)Exhaust Temperature - F (C)........1021 (549) 1016 (547) 1076 (580) 1095 (591)Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)Minimum Exhaust Pipe Dia. - in. (mm)**.. 3 (76)
Fuel SystemFuel Consumption - gal./hr. (L/hr.) 3.8 (14.4) 5.3 (20.1) 5.6 (21.2) 5.8 (22.0)Fuel Return - gal./hr. (L/hr.) 7.9 (29.9) 8.5 (32.2) 9.0 (34.1) 9.5 (36.0)Total Supply Fuel Flow - gal./hr. (L/hr.) 11.7 (44.3) 13.8 (52.3) 14.6 (55.3) 15.3 (58.0)Fuel Pressure - lb./in.2 (kPa).. 3-6 (21-41)
.50 Schedule 40 Steel PipePipe Outer Diameter in. (mm).......... .848 (0.33)
.375 Schedule 40 Steel PipePipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump SuctionWith Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)Fuel Filter Micron Size 5
Heater SystemJacket Water Heater
Wattage (Nominal)..1500Voltage - AC, 1P..115 (+5%, -10%)Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage(Required Option When Ambient is Below 40F (4C)
Induction Air SystemAir Cleaner TypeIndoors Service Only - WashableAir Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 140 (4.0) 155 (4.4) 166 (4.7) 186 (5.3)Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***.130 (54)
Lubrication SystemOil Pressure - normal - lb./in.2 (kPa) 35-50 (241-345)In Pan Oil Temperature - F (C).. 220-245 (104-118)Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)Total Oil Capacity with Filter - qt. (L) 9 (8.5)
PerformanceBMEP - lb./in.2 (kPa). 98 (677) 92 (634) 88 (608) 83 (573)Piston Speed - ft./min. (m/min.) 1467 (447) 1750 (533) 1958 (597) 2167 (661)Mechanical Noise - dB(A) @ 1m...........Power Curve
Minimum Line Size - Supply - (in.)..........
pressure drop no greter than one half the max. allowable back pressure.)
*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)
JU4H-UF20 & JU4H-UF22INSTALLATION & OPERATION DATA (Continued)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations. (Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
C13907 (UF20) & C13908 (UF22) C13476 (UF20) & C13561 (UF22)
USA Production
Minimum Line Size - Return - (in.)........
C13611 rev JDSP 25FEB08
-
CLARKE Fire Protection Products
Basic Engine DescriptionJohn Deere Co.Compression (Diesel)44.19(106) x 5.00(127) 4.5 (275)17.0:1
Valves per cylinder - 11Direct InjectionRotary, 4 Stroke CycleNaturally Aspirated1-3-4-2
Rotation (Viewed from Front) - StandardNot AvailableOpenD-545
Cooling System - 3 Pass 1760 2100 2350 260020 (19) 30 (28) 42 (40) 44 (42)
14.0 (13.0) 16.0 (15.0) 17.0 (16.0) 18.0 (17.0)
15 (4) 23 (6) 30 (8) 38 (10)
23 (6) 30 (8) 38 (10) 45 (12)
4 (60) (400)100 (26)
Thermostat, 86 (187)91 (196)14 (15)69 (10)93 (200)
71 (160)
Electric System - DC12 24
12 241 24D-640 4D-640640 640285 2850.0012 0.0012
0 -120 m 00 00121 - 160 m 000 000161 - 200 m 0000 0000
40 40380 250
Battery Cable Minimum Size
Starter Cranking Amps - @ 15C (60F).........
Circuit* Length............Circuit* Length.............Circuit* Length.............
Charging Alternator Output - Amp..........
SAE size per J537............CCA @ -18C (0F)..............Reserve Capacity - Minutes............
Battery Cable Circuit*, Max Resistance - ohm...........
System Voltage (Nominal).........Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................Qty. per Battery Bank..........
Engine Coolant Capacity - L (qt.)..........Coolant Pressure Cap - kPa (lb./in.2).......Maximum Engine H20 Temperature - C (F)......
Minimum Engine H20 Temperature - C (F).....
Inlet Pressure - bar (lb./in.2) (kPa).........Flow - L/min. (gal./min)...........
Start to Open - C (F).........Fully Opened - C (F).............
Heat Exchanger Minimium Flow15C (60F) Raw H2O - L/min. (gal/min.)......
35C (95F) Raw H2O - L/min. (gal/min.)......
Heat Exchanger Maximum Cooling H2O
Engine Crankcase Vent System........Installation Drawing..........
Engine H2O Heat - kW (Btu/sec)..........Engine Radiated Heat - kW (Btu/sec).........
Aspiration..............Firing Order (CW Rotation)..........
Clockwise........Counter-Clockwise..............
Intake............Exhaust............
Combustion System............Engine Type..............
UK Production
JU4H-UF20 & JU4H-UF22 INSTALLATION & OPERATION DATA
*Positive and Negative Cables Combined Length
Engine Manufacturer....Ignition Type......................Number of Cylinders.............Bore and Stroke - mm (in.)..........Displacement - L (in.3)..........Compression Ratio............
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
-
CLARKE Fire Protection Products
Exhaust System 1760 2100 2350 260011.0 (379) 12.0 (415) 13.0 (469) 15.0 (531)549 (1021) 547 (1016) 580 (1076) 591 (1095)
7.4 (30) 76 (3)
Fuel System14.4 (3.8) 20.1 (5.3) 21.2 (5.6) 22.0 (5.8)29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)44.3 (11.7) 52.3 (13.8) 55.3 (14.6) 58.0 (15.3)
21-41 (3-6) .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).................. .033 (.848) .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).................. .026 (.675)
0.8 (31) 1.4 (4.5) 5
Heater System
1500 115 (+5%, -10%) 230 (+5%, -10%)
Induction Air SystemIndoors Service Only - Washable
2.5 (10)1.2 (5)
4.0 (140) 4.4 (155) 4.7 (166) 5.3 (186)54 (130)
Lubrication SystemOil Pressure - normal - kPa (lb./in.2)........241-345 (35-50)In Pan Oil Temperature - C (F)..........104-118 (220-245)Oil Pan Capacity - High - L (qt.).........8 (7.5)
Low - L (qt.).. 7 (6.5)Total Oil Capacity with Filter - L (qt.).... 9 (8.5 )
Performance6.9 (98) 6.5 (92) 6.1 (88) 5.9 (83)
447 (1467) 533 (1750) 597 (1958) 661 (2167)Mechanical Noise - dB(A) @ 1m............. Consult Factory
C131935 (UF20) & C131936 (UF22)Power Curve................
BMEP - kg/cm2 (lb./in.2).............Piston Speed - m/min. (ft./min.)..........
Engine Air Flow - m3/min. (ft.3/min.)........Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
Air Cleaner Type..........Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20).............Clean Air Cleaner - kPa (in. H20)............
Optional Voltage - AC, 1P..........
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)..........Fuel Filter Micron Size..........
Jacket Water HeaterWattage (Nominal)..............
*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations. (Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
Exhaust Flow - m3/min. (ft.3/min.)...........Exhaust Temperature - C (F).............Maximum Allowable Back Pressure - kPa (in. H20)...Minimum Exhaust Pipe Dia. - mm (in.)**.........
Minimum Line Size - Supply - (in.).............
Minimum Line Size - Return - (in.).............
Maximum Allowable Fuel Pump Suction
JU4H-UF20 & JU4H-UF22 INSTALLATION & OPERATION DATA (Continued)
UK Production
pressure drop no greater than one half the max. allowable back pressure.)
With Clean Filter - m H20 (in. H20)........
Fuel Consumption - L/hr. (gal./hr.)............Fuel Return - L/hr. (gal./hr.)..........Total Supply Fuel Flow - L/hr (gal./hr.)..........Fuel Pressure - kPa (lb./in.2)...........
Voltage - AC, 1P.............
C131235 revF16AUG07 DSP
-
CLARKE Fire Protection Products
Basic Engine DescriptionJohn Deere Co.Compression (Diesel)44.19 (106) x 5.00 (127)275 (4.5)17.0:1
Valves per cylinder - 11Direct InjectionRotary, 4 Stroke CycleNaturally Aspirated1-3-4-2
Rotation (Viewed from Front) - StandardNot AvailableOpenD-534
Weight - lb (kg).......910 (413)
Cooling System - 3 Pass 2350 2600 2800 300040 (42) 42 (44) 44 (46) 45 (47)16 (17) 17 (18) 18 (19) 19 (20)
8 (30) 9 (34) 10 (37) 11 (40)
10 (38) 11 (42) 12 (45) 13 (48)
4 (60) (400)40 (151)
Thermostat, 187 (86)196 (91)15 (14)10 (69)200 (93)
160 (71)
Electric System - DC12 (Standard) 24 (Optional)
12 241 24D-640 4D-640640 640285 2850.0012 0.0012
0 -120 m 00 00121 - 160 m 000 000161 - 200 m 0000 0000
40 40380 250
USA Production
JU4H-UF24INSTALLATION & OPERATION DATA
*Positive and Negative Cables Combined Length
Engine Manufacturer....Ignition Type......................Number of Cylinders.............Bore and Stroke - in. (mm)..........Displacement - in.3 (L)..........Compression Ratio............
Intake............Exhaust............
Combustion System............Engine Type..............Aspiration..............Firing Order (CW Rotation)..........
Clockwise........Counter-Clockwise..............
Engine Crankcase Vent System........Installation Drawing..........
Engine H2O Heat - Btu/sec (kW)..........Engine Radiated Heat - Btu/sec (kW).........Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)......
95F (35C) Raw H2O - gal/min. (L/min.)......
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........Flow - gal./min (L/min.)..............
Start to Open - F (C).........Fully Opened - F (C).............
Engine Coolant Capacity - qt. (L)..........Coolant Pressure Cap - lb./in.2 (kPa).......Maximum Engine H20 Temperature - F (C)......
Minimum Engine H20 Temperature - F (C).....
System Voltage (Nominal).........Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)................Qty. per Battery Bank..........SAE size per J537............CCA @ -18F (0C)..............Reserve Capacity - Minutes............
Battery Cable Circuit*, Max Resistance - ohm...........Battery Cable Minimum Size
Starter Cranking Amps - @ 60F (15C).........
Circuit* Length............Circuit* Length.............Circuit* Length.............
Charging Alternator Output - Amp..........
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
-
CLARKE Fire Protection Products
Exhaust System 2350 2600 2800 3000Exhaust Flow - ft.3/min. (m3/min.)..469 (13) 531 (15) 581 (16) 630 (18)Exhaust Temperature - F (C).............1076 (580) 1095 (591) 1110 (599) 1125 (607)Maximum Allowable Back Pressure - in. H20 (kPa).30 (7.5)Minimum Exhaust Pipe Dia. - in. (mm)**...3 (76)
Fuel SystemFuel Consumption - gal./hr. (L/hr.).5.6 (21.2) 5.8 (22.0) 6.0 (22.7) 6.2 (23.5)Fuel Return - gal./hr. (L/hr.).9.0 (34.1) 9.5 (36.0) 9.9 (37.5) 10.3 (39.0)Total Supply Fuel Flow - gal./hr. (L/hr.).14.6 (55.3) 15.3 (58.0) 15.9 (60.2) 16.5 (62.5)Fuel Pressure - lb./in.2 (kPa)...3-6 (21-41)
.50 Schedule 40 Steel PipePipe Outer Diameter in. (mm).................. .848 (0.33)
.375 Schedule 40 Steel PipePipe Outer Diameter in. (mm).................. .675 (0.26)
Maximum Allowable Fuel Pump SuctionWith Clean Filter - in. H20 (mH20).31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m)4.5 (1.4)Fuel Filter Micron Size.2
Heater SystemJacket Water Heater
Wattage (Nominal)...1500Voltage - AC, 1P...115 (+5%, -10%)Optional Voltage - AC, 1P...230 (+5%, -10%)
Lube Oil Heater Wattage(Required Option When Ambient is Below 40F (4C)
Induction Air SystemAir Cleaner Type.Indoors Service Only - WashableAir Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)...10 (2.5)Clean Air Cleaner - in. H20 (kPa).5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.)...166 (4.7) 186 (5.3) 202 (5.7) 218 (6.2)Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..130 (54)
Lubrication SystemOil Pressure - normal - lb./in.2 (kPa). 35-50 (241-345)In Pan Oil Temperature - F (C)... 104-118 (220-245)Oil Pan Capacity - High - qt. (L)..8 (7.5)
Low - qt. (L).7 (6.5)Total Oil Capacity with Filter - qt. (L).9 (8.5)
PerformanceBMEP - lb./in.2 (kPa). 88 (608) 83 (573) 79 (545) 75 (517)Piston Speed - ft./min. (m/min.).1958 (597) 2167 (661) 2334 (711) 2501 (762)Mechanical Noise - dB(A) @ 1m...........Power Curve.
JU4H-UF24INSTALLATION & OPERATION DATA (Continued)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations. (Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
Minimum Line Size - Return - (in.)................
Minimum Line Size - Supply - (in.)..........
Consult FactoryC131089
USA Production
pressure drop no greater than one half the max. allowable back pressure.)
*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)
C131264 revDDSP 30AUG07
-
CLARKE Fire Protection Products
Basic Engine DescriptionJohn Deere Co.Compression (Diesel)4106 (4.19) x 127 (5.00)4.5 (275)17.0:1
Valves per cylinder - 11Direct InjectionRotary, 4 Stroke CycleNaturally Aspirated1-3-4-2
Rotation (Viewed from Front) - StandardNot AvailableOpenD-545
Cooling System - 3 Pass 2350 2600 2800 300040 (42) 42 (44) 44 (46) 45 (47)16 (17) 17 (18) 18 (19) 19 (20)
30 (8) 34 (9) 37 (10) 40 (11)
38 (10) 42 (11) 45 (12) 48 (13)
4 (60) (400)100 (26)
Thermostat, 86 (187)91 (196)15 (14)69 (10)93 (200)
71 (160)
Electric System - DC12 24
12 241 24D-640 4D-640640 640285 2850.0012 0.0012
0 -120 m 00 00121 - 160 m 000 000161 - 200 m 0000 0000
40 40380 250
UK Production
JU4H-UF24 INSTALLATION & OPERATION DATA
*Positive and Negative Cables Combined Length
Engine Manufacturer....Ignition Type......................Number of Cylinders.............Bore and Stroke - mm (in.)..........Displacement - L (in.3)..........Compression Ratio............
Intake............Exhaust............
Combustion System............Engine Type..............Aspiration..............Firing Order (CW Rotation)..........
Clockwise........Counter-Clockwise..............
Engine Crankcase Vent System........Installation Drawing..........
Engine H2O Heat - Btu/sec (kW)..........Engine Radiated Heat - Btu/sec (kW).........Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
35C (95F) Raw H2O - L/min. (gal/min.)......
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..................Flow - L/min. (gal./min)...........
Start to Open - C (F).........Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.)..........Coolant Pressure Cap - kPa (lb./in.2).......Maximum Engine H20 Temperature - C (F)......
Minimum Engine H20 Temperature - C (F).....
System Voltage (Nominal).........Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................Qty. per Battery Bank..........SAE size per J537............CCA @ -18C (0F)..............Reserve Capacity - Minutes............
Battery Cable Circuit*, Max Resistance - ohm...........Battery Cable Minimum Size
Starter Cranking Amps - @ 15C (60F).........
Circuit* Length............Circuit* Length.............Circuit* Length.............
Charging Alternator Output - Amp..........
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
-
CLARKE Fire Protection Products
Exhaust System 2350 2600 2800 300013 (469) 15 (531) 16 (581) 18 (630)
580 (1076) 591 (1095) 599 (1110) 607 (1125)7.5 (30)76 (3)
Fuel System21.2 (5.6) 22.0 (5.8) 22.7 (6.0) 23.5 (6.2)34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
55.3 (14.6) 58.0 (15.3) 60.2 (15.9) 62.5 (16.5) 21-41 (3-6) .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).................. .033 (.848) .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).................. .026 (.675)
0.8 (31) 1.4 (4.5) 2
Heater System
1500115 (+5%, -10%)230 (+5%, -10%)
Induction Air SystemIndoors Service Only - Washable
2.5 (10)
1.2 (5)
4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)54 (130)
Lubrication SystemOil Pressure - normal - kPa (lb./in.2)......... 241-345 (35-50)In Pan Oil Temperature - C (F)........... 104-118 (220-245)Oil Pan Capacity - High - L (qt.).......... 7.5 (8)
Low - L (qt.)... 6.5 (7)Total Oil Capacity with Filter - L (qt.)..... 8.5 (9)
Performance608 (88) 573 (83) 545 (79) 517 (75)
597 (1958) 661 (2167) 711 (2334) 762 (2501)Mechanical Noise - dB(A) @ 1m..............
UK Production
pressure drop no greater than one half the max. allowable back pressure.)
*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)
JU4H-UF24 INSTALLATION & OPERATION DATA (Continued)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations. (Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
Exhaust Flow - m3/min. (ft.3/min.)...........Exhaust Temperature - C (F).............Maximum Allowable Back Pressure - kPa (in. H20)...Minimum Exhaust Pipe Dia. - mm (in.)**.........
Minimum Line Size - Supply - (in.).........
Minimum Line Size - Return - (in.)............
Maximum Allowable Fuel Pump SuctionWith Clean Filter - m H20 (in. H20)........
Fuel Consumption - L/hr. (gal.hr.)............Fuel Return - L/hr. (gal./hr.)..........Total Supply Fuel Flow - L/hr. (gal./hr.)..........Fuel Pressure - kPa (lb./in.2)............
Voltage - AC, 1P.............Optional Voltage - AC, 1P..........
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.).........Fuel Filter Micron Size...............
Jacket Water HeaterWattage (Nominal)..............
Engine Air Flow - m3/min. (ft.3/min.)........Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
Air Cleaner Type...........Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)..............
Clean Air Cleaner - kPa (in. H20).............
Consult Factory C131944Power Curve................
BMEP - kPa (lb./in.2).............Piston Speed - m/min. (ft./min.)..........
C131265 revD16AUG07 DSP
-
CLARKE Fire Protection Products
Basic Engine DescriptionEngine Manufacturer.....John Deere Co.Ignition Type....Compression (Diesel)Number of Cylinders...4Bore and Stroke - in.(mm)....4.19(106) x 5.00(127)Displacement - in.3 (L).........275 (4.5)Compression Ratio....17.0:1Valves per cylinder - Intake....1
Exhaust....1Combustion System..Direct InjectionEngine Type....In-Line, 4 Stroke CycleAspiration....TurbochargedFiring Order (CW Rotation)...1-3-4-2Charge Air Cooling Type...NoneRotation (Viewed from Front) - Clockwise Standard
Counter-Clockwise. Not AvailableEngine Crankcase Vent System.OpenInstallation Drawing.D-534Weight - lb (kg)935 (424)
Cooling System 1760 2100 2350 2600Engine H2O Heat -Btu/sec.(kW).....40 (42) 47 (50) 47 (50) 53 (56)Engine Radiated Heat - Btu/sec.(kW).14 (15) 18 (19) 19 (20) 19 (20)Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...8 (30) 10 (38) 10 (38) 10 (38)95F (35C) Raw H2O - gal/min. (L/min.)...10 (38) 11 (42) 11 (42) 14 (53)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...4 (60) (400)Flow - gal./min (L/min.)..40 (151)
Thermostat, Start to Open - F (C)...187 (86)Fully Opened - F (C)...196 (91)
Engine Coolant Capacity - qt. (L)....15 (14)Coolant Pressure Cap - lb./in.2(kPa)...10 (69)Maximum Engine H20 Temperature - F (C)....200 (93)Minimum Engine H20 Temperature - F (C).....160 (71)
Electric System - DCSystem Voltage (Nominal)...12(Standard) 24(Optional)Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)...12 24Qty. per Battery Bank.1 2SAE size per J537.....4D-640 4D-640CCA @ 0F (-18C)....640 640Reserve Capacity - Minutes.....285 285
Battery Cable Circuit*, Max Resistance - ohm........0.0012 0.0012Battery Cable Minimum Size
0 -120 in. Circuit* Length.00 00121 - 160 in. Circuit* Length....000 000161 - 200 in. Circuit* Length.0000 0000Charging Alternator Output - Amp......40 40Starter Cranking Amps - @ 60F (15C).380 250
JU4H-UF30 & JU4H-UF32INSTALLATION & OPERATION DATA
*Positive and Negative Cables Combined Length
USA Production
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
-
CLARKE Fire Protection Products
Exhaust System 1760 2100 2350 2600Exhaust Flow - ft.3/min. (m3/min.). 330 (9) 448 (13) 518 (15) 572 (16)Exhaust Temperature - F (C)........744 (396) 781 (416) 761 (405) 731 (388)Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)Minimum Exhaust Pipe Dia. - in. (mm)**.. 4 (102)
Fuel SystemFuel Consumption - gal./hr. (L/hr.) 1.7 (6.4) 2.2 (8.3) 2.7 (10.2) 3.5 (13.2)Fuel Return - gal./hr. (L/hr.) 7.9 (29.9) 8.5 (32.2) 9.0 (34.1) 9.5 (36.0)Total Supply Fuel Flow - gal./hr. (L/hr.) 9.6 (36.3) 10.7 (40.5) 11.7 (44.3) 13.0 (49.2)Fuel Pressure - lb./in.2 (kPa).. 3-6 (21-41)
.50 Schedule 40 Steel PipePipe Outer Diameter in. (mm).......... .848 (0.33)
.375 Schedule 40 Steel PipePipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump SuctionWith Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)Fuel Filter Micron Size 5
Heater SystemJacket Water Heater
Wattage (Nominal)..1500Voltage - AC, 1P..115 (+5%, -10%)Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage(Required Option When Ambient is Below 40F (4C)
Induction Air SystemAir Cleaner TypeIndoors Service Only - WashableAir Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 147 (4.2) 194 (5.5) 227 (6.4) 252 (7.1)Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***.130 (54)
Lubrication SystemOil Pressure - normal - lb./in.2 (kPa) 35-50 (241-345)In Pan Oil Temperature - F (C).. 220-245 (104-118)Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)Total Oil Capacity with Filter - qt. (L) 9 (8.5)
PerformanceBMEP - lb./in.2 (kPa). 105 (724) 108 (745) 104 (717) 94 (648)Piston Speed - ft./min. (m/min.) 1467 (447) 1750 (533) 1958 (597) 2167 (661)Mechanical Noise - dB(A) @ 1m...........Power Curve
*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations. (Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
C13909 (UF30) C13648 (UF30) & C13649 (UF32)
JU4H-UF30 & JU4H-UF32INSTALLATION & OPERATION DATA (Continued)
USA Production
pressure drop no greter than one half the max. allowable back pressure.)
Minimum Line Size - Supply - (in.)..........
Minimum Line Size - Return - (in.)........
C13664 revJDSP 25FEB08
-
CLARKE Fire Protection Products
Basic Engine DescriptionJohn Deere Co.Compression (Diesel)44.19(106) x 5.00(127) 4.5 (275)17.0:1
Valves per cylinder - 11Direct InjectionIn-Line, 4 Stroke CycleTurbocharged1-3-4-2
Rotation (Viewed from Front) - StandardNot AvailableOpenD-545
Cooling System - 3 Pass 1760 2100 2350 260042 (40) 50 (47) 50 (47) 56 (53)
15.0 (14.0) 19.0 (18.0) 20.0 (19.0) 20.0 (19.0)
30 (8) 34 (9) 38 (10) 45 (12)
38 (10) 42 (11) 45 (12) 53 (14)
4 (60) (400)100 (26)
Thermostat, 86 (187)91 (196)14 (15)69 (10)93 (200)
71 (160)
Electric System - DC12 24
12 241 24D-640 4D-640640 640285 2850.0012 0.0012
0 -120 m 00 00121 - 160 m 000 000161 - 200 m 0000 0000
40 40380 250
UK Production
Starter Cranking Amps - @ 15C (60F).........
Circuit* Length............Circuit* Length.............Circuit* Length.............
Charging Alternator Output - Amp..........
CCA @ -18C (0F)..............Reserve Capacity - Minutes............
Battery Cable Circuit*, Max Resistance - ohm...........Battery Cable Minimum Size
Battery Capacity for Ambients Above 0C (32F)Voltage (Nominal)................Qty. per Battery Bank..........SAE size per J537............
Coolant Pressure Cap - kPa (lb./in.2).......Maximum Engine H20 Temperature - C (F)......
Minimum Engine H20 Temperature - C (F).....
System Voltage (Nominal).........
Flow - L/min. (gal./min)...........Start to Open - C (F).........Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.)..........
15C (60F) Raw H2O - L/min. (gal/min.)......
35C (95F) Raw H2O - L/min. (gal/min.)......
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...........
Installation Drawing..........
Engine H2O Heat - kW (Btu/sec)..........Engine Radiated Heat - kW (Btu/sec).........Heat Exchanger Minimium Flow
Firing Order (CW Rotation)..........Clockwise........Counter-Clockwise..............
Engine Crankcase Vent System........
Exhaust............Combustion System............Engine Type..............Aspiration..............
JU4H-UF30 & JU4H-UF32 INSTALLATION & OPERATION DATA
*Positive and Negative Cables Combined Length
Engine Manufacturer....Ignition Type......................Number of Cylinders.............Bore and Stroke - mm (in.)..........Displacement - L (in.3)..........Compression Ratio............
Intake............
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
-
CLARKE Fire Protection Products
Exhaust System 1760 2100 2350 26009.0 (330) 13.0 (448) 15.0 (518) 16.0 (572)396 (744) 416 (781) 405 (761) 388 (731)
7.4 (30) 102 (4)
Fuel System6.4 (1.7) 8.3 (2.2) 10.2 (2.7) 13.2 (3.5)29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)36.3 (9.6) 40.5 (10.7) 44.3 (11.7) 49.2 (13.0)
21-41 (3-6) .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).................. .033 (.848) .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).................. .026 (.675)
0.8 (31) 1.4 (4.5) 5
Heater System
1500 115 (+5%, -10%) 230 (+5%, -10%)
Induction Air SystemIndoors Service Only - Washable
2.5 (10)1.2 (5)
4.2 (147) 5.5 (194) 6.4 (227) 7.1 (252)54 (130)
Lubrication SystemOil Pressure - normal - kPa (lb./in.2)....... 241-345 (35-50)In Pan Oil Temperature - C (F)......... .104-118 (220-245)Oil Pan Capacity - High - L (qt.).......... 8 (7.5)
Low - L (qt.).. 7 (6.5)Total Oil Capacity with Filter - L (qt.).... 9 (8.5)
Performance7.3 (105) 7.6 (108) 7.3 (104) 6.6 (94)
447 (1467) 533 (1750) 597 (1958) 661 (2167)Mechanical Noise - dB(A) @ 1m.............
Wattage (Nominal)..............
Fuel Return - L/hr. (gal./hr.)..........
Power Curve................
BMEP - kg/cm2 (lb./in.2).............Piston Speed - m/min. (ft./min.)..........
Engine Air Flow - m3/min. (ft.3/min.).........Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
Optional Voltage - AC, 1P..........
Air Intake Restriction Maximum Limit
Clean Air Cleaner - kPa (in. H20)...........
JU4H-UF30 & JU4H-UF32 INSTALLATION & OPERATION DATA (Continued)
UK Production
Air Cleaner Type..........
Fuel Filter Micron Size...............
Jacket Water Heater
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)....
Maximum Allowable Fuel Pump SuctionWith Clean Filter - m H20 (in. H20).........
Fuel Consumption - L/hr. (gal./hr.)............
Voltage - AC, 1P.............
pressure drop no greater than one half the max. allowable back pressure.)
*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations. (Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
Dirty Air Cleaner - kPa (in. H20)............
Total Supply Fuel Flow - L/hr (gal./hr.)..........Fuel Pressure - kPa (lb./in.2).............
C131937 (UF30) C131938 (UF32)
Exhaust Flow - m3/min. (ft.3/min.)...........Exhaust Temperature - C (F).............Maximum Allowable Back Pressure - kPa (in. H20)...
Consult Factory
Minimum Exhaust Pipe Dia. - mm (in.)**.........
Minimum Line Size - Supply - (in.)...........
Minimum Line Size - Return - (in.)................
C131228 revF16AUG07 DSP
-
CLARKE Fire Protection Products
Basic Engine DescriptionEngine Manufacturer.. . John Deere Co.Ignition Type... Compression (Diesel)Number of Cylinders. . 4Bore and Stroke - in.(mm)... 4.19(106) x 5.00(127)Displacement - in.3 (L).... 275 (4.5)Compression Ratio. . 17.0:1Valves per cylinder - Intake... 1
Exhaust... 1Combustion System. . Direct InjectionEngine Type... In-Line, 4 Stroke CycleAspiration.. TurbochargedFiring Order (CW Rotation)... 1-3-4-2Charge Air Cooling Type.. NoneRotation (Viewed from Front) - Clockwise . Standard
Counter-Clockwise. .. Not AvailableEngine Crankcase Vent System.. . OpenInstallation Drawing . D-534Weight - lb (kg)935 (424)
Cooling System 1470 1760Engine H2O Heat -Btu/sec.(kW).. . 34 (36) 40 (42)Engine Radiated Heat - Btu/sec.(kW)........ 14 (15) 16 (17)Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)... 6 (24) 8 (30)95F (35C) Raw H2O - gal/min. (L/min.)... 9 (35) 10 (38)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).. 4 (60) (400)Flow - gal./min (L/min.)... 40 (151)
Thermostat, Start to Open - F (C). 187 (86)Fully Opened - F (C)... 196 (91)
Engine Coolant Capacity - qt. (L)....... 15 (14)Coolant Pressure Cap - lb./in.2(kPa)... 10 (69)Maximum Engine H20 Temperature - F (C)....... 200 (93)Minimum Engine H20 Temperature - F (C).... 160 (71)
Electric System - DCSystem Voltage (Nominal)... 12(Standard) 24(Optional)Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24Qty. per Battery Bank. 1 2SAE size per J537... 4D-640 4D-640CCA @ 0F (-18C)... 640 640Reserve Capacity - Minutes..... 285 285
Battery Cable Circuit*, Max Resistance - ohm........ 0.0012 0.0012Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00121 - 160 in. Circuit* Length.. 000 000161 - 200 in. Circuit* Length.. 0000 0000Charging Alternator Output - Amp...... 40 40Starter Cranking Amps - @ 60F (15C)... .. 380 250
JU4H-UFH8INSTALLATION & OPERATION DATA
*Positive and Negative Cables Combined Length
USA Production
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
-
CLARKE Fire Protection Products
Exhaust System 1470 1760Exhaust Flow - ft.3/min. (m3/min.). 264 (7.5) 362 (10)Exhaust Temperature - F (C)........780 (416) 794(423)Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4) 30 (7.4)Minimum Exhaust Pipe Dia. - in. (mm)**.. 4 (102) 4 (102)
Fuel SystemFuel Consumption - gal./hr. (L/hr.) 1.8 (6.8) 2.1 (7.9)Fuel Return - gal./hr. (L/hr.) 7.4 (28.0) 7.9(29.9)Total Supply Fuel Flow - gal./hr. (L/hr.)9.2 (34.8) 10 (37.8)Fuel Pressure - lb./in.2 (kPa)..3-6 (21-41)
.50 Schedule 40 Steel PipePipe Outer Diameter in. (mm).......... .848 (0.33)
.375 Schedule 40 Steel PipePipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump SuctionWith Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)Fuel Filter Micron Size 5
Heater SystemJacket Water Heater
Wattage (Nominal)..1500Voltage - AC, 1P..115 (+5%, -10%)Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage(Required Option When Ambient is Below 40F (4C)
Induction Air SystemAir Cleaner TypeIndoors Service Only - WashableAir Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 103 (2.9) 154 (4.4)Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***. 130 (54)
Lubrication SystemOil Pressure - normal - lb./in.2 (kPa) 35-50 (241-345)In Pan Oil Temperature - F (C).. 220-245 (104-118)Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)Total Oil Capacity with Filter - qt. (L) 9 (8.5)
PerformanceBMEP - lb./in.2 (kPa). 119 (821) 120 (825)Piston Speed - ft./min. (m/min.)1240(378) 1467 (447)Mechanical Noise - dB(A) @ 1m...........Power Curve
JU4H-UFH8INSTALLATION & OPERATION DATA (Continued)
USA Production
pressure drop no greater than one half the max. allowable back pressure.)
Minimum Line Size - Return - (in.)........
Minimum Line Size - Supply - (in.)..........
*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations. (Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, a